Danfoss RT 260A, RT 262A, RT 265A, RT 260AL, RT 262AL Installation guide [da]

...
Installation guide
Differential pressure switch
RT 260A, RT 262A, RT 265A, RT 260AL, RT 262AL, RT 263AL, RT 266AL
Refrigerants*): R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D, R507A, R717
017R9506
RT 260 A RT 262 AL
Fig. 1 Fig. 2
017R9506
s
Fig. 3 Fig. 4
Fig. 5 Fig. 6
Fig. 7 Fig. 8 Fig. 9
© Danfoss | DCS (rm) | 2019.09
DKRCC.PI.CE0.B2.53 | 520H11632 | 1
ENGLISH
Differential pressure switches
*) For complete list of approved refrigerants, www.products.danfoss.com and search for
individual code numbers, where refrigerants
are listed as part of technical data.
Technical data
Differential
Typ e
RT 260A
RT 260A
RT 260A
RT 262A
RT 265A
RT 260AL
RT 262AL
RT 263AL
RT 266AL
pressure
range p
1.5 – 11 -1 – 31 0.5 42
0.1 – 1. 5 -1 – 9 0.1 11
0.1 – 1. 5 -1 – 9 0.1 11
0.1 – 1. 0 -1 – 6 0.05 7
Neutral zone, p Nz RT 260AL: 0.3 bar – 0.9 bar RT 262AL: 0.1 bar – 0.33 bar RT 263AL: 0.05 bar – 0.23 bar RT 266AL: 0.05 bar – 0.23 bar
Max. test pressure, p' = 1.1 × MWP Permissible temperature range: -40 °C – 70 °C
Contact load
See contact cover or fig. 3. If the contact load is given as, for example, 10 (4) A, 400 V AC, it means that the connected load must be max. 10 A ohmic and 4 A inductive at 400 V AC. The permissible starting current on motor cut-in can be up to seven times the inductive load, but max. 28 A. The switch meets the requirements of VDE* 0660.
*VDE = Verband Deutscher Elektrotechniker
Installation
A set of Pg13.5 cable gland is attached to the RT in a separate bag. To ensure IP66 (units with automatic reset) or IP54 (units with external reset) grade of RT enclosure it is necessary to assemble this gland as shown in the fig. 4. If this gland is not used with a cable, a metal blinding should be also assembled.
The differential pressure control must be mounted on a valve panel or, for example, direct on a compressor. Use the fixing holes (25). If the unit can be exposed to vibration, it should to be mounted on a resilient pad.
Product must be always mounted vertically with the LP side placed on the top and the HP side placed on the bottom (as shown in the fig. 1).
Electrical connection
See fig. 5. START = make. STOP = break DIFF = fixed contact differential Cable diameter: 6 – 14 mm Connect earth to the earth screw (38)
Setting
Set the required differential pressure with the setting disc (5) while at the same time reading the scale (9). Find the required neutral zone for RT 260AL, RT 262AL, RT 263AL, RT 266AL from the diagram. The setting value for the
Operation
LP bellows
[bar]
0.5 – 4 -1 – 18 0.3 22
0.5 – 6 -1 – 36 0.5 42
1 – 6 -1 – 36 0.5 42
0.5 – 4 -1 – 18 0. 3 22
0 – 0.9 -1 – 6 0.05 7
range for
[bar]
Mechani-
cal
differen-
tial
[bar]
Max. working pressure
MWP
[bar]
neutral zone (40) can be read from the lowest scale on the diagram.
Example 1
RT 262A with terminals 1 – 4 connected. Set differential pressure p = 0.5 bar. The RT 262A breaks at a differential pressure of 0.5 bar and makes at a differential pressure + contact differential = 0.5 bar + 0.1 bar = 0.6 bar.
