The design guide provides the information required to
select and plan installation of the right brake resistor for
an application:
Selection of the correct brake resistor.
•
Pre-installation considerations.
•
Programming.
•
As an alternative to using a brake resistor, other braking
methods can be applied depending on the braking prole
of the application, see chapter 7 Special Conditions.
More technical literature is also available online at
When in use, the brake resistor surface temperature
rises.
DO NOT touch the brake resistor during
•
operation.
WARNING
HAZARD DURING OPERATION
Work on a brake resistor in operation can result in
serious injury.
Never work on a brake resistor in operation.
•
Ensure that only trained and qualied personnel
•
can work on a brake resistor.
Table 1.1 Approval
1) See Table 9.2 and Table 9.4 for UL conformity.
What is CE conformity and labeling
The purpose of CE labeling is to avoid technical trade
obstacles within EFTA and the EU. The EU has introduced
the CE label as a simple way of showing whether a
product complies with the relevant EU directives. The CE
label says nothing about the
the product. Brake resistors are regulated by the following
EU directive:
The Low Voltage Directive (2014/35/EU)
Brake resistors must be CE labeled in accordance with the
Low Voltage Directive of April 20, 2016. The directive
applies to all electrical equipment and appliances used in
the 50–1000 V AC and the 75–1500 V DC voltage ranges.
Danfoss CE-labels in accordance with the directive and
issues a declaration of conformity after request.
specications or quality of
NOTICE
Never attempt to repair a defective brake resistor.
When the speed reference of a frequency converter is
reduced, the motor acts as a generator and the frequency
converter brakes. When a motor acts as a generator, it
supplies energy to the frequency converter which is
collected in the DC link. The function of the brake resistor
is to provide a load on the DC link during braking, thereby
ensuring that the braking power is absorbed by the brake
resistor.
If a brake resistor is not used, the DC-link voltage of the
frequency converter continues to increase, until disconnecting for protection. The advantage of using a brake
resistor is that it enables braking of a heavy load quickly,
for example on a conveyor belt.
22
Illustration 2.2 Vertical Loads
The brake resistor range is intended to cover the general
braking requirements for horizontal and vertical brake
applications.
To select the best brake resistor for an application, refer to
chapter 8.1 Selection Flow Chart. The ow chart links to
further information, either selection tables or calculations
of inertia or duty cycle.
The brake resistors in this series are all external
components. Therefore, the brake resistor does not form
an integral part of the frequency converter.
The external brake resistor provides the following
advantages:
The resistor time cycle can be selected as
•
required.
The heat developed during braking can be
•
conveyed beyond the panel cabinet to allow the
energy to be used.
The electronic components do not overheat, even
•
when the brake resistor is overloaded.
Horizontal or Vertical Load
2.2
2.2.1 How to Select
The Danfoss brake resistor range consists of 2 groups:
Brake resistors for horizontal loads (conveyors,
•
trolleys, gantry cranes, and so on), see
Illustration 2.1;
Brake resistors for vertical loads (cranes, hoists,
•
elevators), see Illustration 2.2.
To cater for both the horizontal and vertical ranges, 3
types of brake resistors are available:
Aluminum-housed at-pack brake resistors.
•
Aluminum-housed compact brake resistors.
•
Steel grid brake resistors.
•
Aluminum-housed Brake Resistors
2.3
2.3.1 Aluminum-housed Flat-pack Brake
Resistors
The at-pack brake resistor is an anodized aluminumhoused resistor suitable for wall mounting or on a
footprint or an L-prole bracket. The L-prole bracket is
used for rear mounting. The brake resistor is designed for
high pulse loads of up to 40 times the nominal load and is
therefore suitable for both vertical and horizontal
applications. The enclosure protection is IP54 or IP65.
The steel grid brake resistor is steel grid housed and
22
The compact brake resistor is housed in aluminum proles
with pre-mounted brackets for wall mount. It is designed
for high pulse loads of up to 60 times the nominal load
and is therefore used for both horizontal and vertical loads.
The enclosure protection class is either IP21, IP54, or IP65.
The brake resistor IP classes IP21 and IP65 are equipped
with a connection box containing cable glands and cable
connection to the resistor and the temperature switch.
