Danfoss NovoCon S, NovoCon M, NovoCon L, NovoCon XL Fact sheet

Fact sheet
Fact sheet
Data sheet
Headline Myriad Pro
Danfoss Digital Hydronics™
min. 18/18 pt max. 26/26 pt.
Modular hydronic HVAC 4.0 design solution with AB-QM, NovoCon® and Flow sensor
Fact sheet NovoCon® S, M, L, XL and Flow sensor
Novo Con® XLNovo Con® LNovo Con® S Novo Con® M
Introduction
Danfoss Digital Hydronics™ offers you a highly flexible, modular solution for hydronic HVAC 4.0 designs. The digitalization of HVAC systems opens a world of possibilities to increase energy efficiency and user comfort to new levels. To achieve this, it is highly important to establish a dynamic hydronic balance throughout the building. BMS connected digital actuators not only provide highly accurate temperature control, but their data inputs are also essential. Optional temperature and flow data expand the insights and allow continuous energy optimization. Danfoss Digital Hydronics™ covers all what is needed to establish a fully digital hydronic HVAC system. In this factsheet we describe how the different components in the solution are best combined. This is split into different application needs, based on required design flows.
For e.g. Terminal units up to DN 32, the combination consists of AB-QM (4.0) + NovoCon S +SonoSensor 30 For e.g. Air Handling Units up to DN 100, the combination exists of AB-QM + NovoCon M +SonoSensor 30 For e.g. Chillers and District cooling up to DN 250, the combination exists of AB- QM + NovoCon L/XL + SONO 3500 CT
Table of contents
1. NovoCon® S ............................................................................................3
1.1 Description ..................................................................................3
1.2 Ordering .......................................................................................3
1.3 Technical data ...........................................................................4
1.4 I/O points on NovoCon S ...................................................... 4
1.4.1 I/O cables ...............................................................................4
1.5 Temperature sensors.............................................................5
1.5.1 Immersed sensor ................................................................5
1.6SonoSensor 30 ...........................................................................6
1.6.1 Description ...........................................................................6
1.6.2 Technical specifications .................................................. 6
1.7 Cross reference table.............................................................7
1.8 Commissioning/connection of flow sensor to .........8
1.9 BACnet and Mo dbus ..............................................................9
1.9.1 Modbus registers ................................................................9
1.9.2 BACnet objects ....................................................................9
2. NovoCon® M ..........................................................................................11
2.1 Description .................................................................................11
2.2 Ordering .......................................................................................11
2.3 Technical data ...........................................................................12
2.4 I/O connecti ons on NovoCon® M .....................................12
2.5 Immersed sensor .....................................................................12
2.6SonoSensor 30 ...........................................................................13
2.6.1 Description ...........................................................................13
2.6.2 Technical specifications ..................................................13
2.7 Cross r eference table ............................................................14
2.8 Commissioning/connection of flow sensor to.........14
2.9 BACnet and Modbu s ..............................................................15
2.9.1 Modbus registers ...............................................................15
2.9.2 BACnet objects ................................................................... 16
3. NovoCon® L , XL ....................................................................................17
3.1 Description .................................................................................17
3.2 Ordering .......................................................................................17
3.3 Technical data ........................................................................... 18
3.4 I/O conn ections on NovoCon® L, XL ............................... 18
3.5 Immersed sensor .....................................................................19
3.6 SONO 3500 CT ........................................................................... 19
3.6.1 Description ...........................................................................19
3.6.2 Technical specifications ................................................. 20
3.7 Cross re ference table ........................................................... 20
3.8 Commissioning/connection of flow sensor to ........ 21
3.9 BACnet and Modbus ............................................................. 22
3.9.1 Modbus registers............................................................... 22
3.9.2 BACnet objects .................................................................. 23
2 | AM394433983821en-010103 © Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
1. NovoCon® S
1.1 Description
1.2 Ordering
DN15 - DN32
With latest update on firmware for NovoCon®, flow sensor can be connected to NovoCon® actuator, for precise measurement of flow.
Flow sensor can be connected on any input on NovoCon®. Danfoss recommends using AI input,
so energy features can stay functional. NovoCon® S actuator can be used for solutions with sizes from DN15 to DN32.
AB-QM 4.0 threaded version (with test plugs and without test plugs) - External thread
With test
plugs
Code No. Code No.
003Z8200 003Z8220
003Z 8201 003 Z8221
003Z8203 003Z8223
Picture DN
15 LF
15 650
15 HF
20
20 HF
Typ e
Q
nom.
(l/h)
200
1,200 003Z8202 003Z8222 1,100 1,90 0 0 03Z8204 003Z8224
Ext. thread
(ISO 228/1)
G ¾A
G 1A
Without test
plugs
AB-QM threaded version (with test plugs and without test plugs) - External thread
With test
plugs
Code No. Code No.
00 3Z1214 0 03Z1204
-
00 3Z1215 003Z1205
-
Picture DN
25
25HF
32
32 HF
Typ e
Q
nom.
(l/h)
1,70 0 2,700 3,200 4,000
Ext. thread
(ISO 228/1)
G 1 ¼A
G 1 ½A
-
AB-QM 4.0 threaded version (with test plugs and without test plugs) - Internal thread
Typ e
Picture DN
15 LF 200
15 650 003Z 8301 003Z8321
15 HF 1,200 003Z 8302 003Z8322
20 1,100
20 HF 1,900 003Z8304 003Z8324
Temperature sensors
Typ e
Immersed Pt 1000 / Ø 5.2 mm / 1.5 m cable, MID Immersed Pt 1000 / Ø 5.2 mm / 3.0 m cable, MID
Q
nom.
(l/h)
Code No.
187F3 418
187F3419
Int. thread
(I SO 7/1)
Rp ½
Rp ¾
Accessories
Designation Code No.
Immersion brass-pockets, 35 mm, Ø 5.2 pair, MID. For pipes DN15-32
With test
plugs
Code No. Code No.
003Z8300 003Z8320
003Z8303 003Z8323
Without test
plugs
00 3Z1224
003Z1225
Without test
plugs
087G6053
AM394433983821en-010103 | 3© Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
Red
AI:2 / 33220
Read / writeable via fieldbus
Read / writeable via fieldbus
AI:2 / 33220
1.3 Technical data
DN15 - DN32
Power supply range 24 V AC/DC, 50 / 60 Hz *
Power consumption
Protection class III safet y extra-low voltage
Control signal NovoCon® S
Impedance
Actuator sp eed selections (o pen to close) Stroke 7 mm Force 90 N Position accuracy ± 0.05 mm Ambient temp. range −10° C to 50° C Ambient humidity 98% r.h., non-condensing (according to EN 60730-1) Max. medium temp. 120 ° C Storage temp. range –40 to 70 °C Grade of enclosure IP 54 (IP 40 upside down) Weight 0.4 kg
* NovoCon® S is designe d to operate at power deviatio ns up to ±25%.
0-10 VDC, 0-5 VDC, 2-10 VDC, 5-10 VDC, 2-6 VDC, 6-10 VDC, 0-20 mA, 4-20 mA
Operating: 2.7 VA@24VAC / 1.2 W@24VDC
Standby: 1.8 VA@24VAC / 0.7 W@24VDC
BACnet MS/TP, Modbus RTU
Rin AI:0 >100 kΩ (V); 500 Ω (mA)
Rout AO: 1500 Ω
3 sec/mm, 6 sec/mm, 12 sec/mm, 24 sec/mm, Constant Time
BACnet data
Typ e Description
BACnet device profile BACnet Application Specific Controller (B-ASC) BACnet protocol BACnet Master Slave / Token Passing (MS/TP) BACnet baud rates supported
Auto baud rate detection* / 9600 bps / 19200 bps / 38400 bps / 56700 bps / 76800 bps / 115200bps
Modbus RTU data
Supported baud rates Supported transmission
modes
* Default
Auto baud rate detection* / 9600 bps / 19200 bps / 38400 bps / 56700 bps / 76800 bps / 115200bps
Parity: None (1-8-N-2) / Odd (1-8-O-1) / Even (1-8-E-1) / None (1-8-N-1) / Auto parity*
Data format: Parity (Start bit - Data bits - Parity - Stop bits)
1.4 I/O points on NovoCon S
1.4.1 I/O cable (003Z8612) or temperature cable
(003Z8613)
BACnet object / Modbus register
BACnet object / Modbus register
Black Blue Grey White Yellow
0-20mA
AI:0 / 33216
0-10V
0-10V
0-10V
AO:0 / 33286
10kΩ
AI:1 / 33218
0-10V
0-20mA
AI:0 / 33216
10kΩ
0-10V
AO:0 / 33286
AI:1 / 33218
Orange
Cable NovoCon® I/O
Red Power 24V (in/out) Black Blue Grey V/mA input signal
Yellow O-ring
White V output signal Yellow T1 or resistance input Orange T2 or resistance input
The red and black wires can be used to boost the power on the line. They may also be used to power external devices, a separate calculation must be made for available power.
