Danfoss MCD Profibus Module Operating guide

MCD Profibus Module Instructions Important User Information
CAUTION Remove mains and control voltage from the soft starter before attaching or removing accessories. Failure to do so may damage the equipment.
Remove the Profibus Module using the following procedure:
1. Remove control power and mains supply from the soft
starter.
2. Disconnect all field wiring from the module.
3. Fully pull out the top and bottom retaining clips on the
module.
4. Pull the module away from the soft starter.
Installation Instruction: MCD Profibus Module
Order Code: 175G9001
1. Important User Information
It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.
2. Installation
1. Remove control power and mains supply from the soft starter.
2. Attach the module to the soft starter as illustrated.
3. Set the module address to match the address set in the Master configuration tool.
4. Apply control power to the soft starter.
5. Insert the network connector and power up the module.
2.2. Physical Installation
1. Fully pull out the top and bottom retaining clips on the module.
2. Line up the module with the comms port slot.
3. Push in the top and bottom retaining clips to secure the module to the starter.
MG17GA02 - VLT® is a registered Danfoss trademark 1
Configuration MCD Profibus Module Instructions
N.B.!: The Profibus Module has a slave address range of 0 to 99.
N.B.!: If the Communication Timeout parameter is set to 0, the current state of the soft starter will remain unchanged on a network failure. This gives the user the option of operating the soft starter via local control, but is NOT failsafe.
3. Configuration
Import the latest .gsd file into your Master configuration tool. This file is available from www.danfoss.com/drives.
If your Master uses on-screen icons, two graphic bitmap files are available from the website. SSPM_N.bmp indicates normal mode. SSPM_D.bmp indicates diagnostic mode.
If the Profibus network fails, the module will leave data exchange mode after the network watchdog timeout period has expired. This timeout period is set at the Master configuration tool.
A Communication Timeout parameter in the GSD file sets how soon after this event the soft starter will be forced into a trip state.
The user can adjust the Communication Timeout parameter in the GSD file to any setting between 0 and 100 seconds. The default setting is 10 seconds.
4. Adjustment
Before powering up the Profibus Module, set the two rotary switches so that the module address matches the address set in your Master configuration tool (the diagram shows the factory default setting for the rotary switches).
The module automatically detects the network data rate.
MG17GA02 - VLT® is a registered Danfoss trademark 2
MCD Profibus Module Instructions Connection
MCD 200
MCD 500
MCD 200
MCD 500 (Auto On mode)
17, 18: Stop
25, 18: Reset
Profibus Module
Profibus Module
External 24 VDC supply required if not powered through bus
External 24 VDC supply required if not powered through bus
9-pin Sub-D connector to Profibus network
9-pin Sub-D connector to Profibus network
9-pin Sub-D connector
Pin No.
Assignment
1
Shield
2
24 VDC negative (optional)
3
RxD/TxD-P
4
Not used
5
DGND
6
VP (end of bus slave only)
7
24 VDC positive (optional)
8
RxD/TxD/-N
9
DGND
N.B.!: If MCD 500 parameter 3-2
Comms in Remote
is set to Disable Comms in Remote, the starter will not accept start or stop commands from the serial network (the starter will still accept reset commands and allow status monitoring).
5. Connection
The module connects to the Profibus network via a standard 9-pin Sub-D connector.
The Profibus Module can be powered either through the network cable or externally (24 VDC).
MCD 200: For the Profibus Module to accept serial commands, a link must be fitted across terminals A1-N2 on the soft starter.
In order for the MCD 500 to accept commands from the serial network, the soft starter must be in Auto On mode and links must be fitted to terminals 17, 18 and 25, 18.
In Hand On mode, the starter will not accept commands from the serial network but the starter's status can still be monitored.
MG17GA02 - VLT® is a registered Danfoss trademark 3
Power Status LED (Red) and Bus Status LED (Green) MCD Profibus Module Instructions
OFF
ON
Power status (red)
Module not powered up
Module powered up and ready to go online
Bus status (green)
No connection, offline or data exchange failure
Module online and in data exchange state
N.B.!: If communication fails between the module and the network, the Bus Status LED will go off. When communication is restored, the Bus Status LED will come back on.