Example 2
RT 262AL Required differential pressure p = 0.5 bar. Required neutral zone Nz = 0.25 bar. As can be seen on the diagram, fig. 6., the required neutral zone of 0.25 bar is obtained by setting the neutral zone disc (40) at 2.5. Because the contact differential is 0.1 bar, the make and break differential pressures for the switch are:
Make differential pressure for contacts 1 – 4 = 0.5 bar + 0.1 bar = 0.6 bar. Break differential pressure for contacts 1 – 4 = 0.5 bar (= set value p). Make differential pressure for contacts 1 – 2 = 0.6 bar – 0.25 bar = 0.35 bar. Break differential pressure for contacts 1 – 2 = 0.35 bar + 0.1 bar = 0.45 bar.
DANSK
Differenspressostater
*)
For komplet liste over godkendte kølemidler,
besøge www.products.
efter individuelle bestillingsnumre, hvor kølemidler er opført som en del af tekniske data.
Tekniske data
Differens-
Typ e
RT 260A
RT 260A
RT 260A
RT 262A
RT 265A
RT 260AL
RT 262AL
RT 263AL
RT 266AL
trykområde
p
[bar]
0.5 – 4 -1 – 18 0. 3 22
0.5 – 6 -1 – 36 0.5 42
1.5 – 11 -1 – 31 0.5 42
0.1 – 1. 5 -1 – 9 0.1 11
1 – 6 -1 – 36 0.5 42
0.5 – 4 -1 – 18 0. 3 22
0.1 – 1. 5 -1 – 9 0.1 11
0.1 – 1. 0 -1 – 6 0.05 7
0 – 0.9 -1 – 6 0.05 7
Neutralzone, p Nz RT 260AL: 0.3 bar – 0.9 bar RT 262AL: 0.1 bar – 0.33 bar RT 263AL: 0.05 bar – 0.23 bar RT 266AL: 0.05 bar – 0.23 bar
Maks. prøvetryk, p' = 1.1 × PB Tilladelig temperatur: -40 °C – 70 °C
Kontaktbelastning
Se kontaktdæksel eller fig. 3. Er kontaktbelastningen eksempelvis angivet som 10 (4) A, 400 V AC betyder det, at der maks. må tilsluttes 10 A ohmsk og 4 A induktiv belastning ved 400 V AC Maksimal startstrøm ved indkobling af motor må være op til syv gange den induktive belastning – dog maks. 28 A. Kontaktsystemet opfylder betingelserne i
*VDE = Verband Deutscher Elektrotechniker
danfoss.com og søg
Driftsom-
råde for
LP-bælg
[bar]
Mekanisk
differens
[bar]
ladeligt
drifts-
tryk PB
[bar]
Til-
Montering
Et sæt Pg13,5 kabelforskruning er vedlagt produktet i en separat pose. For at sikre kapslingsgrad IP66 (enheder med automatisk reset) eller IP54 (enheder med ekstern DANSK RESET) er det nødvendigt at montere denne kabelforskruning som vist i fig. 4. Hvis denne kabelforskruning ikke bruges sammen med et kabel, bør der monteres en blindprop (metal skive).
Differenspressostaten monteres på en ventilt­avle eller f.eks. direkte på en kompressor. Benyt monteringshullerne (25). Hvis apparatet kan blive udsat for vibrationer, bør det monteres på et blødt underlag.
Produktet skal altid monteres lodret med LP-siden placeret øverst og HP-siden nederst (som vist i fig. 1).
El-tilslutning
Se fig. 5. START = slutte. STOP = bryde DIFF = fast kontaktdifferens. Kabeldiameter: 6 – 14 mm. Jordforbindelse tilsluttes jordskruen (38).
Indstilling
Det ønskede differenstryk indstilles ved hjælp af indstillingsskiven (5) under samtidig aflæsning af skalaen (9). Den ønskede neutralzone for RT 260AL, RT 262AL, RT 263AL, RT 266AL opsøges i diagrammet. På diagrammets nederste skala aflæses den værdi, neutralzonerullen (40) skal indstilles på.
Eksempel 1
RT 262A med klemme 1 – 4 tilsluttet.Indstillet differenstryk p = 0.5 bar. RT 262A bryder ved differenstrykket
0.5 bar og slutter ved differenstrykket + kontaktdifferensen = 0.5 bar + 0.1 bar = 0.6 bar.