Cable NovoCon® Temperature I/O
Blue O-ring
Power ground (in/out) Ground T1, T2, V/mA input & V output signal
Red Power 24V (in/out) Black
Power ground (in/out)
Blue
Ground T1, T2, V/mA input & V output signal Grey V/mA input signal White V output signal T1 T2
4 | AM394433983821en-010103 © Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
1.5 Temperature sensors
1.5.1 Immersed sensor
Functional description
The sensor unit consists of a platinum element, the resistance value of wich, changes proportionally with the temperature.
Pt 1000 ohm sensor (1000 ohm at 0°C). The sensor is adjusted and meets the tolerance requirements of EN 60751 Class B. The accuracy of temperature measurement is approximately 0.5° in typical operating range. It is unlikely, that during calculation of ∆T, deviation of both sensors would be summed up. Therefore, it is estimated that ∆T measurement accuracy is 0.5° when the sensors are mounted correctly. It is not recommended to use longer wires on temperature sensors than 2m due to risk of electromagnetic interference. If long or thin wires are used it may be necessary to make an offset of the temperature reading in the BMS system.
Temperature sensors Installation Ty pe
Immersed (direct) or
in pocket (indirect)
Surface temperature sensor
Diameter
D (mm)
Pt 1000 Ø5.2 45 187F3 418
Length
L (mm)
Code no.
Sensors pockets Typ e Brass Code no.
Sensor
diameter
Length
(mm) Ø 5. 2
087G6053
L1 (mm ) 47
L (mm) 35
AM394433983821en-010103 | 5© Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
1.6SonoSensor 30
1.6.1 Description
MID examination certificate no.: LT-1621-MI004-030
SonoSensor 30 is an ultrasonic flow sensor especially designed for heating, cooling or combined heating/cooling application in local and district energy systems. It can be used in conjunction with the type approved heating/ cooling energy calculator (e.g. Infocal 9) to form combined heating/cooling energy meter. SonoSensor 30 has been approved according to MID in accuracy class 2. The flow sensor can be mounted in both flow and return pipe.
Features
• Available in nominal flow rates qp 0.6, 1.0, 1.5,
2.5, 3.5, 6.0, 10.0, 15.0, 25.0, 40.0, and 60.0 m³/h
• Housings with thread (G3/4 to G2) or flange (DN20 to DN100) connections
• MID approval for ultrasonic flow sensor with dynamic range of 1:100 (qi:qp) in class 2
• Optional dynamic range of 1:250 in class 2 (with the exceptions of sensors qp 0.6 m3/h,
1.0 m3/h and 3.5 m3/h)
• Temperature range: 5 - 130 °C
• Operating pressure PN 16 or PN 25 bar
• Flow sensor with IP65 protection class and IP67 for heating/cooling application.
• Battery lifetime not less than 12 years
• Low pressure loss, insensitive to dirt
• No inlet or outlet restrictions up to DN50
• Short overload temperature up to 150 °C
1.6.2 Technical specifications
Diameter DN 15 DN 20 DN25, DN32
Connection type G1 G1¼
Overall length, mm 110
Flow rate
Nominal, m3/h 0.6 1.5 0.6 1. 5 2.5 1.5 2.5 3.5 6.0 Maximum, m3/h 1.2 3.0 1. 2 3.0 5.0 3.0 5.0 7 12 Minimum, l/h 6 6 15 6 6 15 10 25 15 10 25 35 24 60 Starting flow rate, l/h 3 3 3 5 5 17 12 Pressure loss at qp, mbar 70 17 1 90 58 94 72 198 40 100
Max. operating pressure
Flow sensor temp. range 5 to 130°C (short overload 150°C) Flow sensor to electronic
box cable length Medium Water quality with pH 7 to 9.5 Volume measuring cycles 1 second
Supply voltage
Battery lifetime Not less than 12 years Approval EN1434 class 2 Environmental class class C Ambient class E2 + M1 Protection class IP65 (IP67 for heating/cooling) Ambient operating temp. +5°C to +55°C Max. ambient humidity <93% rel. humidity
110 ;
165
3.6V DC Lithium batter y (AA-cell)/ Mains supply 24V AC/DC
Mains supply 230V AC (with external 230V to 24V AC transformer)
190 130 260
Thread 16 bar Flange 25 bar
1.2m up to DN32
2.5m up to DN40 to DN100
6 | AM394433983821en-010103 © Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
1.7 Cross reference table AB-QM – Flow sensor - NovoCon® S:
Valve code Valve name
003Z8220 AB-Q M4 DN15 LF 0.2 m3/h thread 003Z8504 Novo Con® S 187F3771 S onoS30 DN15 Qp 0.6 m3/h thread
003Z 8221 A- BQM4 DN15 0.65 m3/h thread 003Z8504 N ovoCon® S 187F3771 SonoS30 D N15 Qp 0.6 m3/h thread
003Z8222 AB- QM4 DN15 HF 1.2 m3/h thread 003Z8504 N ovoCon® S 187F3772 SonoS30 D N15 Qp 1.5 m3/h thread
003Z8223 AB -QM4 DN20 1.1 m3/h thread 003Z8504 N ovoCon® S 187F3772 SonoS30 DN15 Qp 1.5 m3/h thread
003Z8224 AB -QM4 DN20 HF 1.9 m3/h thread 003Z850 4 NovoCon® S
003Z8320 AB-QM4 D N15 L F 0.2 m3/h int. thread 003Z8504 N ovoCon® S 187F3771 SonoS30 DN15 Qp 0.6 m3/ h thread
003Z8321 AB- QM4 DN15 0.65 m3/h int. thread 003Z8504 N ovoCon® S 187F3771 SonoS30 D N15 Qp 0.6 m3/h thread
003Z8322 AB -QM4 DN15 HF 1.2 m3/h int. thread 003Z85 04 No voCon® S 187F3772 SonoS30 DN15 Qp 1.5 m3/h thread
003Z8323 A B-QM4 DN20 1.1 m3/h int. thread 003Z8504 No voCon® S 187F3772 SonoS30 DN15 Qp 1.5 m3/h thre ad
003Z8324 AB- QM4 DN20 HF 1.9 m3/h int. thread 003Z85 04 No voCon® S 187F3772 SonoS30 DN15 Qp 1.5 m3/h thread
003 Z1204
003 Z1224 AB- QM DN25 HF 2.7 m3/h thread 003Z8504 N ovoCon® S 187F3773 SonoS30 DN20 Qp 2. 5 m3/h thread
003 Z1205 AB-Q M DN32 3.2 m3/h thread 003Z8504 NovoCon® S 187F3774 SonoS3 0 DN25 Qp 3.5 m3/h thread
003 Z1225 AB -QM DN32 HF 4.0 m3/h thread 003Z8504 N ovoCon® S 187F3774 SonoS30 DN25 Qp 3. 5 m3/h thread
AB-Q M DN25 1.7 m3/h thread 003Z8504
Valve
connection
Actuator
code
Actuator
name
NovoC on® S
* IO cable with sur face sensor (PT1000)
Flow
sensor
code
187F3772 SonoS30 D N15 Qp 1.5 m3/h thread
187F3773 SonoS30 DN20 Qp 2. 5 m3/h thread
Flow sensor name
sensor
connection
Flow
NovoCon S
cable
003Z8613* / /
003Z8612 187F 3418 087G6053
003Z8613* / /
003Z8612 187F 3418 087G6053
003Z8613* / /
003Z8612 187F 3418 087G6053
003Z8613* / /
003Z8612 187F 3418 087G6053
003Z8613* / /
003Z8612 187F 3418 087G6053
003Z8613* / /
003Z8612 187F 3418 087G6053
003Z8613* / /
003Z8612 187F 3418 087G6053
003Z8613* / /
003Z8612 187F 3418 087G6053
003Z8613* / /
003Z8612 187F 3418 087G6053
003Z8613* / /
003Z8612 187F 3418 087G6053
003Z8613* / /
003Z8612 187F 3418 087G6053
003Z8613* / /
003Z8612 187F 3418 087G6053
003Z8613* / /
003Z8612 187F 3418 087G6053
003Z8613* / /
003Z8612 187F 3418 087G6053
Temperature
sensor code
(PT1000)
Temperature pockets code
AM394433983821en-010103 | 7© Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
1.8 Commissioning/ connection of flow sensor to:
NovoCon® S
NovoCon® S supports connection of flow sensor directly to NovoCon® IO cable. Flow sensor must be connected to AI and AO terminal. NovoCon must be set to digital mode (MSV:9/32810 = 2), output functionality set to Inactive (BV:3/32817 = 0) and value of output (AO:0/33286 = 10) on 10 V. You also need to select AI (MSV: 41/32821) input for connecting flow sensor.