IP54 versions have xed unshielded cables.
Illustration 2.4 CBR-V-CT IP54
consists of multiple elements. This brake resistor is suitable
for pulse loads between 10 and 20 times the nominal load,
suitable for frequent braking applications such as cranes,
hoists, and elevators. It is supplied in an IP20 enclosure
with cable glands and has a built-in temperature switch.
The brake resistors are cooled by natural convection, and
the specied minimum clearances must be observed to
ensure ecient ventilation. The ventilation must be
ecient enough to dispatch the regenerative power in the
brake resistor.
NOTICE
When installing the brake resistor, ensure that all
precautions are in place to avoid the risk of overloading.
Overloading can lead to a re hazard due to the heat
generated in the brake resistor.
The brake resistor is hot during or after braking. The
brake resistor must be located in a secure environment
to avoid re risk.
Mount the brake resistor free of any combustible
•
materials at a well-ventilated location.
The VLT® Brake Resistors MCE 101 brake resistors
•
product type 9xx contain a built-in temperature
switch (for overtemperature protection purposes.
See chapter 3.3 Protective Functions).
3.1.1 Aluminum-housed Compact Brake
Resistors and Flat-pack Brake Resistors
33
Illustration 3.1 Vertical Mounting, IP54
Versions with Fixed Cables
The aluminum-housed compact and at-pack brake
resistors are designed for vertical mounting for optimum
cooling performance. However, horizontal mounting is
possible for both at-pack and compact brake resistors.
Derating with 20% is required when mounting the
compact brake resistors horizontally. No derating for at-packs are required. The enclosure protection of the IP21
types is reduced to IP20 when mounted horizontally.
NOTICE
All resistors are cooled by natural convection. To ensure
sucientairow and cooling, follow minimum clearance
in Illustration 3.1 to Illustration 3.8.
Vertical mounting, IP54
For minimum clearances for vertical mounting for all
aluminum-housed compact and at-pack brake resistors,
see Illustration 3.1 and Illustration 3.2.
For minimum clearances for horizontal mounting for all
aluminum-housed compact and at-pack brake resistors,
IP54 versions (versions with xed cables), see Illustration 3.4
(side view).
33
Illustration 3.4 Horizontal mounting, IP54
Versions with Fixed Cables
Vertical mounting, IP21 and IP65
For minimum clearances for vertical mounting for all
aluminum-housed compact brake resistors, see
Illustration 3.5 and Illustration 3.6.
Illustration 3.2 Vertical Mounting, IP54
Versions with Fixed Cables
Horizontal mounting, IP54
For minimum clearances for horizontal mounting for all
aluminum-housed compact and at-pack brake resistors,
see Illustration 3.3 (top view).
The steel grid brake resistors are designed for horizontal
mounting only.
33
NOTICE
All resistors are cooled by natural convection. To ensure
sucientairow and cooling, follow minimum clearances
in Illustration 3.10 and Table 3.3.
Illustration 3.10 Minimum Clearances of all Steel Grid Brake
Resistors - Top View
Illustration 3.9 Orientation of Compact and Flat-pack Brake
Resistors
Derating with 20% is required when mounting the
compact brake resistors horizontally. The enclosure
protection of the IP21 types is reduced to IP20 when
mounted horizontally.
Illustration 3.11 Minimum Clearances of all Steel Grid Brake
Illustration 3.12 Orientation of Steel Grid Brake Resistors
3.1.3 Accessories
Footprint brackets
The footprint bracket is an accessory used for mounting
at-pack brake resistors.
Use the footprint bracket to mount the brake resistor at
the rear of the frequency converter. Once mounted, the
combined brake resistor and frequency converter occupy
the same space in the cabinet as the frequency converter
alone.
1Frequency converter
2Footprint mounting bracket
3Flat-pack brake resistor
Illustration 3.13 Flat-pack Brake Resistor Mounted at Rear of
Frequency Converter
Part number Compatible brake resistor Compatible frequency
converter enclosure
size
175U0085
175U0087
175U0086
175U0088
Table 3.1 Selection Table
1x100 W at-pack
1x200 W at-pack
2x100 W at-pack
2x200 W at-pack
2x100 W at-pack
2x200 W at-pack
1x100 W at-pack
1x200 W at-pack
A2
A2
A3
A3
For mechanical dimensions for footprint brackets, see
chapter 9.8.2 Mounting Brackets: Footprint.