Eksempel 2
RT 262AL Ønsket differenstryk p = 0.5 bar. Ønsket neutralzone Nz = 0.25 bar. Som det kan ses af diagrammet fig. 5., opnås den ønskede neutralzone på 0.25 bar ved at indstille neutralzonerullen (40) på værdien 2.5. Slutte- og brydedifferenstrykkene for kontaktsystemet (se fig. 4.) bliver herved, idet kontaktdifferensen er 0.1 bar:
Sluttedifferenstryk for kontakterne 1 – 4 = 0.5 bar + 0.1 bar = 0.6 bar. Brydedifferenstryk for kontakterne 1 – 4 = 0.5 bar (= indstillingsværdi, p). Sluttedifferenstryk for kontakterne 1 – 2 = 0.6 bar – 0.25 bar = 0.35 bar. Brydedifferenstryk for kontakterne 1 – 2 = 0.35 bar + 0.1 bar = 0.45 bar.
2 | 520H11632 | DKRCC.PI.CE0.B2.53
© Danfoss | DCS (rm) | 2019.09
DEUTSCH
Differenzpressostate
*) Gehen Sie zu www.products.danfoss.com und beachten Sie auf der Produktseite die Übersicht der zugelassenen Kühlmedien.
Technische Daten
Differenz-
druck-
Typ
RT 260A
RT 260A
RT 260A
RT 262A
RT 265A
RT 260AL
RT 262AL
RT 263AL
RT 266AL
bereich
[bar]
0.5 – 4 -1 – 18 0. 3 22
0.5 – 6 -1 – 36 0.5 42
1.5 – 11 -1 – 31 0.5 42
0.1 – 1. 5 -1 – 9 0.1 11
1 – 6 -1 – 36 0.5 42
0.5 – 4 -1 – 18 0. 3 22
0.1 – 1. 5 -1 – 9 0.1 11
0.1 – 1. 0 -1 – 6 0.05 7
0 – 0.9 -1 – 6 0.05 7
Neutralzone, p Nz RT 260AL: 0.3 bar – 0.9 bar RT 262AL: 0.1 bar – 0.33 bar RT 263AL: 0.05 bar – 0.23 bar RT 266AL: 0.05 bar – 0.23 bar
Max. Prüfdruck, p' = 1.1 × PB Zulässige Temperatur: -40 °C – 70 °C
Kontaktbelastung
Wenn die Kontaktbelastung z.B. mit 10 (4) A, 400 V ~ angegeben ist, bedeutet das, daß max. 10 A ohmsche und 4 A induktive Belastung bei 400 V ~ angeschlossen werden dürfen. Der maximale Anlaufstrom darf beim Einschalten des Motors bis zu siebenmal so groß sein wie die induktive Belastung – jedoch max. 28 A. Das Kontaktsystem erfüllt die Bedingungen in VDE* 0660.
*VDE = Verband Deutscher Elektrotechniker
Montage
Die Kabelverschraubungen PG13,5 sind in einem separaten Beutel verpackt. Zum erreichen des IP66 Schutzgrades (Geräte mit automatischen Reset) oder IP54 (Geräte mit externen Reset) ist eine Montage dieser Verschraubung notwendig, (siehe Abb. 4.). Wenn diese Kabelverschraubung nicht benötigt wird ist ein Metall Blindstopfen zu verwenden.
Der Differenzpressostat ist an eine Ventiltafel oder z.B. direkt an einen Kompressor zu montieren. Die Montagelöcher (25) sind zu benutzen. Wenn das Gerät Vibrationen ausgesetzt wird, sollte es auf eine weiche Unterlage montiert werden.
Bringen Sie das Produkt immer vertikal an, mit der Niederdruckseite oben und der Hochdruckseite unten (wie in Abb. 1 dargestellt).
Elektr. Anschluß
Siehe Abb.5 START = Ein. STOP = Aus DIFF = feste Kontaktdifferenz Kabeldurchmesser: 6 – 14 mm Der Erdanschluß ist an die Erdungsschraube (38) anzuschliessen.
p
Betrieb­sbereich
Wellrohr
für ND
[bar]
Mecha-
nische
Differenz
[bar]
Zul.
