Danfoss RLV-KDV Data sheet

Data Sheet
RLV-KDV H-Piece for valve radiators - blockable and
drainable, with integrated differential pressure control
Application
System
RLV-KDV is a Dynamic H-piece designed for radiators with integrated valves (valve radiators)
integrated valve and working on optimal
conditions in full and partial demand. in 2-pipe systems. RLV-KDV combines the following functions:
• Integrated differential pressure controller using membrane technology.
This results in lowered return temperature,
energy saving and preventing claims due to noise
in the radiator.
• Constant pressure over the radiator and valve in full and partial load.
• Self-balancing to optimal pressure conditions once the flow presetting on the integrated radiator-valve is done.
Self sealing connection pieces ensure that
RLV-KDV can be used both for radiators
with an internal thread of G ½ and with an
external thread of G ¾ A.
• Lockshield on supply and return.
• Filling and draining possibility (with fill and drain tap 003L0152).
• Self sealing connection pieces to the radiator for G ½ internal thread and G ¾ external thread.
The flow adjustment presetting is done on the radiator valve. As a result the heating system is self balancing to the preset volume in the
A fill and drain tap is available as an accessory.
Connection to copper, soft steel, PEX and Alupex
pipes is made with Danfoss compression fittings.
See separate datasheet.
In order to avoid deposition and corrosion, the
composition of the hot water should be in
accordance with the VDI 2035 guideline
(Verein Deutscher Ingenieure).
Two-pipe system with valve radiators, typical connection types.
RLV-KD V Straight Left
RLV-KD V Straight Right
RLV-KD V angle Right
RLV-KD V angle Left
Ordering and data
Type Version
Straight R & L
RLV-KDV with constant differential pressure control
Angle Right
Angle Left
Straight R & L
Angle Right
Angle Left
Connection
Radiator System
G ½ G ¾ A
G ¾ G ¾ A
© Danfoss Climate Solutions | 2021.06 | AI325141533218en-000102
Max.
operation
pressure
10 bar 16 bar 95 ˚C
Test
pressure
Max. water temp.
p min/p max
0.15 bar /
0.60 bar
Code no.
013G7870
013G7871
013G7872
013G7873
013G7874
013G7875
1
Data Sheet RLV-KDV H-Piece for valve radiators with integrated differential pressure control
Capacities
RA-N
Presetting 1 2 3 4 5 6 7 N
No Sensor Max. (l/h) 43 55 71 85 117 139 148 159
Gas Sensor
Liquid Sensor
* kv-value used for presetting of non-Danfoss integrated valves in radiators
Xp1 35 50 65 75 95 105 115 125
Xp2 35 50 65 75 110 120 135 150
Valve-kv* 0.088 0.131 0.163 0.200 0.288 0.369 0.456 0.544
Xp1 28 40 50 55 70 75 80 85
Xp2 35 50 65 75 95 105 120 130
(Capacities comply to all radiators inside a -+ 10% span depending on the radiator type and size.)
2
© Danfoss Climate Solutions | 2021.06 | AI325141533218en-000102
Data Sheet RLV-KDV H-Piece for valve radiators with integrated differential pressure control
10
100
0.05
0.5
L/hr
Bar
Prese tting N
Presetting 2
Presetting 3
Presetting 4
Presetting 5
Presetting 6
Presetting 7
Presetting
1
50
120
80
40
0,10 0,350,300,250,200,15
0,450,40 0,6
70
90
60
30
20
Capacities
RA-U
Presetting 1 2 3 4 5 6 7 N
No Sensor Max. (l/h) 16 16 21 35 40 50 70 110
Gas Sensor
Liquid Sensor
* kv-value used for presetting of non-Danfoss integrated valves in radiators
Xp1 12 14 16 25 30 40 60 80
Xp2 12 14 16 25 35 45 65 100
Valve-Kv* 0.025 0.031 0.044 0.056 0.081 0.113 0.150 0.213
Xp1 10 12 14 20 25 30 45 60
Xp2 10 12 14 20 30 40 60 80
Presetting the Built-in valve
(Capacities comply to all radiators inside a -+ 10% span depending on the radiator type and size.)