The L prole bracket is an accessory used for mounting
at-pack brake resistors. The L prole brackets support
3.2.1 EMC Precautions
both horizontally and vertically mounting on a xed
surface optimizing the required footprint.
33
The following EMC precautions are recommended to
achieve interference-free operation of
eldbus cable(s) and
digital and analog inputs and outputs.
Observe relevant national and local regulations, for
example regarding protective earth connection. Keep the
eldbus cable(s) away from motor cables and brake resistor
cables to avoid coupling of high frequency noise from one
cable to another. Normally, a distance of 200 mm (8
inches) is sucient, but keeping the greatest possible
distance between the cables is recommended, especially
where cables run in parallel over long distances. When
crossing is unavoidable, the eldbus cable(s) must cross
motor cables and brake resistor cables at an angle of 90°,
see Illustration 3.15.
Illustration 3.14 L Prole Bracket
Part numberCompatible brake resistor
175U00091x200 W at-pack
175U0011
Table 3.2
1) Order 2x175U0011 for 300 W at-pack brake resistors.
To comply with EMC emission specications, shielded/
armored cables are recommended.
NOTICE
Cables general: All cabling must comply with national
and local regulations on cable cross-sections and
ambient temperature.
33
See Table 3.3 for recommended temperature ratings for all
cables and conductors connected to the brake resistor as
ground connection, thermal switch, and brake power.
IP classRecommended cables
IP20
IP21
IP54
IP65
Table 3.3 Cable Temperature Ratings
1) For ground connection.
How to connect more than 1 resistor
Star parallel connection to ensure that load is shared
evenly between 2 or more resistors.
≥80 °C (176 °F)
≥80 °C (176 °F)
≥90 °C (194 °F)
≥90 °C (194 °F)
1)
(1)Twisted pair
(2)Shielded cable
Illustration 3.17 Twisted Cables
3.2.3 Brake Cable
Maximum length: 20 m (66 ft) shielded cable.
Ensure the connection cable to the brake resistor is
shielded. Connect the shielding to the conductive back
plate of the frequency converter and to the brake resistor
metal cabinet, using cable clamps.
Protective Functions
3.3
3.3.1 Overtemperature Protection
Danfoss VLT® Brake Resistors MCE 101 is equipped with a
galvanic isolated temperature switch (PELV) that is closed
under normal operating conditions and open if the brake
resistor is overheated.
NOTICE
Use the temperature switch as overtemperature
protection feature to prevent damage of the brake
resistor caused by overtemperature. To prevent damage
to the brake resistor, perform an immediate stop or a
ramp down.
There are several ways the temperature switch can be
Illustration 3.16 Connection of Several Brake Resistors
Brake resistors with xed cables
To reduce the electrical noise from the wires between the
brake resistor and the frequency converter, twist the wires.
For enhanced EMC performance, a metal shield can be
used.
The temperature switch as digital input to frequency
converter
Example 1
1.Connect terminal T1 of the brake resistor to the
frequency converter terminal 12 or 13.
2.Connect terminal T2 of the brake resistor to a
digital input, for example terminal 18.
Automatic restart after enabling of the temperature
switch:
Select coast inverse for the selected digital input.
81
82
99
91 92 93 95
96 97 98 99
12
18
L1 L2 L3 PE
U V W PE
VLT
MCE 101
Brake resistor
T1
T2
RB1
RB2
L1
L2
L3
PE
F1
PE
R-
R+
PE
+24V
D-in
M
3~
130BD553.11
91 92 93 95
96 97 98 99
M
3~
12
27
L1 L2 L3 PE
VLT
MCE 101
Brake resistor
T1
T2
RB1
RB2
99
PE
81
R -
82R+
PE
L1
L2
L3
N
PE
F1
S1K1
F2
S2
K1
K1
U V W PE
130BD554.11
Installation
VLT® Brake Resistor MCE 101
Prevent automatic restart:
Example 2
Select latched start for the selected digital input.
