Datasheets
SC10GHH
Heat pump Compressor
R134, 220-240V 50Hz
General
Code number 104G8071
Approvals EN 60335-2-34
Compressors on pallet 80
Application
Application HBP
Frequency Hz 50 60
Evaporating temperature °C -15 to 15 –
Voltage range V 198 - 254 –
Max. condensing temperature continuous (short) °C 60 (70) –
Max. winding temperature continuous (short) °C 125 (135) –
Cooling requirements
Frequency Hz 50 60
Application
32°C – – O – – O
38°C – – O – – O
43°C – – O – – O
Remarks on application:
Motor
Motor type CSR
LRA (rated after 4 sec. UL984), HST | LST A 8.9 –
Cut in Current, HST | LST A 8.9 –
Resistance, main | start winding (25°C) Ω 10.9 37.3
LBP MBP HBP LBP MBP HBP
S =Staticcoolingnormallysufcient
O = Oil cooling
F1 = Fan cooling 1.5 m/s
(compressor compartment temperature
equal to ambient temperature)
F2 = Fan cooling 3.0 m/s necessary
SG =Suctiongascoolingnormallysufcent
– = not applicable in this area
Design
Displacement cm
Oil quantity (type) cm
Maximum refrigerant charge g 1300
Free gas volume in compressor cm
Weight without electrical equipment kg 13.3
Dimensions
Height mm A 209
Suction connector location/I.D. mm | angle C 10.2 | 37°
material | comment Copper | Rubber plug
Process connector location/I.D. mm | angle D 6.2 | 37°
material | comment Copper | Rubber plug
Discharge connector location/I.D. mm | angle E 8.2 | 37°
material | comment Copper | Rubber plug
Oil cooler connector location/I.D. mm | angle F 8.2 | –
material | comment Copper | Rubber plug
Connector tolerance I.D. mm ±0.09
Remarks:
3
3
3
450 (polyolester)
B 203
B1 183
B2 100
10.29
1640
© Danfoss | DCS (CC) | 2017.04
DEHC.ED.200.E6.02 | 1
EN 12900 Household (CECOMAF) 220V, 50Hz, fan cooling F
Danf
already on order pro
All trademarks in this material are property of the respec
1
Evap. temp. in °C -45 -40 -35 -30 -25 -23.3 -20 -15 -10 -6.7 -5 0 5 7.2 10 15 20
Capacity in W 259 352 412 467 604 762 855 942 1144
Power cons. in W 230 260 272 290 318 345 367 371 395
Current cons. in A 1.03 1.15 1.20 1.28 1.40 1.53 1.60 1.66 1.77
COP in W/W 1.13 1.35 1.51 1.61 1.90 2.21 2.33 2.54 2.90
ASHRAE HBP 220V, 50Hz, fan cooling F
1
Evap. temp. in °C -45 -40 -35 -30 -25 -23.3 -20 -15 -10 -6.7 -5 0 5 7.2 10 15 20
Capacity in W 319 434 496 577 746 943 1060 1168 1421
Power cons. in W 230 260 272 290 318 345 367 371 395
Current cons. in A 1.03 1.15 1.20 1.28 1.40 1.53 1.60 1.66 1.77
COP in W/W 1.39 1.67 1.82 1.99 2.35 2.73 2.89 3.15 3.60
Accessories for SC10GHH Figure Code number Test conditions
Sarting device 550 mm cable length
1000 mm cable length 117-7014 Ambient temperature 32°C 32°C
a3
117-7025 Condensing temperature 55°C 55°C
EN 12900/CECOMAF
ASHRAE HBP
Cover b 103N2009 Suction gas temperature 32°C 32°C
Starting relay a2
Start. capacitor c
Run capacitor e Mounting accessories Code number
Components
of starting
device
Liquid temperature 55°C 32°C
Cord relief d 103N1004 Bolt joint for one comp. Ø: 16 mm 118-1917
Bolt joint in quantities Ø: 16 mm 118-1918
Snap-on in quantities Ø: 16 mm 118-1919
oss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
vided that such alterations can be made without subsequential changes being necessary eady agreed.
tive companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
2 |© Danfoss | DCS (CC) | 2017.04 DEHC.ED.200.E6.02