To get right flow sensor value it is verry important to set right value of liters per pulse on NovoCon® (AV: 43/32864). Usually this is written on flow sensor specification sheet. If we would like to use flow sensor for calculating energy we must also change register MSV12/32814*.
AI
Cable NovoCon® I/O
Yellow O-ring
Red Power 24V (in/out)
SonoSensor 30
19 18
Terminal Nr. Description 18 Volume pulse putput (+) 19 Ground (-)
Black Power ground (in/out) Blue Ground T1, T2 V/mA input & V output signal Grey V/mA input signal White V output signal Yellow T1 or resistance input Orange T2 or resistance input
Object/Register Write/read value Description
MSV:9 / 32810 2: Digital mode Application mode BV:3 / 32817 0: Inactive Output feedback AO:0 / 33286 10 Value on output MSV:41 / 32821 3: Flow sensor AI input AV:43 / 32864 0,04 (depends on flow sensor) Pulse volume (liter/pulse) MSV:12 / 32814 3: ON, flow sensor on return pipe Energy counting method*
*Energy counting method MSV: 12 / 32814 State 1: Off NovoCon® S is not calculating energy. State 2: On, indicated flow NovoCon® S is calculating energy based on temperature difference between T1 and T2 and using indicated flow. State 3: On, flow sensor on return pipe NovoCon® S is calculating energy based on temperature difference between T1 and T2 and using flow from flow sensor installed on return pipe. State 4: On, flow sensor on supply pipe NovoCon® S is calculating energy based on temperature difference between T1 and T2 and using flow from flow sensor installed on supply pipe.
8 | AM394433983821en-010103 © Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
1.9 BACnet and Modbus
1.9.1 Modbus registers
Configuration
Modbus
Read/
register
0x802E
32814
Modbus
Write
function
R/W 3, 4 & 6 WORD
Configuration #2
Modbus
Read/
register
0x8033
32819
0x8035
32821
0x8036
32822
0x8 037
32823
0x8060
32864
Modbus
Write
function
R/W 3, 4 & 6 WORD
R/W 3, 4 & 6 WORD AI input
R/W 3, 4 & 6 WORD T1 inp ut Dif ferent options fo r T1 terminal
R/W 3, 4 & 6 WORD T2 inp ut Dif ferent options fo r T2 terminal
R/W 3, 4 & 16 FLOAT Pulse volume
Modbus
Data Typ e
Modbus
Data Typ e
Objec t /
Parameter
name
Energy counting
method
Objec t / Parameter
name
T1, T2 temper ature
sensor type
Description
1: Off 2: On, indi cated flow 3: On, flo w sensor on return p ipe 4: On, fl ow sensor on supply p ipe
Description
Selec t the type of Temper ature sensor co nnected for T1 an d T2.
Diffe rent options for an alog input terminal
Pulse volu me of connected f low sensor
Default
Description of usage
State
Sta te 1: Off
NovoCon® is n ot calculating en ergy. State 2: O n, indicated fl ow NovoCon® is calculating energy based on temperature difference between T1 and T2 and u sing indicated f low.
1: Of f
State 3: On , flow sensor on r eturn pipe NovoCon® is calculating energy based on temperature difference between T1 and T2 and u sing flow from f low sensor insta lled on return pip e. State 4: On, flow sensor on supply pipe NovoCon® is calculating energy based on temperature difference between T1 and T2 and using flow from flow sensor installed on supply pipe.
Default
State
3: PT1000 na
2: Analog
input
2: Supply
temp.
3: Return
temp.
0,4 l/p
Unit Description of usage
Select temperature sensor type: 1: NTC10k Type 2
1: Disabled
na
2: Analog i nput (voltage/curr ent) 3: Flow sensor
1: Disabled
na
2: Supply temperature 1: Disabled
na
2: Supply temperature Adapts au tomatically to the s elected AB- QM valve, but can
be overw ritten manuall y. If set to 0 NovoCon onl y count
Litre/
pulses an d do not perform f low measureme nts based on
pulse
receive d pulses. This can b e used to connect e .g. water meter or energy meter.
2: NTC10k Type 3 3: PT1000
3: Return temperature 4: Flow sensor
3: Return temperature 4: Flow sensor
Persistent
Yes /No
Yes
Persistent
Yes /No
Yes
Yes
Yes
Yes
Yes
Operating
Modbus register
0x8 210
33296
0x 8212
33298
Read/ Write
R 3, 4 FLOAT Volume counter Total accumulated water volume 0 L
R 3, 4 FLOAT Pulse counter Total accumulated number of pulses 0 pulse
Modbus function
Modbus
Data
Object / Parameter name Description
Typ e
Alarms & warning
Modbus register
0x8300
33536
Read/ Write
R 3, 4 FLOAT
Modbus function
Modbus
Data
Object / Parameter name Description
Typ e
Warning: Fl ow out of expect ations War ning for lower or hig her flow than exp ected 0: OFF Bit 2 5 0: OFF 1:ON No Warning: N o flow detecte d Flow senso r does not recogni ze any flow, through f low sensor 0 : OFF Bit 26 0: OFF 1:ON No
1.9.2 BACnet Objects - Multi State Value
Ident
MS V:12 Energy counting method R/W
MSV :14**
MSV : 41 AI input R/W
MSV: 42 T1 inpu t R/W
MSV: 43 T2 input R/W
Objec t /
Parameter name
T1, T2 temperat ure sensor type
** Only for No voCon M, L/XL
Read/ Write
1: Off 2: On, indic ated flow 3: On, flow s ensor on return pi pe 4: On, flow sensor on supply pipe
Select t emperature sens or type: 1: NTC10k Type 2 2: NTC10k Type 3
R/W
3: PT1000 4: PT500 5: PT10 0
1: Disabled 2: Analog inp ut (voltage/curre nt) 3: Flow sensor ( pulse counter)
1: Disabled 2: Supply temperature 3: Return temperature 4: Flow sensor
1: Disabled 2: Supply temperature 3: Return temperature 4: Flow sensor
St ate Te xt Default State Description
Default
Stat e 1: Off
NovoCon® is not c alculating ene rgy. State 2: On , indicated flo w NovoCon® is cal culating energ y based on temper ature differe nce between T1 and T 2 and using indica ted
1: Of f
3: PT1000 Select t he type of Temperat ure sensor conne cted for T1 and T2. Yes
2: Analog input Dif ferent options f or analog input ter minal Yes
2: Supply temp.
3: Return temp.
flow. State 3: On, f low sensor on ret urn pipe NovoCon® is cal culating energ y based on temper ature differe nce between T1 and T 2 and using flow f rom flow sens or installed on re turn pipe. State 4: On, flow sensor on supply pipe NovoCon® is cal culating energ y based on temper ature differe nce between T1 and T 2 and using flow f rom flow sensor installed on supply pipe.
Differ ent options for T1 ter minal If MSV:24 or MSV:2 5 or MSV:26 is on value 3, th en value is for resis tance, not tempe rature.
Differ ent options for T2 te rminal If MSV:24 or MSV:2 5 or MSV:26 is on value 3, th en value is for resis tance, not tempe rature.