NOTICE
Coast does not terminate the brake function.
33
Example 1
Illustration 3.19 Temperature Switch in both Motor and Brake
Resistor Disabling Mains Supply by an Input Contactor
Illustration 3.18 Temperature Switch in Brake Resistor
NOTICE
The temperature switch as input to the frequency
converter cannot be considered a primary safety
function.
In case of a malfunction in the brake IGBT, the frequency
converter and brake resistor are only protected by
disconnecting the mains supply to the frequency
converter. The temperature switch must be connected
disabling the mains supply to the frequency converter by
a contactor preventing dangerous overtemperatures.
The temperature switch disabling the mains supply to
VLT by a contactor
Example 2
1.Connect the brake resistor built-in thermal switch
as controlling an input contactor. In this example,
the thermal switch within the brake resistor is
connected in series with the thermal switch
within the motor.
2.Connect start and stop push buttons in series
with the thermal switches.
3.Connect to a contactor in the mains supply in
front of the frequency converter.
Thermal overheating in brake resistor or motor disables the
mains supply to the frequency converter.
Thermo relay disabling the brake resistor
Example 3
Calculate the brake current (I
thermo relay
) setting of the
temperature switch as follows:
P
I
thermo relay
brake resistor max
=
R
br
Rbr is the current brake resistor value calculated in
chapter 4.1.2 Calculation of Brake Resistor Resistance.
Look up the brake current setting of the thermo relay for
Danfoss brake resistors in chapter 8 Selection Guide.
In addition, the brake power monitor function makes it
possible to read out the momentary power and the mean
power for a selected time period. The brake can also
monitor the power energizing and make sure that it does
not exceed a limit selected in parameter 2-12 Brake PowerLimit (kW). In parameter 2-13 Brake Power Monitoring, select
the function to carry out when the power transmitted to
the brake resistor exceeds the limit set in
parameter 2-12 Brake Power Limit (kW).
NOTICE
Monitoring the brake power does not fulll a safety
function. The brake resistor circuit is not ground leakage
protected.
The brake is protected against short-circuiting of the brake
resistor, and the brake transistor is monitored to ensure
that short-circuiting of the transistor is detected. Use a
relay or digital output to protect the brake resistor against
overloading in the event of a fault in the frequency
converter, see chapter 3.3.1 Overtemperature Protection.
33
Overvoltage control (OVC) can be selected as an alternative
brake function in parameter 2-17 Over-voltage Control. If the
DC-link voltage increases, this function is active for all
units. The function ensures that a trip can be avoided. This
is done by increasing the output frequency to limit the
voltage from the DC link. It is a useful function, for
example if the ramp-down time is too short since tripping
of the frequency converter is avoided. In this situation, the
ramp-down time is extended.
To ensure the optimal selection of brake resistor for a
given application, its inertia and braking prole
calculations are required.
44
This chapter explains the calculations required to obtain
values for optimal selection of brake resistor for a given
application.
4.1.1 Brake Set-up
The following sections use expressions and abbreviations
related to the brake set-up in Illustration 4.1.
To prevent the frequency converter from cutting out for
protection when the motor brakes, select resistor values on
the basis of the peak braking power and the DC-link
voltage:
Rbr =
Ω
P
peak
2
Udc
The brake resistor performance depends on the DC-link
voltage (Udc).
Udc is the voltage, where the brake is activated. The FCseries brake function is settled depending on the mains
supply.
DC-link voltage (Udc), VLT® AutomationDrive FC 360
Size [V]
FC 360 3x380–480,
0.37–22 kW (0.5–30
hp)
FC 360 3x380–480,
30–75 kW (40–100
hp)
Brake
active
[V DC]
700–770
N/A
1)
2)
Overvoltage
warning
[V DC]
800800
800800
Overvoltage
alarm
[V DC]
Illustration 4.1 Brake Set-up
Table 4.1 DC-link Voltage (Udc), FC 360
1) Adjustable with parameter 2-14 Brake voltage reduce
2) No built-in brake option
Use the brake resistance R
, to ensure that the frequency
rec
converter is able to brake at the highest braking torque
(M
) (for example 160%). The formula is written as:
br(%)
R
Ω =
η
η
rec
motor
VLT
P
motor
is typically at 0.90
is typically at 0.98
xM
2
U
dc
br ( % )
x 100
x η
VLT
x η
motor
When a higher brake resistor resistance is selected, 160%/
150%/110% braking torque cannot be obtained, and there
is a risk that the frequency converter cuts out of DC-link
overvoltage for protection.