N.B.!: When a communications failure occurs, the soft starter may trip if the Communication Timeout parameter for the network is set greater than zero. When communication is restored, the soft starter must be reset.
Data Structure
Basic Module
Extended Module
Parameter Upload/
Download Module
Soft Starter Control I/O on page 5
Soft Starter Monitoring I/O on page 6
Soft Starter Programming I/O on page 9
6. Power Status LED (Red) and Bus Status LED
(Green)
7. Data Structures
The GSD file contains three operating modules, supporting data I/O structures as follows:
The Basic Module allows the user to start and stop the soft starter and read limited information on operating status.
The Extended Module defines additional bytes allowing the user to read soft starter operating data such as actual motor current and motor temperature.
The Parameter Upload/Download Module allows the user to read and write soft starter parameter values (only applicable to MCD 500 soft starters).
MG17GA02 - VLT® is a registered Danfoss trademark 4
MCD Profibus Module Instructions Soft Starter Control I/O Data Structure
Byte 0
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reserved
Reserved
Reserved
Quick stop
Motor set
Reserved
Reserved
Byte 1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reserved
Reserved
Reserved
Reserved
Reset
Reserved
Reserved
Fwd run
N.B.!: The Quick stop bit must be set to 0 before the soft starter can perform a start.
Byte 0
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Ramping
Hand On
Motor current (% FLC) 1
Byte 1
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reserved
Reserved
Reserved
Reserved
Warning
Fault
On
Ready
8. Soft Starter Control I/O Data Structure
Master > Slave control word is structured as follows:
8.1. Quick stop bit
When Fwd run bit changes from 1 to 0: 0 = stop action will be a soft stop (as selected on the soft starter). 1 = stop action will be a quick stop (i.e. coast to stop).
8.2. Motor set bits
Selects which parameter set to use when starting: 0 = selected from soft starter remote input (programmable input must be set to 'Motor Set Select') 1 = soft starter primary motor set (ensure soft starter programmable input is not set to 'Motor Set Select') 2 = soft starter secondary motor set (ensure soft starter programmable input is not set to 'Motor Set Select') 3 =
Reserved
Slave > Master status word is structured as follows:
1
Motor current (% FLC) represents current as a percentage of the set motor full load current. A maximum value of 63 represents 200% full load current. To convert this value to a readable percentage, divide by 0.315.
Ready is set when the soft starter is ready to start the motor. On is set when the soft starter is starting, running or soft stopping the motor. Warning is set when the soft starter detects a warning condition. Fault is set when the soft starter has tripped. Ramping is set when the soft starter is starting or soft stopping the motor. Hand On is set when the soft starter is set to Hand On mode.
MG17GA02 - VLT® is a registered Danfoss trademark 5
Soft Starter Monitoring I/O Data Structure MCD Profibus Module Instructions
Byte 2
Operating data request (Data request numbers 1 to 14)
Byte 2
Echo data request number
Byte 3
Bits 7 to 1
Reserved
Bit 0 = 1: Invalid data request number
Byte 4
Data value - high byte
Byte 5
Data value - low byte
N.B.!: An invalid data request number will result in the invalid data request number bit being set = 1.
Data Request Number
Data Value High Byte
Data Value Low Byte
0
Reserved
1
Soft starter product type code 1
Soft starter software version number
2
Trip/Warning code
Soft starter status
3 2
Average current (high byte)
Average current (low byte)
4 3
Motor 2 temperature
Motor 1 temperature
5
Reserved
Percentage power factor
6
Power (kW)
7
Power (kVA)
8
Average voltage
9 2
L1 current
10
L2 current
11
L3 current
12
L1 voltage
13
L2 voltage
14
L3 voltage
15
Software major version number
Software minor revision number
16
Reserved
Digital input state
N.B.!: Data request numbers 5 to 11 are only valid for MCD 500 starters. MCD 200 starters will return zero values.