Unit Description of usage
State
Total accumul ated water volume pa ssed through th e valve, combined f rom both heating and cooling Total accumul ated number of puls es received from flow sensor
Default
State
Description of
usage
Persistent
Yes /No
Persistent
Yes /No
Persistent
Yes /No
Yes
Yes
Yes
Yes
Yes
AM394433983821en-010103 | 9© Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
BACnet Objects - Analog Value
Ident
AV:27
Objec t /
Parameter name
Alarm summary count No unit s R na na 0 na
Unit
Read/
Write
Min Max
Default
State
Resolution Description
Numerical overview about pending errors detected. Coding for AV:27 Ala rm summary count i s: If BV:10 is active then AV:27 is 1.0. If BV:11 is active then AV:27 is 2.0. If BV:12 is active then AV:27 is 4.0 . If BV:13 is active then AV:27 is 8. 0. If BV:14 is active then AV:27 is 16.0. If BV:15 is active then AV:27 is 32.0 . If BV:16 is active then AV:27 is 6 4.0. If BV:17 is active then AV:27 is 128.0. If BV:18 is active then AV:27 is 25 6.0. If BV:19 is active then AV:27 is 512.0. If BV:20 is act ive then AV:27 is 1024.0. If BV:21 is active t hen AV:27 is 2048.0. If BV:22 is act ive then AV:27 is 4096.0. If BV:23 is act ive then AV:27 is 8192.0. If BV:24 is acti ve then AV:27 is 16384.0. If BV:25 is act ive then AV:27 is 32768.0. If BV:26 is acti ve then AV:27 is 65536.0. e.g. if both BV:11 & BV:12 are active then AV:27 is 6.0 . This objec t is supporte d by COV
Persistent
Yes /No
No
Ident
AV: 43 Pulse volume
AV: 44 Volume counter m3 R 0 na 0 Total accumulated water volume
AV: 45 Pulse counter pulse R 0 na 0 Total accumulated number of pulses Total accumulated n umber of pulses re ceived from flo w sensor Yes
Objec t /
Parameter name
Litre/pulse
Read/
Unit
(l/p)
Min Max
Write
R/W 0 na 0 Pulse v olume of connec ted flow sensor
Default
Description Information
State
Adapts auto matically to the se lected AB- QM valve, but can be o verwritten manually. If se t to 0 NovoCon only cou nt pulses and do not pe rform flow measureme nts based on rece ived pulses. Thi s can be used to conne ct e.g. water meter or energy meter.
Total accumulat ed water volume pas sed through the va lve, combined from both he ating and cooling
BACnet Objects - Binary Value
Objec t /
Ident
Parameter name
BV: 25 Warning: Flow ou t of expectat ions R ON OFF na Warnin g for lower or highe r flow than expe cted No
BV: 26 Warning: No fl ow detected R ON OFF na No flow detected with flow sensor No
Read/ Write
Active Tex t
(1)
Inactive
Text (0)
Default
State
Description
Persistent
Yes /No
Yes
Yes
Persistent
Yes /No
10 | AM394433983821en-010103 © Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
2. NovoCon® M
2.1 Description
2.2 Ordering
DN40 - DN100
With latest update on firmware for NovoCon®, flow sensor can be connected to NovoCon®
NovoCon® M actuator can be used for solutions with sizes from DN40 to DN100.
actuator, for precise measurement of flow.
AB-QM threaded version (with test plugs and without test plugs) - External thread
Picture DN
Typ e
Q
(l/h)
nom.
Ext. thread
(ISO 228/1)
With test plugs Without test plugs
Code No. Code No.
40
50
* AB-QM D N 15 -32 w/o TP can not be upgraded to ve rsion with TP
7,500
12,500
AB-QM flanged version
Picture DN
50 12,500 65 20,000 0 03Z17 73
65 HF 25,000 0 03Z17 93
80 28,000 0 03Z17 74
80 HF 40,000 003 Z1794
100 38,000 00 3Z1775
100 H F 59,000 0 03Z17 95
Temperature sensors
Typ e
Immersed Pt 1000 / Ø 5.2 mm / 1.5 m cable, MID Immersed Pt 1000 / Ø 5.2 mm / 3.0 m cable, MID
Code No.
187F3 418
187F3419
Q
(l/h)
G 2 A
G 2 ½ A
nom.
00 3Z1770
00 3Z1771
Flange
connection
(E N 1092-1)
PN 16
*
Code No.
00 3Z177 2
Accessories
Designation Code No.
Immersion brass-pockets, 52 mm, Ø 5.2 pair, MID. For pipes DN40- 65
Immersion brass-pockets, 85 mm, Ø 5.2 pair, MID. For pipes DN80-125
087G6054
087G6055
AM394433983821en-010103 | 11© Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
2.3 Technical data NovoCon® M
Power supply V 24 ±25% ac/dc
Power consumption
Frequency Hz 50 /60±10%
Control signal
Impedance
Closing force N 550 Max. stroke mm 20 Position accuracy mm ± 0.2 Actuator sp eed selections (open to close) s/mm 3, 6, 12, 24, Constant Time Max. medium temperature Ambient temperature –10 … 50 Storage and transport temperature –40 … 70 Ambient humidity 5-95% r.h., non-condensing (according to EN 60730-1) Protection class III Grade of enclosure IP 54 Weight kg 0.5
running VA <3.5@24Vac / <2. 0@24Vdc standby W 2.0 ac / 0.9 dc
VDC BACnet MS/TP, Modbus RTU, 0 -10, 0-5, 2-10, 5-10, 2-6, 6-10
mA 0 -20, 4 -20
°C
Rin 90k Ω (V). 500 Ω (mA)
Rout 250Ω
120
2.4 I/O connections NovoCon® M
2.5 Immersed sensor
With latest update on firmware for NovoCon®, flow sensor can be connected to NovoCon® actuator, for precise measurement of flow.
NovoCon® M actuator can be used for solutions with sizes from DN40 to DN100.
+24V 0V A+ B− GND T3
R on R off
T2 T1 GND GND AO AI
GND is common for a ll signals
Temperature sensors Installation Ty pe
Immersed
(direct) or in pocket (indirect)
24V AC/DC
BACnet MS/TP or Modbus RTU
Temperature sensor 3
Temperature sensor 1
Analog output
Temperature sensor 2
Analog input
Diameter
D (mm)
Pt 1000 Ø5.2 45
Length
L (mm)
Sensors pockets Typ e Brass
Sensor
diameter
Length
(mm) Ø 5.2
L1 (mm ) 60 93
L (mm) 52 85
12 | AM394433983821en-010103 © Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
2.6SonoSensor 30
2.6.1 Description
MID examination certificate no.: LT-1621-MI004-030
SonoSensor 30 is an ultrasonic flow sensor especially designed for heating, cooling or combined heating/cooling application in local and district energy systems. It can be used in conjunction with the type approved heating/ cooling energy calculator (e.g. Infocal 9) to form combined heating/cooling energy meter. SonoSensor 30 has been approved according to MID in accuracy class 2. The flow sensor can be mounted in both flow and return pipe.
Features
• Available in nominal flow rates qp 0.6, 1.0,
• 1.5, 2.5, 3.5, 6.0, 10.0, 15.0, 25.0, 40.0, and 60.0
• m³/h
• Housings with thread (G3/4 to G2) or flange (DN20 to DN100) connections
• MID approval for ultrasonic flow sensor with dynamic range of 1:100 (qi:qp) in class 2
• Optional dynamic range of 1:250 in class 2 (with the exceptions of sensors qp 0.6 m3/h,
1.0 m3/h and 3.5 m3/h)
• Temperature range: 5 - 130 °C
• Operating pressure PN 16 or PN 25 bar
• Flow sensor with IP65 protection class and IP67 for heating/cooling application.