For braking at lower torque, for example 80% torque, it is
possible to install a brake resistor with lower power rating.
Calculate size using the formula for calculating R
When calculating the braking power, ensure that the brake
resistor is scaled for the average power as well as the peak
power.
The average power is determined by the process
•
period time, that is the length of the braking
time in relation to the process period time.
The peak power is determined by the braking
•
torque, which means that as braking progresses,
the brake resistor must be able to dissipate the
energy input.
Illustration 4.2 shows the relation between the average
power and the peak power.
4.1.5 Calculation of the Brake Resistor
Average Power
The average power is determined by the length of the
braking time in relation to the process period time.
When the kinetic energy (Eb) transferred to the resistor in
each braking sequence is known (see chapter 6.1 ConveyorBelt and chapter 6.2 Centrifuge), calculate the average
power of the brake resistor as follows:
E
b
=
T
p
W
Tb × 100
T
p
%
P
avg
Tp = period time in s, see Illustration 4.2.
When the kinetic energy transferred to the resistor in each
braking sequence is not known, calculate the average
power based on the process period time and the braking
time.
Calculate the duty cycle for the braking sequence as
follows:
Duty cycle =
where
44
T
p
T
b
Illustration 4.2 Relation between Average Power and Peak
Power
Process period time in s
Braking time in s
4.1.4 Calculation of the Brake Resistor Peak
Power
P
the motor shaft. Calculate P
P
P
when the motor brakes.
P
the eciencies of the motor and the frequency converter.
Calculate P
P
When the brake resistor recommended by Danfoss is
selected (R
chapter 8 Selection Guide, the brake resistor is certain to
provide a braking torque of 160%/150%/110% on the
motor shaft.
is the peak power by which the motor brakes on
peak, mec
as follows:
peak, mec
= P
peak, mec
is the braking power dissipated to the brake resistor
peak
is lower than P
peak
= P
peak
motor
× M
motor
as follows:
peak
× M
) on the basis of the tables in
rec
W
BR( %)
since the power is reduced by
peak,mec
× η
× η
BR( %)
motor
VLT
W
Tp = process period time in s
Tb = braking time in s
Danfoss oers brake resistors with a duty cycle of
maximum 10% and 40%. If a 10% duty cycle is applied, the
brake resistors are able to absorb P
for 10% of the
peak
period time. The remaining 90% of the period time is used
on deecting excess heat.
Calculate the average power with 10% duty cycle as
follows:
P
avg
= P
× 10 %
peak
W
Calculate the average power with 40% duty cycle as
follows:
P
avg
= P
× 40 %
peak
W
The calculations apply to intermittent braking using a
period time of 30 s.
NOTICE
Exceeding the specied intermittent braking period time
may result in overheating the resistor.
For descriptions of all available parameters, see VLT
®
AutomationDrive FC 360 Programming Guide, which is
available from drives.danfoss.com/knowledge-center/technical-documentation/.
2-10 Brake Function
Option:Function:
[0]*ONo brake resistor is installed.
[1]Resistor
brake
[2]AC brake Improve braking without using a brake resistor.
A brake resistor is incorporated in the system for
dissipating surplus brake energy as heat.
Connecting a brake resistor allows a higher DC-
link voltage during braking (generating
operation). The brake resistor function is only
active in frequency converters with an integral
dynamic brake.
This parameter controls an overmagnetization of
the motor when running with a generatoric load.
This function can improve the OVC function.
Increasing the electrical losses in the motor
allows the OVC function to increase braking
torque without exceeding the voltage limit.
NOTICE
The AC brake is not as ecient as
dynamic braking with resistor.
AC brake is for VVC+ mode in both open
and closed loop.