9. Soft Starter Monitoring I/O Data Structure
Master > Slave output byte is structured as follows:
Slave > Master input bytes, in response to an operating data request, are structured as follows:
Data values are defined as follows:
1
Product type code:
4 = MCD 200 7 = MCD 500
2
For models MCD5-0428C and smaller this value will be 10 times greater than the value displayed on the LCP.
3
Motor temperature is calculated using the soft starter thermal modelling.
MG17GA02 - VLT® is a registered Danfoss trademark 6
MCD Profibus Module Instructions Soft Starter Monitoring I/O Data Structure
Value (decimal) Bits 0 to 3
Soft Starter Status
0
Unknown (communication error between module and soft starter)
1
Ready to start (waiting)
2
Starting (soft starting)
3
Running (running – full voltage at the motor)
4
Stopping (soft stopping)
5
Not ready (restart or thermal delay and Run simulation)
6
Fault (tripped)
71
Menu or Logs Menu open
81
Jog Forward (slow speed)
91
Jog Reverse (slow speed)
Bit Number
Function
Bit 4
Set if positive phase sequence detected (Bit 6 must = 1)
Bit 5
Set if average current exceeds Motor FLC setting
Bit 6
Set after first start once phase sequence has been confirmed
Bit 7
Set if a communication failure occurs between module and soft starter
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
High Byte
Power scale factor
Power high nibble
Low Byte
Power low byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Low Byte
Reserved
Input A
Reset
Stop
Start
9.1. Soft starter status
The low byte data value of data request number 2 reports soft starter status.
Bits 0 to 3 function as follows:
1
Only available on MCD 500 soft starters.
Bits 4 to 7 function as follows:
9.2. Power
Input bytes for data request numbers 6 and 7 are defined as follows:
Powerscale functions as follows:
0 = multiply Power by 10 to get W 1 = multiply Power by 100 to get W 2 = Power is represented in kW 3 = multiply Power by 10 to get kW
9.3. Digital Input State
The low byte of data request number 16 reports digital input state as follows (0 = open, 1 = closed):
MG17GA02 - VLT® is a registered Danfoss trademark 7
Soft Starter Monitoring I/O Data Structure MCD Profibus Module Instructions
Trip Code
Trip Type
MCD 201
MCD 202
MCD 500
1
Excess start time
2
Motor overload (thermal model)
3
Motor thermistor
4
Current imbalance
5
Frequency (Mains supply)
6
Phase sequence
7
Instantaneous overcurrent
8
Power loss/Power circuit
9
Undercurrent
10
Heatsink overtemperature
11
Motor connection
12
Input A trip
13
FLC too high (FLC out of range)
14
Unsupported option (function not available in inside delta)
15
Starter communication (between module and soft starter)
16
Network communication (between module and network)
17
Internal fault x (where x is the fault code detailed in the table below).
23
Parameter out of Range
25
Bypass fail (bypass contactor)
26
L1 phase loss
27
L2 phase loss
28
L3 phase loss
29
L1-T1 shorted
30
L2-T2 shorted
31
L3-T3 shorted
33
Time-overcurrent (Bypass overload)
35
Battery/clock
36
Thermistor circuit
255
No trip
9.4. Trip Codes
Data request number 2 high byte indicates the soft starter trip or warning code. Details are as follows:
For MCD 500, time-overcurrent protection is only available on internally bypassed models.
MG17GA02 - VLT® is a registered Danfoss trademark 8
MCD Profibus Module Instructions Soft Starter Programming I/O Data Structure
Internal fault
Message displayed on the LCP
70, 71, 72
Current Read Err Lx
73
Power On in Simulation mode
74, 75, 76
Motor connection Tx
77, 78, 79
Firing fail SCRx
80, 81, 82
VZC Fail Px
83
Low Control Volts
84 to 98
Internal fault X Contact your local supplier with the fault code (X).
