Danfoss PCVPQ Operating guide [de]

Instructions
Pilot-controlled Flow Rate and Differential Pressure Controller PCVPQ
English Page 2
Instructions
Hilfsgesteuerter Volumenstrom-, Differenzdruckregler PCVPQ
DN 100 - DN 250 PN 16 / PN 25
© Danfoss | 2016.05
VI.JA.H3.5B | 1
Instructions PCVPQ
Table of Contents 1 Safety Notes ....................................................... 3
2 Definition of Application ............................. 3
3 Description ........................................................... 4
3.1 Construction ..........................................................4
3.2 Mode of Operation ............................................4
4 Technical Data ................................................... 4
5 Scope of Delivery .............................................. 5
6 Assembly .............................................................. 6
6.1 Prior to Assembly ................................................ 6
6.2 Installation Position,
Installation Place ................................................. 6
6.3 When Installaling observe ...............................6
6.4 Impulse Tube Installation ................................. 6
6.5 Insulation ............................................................... 6
6.6 Installation Scheme ............................................ 7
6.7 Assembly Drawings, Dimensions ................. 8
7 Start-up ................................................................10
7.1 Required static Pressure, Pressure
Difference ............................................................10
7.2 Leak and Pressure Test .....................................10
7.3 Filling the System ..............................................10
7.4 Start-up ..................................................................10
7.5 Putting out of Operation ................................10
7.6 Flow Rate Adjustment ......................................11
7.7 Flow Adjusting Curves .................................... 12
7.8 Adjustment of
the Differential Pressure ................................14
7.9 Sealing ..................................................................14
7.10 Adjustement of
the Throttle Valves ...........................................14
7.11 Funstion Test ......................................................15
8 Trouble Shooting ...........................................16
9 Replacement of Valve,
Actuator, Trims ................................................ 17
2 | © Danfoss | 2016.05
9.1 Dismounting and Mounting
Actuator Valve ....................................................17
9.2 Replacement of Trim Valve VFQ 21 ............19
9.3 Dismounting, Mounting
Actuator AVP, AVP-F .........................................20
9.4 Replacement of
Trim Valve AVP, AVP-F .......................................20
VI.JA.H3.5B
Instructions PCVPQ
1 Safety Notes
observe these instructions.
Necessary assembly, start-up, and maintenance work must be performed only by qualified, trained and authorized personnel.
Prior to assembly and maintenance work on the controller, the system must be:
depressurized, cooled down, emptied and cleaned.
Please comply with the instructions of the system manufacturer or system operator.
MAINTENANCE
FREE
Prior to assembly and commissioning to avoid injury of persons and damages of the devices, it is absolutely necessary to carefully read and
2 Definition of
Application
The controller is used for flow rate limitation of water for heating, district heating and cooling systems. The admissible medium temperatures depend on the design and comprise 5-150 °C, 5-200 °C.
The technical data on the rating plates deter­mine the use.
VI.JA.H3.5B
© Danfoss | 2016.05 | 3
Instructions PCVPQ
P (Diff
3 Description
3.1 Construction
ilot controller AVP
erential Pressure)
Throttling valve only by DN150-250
3.2 Mode of Operation
The control unit consists of the PCV-VFQ21 valve unit, installed in the main pipe, and the differential pressure controllers AVP and AVP-F installed as pilot controllers in the bypass. In the bypass line, a throttle element is installed in front of the pilot controllers. The controller keeps the differential pressure for the corresponding section on a constant level and restricts the flow rate to the adjusted setpoints. The valve and the pilot valves are pressure­balanced. The setpoint for the differential pressure is adjusted by pre-stressing the setpoint spring of the pilot controller AVP. The setpoint for the flow rate limitation is adjusted at the adjusting throttle of the valve unit. The valve unit in the main pipe is opening on rising pressure. The pilot controllers in the bypass line are closing on rising pressure.
Differential Pressure Control
In case of small flow rates, the valve in the main pipe remains closed through the pressure spring
Pilot controller AVP-F (Flow Rate)
Adjusting throttle
Throttling element DE
Valve unit PCV-VFQ 21
Throttling valve
in the actuator of the valve unit. The pressure is exclusively controlled by the pilot controller. If the flow rate in the bypass is increased, the pressure in the throttle element (Venturi nozzle) decreases. The reduced pressure acts through an impulse tube upon the lower chamber of the actuator of the valve unit. The main valve is thus opened shock-free and continuously. If the flow rate is reduced, the pressure in the throttle element raises and the main valve closes. This sequential switching guarantees an operation free of vibrations and a small control deviation over a wide positioning range.