2-12 Brake Power Limit (kW)
Range:Function:
Size
related*
[0.001 -
2000
kW]
Parameter 2-12 Brake Power Limit (kW) is the
expected average power dissipated in the
brake resistor over a period of 120 s. It is
used as the monitoring limit for
parameter 16-33 Brake Energy Average and
species when a warning/alarm is given.
To calculate parameter 2-12 Brake Power
Limit (kW), the following formula can be
used.
P
br, avg
P
is the average power dissipated in
br,avg
the brake resistor. Rbr is the resistance of
the brake resistor. tbr is the active breaking
time within the 120 s period Tbr.
Ubr is the DC voltage where the brake
resistor is active. For T4 units, the DC
voltage is 778 V, which can be reduced by
parameter 2-14 Brake voltage reduce.
NOTICE
If Rbr is not known or if Tbr is dierent
from 120 s, the practical approach is
to run the brake application, read out
parameter 16-33 Brake Energy Average,
and then enter this value + 20% in
parameter 2-12 Brake Power Limit
(kW).
W =
2
U
V × tbrs
br
RbrΩ × Tbrs
55
2-11 Brake Resistor (ohm)
Range:Function:
Size
related*
[ 0 -
65535
Ohm]
Set the brake resistor value in Ω. This
value is used for monitoring the power to
the brake resistor. Parameter 2-11 Brake
Resistor (ohm) is only active in frequency
converters with an integral dynamic brake.
Use this parameter for values without
decimals.
2-14 Brake voltage reduce
Range:Function:
0 V* [ 0 - 0 V] Setting this parameter may change the brake
resistor (parameter 2-11 Brake Resistor (ohm)).
2-16 AC Brake, Max current
Range:Function:
100 %* [0 -
160 %]
Enter the maximum allowed current when
using AC brake to avoid overheating of
motor windings.
NOTICE
Parameter 2-16 AC Brake, Max current
has no eect when
parameter 1-10 Motor Construction is
set to [1] PM, non-salient SPM.
Illustration 6.1 shows the relation between the braking
power and the acceleration/braking of a conveyor belt.
Note:
The motor power during braking is negative,
•
since the torque on the motor shaft is negative.
The motor power is time-dependent.
•
The braking power (the power to be dissipated to the
brake resistor) corresponds almost exactly to the negative
motor power plus losses in the motor and the frequency
converter.
Kinetic energy (E) in conveyor belt + motor:
E = 0 . 5 × m × v2 + 0 . 5 × j × ω2Ws
where
m = mass with linear movement [kg].
v = speed of mass with linear movement [m/s].
j = inertia of motor and gear box [kgm2].
ω = motor speed [rad/s].
ω = motor speed =
n × 2π
60
rad/ s
This formula is also expressed as follows:
E = 0 . 50 × m × v2 + 0 . 0055 × j × n2Ws
However, not all of the energy is dissipated in the brake
resistor. The friction of the conveyor belt and the power
loss of the motor also contribute to the braking function.
So, the formula for energy dissipation (Eb) to the brake
resistor is as follows:
Illustration 6.2 shows braking of a centrifuge, which is a
typical application of brake resistors.
The formula for energy dissipation (Eb) to the brake resistor
is:
If the 3-phase winding of the stator is fed with direct
current, a stationary magnetic
stator bore causing a voltage to be induced in the bars of
the cage rotor as long as the rotor is in motion. Since the
electrical resistance of the rotor cage is very low, even
small induced voltages can create a high rotor current. This
current produces a strong braking eect on the bars and
hence on the rotor. As the speed decreases, the frequency
of the induced voltage decreases and with it the inductive
impedance. The ohmic resistance of the rotor gradually
77
becomes dominant and so increases the braking eect as
the speed decreases. The braking torque generated
decreases steeply just before standstill and nally ceases
when there is no further movement. Direct current
injection braking is therefore not suitable for holding a
load at rest.
eldΦ is set up in the
7.1.4 DC Braking
Resistor brake is useful from maximum speed down to a
certain frequency. Below this frequency, DC braking is to
be applied as required. The most ecient way of doing
this is to use a combination of dynamic braking and DC
braking. See Illustration 7.1. The parameters are in
chapter 5 Parameters.
