Danfoss SC12, SC12CL Data sheet

SC12/12CL LBP/MBP Twin Compressor R404A/R507 220-240V 50Hz
General
Code number 104L4088
Approvals EN 60335-2-34
Application
Application LBP/MBP
Frequency Hz 50 60
Evaporating temperature °C -45 to -5
Voltage range V 198 - 254
Max. condensing temperature continuous (short) °C 55 (60)
Max. winding temperature continuous (short) °C 125 (135)
Cooling requirements
Frequency Hz 50 60
Application
32°C F2F2–
38°C F
43°C
Remarks on application:
LBP MBP HBP LBP MBP HBP
2F2
S =Staticcoolingnormallysufcient
O = Oil cooling F1 = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) F2 = Fan cooling 3.0 m/s necessary
SG =Suctiongascoolingnormallysufcent
– = not applicable in this area
Motor
Motor type CSIR
LRA (rated after 4 sec. UL984) *, HST | LST A 2 x 14.8
Cut in Current *, HST | LST A 2 x 14.8
Resistance, main | start winding (25°C) 5.0 13.7
* Operational current for the second compressor time-delayed.
Design
Displacement cm
Oil quantity (type) cm
Maximum refrigerant charge g 2200
Free gas volume in compressor cm
Weight without electrical equipment kg 27.3
Dimensions
Height mm A 249
Suction connector (service valve) location/I.D. mm C 12 | 37°
Suction connector (solder connector) location/I.D. mm C 12 | 37°
Process connector location/I.D. mm | angle D 6.2 | 37°
material | comment Cu-plated steel | Al cap
Discharge connector location/I.D. mm | angle E 6.2 | 37°
material | comment Cu-plated steel | Al cap
Oil cooler connector location/I.D. mm | angle F
material | comment
Connector tolerance I.D. mm ±0.09
Remarks:
3
3
3
1220 (polyolester)
B 244
B1 183
B2 100
2 x 12.87
2820
Dec 2011 Manufactured by Secop for Danfoss - CF.54.G3.02 / 520N1181 1/2
EN 12900 Household (CECOMAF)* 220V, 50Hz, fan cooling F
2
Evap. temp. in °C -45 -40 -35 -30 -25 -23.3 -20 -15 -10 -6.7 -5 0 5 7.2 10 15 20
Capacity in W 115 279 475 706 980 1083 1299 1670 2096 2411 2583
Power cons. in W 379 506 633 761 891 936 1024 1163 1308 1407 1460
Current cons. in A 4.30 4.55 4.85 5.22 5.64 5.80 6.13 6.67 7.27 7.71 7.94
COP in W/W 0.30 0.55 0.75 0.93 1.10 1.16 1.27 1.44 1.60 1.71 1.77
ASHRAE LBP/MBP 220V, 50Hz, fan cooling F
2
Evap. temp. in °C -45 -40 -35 -30 -25 -23.3 -20 -15 -10 -6.7 -5 0 5 7.2 10 15 20
Capacity in W 134 323 550 819 1137 1257 1509 1941 2440 2796 3011
Power cons. in W 379 506 633 761 891 936 1024 1163 1308 1407 1460
Current cons. in A 4.30 4.55 4.85 5.22 5.64 5.80 6.13 6.67 7.27 7.71 7.94
COP in W/W 0.35 0.64 0.87 1.08 1.28 1.34 1.47 1.67 1.87 1.99 2.06
Accessories SC12/12CL pcs. Code number Test conditions
EN 12900/
CECOMAF*
ASHRAE
LBP/MBP
Starting device 470 mm cable length Condensing temperature 45°C 45°C
550 mm cable length 2 Ambient temperature 32°C 32°C
650 mm cable length Suction gas temperature 32°C 32°C
Starting relay 6.3 mm spade connectors 2 117U6005 Liquid temperature no subcooling 32°C
Start. capacitor 80 µF 6.3 mm spade connectors 2 117U5017
Cover 2 103N2009
Cord relief 2 103N1004
Time-delay relay 1 117N0001
Check valve (to be used with time-delay relay) 2 020-1014
Service valve 12 mm 1 118-7350
Solder connector (alternative) 12 mm 1 104B0584
Service valve 16 mm 1
Solder connector (alternative) 16 mm 1
Seal ring for service valve and solder connector 1 118-3638
Mounting accessories pcs. Code number
Bolt joint for one compressor Ø: 16 mm 2 118-1917
Bolt joint in quantities Ø: 16 mm 2 118-1918
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to
productsalreadyonorderprovidedthatsuchalterationscanbemadewithoutsubsequentialchangesbeingnecessaryinspecicationsalreadyagreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
2/2 Manufactured by Secop for Danfoss - CF.54.G3.02 / 520N1181 Dec 2011
Loading...