Installation Guide RSH
Oliepumpe type RSH
Tekniske data
Olietyper
Viskositetsområde:
- selvansugende
- med fødetryk
Omdrejningstal 1400 - 3450 min
Trykområde:
- med specialeder
Fabriksindstilling 21 bar (x 102 kPa)
Medietemperatur -10 til +120 °C
Max. føde- og returtryk 4 bar (x 102 kPa)
Tilslutninger (g. 1)
P = dysetilslutning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G ⁄
S = sugeledning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G ⁄
Fødetryksmåling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G ⁄
R = returledning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G ⁄
M = trykmåling⁄udluftning . . . . . . . . . . . . . . . . . . . . . . . . G ⁄
Bemærk!
Samtlige tilslutninger har anslået pakade beregnet for standardadepakninger. Type RSH leveres som 1-strengs pumpe med omløbet ”G” åbent (g. 4). Ved 2-strengs drift monteres den medleverede skrue ”A” i omløbet ”G” (g. 5). Pumperne er sel vansugende ved vis kositeter o p til 20 m m2/s. Ved højere visikositeter bør pumpen forsynes med positivt fødetryk. Ved 1-strengs drift med underliggende tank bør dyse­ledningen monteres i udluftningsporten ”M” og dyse­porten ”P” afblændes. Der skal her anvendes en afskæ­rings-/lukkeventil på dyseledningen.
Omdrejningsretning
Set fra akselenden har en højregående pumpe omdrej­ningsretning med uret, og en venstregående mod uret.
Udluftning
Ved 1-strengs anlæg udluftes pumpen ved 1-gangs opstart via udluftningsstudsen ”M” (g. 2). Ved 2-strengs anlæg udlufter pumpen automatisk gennem returledningen.
Trykindstilling
Fig. 3 viser trykindstilling af en RSH pumpe. Maks. tryk er afhængig af trykområde.
1-gangs opstart
Med let fyringsgasolie startes brænderen og pumpen justeres til det ønskede tryk. Med svær fyringsolie justeres til min. tryk. Pumpen drejes langsomt til der er varm olie fremme ved trykmålestudsen. Brænderen startes og pumpen justeres jævnt op til det ønskede drifttryk. Samme metode anvendes efter driftstop hvor olien er blevet helt eller delvis kold. Efter denne indjustering arbejder pumpen under normale driftsbetingelser.
Anlæg
Installationen skal forsynes med forlter efter gældende regler/praksis.
Medier
Pumpen er speciceret for drift med mineralske brænd­selsolier, henholdsvis medier med tilsvarende eller hø­jere klassikation.
Tilbehør
Til RSH-serien kan der leveres en løs ange incl. 4 skruer til montage på halsens anlægsade. Bestillingsnummer: 070-0211
Standard fyringsolie
og bio olie (FAME)
4,3 - 20 mm2/(cSt)
20 - 760 mm2/(cSt)
15 - 35 bar (x 102 kPa)
1 - 5 bar (x 102 kPa)
GB
Oil pump type RSH
Technical data
Oil types
Viscosity range:
- self-priming
- with feed pressure
-1
Speed 1400 - 3450 min
Pressure range:
- with special spring
Default settings 21 bar (x 102 kPa)
Temperature of medium -10 to +120 °C
Max. feed and return pressure 4 bar (x 102 kPa)
Connections (g. 1)
P = nozzle connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . G ⁄
S = suction connection . . . . . . . . . . . . . . . . . . . . . . . . . . . G ⁄
Feed pressure measurement. . . . . . . . . . . . . . . . . . . . . . G ⁄
R = return line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G ⁄
M = pressure measurement⁄bleed . . . . . . . . . . . . . . . . .G ⁄
Note!
All connection surfaces are spotfaced for standard gaskets. RSH is supplied as a 1-pipe pump with bypass “G” open (g. 4). For 2-pipe operation, screw “A” supplied must be tted in bypass “G” (g. 5). The pumps are self-priming for viscosities up to 20 mm2/s. For higher viscosities, the pump should be connected to positive feed pressure. For 1-pipe operation with underlying tank, the nozzle line should be connected to vent port “M”, with nozzle port “P” blanked o. In this case a shut-o valve must be installed in the nozzle line.
Direction of rotation
The direction of rotation of a righthand pump is clock­wise, a lefthand pump counterclockwise, when looking on the end of the shaft.
