Danfoss RA-N/HC, RLV-S/HC Data sheet

Data Sheet
Valve Set for Hydro Cable - Valve Body RA-N/HC & Lockshield Valve RLV-S/HC
with self sealing tail piece
Application
RA-N/HC and RLV-S/HC,
radial
RA-N/HC radiator valve
All RA-N/HC valve bodies can be used to­gether with all types of thermostatic elements with Danfoss RA connection in two-pipe heating systems.
RA-N/HC valves are fitted with a kv limiting device for presetting of max. water flow within a range of 0.04 to 0.69 m3/h.
The valve bodies are supplied with a protec­tive cap which can be used for manual regula­tion during the construction phase. The pro­tective cap must not be used as a manual shut off device. A special manual shut off device (code no. 013G5002) should be used. To be able to distinguish between other valve bodies of the RA 2000 series the RA-N/HC protective cap is red.
RA-N/HC has a connection for PEX 12 x 1.1 mm and 16 x 1.5 mm hydro cable, both axial and radial compression fittings are available. RA-N/ HC are also available with 1/2” conection.
RA-N/HC and RLV-S/HC,
axial
RLV-S/HC lockshield valve
RLV-S/HC is intended for mounting on the outlet of the radiator.
Using RLV-S/HC each radiator can be shut off individually to allow trouble-free maintenan­ce or repair without affecting other radiators in the system.
RLV-S/HC is available in angle version with a connection for PEX 12 x 1.1 mm and 16 x 1.5 mm hydro cable, both axial and radial com­pression fittings are available.
RLV-S/HC is also available with 1/2” connec­tion.
Default setting is fully open valve. Dimensions correspond to DIN 3842-1.
In order to avoid deposition and corrosion the composition of the hot water must be in accordance with the VDI 2035 guideline (Verein Deutscher Ingenieure).
Valve bodies are manufactured from brass with nickel plating. The pressure pin of the gland seal is of chrominium steel and works in a lifetime lubricated O-ring. The complete gland assembly can be replaced without drai­ning down the system.
Should water treatment be used it is essential that dosing instructions of the manufacturer are strictly observed. It is recommended that formulations containing mineral oil are avoi­ded.
VDLXB102 © Danfoss 02/2017 1
Datasheet Valve Set for Hydro Cable - Valve Body RA-N/HC & Lockshield Valve RLV-S/HC
Principles
Closing and Opening RLV-S/HC
Use an 8 mm Allen key to close the RLV-S/HC by turning it clockwise. Open the RLV-S/HC by turning the Allen key anti-clockwise. With 4 turns the valve will be fully open.
Technical Data and Ordering
Presetting RA-N/HC & RLV-S/HC
RA-N/HC UK 50 RLV-S/HC 45
RA-N/HC UK 50 RLV-S/HC 45
RA-N/HC UK 75 RLV-S/HC 75
RA-N/HC UK 75 RLV-S/HC 75
RA-N/HC UK 50 RLV-S/HC 45
RA-N/HC UK 75 RLV-S/HC 75
1) The kv-value indicates the water flow (Q) in m3/h at a pressure drop (Δp) across the valve of 1 bar; kv = Q: √Δp. The kv-value is stated according to EN 215, at XP = 2K, i.e. the valve is closed at 2°C higher room temperature. At lower settings the XP value is reduced to 0.5K. The kvs-value states the flow Q at a maximum lift, i.e. at fully open valve.
2) Kvs-value for RLV-S/HC: 1.26 m3/h
Design
1 2 3 4 5 6 7 N N
Radial 12mm
Radial 16mm 013G2291
Radial 12mm 013G2292
0.04 0.06 0.10 0.15 0.21 0.28 0.36 0.44 0.69
Radial 16mm 013G2293
Axial 12mm 013G2294
Axial 12mm 013G2295
kv-value¹⁾ Kvs ²⁾
Code No.
013G2290
Technical Data
Max. working pressure³ 10 bar Max. differential pressure 0.6 bar Test pressure 16 bar Max. working temperature 120 °C
3) Working pressure = static + differential pressure. The maximum differential pressure specified is the maximum pressure at which the valves give satisfactory regulation. As with any device which imposes a pressure drop in the system, noise may occur under certain flow/pressure conditions. To ensure quiet operation, maximum pressure drop should not exceed 30 to 35 kPa. The differential pressure can be reduced by the use of the Danfoss differential pres­sure regulators.
VDLXB102 © Danfoss 02/2017 2
Loading...
+ 2 hidden pages