Danfoss SVA-S, SVA-L, SCA-X, CHV-X, FIA Data sheet

...
Data Sheet
Strainer housing Type FIA
Design makes the strainer easy to install
FIA strainers are a range of angleway and straightway strainers, which are carefully designed to give favourable ow conditions. The design makes the strainer easy to install, and ensures quick strainer inspection and cleaning.
FIA strainers are used ahead of automatic controls, pumps, compressors etc., for initial plant start-up and where permanent ltration of the refrigerant is required. The strainer reduces the risk of undesirable system breakdowns and reduces wear and tear on plant components.
FIA strainers are equipped with a screen mesh of stainless steel, available in sizes 100, 150, 250 and 500μ (microns), (US 150, 100, 72, 38*).
* Mesh is the number of threads per inch. μ (microns) is the distance between two threads (1μ = 1/1000 mm).
AI365917233048en-00101
Strainer housing, Type FIA
Features
• Modular Concept:
Each valve housing is available with buttweld F connection and with several dierent sizes.Possible to convert FIA strainers to any other product in the SVL family (Shut-o valve, regulating valve, check &
stop valve or check valve) just by replacing the complete top part.
• Fast and easy overhaul service. It is easy to replace the top part and no welding is needed.
• Filter net of stainless steel mounted direct without extra gaskets means easy servicing.
• Two types of strainer inserts are available:
A plain insert of stainless steel.A pleated insert (DN 15-200) with extra large surface, which ensures long intervals between cleaning and low
pressure drop.
• FIA 15-40 (½ – 1 ½ in.): A special insert (50μ) can be used in combination with a standard version when cleaning a plant during commissioning.
• FIA 50-200 (2 - 8 in.): A large capacity lter bag (50μ) can be inserted for cleaning plant during commissioning.
• FIA 65-200 (2½ - 8 in.) can be equipped with a magnetic insert for detention of iron particles and other magnetic particles.
• Each strainer clearly marked with type, size and performance range.
• Housing and bonnet of low temperature steel in accordance with the requirements of the Pressure Equipment Directive and those of other international classication authorities.
Classication: DNV, CRN, BV, EAC etc. To get an updated list of certication on the products please contact your local Danfoss Sales Company.
© Danfoss | Climate Solutions | 2021.03 AI365917233048en-00101 | 2
Strainer housing, Type FIA
Media
Refrigerants
Applicable to HCFC, HFC, R717 (Ammonia) and R744 (CO2). For further information refer to the product instruction for FIA.
New refrigerants
Danfoss products are continually evaluated for use with new refrigerants depending on market requirements.
When a refrigerant is approved for use by Danfoss, it is added to the relevant portfolio, and the R number of the refrigerant (e.g. R513A) will be added to the technical data of the code number. Therefore, products for specic refrigerants are best checked at store.danfoss.com/en/, or by contacting your local Danfoss representative.
© Danfoss | Climate Solutions | 2021.03 AI365917233048en-00101 | 3
Features
Description
Temperature range
-60 °C/+150 °C (-76 °F/+302 °F).
Max. working pressure
52 bar(g) (754 psig) for DN15 to DN 125
25 bar(g) (362 psig) for DN 150 to DN 200
20
23
26
29
32
35
38
41
44
47
50
53
-60 -30 0 30 60 90 120 150
DN 15 to DN 50 + DN 80
DN 65 to DN 100
DN 125
DN 150
DN 200
Temperature [°C]
Pressure / Temperature range
Pressure [bar]
Strainer housing, Type FIA
Product specication
Pressure and temperature data
Table 1: Pressure and temperature data
For more detail on pressure and temperature range; see Table 2: Pressure/Temperature range chart for SVL product
range with butt-weld connection F
Figure 1: Pressure/Temperature range chart for SVL product range with butt-weld connection F
For valve sizes DN 15 to DN 50 and DN 80:
52 bar(g) (754 psig) at -60 °C to +150 °C (-76 °F to +302 °F).
For valve sizes DN 65 and DN100:
52 bar(g) (754 psig) at -60 °C to +100 °C (-76 °FF to +212 °F), 45 bar(g) (652 psig) at +100 °C to +150 °C (+212 °F to +302 °F).
For valve size DN 125:
52 bar(g) (754 psig) at -40 °C to +50 °C (-40 °F to +122 °F) 43 bar(g) (623 psig) at -60 °C to -40 °C (- 76 °F to -40 °F), 42 bar(g) (609 psig) at +50 °C to +100 °C (+122 °F to +212 °F), 36 bar(g) (522 psig) at +100 °C to+150 °C (+212 °F to +302 °F).
For valve size DN 150:
25 bar(g) (362 psig) at -60 °C to +150 °C (-76 °F to +302 °F).
For valve size DN 200:
25 bar(g) (362 psig) at -60 °C to +100 °C (-76 °F to +212 °F), 23 bar(g) (333 psig) at +100 °C to +150 °C (+212 °F to +302 °F).
SVL housings with other connection types (DIN, ANSI, SOC and thread) are approved for a maximum working pressure of 52 bar(g) (754 psig) at –60 °C to +150 °C (–76 °F to +302 °F) for all sizes.
The reduced pressure in some of the SVL housings with connection type F is caused by the welding onto stainless steel pipes with reduced pipe size.
© Danfoss | Climate Solutions | 2021.03 AI365917233048en-00101 | 4
Size
[DN]
SVA-S
SVA-L
SCA-X
CHV-X
FIA
REG-SA
REG-SB
ANG
STR
ANG
STR
ANG
ANG
ANG
STR
ANG
STR
ANG
STRH-WHEEL
CAP
H-
WHEEL
CAP
H-
WHEEL
CAP
H-
WHEEL
CAP
CAP
CAP
CAP
CAP
CAP
CAP
CAP
CAP
15XXXXXXXXXXXXXXXX20XXXXXXXXXXXXXXXX25XXXXXXXXXXXXXXXX32XXXXXXXXXXXXXXXX40XXXXXXXXXXXXXXXX50XXXXXXXXX65XXXXXXXXX80XXXXXXXX100XXXXXXXX
125XXXXXXXX
150XXXXXX
200XXXXXX
ØD
T
DANFOSS
A148B15.10
Size
SizeøDTøDTmmin.mmmm
in.
in.
15½21.320.839
0.07920¾
26.921.059
0.079251
33.721.327
0.079321¼
42.421.669
0.079401½
48.321.902
0.079502
60.322.37
0.079652½
76.123
0.079803
90.933.579
0.118
1004116.334.579
0.118
1255141.735.579
0.118
1506170.336.705
0.118
2008221.1338.705
0.118
Strainer housing, Type FIA
Table 2: Pressure/Temperature range chart for SVL product range with butt-weld connection F
Connection
Figure 2: F connection
Table 3: Dimensions
Available with the following connections:
• Butt-weld connection "F"
• DN 15 to 65 size: 2mm thick
• DN 80 -200 size: 3 mm thick
Installation/Maintenance
The strainer is designed to resist high internal pressures. However, the piping system in general should be designed to avoid liquid traps and reduce the risk of hydraulic pressure caused by thermal expansion. Install the strainer with the cover in downward position.
© Danfoss | Climate Solutions | 2021.03 AI365917233048en-00101 | 5
Loading...
+ 10 hidden pages