New setup with Danfoss Built-in-valve:
1
When installing the Danfoss Dynamic H-Piece, then after finding the l/h needed for the radiator, go into the graph for the valve type (N or U) and pre-set the Built-in-valve according to the graph.
Replacing old H-Piece with Dynamic H-Piece, using Danfoss Built-in-valve:
When replacing the H-Piece, first identify the Built-in-valve type mounted on radiator (N or U). This is done
2
according to the Danfoss Valve Marking (see below). Hereafter, find the required l/h and use graph of the Built-in-valve type above to find the pre-setting of the Built-in-valve.
Build-in valves from other manufacturers:
When mounting on radiator with Built-in-valve from other manufacturer, then first find the required l/h
3
needed for the radiator. Thereafter, look in the graph above to find the danfoss pre-setting. Then, use Capacity table to find the kv-valvue for the found pre-setting. Use this kv-value to pre-set the Built-in-valve with the help from manufactures data.
© Danfoss Climate Solutions | 2021.06 | AI325141533218en-000102
3
Data Sheet RLV-KDV H-Piece for valve radiators with integrated differential pressure control
Danfoss valve marking
Draining the radiator
1 2
Valve Type
RA-N
RA-U
Marking
NA, ND, NI, NJ, NK, NE, NM, NL, NO, NG
UA, UD, UI, UJ, UK, UO
To drain the radiator, first unscrew the cover caps. Then shut off the inlet and return flow.
Accessories
© Danfoss Climate Solutions | 2021.06 | AI325141533218en-000102
4
Product Code no.
Fill and drain tap without nickel plating, with ¾” external thread and hose nozzle 003L0152
Adapter including seal for valve radiator with G¾ A external thread 003L0294
Self-sealing connection nipple for valve radiator with G½ internal thread 003L0295
RLV Cover caps Ø25, M22, Nickle 003L0103
When the drain tap has been mounted (1), open by turning the Allen key (2).
Data Sheet RLV-KDV H-Piece for valve radiators with integrated differential pressure control
Design
1. Valve radiator
2. Integrated valve
3. Self-sealing adapter DN20
4. Seal
5. Shut-off inlet
6. Shut-off outlet
7. Draining facility, outlet
8. Self-sealing adapter DN15
2
1
9. DeltaP Regulator
1
8
3
4
5
7
6
9
Materials in contact with water
Valve body and other brass parts MS58
Spring SS EN 10270-3
Membrane EPDM
O-rings EPDM/NBR
Valve plate NBR
Washer CW452K
Seal EPDM
5
© Danfoss Climate Solutions | 2021.06 | AI325141533218en-000102
Data Sheet RLV-KDV H-Piece for valve radiators with integrated differential pressure control
29
70
81
50
41
52
34
50
41
52
34
50
29
32
40
50
50
32
40
34
50
34
32
40
G1/2"
G3/4"
G1/2"
G3/4"
G1/2"
G3/4"
G3/4"
G3/4"
G3/4"
G3/4"
013G7870
013G7871
013G7872
013G7873
013G7874
013G7875
G3/4"
G3/4"
50
50
50
50
50
50
Dimensions
Radiator Connection
Version Code no.
Straight Supply­line
013G7870
Right & Left
Angle
Supply­line
013G7871
Right
Angle Supply­line Left
013G7872
Straight
Supply­line Right & Left
Angle Supply­line Right
Angle Supply­line Left
Fill and drain tap
013G7874
013G7875
013G7873
003L0152
Danfoss A/S
Heating Segment, Salg Danmark varme.danfoss.dk +45 6991 8080 E-Mail: kundeservice.dk@danfoss.com
Danfoss påtager sig intet ansvar for mulige fejl i kataloger, brochurer og andet trykt materiale. Danfoss forbeholder sig ret til uden forudgående varsel at foretage ændringer i sine produkter, herunder i produkter, som allerede er i ordre, såfremt dette kan ske uden at ændre allerede aftalte specikationer. Alle varemærker i dette materiale tilhører de respektive virksomheder. Danfoss og alle Danfoss logoer er varemærker tilhørende Danfoss A/S. Alle rettigheder forbeholdes.
© Danfoss Climate Solutions | 2021.06 | AI325141533218en-000102
6