Betriebs-
über-
druck PB
[bar]
Einstellung
Der gewünschte Differenzdruck ist mit Hilfe der Einstellscheibe (5) und unter
gleichzeitigem Ablesen der Skala (9) einzustellen. Die gewünschte Neutralzone für RT 260AL, RT 262AL, RT 263AL, RT 266AL ist auf dem Diagramm aufzusuchen. Auf der untersten Skala des Diagrammes ist der Wert abzulesen, auf den die Neutralzonenrolle (40) eingestellt werden muß.
Beispiel 1
RT 262A mit Klemme 1 – 4 angeschlossen. Eingestellter Differenzdruck p = 0.5 bar. RT 262A schaltet aus beim Differenzdruck 0.5 bar und schaltet ein beim Differenzdruck und der Kontaktdifferenz = 0.5 bar + 0.1 bar = 0.6 bar.
Beispiel 2
RT 262AL Gewünschter Differenzdruck p = 0.5 bar. Gewünschte Neutralzone Nz = 0.25 bar. Wie auf dem Diagramm Abb. 6 zu sehen ist, wird die gewünschte Neutralzone von 0.25 bar durch Einstellen der Neutralzonenrolle (40) auf den Wert von 2.5 erreicht. Da die Kontaktdifferenz 0.1 bar beträgt, nehmen die Ein- und Ausschaltdifferenzdrücke für das Kontaktsystem (siehe Abb. 4), folgende Werte an:
Einschaltdifferenzdruck für die Kontakte 1 – 4 = 0.5 bar + 0.1 bar = 0.6 bar. Ausschaltdifferenzdruck für die Kontakte 1 – 4 = 0.5 bar (= Einstellwert, p). Einschaltdifferenzdruck für die Kontakte 1 – 2 = 0.6 bar – 0.25 bar = 0.35 bar. Ausschaltdifferenzdruck für die Kontakte 1 – 2 = 0.35 bar + 0.1 bar = 0.45 bar.
FRANÇAIS
Pressostats différentiels
*) Pour consulter la liste complète liste de fluides frigorigènes, rendez-vous sur www.products. danfoss.com et recherchez les numéros de code individuel, où les fluides sont répertoriés dans le
cadre de données techniques.
Caractéristiques techniques
p
Plage de
fonctionne-
ment pou r
soufflets
basse pres-
sion (LP)
[bar]
Diffé-
rentiel
mécan-
ique
[bar]
Pression
de service­maxi PB
[bar]
Plage de pression
Typ e
RT 260A
RT 260A
RT 260A
RT 262A
RT 265A
RT 260AL
RT 262AL
RT 263AL
RT 266AL
différentielle
[bar]
0.5 – 4 -1 – 18 0. 3 22
0.5 – 6 -1 – 36 0.5 42
1.5 – 11 -1 – 31 0.5 42
0.1 – 1. 5 -1 – 9 0.1 11
1 – 6 -1 – 36 0.5 42
0.5 – 4 -1 – 18 0. 3 22
0.1 – 1. 5 -1 – 9 0.1 11
0.1 – 1. 0 -1 – 6 0.05 7
0 – 0.9 -1 – 6 0.05 7
Zone neutre, p Nz RT 260AL: 0.3 bar – 0.9 bar RT 262AL: 0.1 bar – 0.33 bar RT 263AL: 0.05 bar – 0.23 bar RT 266AL: 0.05 bar – 0.23 bar
Pression d’aissai max. p' = 1.1 × PB Température admissible: -40 °C – 70 °C
Pouvoir de coupure
Voir couvercle du contact ou fig. 3. Un pouvoir de coupure, par exemple, de 10 (4) A, 400 V
CA signifie que la charge maximale est de 10 A ohmique et de 4 A inductif pour 400 V CA. Le courant de démarrage maximal lors de l’enclenchement du moteur est de sept fois la charge inductive, mais de 28 A maxi. Le contact réponds aux exigences de la norme VDE* no 0660.
