Danfoss RA-N Radiator Valves Data sheet

Data Sheet
RA-N Radiator Valves with Integrated Presetting and Self-Sealing Tailpiece
Application
Straight version Angle version Horizontal angle version
All RA-N valve bodies can be used together with all types of thermostatic elements in the RA 2000 series and with TWA-A thermal actuators.
RA-N valves are used in two-pipe heating systems and are available in series D and series F to fit local standards.
RA-N valves are fitted with a kv-limiting device for pre-setting of max. water flow and are available
with the following setting ranges:
RA-N 15:
Each valve body is supplied with a red protective cap, which can be used for manual regulation during the construction phase.
The protective cap must not be used as a manual shut off device. A special manual shut off device is available as an accessory.
kv = 0.04 - 0.73 m³/h
RA-N valve bodies are manufactured from brass with nickel plating.
The pressure pin of the gland seal is of chromium steel and works in a lifetime lubricated O-ring. The complete gland seal assembly can be replaced without draining down the system.
In order to avoid deposition and corrosion the composition of the hot water must be in accordance with the VDI 2035 guideline (Verein Deutscher Ingenieure). It is recommended that formulations containing mineral oil are avoided.
A comprehensive range of compression fittings for PEX, AluPEX, copper and steel tubes are available - please require special data sheet for Danfoss compression fittings.
Approved to EN 215
Quality
Danfoss Heating Solutions VDSXL202 © Danfoss 02/2011 1
RA-N radiator valves with integrated presetting and self-sealing tailpiece are manufactured to the highest standards,
and are approved to the European standard EN
215.
All Danfoss RA 2000 radiator thermostats are manufactured to the highest standards, and are approved to the European standard EN 215.
All Danfoss radiator thermostats are manufactured in factories, assessed and certified by BSI (British Standards Institution) against ISO 9000 and ISO14001.
1
2
3
Data Sheet RA-N Radiator Valves with Integrated Presetting and Self-Sealing Tailpiece
Presetting
The presetting values of RA-N valves can be adjusted easily and accurately without the use of tools (factory setting = N):
Remove protective cap/thermostatic sensor
Find reference mark
Lift and turn setting ring until the aquired
presetting aligns with the reference mark.
Presetting can be selected in steps from 1 to 7. At setting N the valve is fully open. This setting can be used as a flushing position, if the system has to be flushed out because of dirt problems. In one-pipe installations, the setting N must be used.
Settings outside 1 to 7 and N should be avoided.
When the thermostatic sensor has been installed, the presetting is protected against unintended regulation.
1. Presetting range
2. Factory setting and one-pipe system
3. Reference mark
Data and Ordering
Type Design
Connections
Max. work.
press.
Max. diff.
press.
1)
Test
Max. work.
temp.
Code no.Inlet Outlet
Rp R bar bar bar ˚C
Angle, F
013G0113
Straight, F 013G0114
RA-N 15
Angle, D 013G0115
1/2 1/2 10 0.6 16 120
Straight, D 013G0116
Horiz. angle, D 013G0117
Pre-setting
2)
k
Type Design
(m³/h at Δp = 1 bar)
v-max.
1 2 3 4 5 6 7 N N
Angle, F
Straight, F
RA-N 15
Angle, D
0.04 0.09 0.16 0.25 0.36 0.43 0.52 0.73 0.90
Straight, D
Horiz. angle, D
1)
Working pressure = static + differential pressure. The maximum differential pressure specified is the maximum pressure at which the valves give satisfactory regulation. As with any device which imposes a pressure drop in the system, noise may occur under certain flow/pressure conditions. To ensure quiet operation, maximum pressure drop should not exceed 30 to 35 kPa. The differential pressure can be reduced by the use of the Danfoss differential pressure regulators types AVD, AVDL, AVDS, IVD or ASV-P.
2)
The kv-value indicates the water flow (Q) in m³/h at a pressure drop (∆p) across the valve of 1 bar;
k
vs
. At setting N the kv-value is stated according to EN 215, at XP = 2K i.e. the valve is closed at 2°C
higher room temperature. At lower settings the XP-value is reduced to 0.5K of the setting value 1. The kvs-value states the flow Q at a maximum lift, i.e. at fully open valve at setting N.
2 VDSXL202 © Danfoss 02/2011 Danfoss Heating Solutions
Data Sheet RA-N Radiator Valves with Integrated Presetting and Self-Sealing Tailpiece
Accessories
Operating Principle
Product Dimension For valve body Code no. Gland seal All RA valves 013G0290
Compression fittings for steel and copper tubes
All accessories comes in boxes of 10 pcs.
The radiator thermostats consist of the thermostatic elements of the RA 2000 series and the valve body RA-N. The element and the valve body are ordered separately.
Rp 1/2 x Ø 10 Rp 1/2 x Ø 12 013G4112 Rp 1/2 x Ø 15 013G4115
1. Gland seal
2. O-Ring
3. Pressure pin
4. Seal
5. Regulation spring
6. Setting dial
7. Valve body
8. kv-nozzle
A clamping band with Allen screw ensures a simple, firm connection between element and valve body. The gland seal of the valve can be changed in operation, i.e. with water and pressure on the system.
RA-N 15
013G4110
Principles
Valve body and other metal parts
Kv-limiter PPS O-ring EPDM
Valve cone NBR Pressure pin and valve spring Chrome steel Nozzle PP
The valve bodies are nickle-plated on the outside.
Ms 58, brass
Max. ambient temperature 60 ˚C Max. medium temperature 120 ˚C Max. working pressure 10 bar Test pressure 16 bar
Danfoss Heating Solutions VDSXL202 © Danfoss 02/2011 3
Loading...
+ 5 hidden pages