Danfoss RLV-S/HC Data sheet

Data Sheet
Valve Body Type RA-FN/HC, Lock Shield Valve Type RLV-S/HC
Application
RA-FN/HC Angle RA-FN/HC Reversed angle (UK)
RA-FN/HC:
All RA-FN/HC valve bodies can be used together with all types of thermostatic elements with RA connection. The valve body RA-FN/HC is used in two-pipe heating systems. The valve bodies are supplied with a protective cap which can be used for manual regulation during the construction phase. The protective cap must not be used as a manual shut off device. A special manual shut off device (code no. 013G5002) should be used. To be able to distinguish between other valve bodies of the RA 2000 series the RA-FN/HC pro­tective cap is grey. RA-FN/HC has connection for 12 mm hydro cable both axial and radial compression fittings are available. RA-FN/HC are also available with 1/2” conection. Valve bodies are manufactured from brass with nickel plating. The pressure pin of the gland seal is of chrominium steel and works in a lifetime lu­bricated O-ring. The complete gland assem­bly(stuffing box) can be replaced without drain­ing down the system. Should water treatment be used it is essential that dosing instructions of the manufacturer are strictly observed. It is recommended that formu­lations containing mineral oil are avoided.
RLV-S/HC:
By means of a lockshield valve, type RLV-S/HC, every radiator can be shut off individually to al­low trouble-free maintenance or repair without affecting other radiators in the system. RLV-S/HC is intended for mounting on the outlet of the radiator. RLV-S/HC lockshield valves are available in angle version. RLV-S/HC has connection for 12 mm hy­dro cable both axial and radial compression fit­tings are available. RLV-S/HC are also available with 1/2” conection.
kvs-value RLV-S/HC 15 = 1.26 m³/h
Factory setting is fully open valve. Dimensions correspond to DIN 3842-1.
In order to avoid deposition and corrosion the composition of the hot water must be in accord­ance with the VDI 2035 guideline (Verein Deutscher Ingenieure).
Principles
Danfoss Heating Solutions VDSXD302 © Danfoss 02/2013 1
Data Sheet Valve Body Type RA-FN/HC, Lock Shield Valve Type RLV-S/HC
Closing/Opening RLV-S
Data and Ordering
Close the valve by means of an 8 mm allen key (turn allen key right).
Open RLV-S with 4 turns and the valve will be fully open (turn allen key left).
kv-value (RA-FN/HC)1) (m³/h at 1 bar
Pat­tern
Type RA-
FN 15/
RLV-S 15
Code No.
pressure drop) P-band = K
0.5K 1.0K 1.5K
C/C 33/45, Axial press
013G3190 0.13 0.26 0.38 0.49 0.94 10 0.6 16 90
fit
C/C 33/45,
Radial
013G3191 0.13 0.26 0.38 0.49 0.94 10 0.6 16 90
press fit
C/C 75,
An-
gle
Axial press
fit
013G3192 0.13 0.26 0.38 0.49 0.94 10 0.6 16 90
C/C 75, Ra-
dial press
013G3189 0.13 0.26 0.38 0.49 0.94 10 0.6 16 90
fit
C/C 75,
1/2”
013G3200 0.13 0.26 0.38 0.49 0.94 10 0.6 16 90
thread
C/C 50/45,
Axial press
013G3195 0.14 0.27 0.39 0.49 0.71 10 0.6 16 90
fit
C/C 50/45,
Radial
013G3196 0.14 0.27 0.39 0.49 0.71 10 0.6 16 90
press fit
C/C 75,
UK
Axial press
013G3197 0.14 0.27 0.39 0.49 0.71 10 0.6 16 90
fit
C/C 75, Ra-
dial press
013G3198 0.14 0.27 0.39 0.49 0.71 10 0.6 16 90
fit
C/C 75,
1/2”
013G3199 0.14 0.27 0.39 0.49 0.71 10 0.6 16 90
thread
Kv,
2.0K
K
vs
Fully
open
Test
Max.
Work-
ing
temp.
°C
Max. pressure
3)
Work-
ing (bar)
Diff.
2)
(bar)
(bar)
1)
The kv-value indicates the water flow (Q) in m³/h at a pressure drop (∆p) across the valve of 1 bar;
. The kv-value is stated according to EN 215, at XP = 2K i.e. the valve is closed at 2°C higher room
temperature. At lower settings the XP value is reduced to 0.5K. The kvs-value states the flow Q at a maxi­mum lift, i.e. at fully open valve.
2)
Working pressure = static + differential pressure. The maximum differential pressure specified is the maximum pressure at which the valves give satisfactory regulation. As with any device which imposes a pressure drop in the system, noise may occur under certain flow/pressure conditions. To ensure quiet operation, maximum pressure drop should not exceed 30 to 35 kPa. The differential pressure can be reduced by the use of the Danfoss differential pressure regulators.
3)
Note: The Kvs-value for RLV-S/HC is 1,26m³/h.
2 VDSXD302 © Danfoss 02/2013 Danfoss Heating Solutions
Data Sheet Valve Body Type RA-FN/HC, Lock Shield Valve Type RLV-S/HC
Capacities
Construction
Note: As with any device which imposes a pressure drop in the system, noise may occur under cer­tain flow/pressure conditions.
RA-FN/HC
To ensure quiet operation, maximum pressure drop should not exceed 30-35 kPa (3-3,5 mwg).
1. Gland seal
2. O-Ring
3. Pressure pin
4. Seal
5. Regulation spring
6. Elbow
7. Valve body
8. Union nut
9. Tail piece
10. Fitting
Danfoss Heating Solutions VDSXD302 © Danfoss 02/2013 3
Loading...
+ 5 hidden pages