Data sheet
Oil Pump Type RSA Size 28, 40, 60, 95, 125
Application RSA oil pumps are designed for small/medium
sized domestic and commercial oil burners up to
255 l/h.
The pumps have a built-in pressure regulator
with shut-off function.
A special regulation spring is available for feed/
transfer applications.
Function
Features
• Light oil and Kerosene
• 1 or 2-pipe operation
• 1-stage
• Built-in pressure regulator with shut-off
• Ring filter
• Spec. spring available for feed/transfer
applications
Pressure Suction Return
From the suction inlet (S) oil is drawn through the
gear set, where the pressure is increased. By
means of the piston and the spring in the pressure
regulator the pressure is kept constant at the value
set on adjustment screw (P1).
In 2-pipe systems the excess oil is led back to the
return outlet (R). In 1-pipe systems with plugged
return outlet (R) and removed by-pass screw (A),
the oil is returned internally to the gear set (see
figure).
When the pump is stopped the pressure drops
and the spring force in the pressure regulator will
move the piston until it seats and the oil flow is
shut off effectively.
Bleeding
In 2-pipe systems the pumps are self-priming, i.e.
bleeding is performed via the constriction (O) to
the return outlet (R).
In 1-pipe systems wi th plugged return outlet (R) and
by-pass screw (A) removed, bleeding must be
performed through the pressure gauge port (Pn).
In 1-pipe systems with underlying tank, the closing
function of the regulating valve must be rendered
inoperative. This is made by connecting the nozzle
line to the pressure gauge port (Pn) and plug the
pressure port (P). In this application a cut-off valve
must be installed in the nozzle line.
Warranty
For pumps used outside the stated technical data
and used with oil containing abrasive particles
Danfoss cannot give any warranty.
© Danfoss | 2020.08
AI055186452291en-000305 | 1
Data sheet Oil Pump Type RSA Size 28, 40, 60, 95, 125
Identification Example:
RSA 60
Nozzle capacity at 4.3 cSt., 10 bar, 2800 min-1.
28 = Capacity 46 l/h
40 = Capacity 75 l/h
60 = Capacity 120 l/h
95 = Capacity 184 l/h
125 = Capacity 255 l/h
Technical data
RSA 28 40 60 95 125
Oil types Kerosene, standard fuel gas oil and bio fuels
Viscosity range (measured
in suction inlet)
1.3 - 75 cSt. (mm²/s)
Filter area / mesh 75 cm² / 150 μm 170 cm² / 150 μm
Pressure range, stage 5.5-15 bar 5.5-21 bar
Factory setting 7 ±1 bar 10 ±1 bar
Max. pressure in suction
inlet/return outlet
Speed
2400-3450
-1
min
4 bar
1400-3450 min
-1
Max. starting torque 0.20 Nm 0.22 Nm 0.24 Nm 0.30 Nm 0.35 Nm
Ambient temperature –20 to +120 °C
Storage temperature –25 to +120 °C
Temperature of medium –10 to +120 °C
Neck / Flange EN 225
Nozzle capacity Operating torque Power consumption
2 | © Danfoss | 2020.08
AI055186452291en-000305