* VDE signifie Verband Deutscher Elektrotechniker
Montage
Un ensemble presse étoupe Pg13.5 est joint au RT dans un sac séparé. Pour assurer l’indice IP66 du RT (pressostat avec réarme­ment automatique) ou IP54 (pressostat avec réarmement manuel), il faut assembler le presse étoupe comme indiqué sur la fig. 4. Si le presse étoupe n’est pas utilisé avec un câble, il faut le boucher avec une pièce métallique.
Monter le pressostat différentiel sur tableau ou à même l’appareil à commander, par exemple, un compresseur. Utiliser les trous de montage (25). S’il y a risque de vibrations, monter l’appareil sur caoutchouc amortisseur.
Le produit doit toujours être monté à la verticale avec le côté BP positionné vers le haut et le côté HP positionné vers le bas (comme indiqué sur l'image 1).
Raccordement électrique
Voir fig. 5. START: fermeture. STOP: ouverture DIFF: différentiel de contact fixe Diamètre de câble: 6 – 14 mm Mise à la terre par la vis (38).
Réglages
Régler la pression différentielle à l’aide du disque (5). Voir l’index (9). Chercher la zone neutre désirée pour RT 260AL, RT 262AL, RT 263AL, RT 266AL dans le tableau. L’échelle inférieure permet de repérer la de réglage du rouleau de zone neutre (40).
Exemple n° 1
RT 262A avec raccordement par les bornes 1 – 4. Pression différentielle réglée, p = 0.5 bar. RT 262A s’ouvre à la pression différentielle de
0.5 bar et se ferme à la pression différentielle + le différentiel de contact = 0.5 bar + 0.1 bar = 0.6 bar.
Exemple n° 2
RT 262AL Pression différentielle p désirée = 0.5 bar. Comme il ressort du schéma fig. 6., la zone neutre de 0.25 bar est obtenue avec le rouleau (40) sur la valeur 2.5. Les pressions différentielles de fermeture et d’ouverture pour le système de contact (voir fig. 4.) seront alors (différentiel de contact de
0.1 bar):
Pression différentielle de fermeture pour les contacts 1 – 4 = 0.5 bar + 0.1 bar = 0.6 bar. Pression différentielle d’ouverture pour les contacts 1 – 4: 0.5 bar (égale à la valeur de consigne, p). Pression différentielle de fermeture pour les contacts 1 – 2: 0.6 bar – 0.25 bar = 0.35 bar. Pression différentielle d’ouverture pour les contacts 1 – 2: 0.35 bar + 0.1 bar = 0.45 bar.
valeur
© Danfoss | DCS (rm) | 2019.09
DKRCC.PI.CE0.B2.53 | 520H11632 | 3
ESPAÑOL
Pressostatos diferenciales
*) Visitar www.products.danfoss.com para consultar la lista completa de refrigerantes aprobados.
Puede buscarse por códigos, donde los refrigerantes
se muestran como parte de datos técnicos.
Características técnicas
Rango de
trabajo p ara
p
[bar]
1 – 6 -1 – 36 0.5 42
fuelles
Tipo
RT 260A
RT 260A
RT 260A
RT 262A
RT 265A
RT 260AL
RT 262AL
RT 263AL
RT 266AL
Gama de
presión
diferencial
0.5 – 4 -1 – 18 0. 3 22
0.5 – 6 -1 – 36 0.5 42
1.5 – 11 -1 – 31 0.5 42
0.1 – 1. 5 -1 – 9 0.1 11
0.5 – 4 -1 – 18 0. 3 22
0.1 – 1. 5 -1 – 9 0.1 11
0.1 – 1. 0 -1 – 6 0.05 7
0 – 0.9 -1 – 6 0.05 7
Zona neutra, p Nz RT 260AL: 0.3 bar – 0.9 bar RT 262AL: 0.1 bar – 0.33 bar RT 263AL: 0.05 bar – 0.23 bar RT 266AL: 0.05 bar – 0.23 bar
Presión de prueba máx. p' = 1.1 × PB Temperatura admisible: -40 °C – 70 °C
Carga de Los contactos
Véase cubierta de Los contactos o figura 3. Si se indica una cargo de los contactos de por ejemplo 10 (4) A, 400 V CA, esto significa que la carga conectada debe ser como máximo de 10 A si es una carga ohmica, y de 4 A si es una carga inductiva a 400 V CA. La corriente de arranque admisible en el momento de la conexión del motor puede ser igual a 7 veces la carga inductiva, sin rebasar el valor máximo de 28 A. El conmutador satisface los requisitos de VDE* 0660.
