Danfoss REPI-2, REPI-2N, REPI-4N, REPI-4 Data sheet

REPI Series Digital Thermostat Manual
REPI series thermostats are used to control room temperature in industrial, commercial
and residential environment via controlling electric modulating valve with 0-10VDC (4-20mA)
control signal or floating control as well as damper actuator of VAV system.
Electronic control technology is adopted, with green backlit LCD display of: working mode
(cooling “
auto “
changeover “ ”; fan speed choose “ ” and temperature adjustment “ ” and “ ”.
”); room temperature; setting temperature etc. push button: On/Off “ ”; mode
Shell: PC + ABS retardant material.
Function :
Detect and Display room temperature
Room temperature setting
Fahrenheit or Celsius degree display
Timing sleep
Control On/Off of cooling and heating equipment
Selectable single speed or three speed fan control
Order Guide:
Model
Floating Modulation
REPI-2 Cooling/Heating REPI-2N Cooling/Heating REPI-4 Cooling&Heating REPI-4N Cooling&Heating
Fan: thermostat with fan functions, can be selected with single speed fan or three speed fan by setting parameter.
Remote Control: input signal can be selected by setting parameter.
Output signal
Fan
(Single/3-speed)
RS485
Network
Input
Control
Remote
Sensor
Specification :
Set temperature range: 0 - 99.5 adjustable
Accuracy displayed:
Accuracy: ±0.5
Rated Power: < 1 W
Sensor type:
Display:
LCD
0.1
NTC
Power:
Output signal:
Input signal: dry contact (NO)
Dimensions: 86×86×23mm (W×H×D)
Fixing screw width : 60mm (Standard)
AC 24V±10%, 50Hz/60Hz
AC 24V×2 (0.5A resistive) ,
0 - 10VDC(5mA) / 4 - 20mA (600Ω)
Operations:
" On/Off: Press “ ” buttons to turn on; press “ ” again to turn off.
" Setpoint: With thermostat on, press “
0.5, the setpoint will be confirmed automatically after 5 seconds, and then return to dispay status, press “ ” or “ ” to
check setpoint.
" Mode: With thermostat on, press “
( Auto is available REPI-4/ REPI-4N).
" Fan Speed: With thermostat on, press “
”, auto “ ”. If single speed fan available, there’s only med speed “ ”.
Under auto speed fan, the fan speed will be changed automatically as below: in low speed when room temperature
is 1 difference with setpoint;in med speed when room temperature is 2 difference with setpoint ; in High speed when
room temperature is 3 difference with setpoint.
" Sleep: Thermostat will get into sleep function after programming.The set Temperature should to be.
” to reduce the setpoint, press “ ” to increase the setpoint, the setpoint step is
” to change the working mode – Cooling “ Heating “ ”, Vent " ", Auto “
” to select the desired speed – low speed “ ”, Med speed “ ”, High speed
Page 1 of 3
To set:Press “ ” button for 3 seconds till “ ” display, there’s a number of count down in the center of LCD, Use “ ” or
” to adjust the desired sleep time: the max. = 48 hours; thermostat will return to the working status after 5
seconds, “ ” is flashing to start counting down. The setpoint should be replaced by the sleep setpoint.
To quit: When thermostat get into Sleep function, “
" Keypad lock: press “ ” and “ ” for 10 seconds till to “ ” display to activate, under this function, any keypad is locked.
Press “ ” and “ ” for 10 seconds till “ ” disappear to quit the function.
" Set Parameters: With thermostat off, press “
” will flash, press “ ” or “ ” to quit.
” for 10 seconds to enter menu to set the parameters.
Parameter table
Paramete Description Default Range Step
1 Power on status (0: Off; 1: On; 2: Hold) 2 0 - 2
2 Fan speed (0: Single Speed; 1: Three Speed) 1 0 - 1
3 Fan mode (DA; DB) 0
4 Sensor selection (0: Internal; 1: Remote) 1 0 - 1
5 Temperature format (0: Celsius; 1: Fahrenheit) 0 0 - 1 0.1
6 Temperature calibration 0 -20.0 -20.0 0.1
7 Minimum setpoint 5℃/41℉ 0 - 99.5 0.5
8 Maximum setpoint 35/96 0 - 99.5 0.5
9 Dead band (REPI-4) 2 0 - 10 0.5
10 Heating & Auto sleep setpoint 7℃/45℉ 0 - 99.5 0.5
11 Cooling sleep setpoint 28/82 0 - 99.5 0.5
12 Comms# (REPI-2N;REPI-4N) 1 1 - 32 1
Input Signal Mode
0: Invalid
13
1: Changeover(REPI-2)
2: thermostat will be sleep without input signal
3: thermostat will be Off without input signal
0 0 - 3
14 Heating reset time 90 sec. 10 - 300 sec. 10 sec.
15 Cooling reset time 90 sec. 10 - 300 sec. 10 sec.
16 Ports mode (0: Modulation & Floating; 1: On/Off) 0 0 - 1
17 Valve status as turn off (0: Close; 1:Hold; 2: Open ) 0 0 - 2
18 Port1 Modulation direction(0:10V Open; 1:10V Close) 0 0 - 1
19 Port1 Modulation minimum signal 0Bit 0-128Bit(5V/10mA) 0.04V/Bit(0.08mA/Bit)
20 Port1 Modulation proportional 2 1 - 20 0.5
21 Port2 Modulation direction(0:10V Open;1:10V Close) 0 0 - 1
22 Port2 Modulation minimum Signal 0 Bit 0-128Bit(5V/10mA) 0.04V/Bit(0.08mA/Bit)
23 Port2 Modulation proportional 2 1 - 20 0.5
24 Port1 Floating minimum time 1 sec. 1 - 9 sec. 1 sec.
25 Port1 Floating maximum time 30 sec. 10 - 300 sec. 10 sec.
26 Port1 Floating minimum time 1 sec. 1-9 sec. 1 sec.
27 Port1 Floating maximum time 30 sec. 10 - 300 sec. 10 sec.
28
29
30
Disable / Enable bypass PID control
( 0: Disable; 1: Enable )
Override output value when bypass PID control
Display output value when enable PID control
Override output value when bypass PID control
Display output value when enable PID control
0 0 - 1
0 - 255
0 - 255
Page 2 of 3