Danfoss RSH 32, RSH 63, RSH 95, RSH 125 Data sheet

Data sheet
Oil Pump Type RSH Size 32, 63, 95, 125
Application RSH oil pumps are designed for small/medium
sized domestic and commercial oil burners up to 285 l/h. The pumps have a built-in pressure regulator with shut-off function. A special regulation spring is available for feed/ transfer applications.
Function
Features
• Light and heavy oil
• 1 or 2-pipe operation
• 1-stage
• Built-in pressure regulator with shut-off
• Ring filter
• Special spring available for feed/transfer applications
Pressure Suction Return
From the suction inlet (S) oil is drawn through the gear set, where the pressure is increased. By means of the piston and the spring in the pressure regulator the pressure is kept constant at the value set on adjustment screw (P1). In 2-pipe systems the excess oil is led back to the return outlet (R). In 1-pipe systems with plugged return outlet (R) and removed by-pass screw (A), the oil is returned internally to the gear set (see figure). When the pump is stopped the pressure drops and the spring force in the pressure regulator will move the piston until it seats and the oil flow is shut off effectively.
Bleeding
In 2-pipe systems the pumps are self-priming, i.e. bleeding is performed via the constriction (O) to the return outlet (R).
In 1-pipe systems wi th plugged return outlet (R) and by-pass screw (A) removed, bleeding must be performed through the pressure gauge port (Pn). In 1-pipe systems with underlying tank, the closing function of the regulating valve must be rendered inoperative. This is made by connecting the nozzle line to the pressure gauge port (Pn) and plug the pressure port (P). In this application a cut-off valve must be installed in the nozzle line.
Warranty
For pumps used outside the stated technical data and used with oil containing abrasive particles Danfoss cannot give any warranty.
© Danfoss | 2019.03
BD.DA.P3.02 | 1
Data sheet Oil Pump Type RSH Size 32, 63, 95, 125
Identification Example:
RSH 63
Nozzle capacity at 20 cSt., 15 bar, 2800 min-1.
32 = Capacity 91 l/h 63 = Capacity 143 l/h 95 = Capacity 210 l/h 125 = Capacity 285 l/h
Technical data
RSH 32 63 95 125
Oil types Standard fuel gas oil, heavy oil and bio fuels Viscosity range (measured
in suction inlet)
4.3 - 200 cSt. (mm²/s)
Filter area / mesh 75 cm² / 340 μm 170 cm² / 340 μm Pressure range, stage 15-35 bar Factory setting 21 ±1 bar Max. pressure in suction
inlet/return outlet Speed 1400-3450 min
4 bar
-1
Max. starting torque 0.22 Nm 0.25 Nm 0.30 Nm 0.35 Nm Ambient temperature –20 to +120 °C Storage temperature –25 to +120 °C Temperature of medium –10 to +120 °C Neck / Flange EN 225
Nozzle capacity Operating torque Power consumption
2 | © Danfoss | 2019.03
BD.DA.P3.02