• Battery lifetime not less than 12 years
• Low pressure loss, insensitive to dirt
• No inlet or outlet restrictions up to DN50
• Short overload temperature up to 150 °C
2.6.2 Technical specifications
Diameter DN40 DN 50 DN 65 DN 80 DN 100
Connection type G2 FL FL FL FL Overall length, mm 300 270 300 300 360
Flow rate
Nominal, m3/h 10 15 25 40 60 Maximum, m3/h 20 30 50 80 120 Minimum, l/h 40 10 0 60 15 0 25 40 60 Starting flow rate, l/h 20 30 120 200 300 Pressure loss at qp, mbar 180 120 200 180 18 0 Max. operating pressure 25 bar Flow sensor temp. range 5 to 130°C (short overload 150°C) Flow sensor to electronic
box cable length Medium Water quality with pH 7 to 9.5 Volume measuring cycles 1 second
Supply voltage
Battery lifetime Not less than 12 years Approval EN1434 class 2 Environmental class class C Ambient class E2 + M1 Protection class 65 (IP67 for heating/cooling) Ambient operating temp. +5°C to +55°C Max. ambient humidity <93% rel. humidity
3.6V DC Lithium batter y (AA-cell)/ Mains supply 24V AC/DC
Mains supply 230V AC (with external 230V to 24V AC transformer)
1.2m up to DN32
2.5m up to DN40 to DN100
AM394433983821en-010103 | 13© Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
2.7 Cross reference table AB-QM - NovoCon®M - Flow sensor:
Valve
code
00 3Z1770
00 3Z1771
00 3Z177 3
00 3Z179 3
00 3Z1774
00 3Z179 4
00 3Z1775
00 3Z179 5
Valve name
AB-Q M NovoCon DN40
7. 5 m3 /h
AB-Q M NovoCon DN50
12. 5 m3/ h
AB-Q M NovoCon DN65
20.0 m3/h
AB-Q M NovoCon DN65 HF
25.0 m3/h
AB-Q M NovoCon DN80
28.0 m3/h
AB-Q M NovoCon DN80 HF
40.0 m3/h
AB-Q M NovoCon DN100
38.0 m3/h
AB-Q M NovoCon DN100 HF
59.0 m3/ h
Valve
connection
thread
thread
flange
flange
flange
flange
flange
flange
Actuator
code
003Z8540
003Z8540
003Z8540
003Z8540
003Z8540
003Z8540
003Z8540
003Z8540
Actuator
name
NovoCon M
NovoCon M
NovoCon M
NovoCon M
NovoCon M
NovoCon M
NovoCon M
NovoCon M
Flowmeter
code
187F3776
187F3776
187F3777
187F3778
187F3778
187F3779
187F3779
187F3780
SonoS30 DN 40 Qp 10.0 m3/h thread /
SonoS30 DN 40 Qp 10.0 m3/h thread /
SonoS30 DN5 0 Qp 15.0 m3/h flange /
SonoS30 DN 65 Qp 25.0 m3/h flan ge /
SonoS30 DN 65 Qp 25.0 m3/h flan ge /
SonoS30 DN 80 Qp 40.0 m3/h f lange /
SonoS30 DN 80 Qp 40.0 m3/h f lange /
SonoS30 DN100 Qp 6 0.0
Flowmeter name
m3/h
Flowmeter
connection
flange /
NovoCon
S cable
Temperature
sensor code
(PT1000)
Temperature pockets code
187F3 418 087G6054
187F3 418 087G6054
187F3419 087G6054
187F3419 087G6054
187F3419 087G6055
187F3419 087G6055
187F3419 087G6055
187F3419 087G6055
2.8 Commissioning/wiring
NovoCon® M supports connection of flow sensor directly to NovoCon® inputs. Flow sensor must be connected to T3 and GND terminal. NovoCon must be set to digital mode (MSV:9/32810 = 2). You also need to select T3 (MSV: 44/32821) input for connecting flow sensor.
To get right flow sensor value it is verry important to set right value of liters per pulse on NovoCon® (AV: 43/32864). Usually this is written on flow sensor specification sheet. If we would like to use flow sensor for calculating energy we must also change register MSV12/32814*.
T3
NovoCon® M
+24V 0V A+ B− GND T3
R on R off
T2 T1 GND GND AO AI
SonoSensor 30
18 19
Terminal Nr. Description
19 Volume pulse putput (+) 18 Ground (-)
Object/Register Write/read value Description
MSV:44 / 32824 3: Flow sensor T3 input AV:43 / 32864 0,04 (depends on flow sensor) Pulse volume (liter/pulse) MSV:12 / 32814 3: ON, flow sensor on return pipe Energy counting method*
*Energy counting method MSV: 12 / 32814 State 1: Off NovoCon® M is not calculating energy. State 2: On, indicated flow NovoCon® M is calculating energy based on temperature difference between T1 and T2 and using indicated flow. State 3: On, flow sensor on return pipe NovoCon® M is calculating energy based on temperature difference between T1 and T2 and using flow from flow sensor installed on return pipe. State 4: On, flow sensor on supply pipe NovoCon® M is calculating energy based on temperature difference between T1 and T2 and using flow from flow sensor installed on supply pipe.
14 | AM394433983821en-010103 © Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
2.9 BACnet and Modbus
2.9.1 Modbus registers
Configuration
Modbus
Read/
register
0x802E
32814
Modbus
Write
function
R/W 3, 4 & 6 WORD
Configuration #2
Modbus
Read/
register
0x8033
32819
0x8034
32820* *
0x8035
32821
0x8036
32822
0x8 037
32823
0x8038
32824**
0x8060
32864
** Only for No voCon M, L/XL
Modbus
Write
function
R/W 3, 4 & 6 WO RD
R/W 3, 4 & 6 WO RD
R/W 3, 4 & 6 WO RD AI input
R/W 3, 4 & 6 WO RD T1 input Different op tions for T1 termin al
R/W 3, 4 & 6 WO RD T2 inpu t Dif ferent options fo r T2 terminal
R/W 3, 4 & 6 WO RD T3 inpu t Dif ferent options fo r T3 terminal
R/W 3, 4 & 16 FLOAT Pulse volume
Modbus
Data Typ e
Modbus
Da ta Typ e
Objec t /
Parameter
name
Energy counting
method
Objec t / Parameter name
T1, T2 temper ature sensor type
T3 tempe rature sensor type
Description
1: Off 2: On, indi cated flow 3: On, flo w sensor on return p ipe 4: On, fl ow sensor on supply p ipe
Description
Selec t the type of Temper ature sensor co nnected for T1 an d T2.
Selec t the type of Temper ature sensor connected for T3.
Diffe rent options for an alog input terminal
Pulse volu me of connected f low sensor
Default
Description of usage
State
Sta te 1: Off
NovoCon® is n ot calculating en ergy. State 2: O n, indicated fl ow NovoCon® is calculating energy based on temperature difference between T1 and T2 and u sing indicated f low.
1: Of f
State 3: On , flow sensor on r eturn pipe NovoCon® is calculating energy based on temperature difference between T1 and T2 and u sing flow from f low sensor insta lled on return pip e. State 4: On, flow sensor on supply pipe NovoCon® is calculating energy based on temperature difference between T1 and T2 and using flow from flow sensor installed on supply pipe.
Default
State
3: PT1000 na
3: PT1000 na
2: Analog
input
2: Supply
temp.
3: Return
temp.
2: Control
temp.
0,4 l/p
Unit Description of usage
Select temperature sensor type: 1: NTC10k Type 2
Select temperature sensor type: 1: NTC10k Type 2 2: NTC10k Type 3
1: Disabled
na
2: Analog i nput (voltage/curr ent) 3: Flow sensor
1: Disabled
na
2: Supply temperature 1: Disabled
na
2: Supply temperature 1: Disabled
na
2: Control te mperature sens or Adapts au tomatically to the s elected AB- QM valve, but
can be over written manu ally. If set to 0 NovoCon o nly
Litre/
count puls es and do not perf orm flow measur ements
pulse
based on r eceived pulses . This can be used to co nnect e.g. water meter or energy meter.
2: NTC10k Type 3 3: PT1000
3: PT1000 4: PT500 5: PT 100
3: Return temperature 4: Flow sensor
3: Return temperature 4: Flow sensor
3: Flow sensor Yes
Persistent
Yes /No
Yes
Persistent
Yes /No
Yes
Yes
Yes
Yes
Yes
Yes
Operating
Modbus
Read/
register
0x8 210
33296
0x 8212
33298
Modbus
Write
function
R 3, 4 FLOAT Volume counter Total accumulated water volume 0 L
R 3, 4 FLOAT Pulse counter Total accumulated number of pulses 0 pulse
Alarms & warning
Modbus
Read/
register
0x8300
33536
Modbus
Write
function
R 3, 4 F LOAT
Modbus
Data
Object / Parameter name Description
Typ e
Modbus
Da ta Typ e
Object / Parameter name Description
Warning: Fl ow out of expect ations War ning for lower or hi gher flow than ex pected 0: OFF B it 25 0: OFF 1:ON No
Warning: N o flow detecte d Flo w sensor does not re cognize any flow, th rough flow sens or 0 : OFF Bit 26 0: O FF 1:ON No
Default
State
Unit Description of usage
Total accumul ated water volume pa ssed through th e valve, combined f rom both heating and cooling Total accumul ated number of puls es received from flow sensor
Default
State
Description of usage
Persistent
Yes /No
Yes
Yes
Persistent
Yes /No
AM394433983821en-010103 | 15© Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
2.9.2 BACnet Objects - Multi State Value
Ident
MS V:12 Energy counting method R/W
MSV :14**
MSV :15**
MSV : 41 AI input R/W
MSV: 42 T1 inpu t R/W
MSV: 43 T2 input R/W
MSV: 44** T3 input R/W
Objec t /
Parameter name
T1, T2 temperat ure sensor type
T3 temper ature sensor type
** Only for No voCon M, L/XL
BACnet Objects - Analog Value
Ident
AV:27
Objec t /
Parameter name
Alarm summary count No unit s R na na 0 na
Read/
St ate Te xt Defaul t State Description
Write
1: Off 2: On, indic ated flow 3: On, flow s ensor on return pi pe 4: On, flow sensor on supply pipe
Select t emperature sens or type: 1: NTC10k Type 2 2: NTC10k Type 3
R/W
3: PT1000 4: PT500 5: PT10 0
Select t emperature sens or type: 1: NTC10k Type 2 2: NTC10k Type 3
R/W
3: PT1000 4: PT500 5: PT10 0
1: Disabled 2: Analog inp ut (voltage/curre nt) 3: Flow sensor ( pulse counter)
1: Disabled 2: Supply temperature 3: Return temperature 4: Flow sensor
1: Disabled 2: Supply temperature 3: Return temperature 4: Flow sensor
1: Disabled 2: Control temperature 3: Flow sensor
Read/
Unit
Write
Min Max
1: Of f
3: PT1000 Select t he type of Temperat ure sensor conne cted for T1 and T2. Yes
3: PT1000 Select t he type of Temperat ure sensor conne cted for T3 Yes
2: Analog input Dif ferent options f or analog input ter minal Yes
2: Supply temp.
