Danfoss RLV-K Data sheet

Data sheet H-piece valves type RLV-K
for valve radiators
- with adjustable radiator share for one-pipe and two-pipe systems
- blockable and drainable
RLV-K straight, radiator connection G ½ and G ¾ A
Application
System
RLV-K angle, radiator connection G ½ and G ¾ A
By means of the H-piece valve type RLV-K, every valve radiator with a centre distance between the connections of 50 mm can be blocked individually, e.g. in order to carry out trouble-free maintenance without affecting other parts of the system.
H-piece valve type RLV-K is nickel plated and is available in straight and angle versions. Special adapters ensure that the H-piece valve can be used both for radiators with an internal thread of G ½ and with an external thread of G ¾ A. All adapters are self-sealing.
RLV-K can be shifted from two-pipe to one­pipe operation. The factory setting is for two­pipe operation.
Two-pipe system
Fill and drain tap
In one-pipe operation, the water flow to the radiator can be set infinitely variably. The shift to one-pipe operation is simply done by turn­ing the bypass spindle.
A fill and drain tap is available as an acces­sory to RLV-K. The fill and drain tap is only available without nickel plating.
Connection to copper, soft steel, PEX and Alupex pipes is made with Danfoss compres­sion fittings. See separate datasheet.
In order to avoid deposition and corrosion, the composition of the hot water should be in accordance with the VDI 2035 guideline (Verein Deutscher Ingenieure).
One-pipe system
Ordering and data
Type Version Code no.
Angle 003L0282
RLV-K
CD-ST VD.33.W1.02 © Danfoss 08/99
Straight 003L0280
Angle 003L0283
Straight 003L0281
Connection
Radiator System
G 1/2 A G 3/4 A
G 3/4 G 3/4 A
Max.
operation
pressure
10 bar
Test
pressure
16 bar
Max.
water
temperature
120 °C
Data sheet
H-pieces type RLV-K for valve radiators
Accessories
Capacity
Product Code no.
Fill and drain tap without nickel plating, with ¾" external thread and hose nozzle
1)
Adapter
incl. seal for valve radiator with G ¾ A
external thread
Self-sealing connection nippel with G ½ internal thread
Convection brake
1)
for one-pipe systems
1)
for valve radiator
RLV-K is suitable for connecting copper, soft
1)
Packing size = 20 pcs.
003L0152
003L0294
003L0295
003L0296
steel or plastic pipes. Use Danfoss compres­sion fittings.
kv-value (m3/h)
Radiator share 100%2)50% 35% 30% 25% 20%
RLV-K kvs-value 1.4 1.8 2.0
RLV-K with RA-N integrated valve
RLV-K set to 35% k
with RA-N integrated valve
1)
Radiator flow in accordance with the setting of the bypass regulation with radiator and Danfoss inte­grated valve, type RA-N.
2)
Factory setting = two-pipe operation.
3)
The kv-values give the flow volume (Q) in m3/ through the RLV-K union in combination with a Danfoss built-in valve with k
= 0.87 m3/h at Xp = 2 K.
v
1)
1)
3)
kv-value
-value 1.4 1.3 1.2
v
Presetting value N N N 6 5 4
0.7 1.2 1.5
Setting of bypass regula­tion in one-pipe operation
The factory setting RLV-K is for two-pipe op­eration. This means that the integral bypass regulation is turned off.
Shifting to one-pipe operation is made by opening the bypass spindle. The radiator share (flow) can be adjusted infinitely variably.
The connection between flow and number of
can be seen from the diagram next to
turns this text (at setting "N" of the Danfoss inte­grated valve and at Xp = 2 K).
Draining of the radiator To drain the radiator, first unscrew the cover
caps. Then shut-off the inlet and return flow. When the drain tap has been mounted, open it by turning the square (see ill.).
The accompanying hose nozzle can revolve in any direction.
%
Radiator share in %
Number of turns of the bypass spindle
CD-ST VD.33.W1.02 © Danfoss 08/99 2