Flow Rate Limitation
If the flow rate reaches the adjusted setpoint, the differential pressure increases at the adjusting throttle. This differential pressure acts on the actuator AVP-F via the impulse tubes and the valve AVP-F closes. Consequently, the valve of the valve unit is throttled, too, and the flow rate is restricted.
4 Technical Data Technical data, see rating plates and the PCV
data sheet.
4 | © Danfoss | 2016.05
VI.JA.H3.5B
Instructions PCVPQ
5 Scope of Delivery
DN 100-125
Assembly kit valve unit PCV-VFQ 21 Pilot controller DN 25
AVP
DN 25
Throttling element
Cu pipe Ø 6 × 1 × 1500 mm
Cu pipe Ø 10 × 1 × 3000 mm
AVP- F
DN 150-250
Assembly kit valve unit PCV-VFQ 21 Pilot controller DN 40
AVP
DN 40
Throttling element
Cu pipe Ø 6 × 1 × 1500 mm
Cu pipe Ø 10 × 1 × 3000 mm
AVP- F
VI.JA.H3.5B
© Danfoss | 2016.05 | 5
Instructions PCVPQ
6 Assembly 6.1 Prior to Assembly:
Depressurized system before any assembly work !
CAUTION!
• Clean pipeline system.
• Install strainer in front of the controller.
• Install shut-off units in front of and behind the controller.
6.2 Installation Position, Installation Place
• Installation is only permitted in horizontal pipelines with the actuators hanging in a downward position.
• The controller may be installed in the supply as well as in the return line.
6.3 When installing:
• Observe direction of flow.
• Design with welded ends:
6.4 Impulse Tube Installation
See installation scheme, section 6.6. For CU pipes Ø 10 × 1, insert sockets 1 on both sides.
1
Care for correct position of the cutting rings 2.
2
pin only
weld
do NOT
weld
• Loads on the valve body and the throttle element by the pipes are not permitted.
6.5 Insulation
The diaphragm actuators must not be insulated when insulating system parts.
6 | © Danfoss | 2016.05
VI.JA.H3.5B
Instructions PCVPQ
Valve unit PCV - VFQ 21
lay impulse tube during mounting
250)
Pilot controller AVP-F
6 Assembly 6.6 Installation Scheme
Valve unit PCV - VFQ 21
Installation in the Return Line
Throttling valve
Throttling element
Throttling valve
(only by DN 150 -
Bypass controller PCVPQ
Installation in the Supply Line
Pilotregler AVP-F
Pilotregler AVP-F
Throttling valve
Throttling element Throttling valve (only by DN 150 - 250)
Bypass controller
PCVPQ
VI.JA.H3.5B
© Danfoss | 2016.05 | 7
Instructions PCVPQ
CU pipe Ø 6 x 1
DN 25: pipe Mater (not
6 Assembly
6.7 Assembly Drawings, Dimensions
Lay when assembling.
to the return flow
to the supply flow
Install impulse tubes laterally because of dir t
Cu pipe Ø 10 x 1 Lay when assembling.
DN 100-125
Ø 33.7 x 3.2
ial: ST 35.8
part of the delivery)
Pilot controller AVP
Pilot controller AVP-F
Throttling element
DN 25 SW 50
8 | © Danfoss | 2016.05
VI.JA.H3.5B
Instructions PCVPQ
laterally because of dirt
CU pipe Ø 6 x 1
DN 40: pipe Mater (not part of the delivery)
6 Assembly
to the return flow
to the supply flow
Install impulse tubes
Lay when assembling.
Cu pipe Ø 10 x 1 Lay when assembling.
DN 150-250
Ø 48.3 x 3.2
ial: ST 35.8
Dimensions
Nominal diameter DN 100 125 150 200 250
L1
350 400 480 600 730 H1 530 530 619 647 697 H2 - 245 300 325 D2 263 380
mm
D1 150 250 320 385 500
B 200 210 310 336 412
A ≥ 290 320 350 410
VI.JA.H3.5B
© Danfoss | 2016.05 | 9
Instructions PCVPQ
5
4
3
p2 p1
867
7 Start-up
7.1 Required Static Pressure, Pressure Difference
For a proper functioning, a minimum pressure difference of p1 - p2 ≥ 0.5 bar is required.
