Danfoss NovoCon S, NovoCon M, NovoCon L, NovoConXL Fact sheet

Fact sheet
Termix BV
Instantaneous water heater for large apartment houses, sports arenas and schools
Application
The Termix BV substation is an instantaneous water heater featuring superb heat extraction and high performance. The substation is delivered with thermostatic or automatic controls. The Termix BV is suitable for large apartment houses, sports arenas and schools, where large amounts of hot water are needed. The hot water systems are available in 7 different sizes with an output from 77-222 kW. The Termix BV unit is supplied with PU insulated heat exchangers.
Domestic hot water (DHW)
The domestic hot water is prepared in a plate heat exchanger and the temperature is regulated with thermostatic or automatic controls. The thermostatic solution is regulated with self-acting thermostatic control valves. The substations with high output are controlled with two valves connected in cascade in order
to control both small and large demands for hot water in an efficient manner. The Termix BV can also be mounted with automatic controls. There is no additional pressure loss on the secondary side of the heat exchanger with a thermostatic or automatic control valve. Therefore this type of regulation can be used by low pressure in the cold water mains.
Domestic hot water circulation
The Termix BV substation is supplied with connections for DHW circulation including circulation pump and a non­return valve as a standard.
Options
The substation can be supplied with a safety valve and a thermostatic circulation valve.
Construction
All pipes are made of stainless steel. The connections are made by nuts and gaskets. The Termix BV substation can be delivered with a white-lacquered steel cover in modern design.
FEATURES AND BENEFITS
• Instantaneous water heater
• DHW regulation with thermostatic or automatic controls
• Capacity: 77-222 kW DHW
• DHW in sufficient quantity
• Operates independent of differential pressure and flow temperature
• Minimum space required for installation
• Pipes and plate heat exchanger made of stainless steel
• Minimized risk of lime scale and bacteria formation
www.danfoss.com
CIRCUIT DIAGRAM - EXAMPLE
DH
supply
DH
return
Diagram for Termix BV type 4-8
Technical parameters:
Nominal pressure: PN16 DH supply temperature: T DCW static pressure: P Brazing material (HEX): Copper
Weight incl. cover: 20-40 kg (incl. packing)
Cover: White-lacquered steel sheet
Dimensions (mm):
Without cover:
H 660 × W 510 × D 240 (type 2-5) H 1000 × W 800 × D 340 (type 6-8)
With cover:
H 800 × W 540 × D 360 (type 2-5) H 1000 × W 950 × D 525 (type 6-8)
= 120 °C
max
= 0,5 bar
min
Connections:
1. District heating (DH) supply
2. District heating (DH) return
3. Circulation
4. Domestic hot water (DHW)
5. Domestic cold water (DCW)
Type 2-5
Type 6-8
Wall
Wall
DHW
DCW
Circ.
Connections sizes:
DH + DCW + DHW: G 1” (int. thread) Circulation: G ¾” (int. thread)
Options:
• White-lacquered steel cover
• Safety valve and non-return valve (10 bar)
• Thermostatic circulation set
B Heat exchanger DHW 2 Non-return valve 7 Thermostatic valve 11 Domestic hot water pump 18 Thermometer
DHW: CAPACITY EXAMPLES
Substation type
Ter mix BV*
BV-2T-CP 77 70 20 45 27,6 BV-3T-CP 93 70 20 45 33,3 BV-4T-CP 122 70 20 45 43,7 BV-5T-CP 157 70 20 45 56,3 BV-6T-CP 150 70 19 45 53,8 BV-7T-CP 160 70 18 45 57,4 BV-8T-CP 222 70 19 45 79,6
© Danfoss | DCS-SGDPT/ PL | 2021. 08
DHW capacity
[kW]
Seen from above
Supply flow primary
[°C]
Return flow primary
[°C]
Pressure loss primary
[kPa]
AM188286466660en-020401
DHW tap load
[l/min]
Loading...