3: Return temp.
2: Control temp.
Default
State
Stat e 1: Off
NovoCon® is not c alculating ene rgy. State 2: On , indicated flo w NovoCon® is cal culating energ y based on temper ature differe nce between T1 and T 2 and using indica ted flow. State 3: On, f low sensor on ret urn pipe NovoCon® is cal culating energ y based on temper ature differe nce between T1 and T 2 and using flow f rom flow sens or installed on re turn pipe. State 4: On, flow sensor on supply pipe NovoCon® is cal culating energ y based on temper ature differe nce between T1 and T 2 and using flow f rom flow sensor installed on supply pipe.
Differ ent options for T1 ter minal If MSV:24 or MSV:2 5 or MSV:26 is on value 3, th en value is for resis tance, not tempe rature.
Differ ent options for T2 te rminal If MSV:24 or MSV:2 5 or MSV:26 is on value 3, th en value is for resis tance, not tempe rature.
Differ ent options for T3 te rminal If MSV:24 or MSV:2 5 or MSV:26 is on value 3, th en value is for resis tance, not tempe rature.
Resolution Description
Numerical overview about pending errors detected. Coding for AV:27 Ala rm summary count i s: If BV:10 is active then AV:27 is 1.0. If BV:11 is active then AV:27 is 2.0. If BV:12 is active then AV:27 is 4.0 . If BV:13 is active then AV:27 is 8. 0. If BV:14 is active then AV:27 is 16.0. If BV:15 is active then AV:27 is 32.0 . If BV:16 is active then AV:27 is 6 4.0. If BV:17 is active then AV:27 is 128.0. If BV:18 is active then AV:27 is 25 6.0. If BV:19 is active then AV:27 is 512.0. If BV:20 is act ive then AV:27 is 1024.0. If BV:21 is active t hen AV:27 is 2048.0. If BV:22 is act ive then AV:27 is 4096.0. If BV:23 is act ive then AV:27 is 8192.0. If BV:24 is acti ve then AV:27 is 16384.0. If BV:25 is act ive then AV:27 is 32768.0. If BV:26 is acti ve then AV:27 is 65536.0. e.g. if both BV:11 & BV:12 are active then AV:27 is 6.0 . This objec t is supporte d by COV
Persistent
Yes /No
Yes
Yes
Yes
Yes
Persistent
Yes /No
No
Ident
AV: 43 Pulse volume
AV: 44 Volume counter m3 R 0 na 0 Total accumulated water volume
AV: 45 Pulse counter pulse R 0 na 0 Total accumulated number of pulses Total accumul ated number of puls es received from f low sensor Yes
Objec t /
Parameter name
Litre/pulse
Read/
Unit
(l/p)
Min Max
Write
R/W 0 na 0 Pulse v olume of connec ted flow sensor
Default
State
Description Information
Adapts auto matically to the se lected AB- QM valve, but can be o verwritten manually. If se t to 0 NovoCon only cou nt pulses and do not pe rform flow measureme nts based on rece ived pulses. Thi s can be used to conne ct e.g. water meter or energy meter.
Total accumulat ed water volume pas sed through the va lve, combined from both he ating and cooling
BACnet Objects - Binary Value
Objec t /
Ident
Parameter name
BV: 25 Warning: Flow ou t of expectat ions R ON OFF na Warning fo r lower or higher f low than expec ted No
BV: 26 Warning: No fl ow detected R ON OFF na No flow detected with flow sensor No
Read/ Write
Active
Tex t (1)
Inactive
Text (0)
Default
State
Description
Persistent
Yes /No
Yes
Yes
Persistent
Yes /No
16 | AM394433983821en-010103 © Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
3. NovoCon® L/XL
3.1 Description
With latest update on firmware for NovoCon® L/ XL, flow sensor can be connected to NovoCon® actuator, for precise measurement of flow. NovoCon® L actuator can be used for solutions with sizes from DN125 to DN150.
NovoCon® XL actuator can be used for solutions with sizes from DN200 to DN250.
Novo Con® XLNovo Con® L
3.2 Ordering
DN125 - DN250
AB-QM flanged version
Picture DN
125 90,000
125 HF 110,000 003Z0 715
150 145,000 003Z0706
150 HF 190,000 003Z 0716
200 200,000 003Z0707
200 HF 270,000 00 3Z0717
250 300,000 003Z070 8
250 HF 370,000 003Z 0718
Temperature sensors
Typ e
Immersed Pt 1000 / Ø 5.2 mm / 3.0 m cable, pair, MID
Code No.
187F3419
Q
(l/h)
nom.
Flange
connection
(E N 1092-1)
PN 16
Code No.
003Z0705
Accessories
Designation Code N o.
Immersion brass-pockets, 85 mm, Ø 5.2 pair, MID. For pipes DN80-125
Immersion brass-pockets, 120 mm, Ø 5.2 pair, MID. For pipes DN150-200
Immersion stainless steel-pockets, 155mm, Ø
5.2 pair, MID. For pipes DN250
087G6055
087G6056
087G6059
AM394433983821en-010103 | 17© Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
3.3 Technical data
1)
Factory se tting of the valve is done at
nominal setting range.
2)
Re gardless of the setting, th e valve
can modulate be low 1 % of set flow.
3)
Wh en set above 100 %, minimum
starting pres sure needed is higher, see figure s in the ().
4)
In case A B-QM is used above 400 k Pa
differe ntial pressure contact Danfoss design center to assure p roper design.
5)
At mi n differential pressure val ve
reaches at leas t 90% of nominal flow. Declarati on of performance is available upon request.
Pc - pressure controll er part Cv - Control valve part
Nominal diameter DN 125 12 5 HF 150 150 HF 200 200 HF 250 250 HF
Flow range
Setting range
Diff. pressure
3),
4),
5)
Q
nom
Q
high
2)
p p
(100 %)
3)
min
max
1)
90,000 110,000 145,000 190,000 200,000 270,000 300,000 370,000
l/h
100,000 120,000 160,000
209,000
% 40 -110
40 (60) 60 (80) 40 (60) 60 (80) 45 (65) 60 (80) 45 (65) 60 (80)
kPa
600 600
600
600 600 600 600 600
220,000
300,000 330,000 407,000
Pressure stage PN 16 Control range 1:1000 Control valve’s characteristic Linear (could be converted by actuator to equal percentage) Leakage rate with recommended
actuators
max.0.01 % of Q
nom
Water and water mixture for closed heating and cooling systems according to plant t ype
Flow medium
I for DIN EN 14868. When used in plant Type II for DIN EN 14868 appropriate protec tive
measures are taken. The requirements of VDI 2035, part 1 + 2 are observed. Medium temperature Storage and transport temp. –40 … 70
°C
−10 ... +120
Stroke mm 30
Connection
flange PN 16 actuator Danfoss standard
Materials in the water
Valve bodies Grey iron EN-GJL-250 (GG 25) Membranes/ Bellow W.Nr.1. 4571 EPDM O-rings EPDM Springs W. Nr.1.4401 W.N r.1.4310 Cone (Pc) W.Nr.1.4404NC W.Nr.1.4021 Seat (Pc) W.N r.1.4027 Cone (Cv) W.Nr.1.4404NC W.N r.1.4021 Seat (Cv) W.N r.1.40 27 Screw W.N r.1.1181 Flat gasket Graphite gasket Non asbestos
3.4 I/O connections on NovoCon® L, XL
Flow sensor can be connected on any input on NovoCon® L/XL. Danfoss recommends using T3 input, so NovoCon® can still be controlled over AI and keep energy features.