*VDE = Verband Deutscher Elektrotechniker
Instalación
En una bolsa separada, se incluye, junto con el RT, un conjunto de prensaestopas Pg13.5.Es necesario instalar el prensaestopas como se muestra en la fig. 4., para garantizar el grado de protección del RT, IP66 (unidades con rearme automático) o IP54 (unidades con rearme manual).Si no se utiliza el prensaestopas con un cable, debería montarse un cegamiento metálico.
El presostato diferencial debe montarse en un panel de válvulas, o, par ejemplo, directamente en un compresor. Utilizar los agujeros de fijación (25). Si la unidad puede estar sometida a vibraciones, se montará sobre un amortiguador elástico.
El producto debe montarse siempre en posición vertical con el lado LP en la parte superior y el lado HP en la parte inferior (según se muestra en la fig. 1).
Conexión eléctrica
Véase figure 5. START = cierre. STOP = abertura DIFF = diferencial de contacto fija Diámetro de cable: 6 – 14 mm Conectar la tierra con el tornillo de tierra (38).
LP
[bar]
Difer­encial
mecáni-
co
[bar]
Presión
de
funcio.
máx. PB
[bar]
Reglaje
Ajustar la presión diferencial requerida con el disco de reglaje (5) mientras se observe el valor marcado en la escala (9).
Buscar la zona neutra requerida para RT 260AL, RT 262AL, RT 263AL, RT 266AL en diagrama. El valor de reglaje de la zona neutra (40) puede ser leido en la escala más baja del diagrama.
Ejemplo 1
RT 262A con terminales 1 – 4 conectados. Ajustar la presión diferencial p = 0.5 bar. El RT 262A abre sus contactos a una presión diferencial de 0.5 bar y cierra los contactos a un valor que corresponde a la presión diferencial + la diferencial de contacto = 0.5 bar + 0.1 bar = 0.6 bar.
Ejemplo 2
RT 262AL Presión diferencial requerida p = 0.5 bar. Zona neutra requerida Nz = 0.25 bar. Como puede verse en el diagrama, figure 6, la zona neutra requerida de 0.25 bar se obtiene ajustando el disco de zona neutra (40) en 2.5. Debido a que la diferencial de contacto es de
0.1 bar, las presiones dife-renciales de cierre y de abertura del conmutador son:
Presión diferencial de cierre de los contactos 1 – 4 = 0.5 bar + 0.1 bar = 0.6 bar. Presión diferencial de abertura de los contactos 1 – 4 = 0.5 bar (= valor ajustado, p). Presión diferencial de cierre de los contactos 1 – 2 = 0.6 bar – 0.25 bar = 0.35 bar. Presión diferencial de abertura de los contactos 1 – 2 = 0.35 bar + 0.1 bar = 0.45 bar.
ITALIANO
Pressostati differenziali
*)
Per elenco completo dei refrigeranti approvati, visitare www.products.danfoss.com ed effettuare
ricerca per i singoli codici, dove i refrigeranti sono elencati come parte dei dati tecnici.