7.1.2 AC-braking
When the motor acts as a brake, the DC-link voltage
increases because energy is fed back to the DC-link. The
principle in AC brake is to increase the magnetization
during the braking and thereby increase the thermal losses
of the motor.
Illustration 7.1 Optimum Braking
How to calculate optimum DC-brake cut in frequency:
7.1.3 Mechanical Holding Brake
n0 − n
n
A mechanical holding brake mounted directly on the
motor shaft normally performs static braking. In some
applications, the static holding torque is working as static
holding of the motor shaft (usually synchronous
permanent motors). A holding brake is either controlled by
a PLC or directly by a digital output from the frequency
converter (relay or solid state).
Slip s =
Synchronous speed n0 =
f = frequency supplied to motor.
p = number of pole pairs.
nn = speed of the rotor.
n
0
× 100
%
f × 60
p
[1/min]
NOTICE
When the holding brake is included in a safety chain:
A frequency converter cannot provide a safe control of a
mechanical brake. A redundancy circuitry for the brake
control must be included in the total installation.
Environment
Ambient temperature range-40 to 70 °C (-40 to 158 °F)
Temperature range during storage/transport-40 to 70 °C (-40 to 158 °F)
Maximum temperature at housing300 °C (572 °F)
Maximum relative humidity5–85%, non-condensation during operation
Power derating as a function of ambient temperature. (100% power rating and pulse-load):
- Steel grid brake resistors, IP20Continuous power 100% @ 40 °C (104 °F) to 70% @ 70 °C (158 °F), linear
- Aluminum-housed compact brake resistors,
IP21Continuous power 100% @ 40 °C (104 °F) to 75% @ 70 °C (158 °F), linear
- Aluminum-housed brake resistors - compact
and at-pack, IP54Continuous power 100% @ 40 °C (104 °F) to 75% @ 70 °C (158 °F), linear
- Aluminum compact brake resistors, IP65Continuous power 100% @ 40 °C (104 °F) to 50% @ 70 °C (158 °F), linear
Power derating at vertical mounted resistor (wall-mounted) when mounted horizontal (100% power rating and pulseload):
Cooling requirements:
The brake resistors are cooled by free natural convection. The power ratings of the resistors refers to cooling conditions
99
with free natural cooling. The requirements for minimum clearances must be observed during installation.
Derating at high altitudes100% @ 1000 m (3281 ft) above sea level
Derating at high altitudes94% @ 1500 m (4921 ft) above sea level
Derating at high altitudes82% @ 3000 m (9843 ft) above sea level
9.2 General Electrical Specications
Electrical specications
Resistance tolerances±10%
Insulation>20 MΩ @ 1000 V
Dielectric strength2500 V AC for 1 minute
Operating voltage:
- Aluminum-housed compact brake resistors, IP54UL: 600 V AC/600 V DC
- Aluminum-housed compact brake resistors, IP54IEC: 690 V AC/1100 V DC
- Aluminum-housed at-pack brake resistors, IP54UL: 1000 V AC/1400 V DC
- Aluminum-housed at-pack brake resistors, IP54IEC: 1000 V AC/1400 V DC
- Aluminum-housed compact brake resistors, IP21, IP65UL: 600 V AC/600 V DC
- Aluminum-housed compact brake resistors, IP21, IP65IEC: 690 V AC/1100 V DC
- Steel grid brake resistors, IP20IEC: 690 V AC/1100 V DC
Power rating (continuous load 100%) with and without temperature switch
- Without temperature switch100% of continuous power rating @ 40 °C (104 °F)
- With temperature switch, steel grid brake resistors, IP20100% of continuous power rating @ 40 °C (104 °F)
- With temperature switch, aluminum-housed brake resistors,
IP21, IP54, IP65Minimum 80% of continuous power rating @ 40 °C (104 °F)
- With temperature switch, aluminum-housed brake
resistors, IP21, IP54, IP65
Electrical data temperature switch:
- Steel grid brake resistors, IP2010 A, 250 V AC, normally closed (NC). Enables at 260 °C (500 °F)
- Aluminum-housed brake resistors, IP21, IP54, IP652 A, 250 V AC, normally closed (NC). Enables at 180 °C (356 °F)
Temperature switch enables at ≥80% of the continuous power rating