GND is common for a ll signals
18 | AM394433983821en-010103 © Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
3.5 Immersed sensor
3.6 SONO 3500 CT
3.6.1 Description
Temperature sensors Installation Ty pe
Sensors pockets Typ e Brass Stainless steel
The SONO 3500 CT is an ultrasonic flow sensor especially designed for heating, cooling or combined heating/cooling application in local and district energy systems. In combination with INFOCAL 9 it becomes energy meter for heating or cooling.
Immersed (direct) or
in pocket (indirect)
Sensor
diameter
Length
Diameter
D (mm)
Pt 1000 Ø 5.2 45
(mm) Ø 5. 2 Ø 5.2
L1 (mm ) 93 128 168
L (mm) 85 120 15 5
Length
L (mm)
The SONO 3500 CT has been approved according to MID class 2. The approved flow sensor consists of a flow sensor pipe, 4 transducers with cables and a transmitter with LCD display.
Features
• Ultrasonic 2-path flow sensor secures measurement and optimum accuracy
• Galvanically isolated digital output for easy connection to energy calculator INFOCAL 9
• 115 / 230 V mains-powered with back-up battery as standard version in case of mains power failure
• Optional battery-powered version
(up to 6 years lifetime)
• Fast measuring frequency 15 Hz / 0.5 Hz (230 V AC / Battery)
• Compact (standard) or remote mounting
• No pressure drop
• Long-term stability
• Easy one-button straight forward display
AM394433983821en-010103 | 19© Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
3.6.2 Technical specifications
Diameter Nominal DN (mm) 100 12 5 150 2 250 300 35 40 500 60 7 800 900 1000 120 0
Nominal qp (m3/h) 120 200 300 500 800 1120 150 0 190 0 2950 430 0 5800 7600 10000 10000 10000
Highest
Flow rate ranges
operatable
Maximum q
Minimum qi (m3/h) 1. 2 2 3 5 8 11 .2 15 19 29.5 43 58 76 100 10 0 200
Cut−o ff m3/h 0. 3 0.5 0.75 1.25 2 2.8 3.75 4.75 7. 375 10.75 14. 5 19 25 30 45
Operating pressure
Maximum PN (bar) 16/40 16/25/4 0 16/2 5 16
Dynamic range qi : q Pulse output value l/p 2.5 2.5 2.5 10 10 10 10 50 50 100 10 0 100 100 100 100 Pulse width ms 5 Flow velocity m/s 0.02 … 9 Measuring frequency Hz 15 Hz (mains supply - standard) / 0.5 Hz (battery supply)
Power supply
Medium Heating water, according to VDI-2035 (pH 8.2 - 10.5), industrial VdTÜV 1466 and AGFW FW510
Media/ surface temperature
Compact
standard
Remote °C 5 … 200
Environmental class MID class E2 + M1
Protection class IP 67 according to EN 60529 and DIN 40050 (NEMA 4X/6)
Basic features
Storage
temperature
Ambient
temperature Pipe material Carbon Steel EN 1.0345 / P235 GH, painted in light-gray
Remote version cable length 5 m / 10 m / 20 m / Max. 30 m between transmitter and flow sensor
qs (m3/h) 180 280 420 700 11 20 156 0 210 2660 4130 6020 812 0 106 40 14000  
(m3/h) 189 294 4 41 735 1176 16 38 2205 2793
max
p
Mains supply
(standard)
Batter y
supply
115 / 230 V AC, including 3.6 V single batter y backup
3.6 V battery version, incl. dual battery pack
1:100 1:50
4336.5
6321 8526 11172 147 00 1470 0 1470 0
°C 5 … 120
°C − 40 … 85
°C −10 … 55
3.7 Cross reference table AB-QM - NovoCon®M - Flow sensor:
Valve
code
003Z0705
003 Z0715
003Z0706
003 Z0716
003Z0707
00 3Z0717
003Z0708 AB-QM DN25 0 300.0 m3/h flange 003Z8 563 Novo Con XL 187F3532 SO NO 3500 CT DN150 Qp 150.0 m3/h flange / 187F3419 087G6059
003 Z0718 AB- QM DN250 HF 370.0 m3/h f lange 003Z8563 Novo Con XL 187F3532 SO NO 3500 CT DN150 Qp 150.0 m3/h flange / 187F3419 087G6059
Valve name
AB-Q M DN12 5 90.0 m3/h
AB-Q M DN12 5 HF 110.0 m3/h
AB-Q M DN15 0 150.0 m3/h
AB-Q M DN15 0 HF 190.0 m3/h
AB-Q M DN200 220.0 m3/h
AB-Q M DN200 HF 285.0 m3/h
Valve
connection
Actuator
code
flange 0 03Z8560 NovoCo n L 187F3530 SONO 350 0 CT DN100 Qp 60.0 m3/h flange / 187F3419 087G6055
flange 0 03Z8560 NovoCo n L 187F3530 SONO 350 0 CT DN100 Qp 60.0 m3/h flange / 187F3419 087G6055
flange 0 03Z8560 NovoCo n L 187F3531 SONO 35 00 CT DN125 Qp 100.0 m3/h f lange / 187F3419 087G6056
flange 0 03Z8560 NovoCo n L 187F3531 SONO 35 00 CT DN125 Qp 100.0 m3/h f lange / 187F3419 087G6056
flange 0 03Z8563 N ovoCon XL 187F3531 SON O 3500 CT DN125 Qp 100.0 m3/h flange / 187F3419 087G6056
flange 0 03Z8563 N ovoCon XL 187F3532 SONO 3500 C T DN150 Qp 150.0 m3/h flange / 187F3419 087G6056
Actuator
name
Flowmeter
code
Flowmeter name
Flowmeter
connection
NovoCon S
cable
Temperature
sensor code
(PT1000)
Temperature
pockets
code
20 | AM394433983821en-010103 © Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
3.8 Commissioning/wiring
NovoCon® L/XL supports connection of flow sensor directly to NovoCon® inputs. Flow sensor must be connected to T3 and GND terminal. NovoCon must be set to digital mode (MSV:9/32810 = 2). You also need to select T3 (MSV: 44/32821) input for connecting flow sensor.
To get right flow sensor value it is verry important to set right value of liters per pulse on NovoCon® (AV: 43/32864). Usually this is written on flow sensor specification sheet. If we would like to use flow sensor for calculating energy we must also change register MSV12/32814*.
T3
GND si common for all signals
Object/Register Write/read value Description
MSV:44 / 32824 3: Flow sensor T3 input AV:43 / 32864 0,04 (depends on flow sensor) Pulse volume (liter/pulse) MSV:12 / 32814 3: ON, flow sensor on return pipe Energy counting method*
NovoCon L/XL
SONO 3500 CT
56 57
Terminal Nr. Description 56 Volume pulse output (+) 57 Ground (-)
*Energy counting method MSV: 12 / 32814 State 1: Off NovoCon® L/XL is not calculating energy. State 2: On, indicated flow NovoCon® L/XL is calculating energy based on temperature difference between T1 and T2 and using indicated flow. State 3: On, flow sensor on return pipe NovoCon® L/XL is calculating energy based on temperature difference between T1 and T2 and using flow from flow sensor installed on return pipe. State 4: On, flow sensor on supply pipe NovoCon® L/XL is calculating energy based on temperature difference between T1 and T2 and using flow from flow sensor installed on supply pipe.
AM394433983821en-010103 | 21© Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
3.9 BACnet and Modbus
3.9.1 Modbus registers
Configuration
Modbus register
0x802E
32814
Read/ Write
R/W 3, 4 & 6 WORD
Modbus function
Modbus
Configuration #2
Modbus
Read/
register
0x8033
32819
0x8034
32820* *
0x8035
32821
0x8036
32822
0x8 037
32823
0x8038
32824**
0x8060
32864
* Not suitable for SO NO 3500 CT! ** Only for No voCon M, L/XL
Modbus
Write
function
R/W 3, 4 & 6 WO RD
R/W 3, 4 & 6 WO RD
R/W 3, 4 & 6 WO RD AI inp ut
R/W 3, 4 & 6 WO RD T1 input Differen t options for T1 term inal
R/W 3, 4 & 6 WO RD T2 input Differen t options for T2 ter minal
R/W 3, 4 & 6 WO RD T3 input Differen t options for T3 ter minal
R/W 3, 4 & 16 FLOAT Pulse volume
Data Typ e
Modbus
Da ta Typ e
Objec t /
Parameter
name
Energy counting
method
Objec t / Parameter name
T1, T2 temper ature
sensor type
T3 tempe rature
sensor type
Description
1: Off 2: On, indi cated flow 3: On, flo w sensor on return p ipe 4: On, fl ow sensor on supply p ipe
Description
Selec t the type of Temper ature sensor co nnected for T1 an d T2.
