Data sheet
RESD Series Thermostat
Description
RESD series thermostat adopts button-hidden fashion appearance design. It is used to control temperature for industry, commercial and residential. Models are available for heating, cooling, ventilating control. The application is Fan Coil control.
RESD series thermostats are with microprocessor and big LCD display included working state (cooling, heating, ventilating), fan speed, ambient temperature, setting temperature
etc. pushbutton includes turn on/off ( ), mode (), clock (), fan speed (
) and temperature adjustment ().
Shell is Fire retardant PC ABS, as figure 86×86 mm, thicker 13 mm.
Model denominations
RESD -
HC2: Control Motorized Valve and 3-speed fan. When the temperature reaches the setpoint, it will close the Motorized Valve and Fan both.
HC4: Control 4 pipe fan coil units, Control two Motorized Valves and 3-speed fan. When the temperature reaches the set-point, it will close the Motorized Valve and Fan both.
Basic features
•Room temperature setting
•Manual or Auto 3-speed changeover
•Defrost (low temperature protection)
•Clock, Timer, 7 days programmable (-T74)
•Blue backlight
•Auto Restart ( Option )
•Keypad Lock ( Option )
Status display
•Working Status: Cool ,
Heat , Ventilation
•Fan Speeds: Low , Medium
, High
and Auto
•Room temperature display
•Temperature setting display
•FCU valve
•Clock week display
Ordering |
|
|
|
|
|
|
|
Type |
Application |
Pipe system |
Control mode to |
Fan running mode |
Code No. |
||
|
|||||||
|
zone valve |
||||||
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
RESD HC 2 |
Heating/Cooling |
2 pipe system |
On / off |
Auto / Manual |
193B0913 |
|
|
|
|
|
|
|
|
|
|
RESD HC 4 |
Heating / Cooling |
4 pipe system |
On / off |
Auto / Manual |
193B0914 |
|
|
|
|
|
|
|
|
DH-SMT/SI |
Vx.xx.xx.xx © Danfoss 09/2010 |
1 |
Data sheet |
RESD Series Thermostat |
|
|
Technical data
Sensing element |
NTC |
Accuracy |
Temperature ± 1 °C, time ± 1min./month |
Set-point range |
5-35 °C |
Display range |
0-55 °C |
Operation environment |
Tmin 0 °C, Tmax 45 °C |
Power supply |
85-260 V~, 50/60 Hz |
Switch current rating |
Resistive 2 A, inductive 1 A |
Switching action |
Type 1B |
Control pollution |
Degree 2 |
Rated impulse V |
2.5 kV |
Ball hardness |
75 °C |
Power reserve |
24 hours minimum |
Setting accuracy |
± 0.5 °C, ±1 min. |
Rated power |
< 1 W |
Wiring |
Screw-in terminals, each terminal capable of accepting 2 × 1.5 mm2 wires |
Housing |
PC + ABS flame retardant |
Dimensions |
86 × 86 × 13 mm (W × H × D) |
Hole pitch |
60 mm (standard) |
Protection class |
IP30 |
Disply |
LCD |
Operation |
• On/Off: Press “ ” to turn on, press “ ” again |
|
|
|
to turn off thermostat and its output. |
•Setting temperature: press “” to reduce temperature, press “” to raise temperature (0.5 °C changed each press) set point
only valid in current period of time; Clock adjustment, turn on/off or 7 days
programming modification, it will perform
new settings.
Note:
When 4 periods function On, press “” or ”” to adjust current set-point, “Override” will show on LCD, it denote the thermostat will run as per current setting instead of 4 periods setting.
•Mode Selection: Press “” to change system working in cooling “
”, heating “
” or ventilation “
” mode, the related icon will flash, and it will be confirmed automatically after 6 seconds.
•Fan speed select: Press “” to select “
(Hi),
(Med),
(Low),
(Auto)”.
In mode “ (Auto)”, the fan-speed changed automatically. Auto LOW-speed when the difference between room-temperature and setting-temperature exceed 1 °C, Auto MEDspeed when exceed 2 °C, Auto HI-speed when exceed 3 °C.
Clock calibration |
• Clock calibration: Press “” till to display |
|
“hh:mm” and “hh” flash, press “” or “” to |
|
adjust hour, press “”, “mm” flash, press “” or |
|
“” to adjust minute; Press “”, “week” flash, |
|
press “” or “” to adjust Mon to Sun. |
Timer ON and timer OFF |
• Timer on: Press “”, till to display “” and |
|
“ON” and all flash, and also “hh” flash, press |
|
“” or “” to adjust hour. Press “”, “mm” |
|
flash, press “” or “” to adjust minute. |
|
• Timer off: Press “”, till to display “” and |
|
“OFF” and all flash, and also “hh” flash, press |
|
“” or “” to adjust hour. Press “”, “mm” |
|
flash, press “” or “” to adjust minute. |
•Canceling timer on: Press “”, till to display “” and “ON” and all flash, and also “hh” flash, press “” or “” to adjust hour to “--:--”. Press “”, “mm” flash, press “” or “” to adjust minute to “--:--”.
•Canceling timer off: Press “”, till to display “” and “OFF” and all flash, and also “hh” flash, press “” or “” to adjust hour to “--:- -”. Press “”, “mm” flash, press “” or “” to adjust minute to “--:--”.
2 |
Vx.xx.xx.xx © Danfoss 09/2010 |
DH-SMT/SI |