Danfoss RA-UN, RA-UR Data sheet

Data Sheet
Valve Bodies Types RA-UN and RA-UR for Small Flow Volumes
Application
RA-UN / RA-UR angle RA-UN / RA-UR straight RA-UN / RA-UR horizontal angle
All RA-UN/UR valve bodies can be used together with all types of thermostatic elements in the RA 2000 series.
The valve bodies are fitted with a kv limiting device for presetting of max. water flow.
RA-UN is for mounting in the flow and RA-UR in the return. An arrow on the valve body indicates the direction of flow.
The valve bodies RA-UN/RA-UR are used in two­pipe heating systems and is available with the following setting ranges for max. water flow:
RA-UN: RA-UR: kv = 0.02 - 0.47 m³/h
The valve bodies are supplied with a protective cap and adjusting screw, which can be used for manual regulation during the construction phase.
kv = 0.02 - 0.48 m³/h
The protective cap must not be used as a manual shut off device. A special manual shut off device (code no. 013G5000) should be used.
To be able to distinguish between other valve bodies of the RA 2000 series the protective cap is yellow.
Compression fittings for 15 mm, 10 mm or 8 mm copper tube are available for valve body RA-UN/ UR with 3/8" and 1/2" BSP connections.
Valve bodies are manufactured from brass with nickel plating. The pressure pin of the gland seal is of chrominium steel and works in a lifetime lubricated O-ring. The gland seal can be replaced without draining down the system.
Should water treatment be used it is essential that dosing instructions of the manufacturer are strictly observed. It is recommended that formulations containing mineral oil are avoided.
Principles
Danfoss Heating Solutions VDSXE302 © Danfoss 02/2011 1
Data Sheet Valve Bodies Types RA-UN and RA-UR for Small Flow Volumes
Data and Ordering
Type Code no. Design
013G3001 Angle
1)
RA-UN 10
013G3002 Straight 013G3041 Horizontal angle 013G3003 Angle
RA-UN 15
1)
013G3043 Horizontal angle
RA-UN 20
013G3005 Angle 013G3006 Straight 013G3299 Angle
RA-UR 10
013G3298 Straight 013G3297 Horizontal angle
RA-UR 15
Type Code no.
013G3229 Angle 013G3228 Straight
1 2 3 4 5 6 7 N
013G3001
1)
RA-UN 10
013G3002 013G3041
RA-UN 15
1)
013G3003 013G3004
0.02 0.06 0.11 0.17 0.23 0.30 0.35 0.48
013G3043
RA-UN 20
013G3005 013G3006 013G3299
RA-UR 10
RA-UR 15
013G3298 013G3297 013G3229 013G3228
0.02 0.03 0.06 0.08 0.14 0.20 0.27 0.47
Connection
Inlet Outlet
Rp 3/8
Rp 1/2
Rp 3/4
Rp 3/8
R 3/8
R 1/2013G3004 Straight
R 3/4
R 3/8
With
actuator
N(kvs)
Max. pressure, bar
Work
0.57 10 0.6 16
00.53 10 1.0 16
Rp1/2
R1/2
Presetting, kv-values with RA 2000 sensor, m³/h
Diff.
3)
2)
Test
1)
The valve inlet is prepared for compression fittings.
2)
The maximum differential pressure specified is the maximum pressure at which the valves give satisfactory regulation. As with any device which imposes a pressure drop in the system, noise may occur under certain flow/pressure conditions. The differential pressure can be reduced by the use of the Danfoss differential pressure regulators.
3)
The kv-value indicates the water flow (Q) in m³/h at a pressure drop (∆p) across the valve of 1 bar an.
. The kvs-value states the flow Q at maximum lift, i.e. at fully open valve at setting N.
Accessories
Product Dimension Code no. Gland seal 1) (10 pcs.)
013G0290 Rp 3/8 x Ø 10 013G4100 Rp 3/8 x Ø 12 013G4102
Compression fittings for steel and copper tubes, incl. compression ring and nipple (10 pcs.)
