Danfoss NovoCon S Operating guide

Operating Guide
NovoCon® S - High Accuracy Actuator
NovoCon® S / 73690900
IP54
DN 15 - 32
NO presetting!
DN 15, 20
10 [100 % ]
IP54
IP40
DN 25, 32
100 %
IP54
Manuel Calibration: Press button until two LED’s are turned on, and then release again. DIP switch: Manual override: Adjust wheel
Common ground shall be used for all devices on the same network.
NovoCon® digital cable
Actuator NovoCon®
NovoCon® Energy cable
- PT1000 surface sensors
NovoCon® Energy cable
- PT1000 immersed sensors
Red Power
Black
Green ´+´ non-inverting signal wire
White/green ´−´ inverting signal wire
ChangeOver
Purple O-ring
Common ground for power and bus signal wire
6
Actuator NovoCon®
ChangeOver6 Energy
Blue O-ring
NovoCon® I/O cable
Cable NovoCon® Temperature I/O
Digital port
Port for CO6 actuator or Energy cable, I/O cable, analog cable or voltage booster.
Digital port
NovoCon® analog cable
Red Power 24V
Black GND
Grey Analog input or Flow sensor
Blue Analog input ground
Actuator NovoCon® ChangeOver6 Flexible
Red Power 24V
Black GND
White CO6 Control signal
Grey CO6 Feedback signal
Red Power 24V Black Blue Ground T1, T2, V/mA input & V output signal Grey V/mA input signal or Flow sensor White V output signal Yellow T1, resistance input or Flow sensor Orange T2, resistance input or Flow sensor
Red Power 24V (in/out) Black Blue Ground T1, T2, V/mA input & V output signal Grey V/mA input signal or Flow sensor White V output signal T1 T2
Power ground
Power ground (in/out)
AQ251486498741en-010602 | 1© Danfoss | 2021.11
NovoCon® S - High Accuracy Actuator
MADE IN SLOVENIA
6430 Nordborg, Denmark
®
NovoCon S
003Z8504
Actuator for AB-QM DN10-32
Control signal: BACnet MS/TP, Modbus RTU, 0-10V, 0-20mA
Power: 24VAC/DC, 50/60 HZ
Force: 90N. Stroke: 7 mm. Speed: 3-24s/mm
Consumption: 3.3VA running. Standby 0.9W
IP54/40, -10T55
DIP Switch
1 2 3 4 5 6 7 8 9 10
DIP Switches 1 to 7 are used to assign the MAC address manually. Default MAC address assignment method is Auto MAC addressing for BACnet MS/TP and DIP Switches for Modbus RTU. For termination of last unit on the field bus, turn DIP Switch 8 ON. Dip switch 9 is not used. Dip switch 10 is used to select between BACnet MS/TP (OFF=Default) and Modbus RTU (ON).
Initial configuration
NovoCon® S
Inverted CO6 without alarms,
Analog inverted CO6 mode
Application mode:
MSV:9 / 32810
Digital control (default),
Analog control,
CO6 mode, Inverted CO6 mode, CO6 without alarms,
Analog CO6 mode,
When the protocol is changed on DIP Switch 10, a power cycle is required.
E100 VXX
01
281624 0030471
III
6430 Nordborg, Denmark
MADE IN SLOVENIA
01
E100 VXX 281624 0030471
Serial number and QR code can be removed from the NovoCon® S label and added to installation drawing.
01
E100 VXX 281624 0030471
Device Object Instance Number
Optional step (connecting flow sensor)
ON
OFF
Terminal Nr. Description
18 Volume pulse output (+)
19 Ground (-)
Select Valve Type
MSV:3 / 32802
(default AB-QM 4.0
ISO DN 15)
Select application
MSV:10 / 32811
Heating (default)
Cooling
Design Flow Rate
AV:30 / 32796
Heating
AV:31 / 32798
Cooling
24 V
SonoSensor 30Cable NovoCon® I/O
GND GND
AI
AO
T1 T2
Activate calibration
MSV:0 / 33284 state 2
or use manual
calibration
19
18
Safety Note
To avoid injury and damage to p ersons and devices, it is absolutely necessar y these instructions are carefull y read and observed prior to asse mbly and commissioning.
Necessary assembl y, start-up, and maintenance work must be performed only by qualified, trained and authorised personnel. Switch off the power lin e before wiring the actuator.
Safety Note
Connect via safety isolating transformer.
Galvanic sep arations shall be provided fo r segments crossing buildin gs.
Part Name
部件名称
Union nut /
连接螺母
O: Indica tes that this hazar dous substance con tained in all of the h omogeneous ma terial for this par t is below the limi t requirement in GB /T 26572; O: 表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572规定的限量要求以下。
X: Indica tes that this hazar dous substance co ntained in at least o ne of the homogen eous material fo r this part is above th e limit requirem entw in GB/T 26572; X: 表示该有害物质至少在该部件的某一均质材料中的含量超出GB/ T 26572规定的限量要求。
Pb/ Hg/ Cd/
X O O O O O
Hazardous Substances Table/有害物质含量表
Safety Note
If the NovoCon® S network is supp lied with two or more AC power boosters , caution must be observed whe n disconnecting one of the transformer s from the high voltage power line. As th e
NovoCons are connected in a da isy chain, there may be high voltage on the primar y side of the disconnected power sup ply. Disconnect always both the primar y and secondary side o f the transformer.
Firmware update
We recommend to validate the firmware version before installation. The latest firmware can be downloaded at www.novocon.com by selecting the tab: Support files.