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte 3
Parameter number to read/write
Byte 4
Reserved
Reserved
Reserved
Reserved
Reserved
Write
parameter
Read
parameter
Reserved
Byte 5
High byte parameter value to write to soft starter/ zero data values for read
Byte 6
Low byte parameter value to write to soft starter/ zero data values for read
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte 6
Echo parameter number
Byte 7
Reserved
Reserved
Reserved
Parameter access
level
Write
access
denied
Invalid
parameter
value
Invalid
parameter
number
Byte 8
High byte parameter value read from soft starter
Byte 9
Low byte parameter value read from soft starter
N.B.!: This operating module only functions with MCD 500 soft starters.
9.4.1. Internal Fault x
The table below details the internal fault code associated with trip code 17.
10. Soft Starter Programming I/O Data Structure
The Soft Starter Programming I/O Data Structure allows the user to upload (read) and download (write) soft starter parameter values over the network.
Master > Slave output bytes are structured as follows.
Slave > Master input bytes are structured as follows.
Parameter access level is defined as follows:
0 = Read only 1 = Operator (MCD 500 parameter groups 1 to 8) 2 = Supervisor (MCD 500 parameter groups 15 and 16) 3 = Commissioning (MCD 500 parameter group 20)
MG17GA02 - VLT® is a registered Danfoss trademark 9
Profibus Diagnostic Telegram and Flag MCD Profibus Module Instructions
Diagnostic Telegram Data Structure
Byte 0
User diagnostic length (Always set = 3)
Byte 1
Trip code
Byte 2
Changed parameter number (MCD 500 only)
11. Profibus Diagnostic Telegram and Flag
The Profibus Module supports external diagnostics. The following telegram will be sent to the Master if the soft starter trips or if a parameter is changed at the soft starter.
11.1. Profibus Trip Code
When the soft starter trips, a diagnostic flag is set at the Master and the trip code is reported in Byte 1. When the soft starter is reset, the diagnostic flag and trip code data are reset = 0, provided the trip condition does not still exist (see page 6 for trip codes).
11.2. Changed Parameter Number
If a parameter is changed via the LCP, the affected parameter number is reported in Byte 2. When the Master reads or writes the changed parameter, Byte 2 is reset = 0.
Soft Starter Monitoring I/O Data Structure
on
A changed parameter number does not set a diagnostic flag.
12. Profibus Freeze Mode
The Profibus Module supports Freeze Mode.
In Freeze Mode, inputs are only updated with new data from the soft starter when another Freeze action is carried out. An Un-Freeze action returns the Profibus Module to normal operation.
13. Profibus Sync Mode
The Profibus Module supports Sync Mode.
In Sync Mode, commands to the soft starter are not processed until another Sync action is carried out. An Un-Sync action returns the Profibus Module to normal operation.
14. Profibus Clear Mode
If the Master sends a global Clear command, the Profibus Module will send a Quick Stop command to the soft starter.
MG17GA02 - VLT® is a registered Danfoss trademark 10
MCD Profibus Module Instructions Specifications
Profibus International ........................................................................................................
15. Specifications
Enclosure
Dimensions ........................................................... 40 mm (W) x 166 mm (H) x 90 mm (D)
Weight .................................................................................................................. 250 g
Protection ............................................................................................................... IP20
Mounting
Spring-action plastic mounting clips (x 2)
Connections
Soft starter ....................................................................................... 6-way pin assembly
Contacts .................................................................................................. Gold flash
Network ....................................................................................................... DB9 female
External power supply .......................................................... 2-way removable screw type
Maximum cable size .................................................................................... 2.5 mm2
Settings
Network address
Setting ......................................................................... MSD and LSD rotary switches
Range .......................................................................................................... 0 to 99
Data rate
Setting ................................................................................................... Auto-detect
Range ...................................................................................... 9.6 kb/s ~ 12.0 Mb/s
Power
Consumption (steady state, maximum) ................................................... 35 mA at 24 VDC
Reverse polarity protected Galvanically isolated
Certification
C ...................................................................................................... IEC 60947-4-2