Selec t the type of Temper ature sensor connected for T3.
Diffe rent options for an alog input terminal
Pulse volu me of connected f low sensor
Default
Description of usage
State
Sta te 1: Off
NovoCon® is n ot calculating en ergy. State 2: O n, indicated fl ow NovoCon® is calculating energy based on temperature difference between T1 and T2 and u sing indicated f low.
1: Of f
State 3: On , flow sensor on r eturn pipe NovoCon® is calculating energy based on temperature difference between T1 and T2 and u sing flow from f low sensor insta lled on return pip e. State 4: On, flow sensor on supply pipe NovoCon® is calculating energy based on temperature difference between T1 and T2 and u sing flow from f low sensor insta lled on supply pi pe.
Default State
3: PT1000 na
3: PT1000 na
2: Analog
input
2: Supply
temp.
3: Return
temp.
2: Control
temp.
0,4 l/p
Unit Description of usage
Select temperature sensor type: 1: NTC10k Type 2
Select temperature sensor type: 1: NTC10k Type 2 2: NTC10k Type 3
1: Disabled
na
2: Analog i nput (voltage/curr ent) 3: Flow sensor*
1: Disabled
na
2: Supply temperature
1: Disabled
na
2: Supply temperature
1: Disabled
na
2: Control te mperature sensor
Adapts au tomatically to the s elected AB- QM valve, but can be over written manu ally. If set to 0 NovoCon o nly
Litre/
count puls es and do not perf orm flow measur ements
pulse
based on r eceived pulses . This can be used to co nnect e.g. water meter or energy meter.
2: NTC10k Type 3 3: PT1000
3: PT1000 4: PT500 5: PT 100
3: Return temperature 4: Flow sensor
3: Return temperature 4: Flow sensor
3: Flow sensor Yes
Persistent
Yes /No
Yes
Persistent
Yes /No
Yes
Yes
Yes
Yes
Yes
Yes
Operating
Modbus
Read/
register
0x8 210
33296
0x 8212
33298
Modbus
Write
function
R 3, 4 FLOAT Volume counter Total accumulated water volume 0 L
R 3, 4 FLOAT Pulse counter Total accumulated number of pulses 0 pulse
Alarms & warning
Modbus
Read/
register
0x8300
33536
Modbus
Write
function
R 3, 4 FLOAT
Modbus
Data
Object / Parameter name Description
Typ e
Modbus
Data
Object / Parameter name Description
Typ e
Warning: Fl ow out of expect ations
Warning: N o flow detecte d
Default
Unit Description of usage
State
Total accumul ated water volume pa ssed through th e valve, combined f rom both heating and cooling
Total accumul ated number of puls es received from flow sensor
Warning for lower or higher f low than expected Flow sensor does not recognize any flow, through flow
sensor
Default State
Description of usage
0: OFF Bit 2 5 0: OFF 1:ON No
0: OFF Bit 26 0 : OFF 1:ON No
Persistent
Yes /No
Yes
Yes
Persistent
Yes /No
22 | AM394433983821en-010103 © Danfoss | 2022.02
Fact sheet NovoCon® S, M, L, XL and Flow sensor
3.9.2 BACnet Objects - Multi State Value
Ident
MS V:12
MS V:14**
MS V:15**
MS V: 41 A I input R/W
MSV: 42 T1 i nput R/W
MSV: 43 T2 inpu t R/W
MSV: 44* * T3 input R/W
* Not suitable for SO NO 3500 CT! ** Only for No voCon M, L/XL
Objec t /
Parameter name
Energy counting
method
T1, T2 temper ature
sensor type
T3 tempe rature
sensor type
Read/
St ate Te xt Defaul t State Description
Write
1: Off 2: On, indi cated flow 3: On, flo w sensor on return
R/W
pipe 4: On, fl ow sensor on supply pipe
Select temperature sensor type: 1: NTC10k Type 2
R/W
2: NTC10k Type 3 3: PT1000 4: PT500 5: PT 100 Select temperature sensor type: 1: NTC10k Type 2
R/W
2: NTC10k Type 3 3: PT1000 4: PT500 5: PT 100 1: Disabled 2: Analog i nput (voltage/ current) 3: Flow sensor* 1: Disabled 2: Supply temperature 3: Return temperature 4: Flow sensor 1: Disabled 2: Supply temperature 3: Return temperature 4: Flow sensor 1: Disabled 2: Control temperature 3: Flow sensor
1: Of f
3: PT1000 Selec t the type of Temper ature sensor conne cted for T1 and T2 . Yes
3: PT1000 Selec t the type of Temper ature sensor conne cted for T3 Yes
2: Analog input Diffe rent options for an alog input termi nal Ye s
2: Supply temp.
3: Return temp.
2: Control temp.
State 1: Off NovoCon® is n ot calculating en ergy. State 2: On, in dicated flow NovoCon® is c alculating ener gy based on tempe rature differ ence between T1 a nd T2 and using indi cated flow. State 3: On, f low sensor on retu rn pipe NovoCon® is c alculating ener gy based on tempe rature differ ence between T1 a nd T2 and using fl ow from flow sens or installed on r eturn pipe. State 4: On, f low sensor on sup ply pipe NovoCon® is c alculating ener gy based on tempe rature differ ence between T1 a nd T2 and using flow from flow sensor installed on supply pipe.
Diffe rent options for T1 te rminal If MSV:24 or MS V:25 or MSV:26 is on value 3, t hen value is for res istance, not temp erature.
Diffe rent options for T 2 terminal If MSV:24 or MS V:25 or MSV:26 is on value 3, t hen value is for res istance, not temp erature.
Diffe rent options for T 3 terminal If MSV:24 or MS V:25 or MSV:26 is on value 3, t hen value is for res istance, not temp erature.
Persistent
Yes /No
Yes
Yes
Yes
Yes
BACnet Objects - Analog Value
Ident
AV:27 Alarm summary count No u nits R na na 0 na
Ident
AV: 43 Pulse vo lume
AV: 44 Volume counter m3 R 0 na 0 Total accumulated water volume
AV: 45 Pulse counter pulse R 0 na 0 Total accumulated number of pulses
Objec t /
Parameter name
Objec t /
Parameter name
Unit
Litre/pulse
(l/p)
Read/
Unit
Read/ Write
R/W 0 na 0 Pu lse volume of conne cted flow sens or
Write
Min Max
Min Max
Default
Default
State
Resolution Description
State
Description Information
Numerical overview about pending errors detected. Coding fo r AV:27 Alarm su mmary count is: If BV:10 is active the n AV:27 is 1.0. If BV:11 is active then AV:27 is 2.0 . If BV:12 is active then AV:27 is 4. 0. If BV:13 is active then AV:27 is 8 .0. If BV:14 is active then AV:27 is 16. 0. If BV:15 is active then AV:27 is 32. 0. If BV:16 is active the n AV:27 is 64.0 . If BV:17 is active then AV:27 is 128.0. If BV:18 is active the n AV:27 is 256.0. If BV:19 is active then AV:27 is 512.0. If BV:20 is ac tive then AV:27 is 1024.0. If BV:21 is acti ve then AV:27 is 2048.0. If BV:22 is ac tive then AV:27 is 4096. 0. If BV:23 is ac tive then AV:27 is 8192.0. If BV:24 is act ive then AV:27 is 16384.0. If BV:25 is ac tive then AV:27 is 32768.0. If BV:26 is ac tive then AV:27 is 65536.0. e.g. if bot h BV:11 & BV:12 ar e active then AV:27 is 6.0. This obje ct is support ed by COV
Adapts au tomatically to the s elected AB- QM valve, but can be over written manu ally. If set to 0 NovoCon o nly count puls es and do not perf orm flow measur ements based on r eceived pulses . This can be used to co nnect e.g. water meter or energy meter. Total accumul ated water volume pa ssed through the valve, com bined from both h eating and coolin g Total accumul ated number of puls es received from flow sensor
BACnet Objects - Binary Value
Ident
BV: 25 Warning: Flow o ut of expecta tions R ON O FF na Warning for l ower or higher fl ow than expect ed
BV: 26 Warni ng: No flow detec ted R ON OFF na No flow detected with flow sensor
Objec t /
Parameter name
Read/ Write
Active
Tex t (1)
Inactive
Text (0)
Default
State
Description
Persistent
Yes /No
No
Persistent
Yes /No
Yes
Yes
Yes
Persistent
Yes /No
No
No
AM394433983821en-010103 | 23© Danfoss | 2022.02