Rp 1/2 x Ø 10 013G4110 Rp 1/2 x Ø 12 013G4112 Rp 1/2 x Ø 15 013G4115
2 VDSXE302 © Danfoss 02/2011 Danfoss Heating Solutions
1
2
Data Sheet Valve Bodies Types RA-UN and RA-UR for Small Flow Volumes
1)
The gland seal of the valve can be replaced under pressure, i.e. while the installation is in operation.
Presetting
The presetting values of the integrated valves can be adjusted easily and accurately without the use of tools (factory setting: ‘N’):
Remove the protective cap or the
thermostatic sensor. Lift up the setting ring.
Turn the setting ring until the desired
presetting aligns with the reference mark. The reference mark will always point
towards the radiator connection. Let go of the setting ring.
Presetting can be selected infinitely variably within the range of 1 to 7. At setting ‘N’ the valve is fully open. Setting in the shaded areas of the drawing should be avoided. When the radiator thermostat has been installed, the presetting is protected against unintended regulation.
1. Presetting range
2. Reference mark
Design
The radiator thermostats consist of a thermostatic element of the RA 2000 series and a valve body. The element and the valve body are ordered separately.
Materials in contact with water
kv-limiter PPS Oring EPDM
Valve cone NBR Pressure pin and valve spring Chrome steel Valve body and other metal
Ms 58
parts Valve body surface Nickel-plated
1. Gland seal 5. Regulation spring
2. O-Ring 6. Setting dial
3. Pressure pin 7. Valve body
4. Seal 8. kv-nozzle
Danfoss Heating Solutions VDSXE302 © Danfoss 02/2011 3
[mwg]
Q [l/h]
[mwg]
Q [l/h]
Data Sheet Valve Bodies Types RA-UN and RA-UR for Small Flow Volumes
Capacities
RA-UN presetting
Capacities with RA2000 sensor with a P-band between 0,5K and 2K
RA-UR presetting
Capacities with RA2000 sensor with a P-band between 0,5K and 2K
4 VDSXE302 © Danfoss 02/2011 Danfoss Heating Solutions
Data Sheet Valve Bodies Types RA-UN and RA-UR for Small Flow Volumes
Dimensions
Straight valve body with thermostatic sensor RA 2990
Angle valve body with thermostatic sensor RA2992
Horizontal angle valve body with thermostatic sensor RA 2990
Type
RA-UN 10 10 RA-UN 10 horiz. angle 10 RA-UN 15 15 RA-UN 15 horiz. angle 15 RA-UN 20 20 RA-UR 10 10 RA-UR 10 horiz. angle 10 RA-UR 15 15
Connection
DN D
Rp 3/8 Rp 3/8 Rp 1/2 Rp 1/2
Rp 1 Rp 3/8 Rp 3/8 Rp 1/2
d
2
R 3/8 60 85 27 52 22 47 96 22 27 R 3/8 59 108 26 51 22 22 27 R 1/2 67 95 30 58 26 47 96 27 30 R 1/2 60 109 29 57 27 27 30
R 1 74 106 34 66 29 47 96 32 37 R 3/8 60 85 28 53 27 47 96 22 27 R 3/8 47 96 28 53 27 22 27 R 1/2 67 95 28 53 27 47 96 22 27
L1L2L3L4L5L6L7L8L9L
10
Arc. flats
S1 S2
Danfoss Heating Solutions VDSXE302 © Danfoss 02/2011 5
Data Sheet Valve Bodies Types RA-UN and RA-UR for Small Flow Volumes
6 VDSXE302 © Danfoss 02/2011 Danfoss Heating Solutions
Data Sheet Valve Bodies Types RA-UN and RA-UR for Small Flow Volumes
Danfoss Heating Solutions VDSXE302 © Danfoss 02/2011 7
Data Sheet Valve Bodies Types RA-UN and RA-UR for Small Flow Volumes
Danfoss A/S Heating Solutions Haarupvaenget 11 8600 Silkeborg Denmark Phone:+45 7488 8000 Fax: +45 7488 8100 Email: heating.solutions@danfoss.com www.heating.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
8 VDSXE302 © Danfoss 02/2011 Danfoss Heating Solutions
Loading...