Dati tecnici
Differenza
Tipo
RT 260A
RT 260A
RT 260A
RT 262A
RT 265A
RT 260AL
RT 262AL
RT 263AL
RT 266AL
pressione
0.5 – 4 -1 – 18 0. 3 22
0.5 – 6 -1 – 36 0.5 42
1.5 – 11 -1 – 31 0.5 42
0.1 – 1. 5 -1 – 9 0.1 11
0.5 – 4 -1 – 18 0. 3 22
0.1 – 1. 5 -1 – 9 0.1 11
0.1 – 1. 0 -1 – 6 0.05 7
0 – 0.9 -1 – 6 0.05 7
Zona morta, p Nz RT 260AL: 0.3 bar – 0.9 bar RT 262AL: 0.1 bar – 0.33 bar RT 263AL: 0.05 bar – 0.23 bar RT 266AL: 0.05 bar – 0.23 bar
Max. pressione di prova p' = 1.1 × PB Temperatura ammessa: -40 °C – 70 °C
Carico contatti
Vedere coperchio copri-contatti o fig.3. Se il carico sui contatti indicato è, ad
Campo di
di
funziona-
mento, lato
p
pressione
[bar]
1 – 6 -1 – 36 0.5 42
bassa
[bar]
Differ-
enziale
mec-
canico
[bar]
Max.
pressione
di ese r­cizio PB
[bar]
esempio,10 (4) A, 400 V CA, significa che il carico collegato dovrà essere rispettivamente di 10 A max. ohmico e 4 A induttivo a 400 V CA La corrente di corto circuito ammessa all’aviamento del motore può essere pari a sette volte il carico induttivo, ma comunque non superiore a 28 A max. risponde alla norma VDE* 0660.
L’interruttore
*VDE = Verband Deutscher Elektrotechniker
Installazione
Un set di pressacavo filettato Pg13.5 è allegto all’RT in una busta a parte. Per assicurare un grado di protezione per l’RT di IP66 (unità con reset automatico) o di IP54 (unità con reset esterno), è necessario assemblare questo pressacavo come illustrato in fig. 4. Se questo pressacavo non è usato con un cavo, un connettore in metallo deve essere assemblato.
Il pressostato differenziale deve essere montato a quadro o, ad esempio, direttamente sul compressore. Utilizzare i fori di fissaggio (25). Nel caso di forti vibrazioni, esso
dovrà essere
montato su un tampone antivibrante.
Il prodotto deve essere sempre montato verticalmente con il lato LP posizionato nella parte superiore e il lato HP posizionato nella parte inferiore (come mostrato nella figura 1).
Collegamenti elettrici
Vedi fig. 5. START = chiude. STOP = apre DIFF = differenziale meccanico fisso Diametro cavi: 6 – 14 mm Collegare a terra il terminale (38).
Taratura
La taratura della pressione differenziale è ottenuta ruotando la ghiera di taratura (5) fino a quando l’indice non coincide con il valore desiderato sulla scala (9). Per trovare il valore di zona morta desiderato, relativo ai pressostati RT 260AL, RT 262AL, RT 263AL, RT 266AL, utilizzare i diagrammi. Sulla scala inferiore riportata sul diagramma si potrà rilevare il valore di taratura della zona morta (40).
Esempio 1
RT 262A con morsetti 1 – 4 collegati. Tarare la pressione differenziale p = 0.5 bar. L’RT 262A apre il contatto ad una pressione differenziale di 0.5 bar e lo chiude a 0.5 bar +
0.1 bar = 0.6 bar, corrispondente a pressione differenziale + differenziale meccanico.
Esempio 2
RT 262AL Pressione differenziale p = 0.5 bar. Zona morta Nz richiesta = 0.25 bar. Come si può rilevare dal diagramma di fig. 6., la zona morta richiesta, con valore 0.25 bar, viene ottenuta posizionando la ghiera di regolazione zona morta (40) su 2.5. Poichè il differenziale meccanico è di
0.1 bar le pressioni differenziali di apertura e chiusura dell’interruttore saranno le seguenti:
Pressione differenziale di chiusura dei contatti 1 – 4 = 0.5 bar + 0.1 bar = 0.6 bar. Pressione differenziale di apertura dei contatti 1 – 4 = 0.5 bar (= valore tarato, p). Pressione differenziale di chiusura dei contatti 1 – 2 = 0.6 bar – 0.25 bar = 0.35 bar. Pressione differenziale di apertura dei contatti 1 – 2 = 0.35 bar + 0.1 bar = 0.45 bar.
4 | 520H11632 | DKRCC.PI.CE0.B2.53