The static pressure p1 in front of the controller must not fall below 1.5 bar (excess pressure). Nonobservance may lead to cavitation and damages in the throttling element 1.
1
7.2 Leak and Pressure Tests
To avoid too high pressures at the diaphragm actuators, the following should be observed prior to any pressure tests:
7.3 Filling the System
Note:
The controller 4 is closed when no pressure is applied and only opens with a defined flow in the bypass. The pilot controller 5 is closing on rising pressure.
To avoid too high pressure differences on the controller, observe the following sequence when starting-up !
This procedure guarantees that there is no overturn of the diaphragm in the valve and the actuators.
1. Open shut-off valves 6 that possibly exist in the impulse tubes.
2. Open units 7 of the system.
3. Slowly open shut-off units in the supply flow 8 and the return flow 9.
Actuator of valve unit:
The admissible operating excess pressure in the actuator 2 is 25 bar 1). For higher pressures, you must:
• Remove the impulse tubes 3 at the actuator and close the connections with a stopper.
• Prior to any leak or pressure test, the instructions in section 7.3 must be complied with.
2
1)
Pre-condi tion: Same pressure on both side s of the diaphragm.
If the pressure lo ad is one-sided, the (+)diaphragm cham ber may have an excess p ressure of 1 bar in comparison to th e (-) diaphragm chamber.
9
7.4 Start-up
During starting-up the filled system, open the units in the same sequence as described in section 7.3.
7.5 Putting out of operation
When putting the system out of operation, first close the shut-off units in the supply flow and then those of the return flow.
10 | © Danfoss | 2016.05
VI.JA.H3.5B
Instructions PCVPQ
Required flo
for the adjusting throttle
7.6 Flow Rate Adjustment
The setting of the setpoint for the flow rate limitation is made by means of flow adjusting curves (see section 7.7) or a heat meter (see page
33).
Adjustment by means of flow adjusting curves
Adjustment is to be made at a shut-down system.
Procedure
1. Unscrew cover 1.
1
2. Loosen the counter nut 2.
4. Turn the adjusting throttle by this number of rotations to the left.
5. The adjusted flow rate can be verified by means of a flow rate measuring device. Perhaps you need to re-adjust the flow rate.
Care for an adequate differential pressure in
the system.
6. Tighten the counter nut without changing the position of the adjusting throttle.
2
2. Screw in the adjusting throttle 3 to its stop.
3
3. Choose diagram, (see section 7.7, Flow Adjusting Curves) Observe effecitve pressure Δpb: 0.2 or 0.5 bar see rating plate on the actuator AVP-F
w rate
7. Re-screw the cap nut 1.
8. The cap nut can be sealed.
VI.JA.H3.5B
The flow rate adjustment is completed. Now, adjust the differential pressure, see section 7.8.
Read rotations
© Danfoss | 2016.05 | 11
Instructions PCVPQ
DN 100kvs 125/DN 125kvs 160/DN 150kvs 320
14
Rotations for the adjusting throttle
Flow rate (m
3
/h)
DN 100kvs 125/DN 125kvs 160/DN 150kvs 320
14
Rotations for the adjusting throttle
Flow rate (m
3
/h)
DN 200kvs 450/DN 250kvs 630
10
adjusting throttle: 4
required flow rate limitation:
DN 200kvs 450/DN 250kvs 630
89
Rotations for the adjusting throttle
Flowrate (m
3
/h)
7 Start-up
7.7 Flow Adjusting Curves
140
p
=0,2
120
100
80
60
40
20
0
200
180
160
140
/h)
3
120
100
80
Flowrate (m
60
40
20
0
b
DN150
0123456789 10 11 12 13
DN 250
01234567 89
Rotations for the adjusting throttle
DN100/125
DN 200
p
=0,2
b
220
200
p
=0,5
b
180
DN 250
DN150
DN100/125
DN 200
p
=0,5
b
160
140
120
100
80
60
40
20
0
0123456789 10 11 12 13
260
240
220
200
180
160
140
120
100
80
60
40
20
0
012345 67
12 | © Danfoss | 2016.05
Example
Ventil DN 200
100 m³/h
necessary rotations of the
VI.JA.H3.5B
Loading...
+ 28 hidden pages