Venting
On 1-pipe operation the pump is vented on rst-time starting via vent port “M” (g. 2). On 2-pipe operation the pump is vented automatically through the return line.
Pressure settings
Fig. 3 shows the pressure setting of an RSH pump. Max. pressure is dependent on the pressure range.
First-time starting
With light fuel oil, the burner must be started and the pump adjusted to the required pressure. With heavy fuel oil the setting must be on minimum and the pump turned slowly, until hot oil appears at the pressure measurement connection. The burner can then be started and the pump adjusted evenly up to the required operating pressure. The same method must be used after an operational stop when the oil has become partially or completely cold. After this adjustment has been made the pump will run under normal operating conditions.
Installation
A prelter must be installed, in accordance with current rules/practice.
Media
The pump is specied for operation with mineral-based fuel oils, or media having a corresponding or higher classication.
Standard fuel gas oil
and bio oil (FAME)
4,3 - 20 mm2/(cSt)
20 - 760 mm2/(cSt)
15 - 35 bar (x 102 kPa)
1 - 5 bar (x 102 kPa)
Accessories
A separate ange with four screws for mounting on the neck of the pump can be supplied for the RSH series. Code no. 070-0211 The RSH can be used as a feed/transport pump after the pressure setting spring has been replaced. A replacement pressure setting spring with a range of 1-5 bar (x 102 kPa) together with a label giving the cor­rect pressure range are obtainable under code number 070-0030.
-1
DE
Ölpumpe Typ RSH
Technische Daten
Öltypen
Viskositätsbereich:
- selbstansaugend
- mit Speisedruck
Drehzahl 1400 - 3450 min
Druckbereich:
- mit Spezialfeder
Werkseinstellung 21 bar (x 102 kPa)
Medientemperatur -10 bis +70 °C
Max. Speise- und Rücklaufdruck
Anschluß (Fig. 1)
P = Düsenanschluß . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G ⁄
S = Saugleitung . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G ⁄
Speisedruckmessung . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G ⁄
R = Rücklaufleitung. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G ⁄
M = Druckmessung⁄Entlüftung . . . . . . . . . . . . . . . . . . . .G ⁄
Achtung!
Sämtliche Anschlüsse haben Dichtächen für Standard­Flachdichtungen. Typ RSH wird als 1-Strang-Pumpe mit oenem Umlauf “G” geliefert (Fig. 4). Bei 2-Strang-Betrieb ist die mitgelieferte Schraube “A” in den Umlauf “G” zu montieren (Fig. 5). Die Pumpen sind selbstansaugend bei Viskositäten bis 20 mm2/s. Bei höheren Viskositäten ist die Pumpe an positiven Speisedruck anzuschließen. Bei 1-Strang-Betrieb mit tieferliegendem Tank muß die Düsenleitung in die Entlüftungsönung “M” montiert und die Düsenönung “P” verschlossen werden. Hier muß ein Abschneide-/Schließventil an der Düsenlei­tung angewendet werden.
Drehrichtung
Auf das Wellenende gesehen, läuft eine rechtdrehende Pumpe im Uhrzeigersinn und eine linksdrehende gegen den Uhrzeigersinn.
Entlüftung
Bei 1-Strang-Anlagen ist die Pumpe bei der erstmaligen Inbetriebnahme durch den Entlüftungsstutzen “M” zu entlüften (Fig. 2). Bei 2-Strang-Anlagen entlüftet die Pumpe automatisch durch die Rücklaueitung.
Druckeinstellung
Fig. 3 zeigt die Druckeinstellung einer RSH-Pumpe. Der max. zulässige Druck ist vom Druckbereich abhängig.
Erstmalige Inbetriebnahme
Bei leichtem Heizöl Brenner einschalten und die Pumpe auf den gewünschten Druck einjustieren. Bei schwerem Heizöl auf min. Druck einjustieren. Pumpe langsam drehen, bis warmes Öl am Manometeranschluß austritt. Brenner einschalten und den gewünschten Betriebs­druck der Pumpe gleichmäßig einjustieren. Nach Be­triebsunterbrechungen mit abgekühltem oder kaltem
Standard Heizöl
und Bio Öl (FAME)
4,3 - 20 mm2/(cSt)
20 - 760 mm2/(cSt)
15 - 35 bar (x 102 kPa)
1 - 5 bar (x 102 kPa)
4 bar (x 102 kPa)
-1
07/2012 BIDFS352 Danfoss Heating Solutions