The VLT® Soft Starter MCD 500 is an advanced digital soft
start solution for 11–850 kW (15–1150 hp) motors. The soft
starters provide a complete range of motor and system
protection features and are designed for reliable
performance in the most demanding installation situations.
1.1.1 Document Version
This operating guide is regularly reviewed and updated. All
suggestions for improvement are welcome. Table 1.1 shows
the document version.
EditionRemarks
MG17K8xxInstruction about using nger guard kits for IP00
installations added to chapter 4 Electrical Installation.
Indicates a potentially hazardous situation that could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could
result in minor or moderate injury. It can also be used to
alert against unsafe practices.
NOTICE
Indicates important information, including situations that
can result in damage to equipment or property.
2.1.1 Qualied Personnel
Correct and reliable transport, storage, installation,
operation, and maintenance are required for the troublefree and safe operation of the soft starter. Only qualied
personnel are allowed to install or operate this equipment.
Qualied personnel is dened as trained sta, who are
authorized to install, commission, and maintain equipment,
systems, and circuits in accordance with pertinent laws and
regulations. Additionally, the personnel must be familiar
with the instructions and safety measures described in this
manual.
WARNING
ELECTRICAL SHOCK HAZARD
VLT® Soft Starter MCD 500 contains dangerous voltages
when connected to mains voltage. Only a qualied
electrician should carry out the electrical installation.
Improper installation of the motor or the soft starter can
cause death, serious injury, or equipment failure. Follow
the guidelines in this manual and local electrical safety
codes.
Models MCD5-0360C ~ MCD5-1600C:
Treat the busbar and heat sink as live parts whenever
the unit has mains voltage connected (including when
the soft starter is tripped or waiting for a command).
WARNING
PROPER GROUNDING
Disconnect the soft starter from mains voltage before
carrying out repair work.
It is the responsibility of the person installing the soft
starter to provide proper grounding and branch circuit
protection according to local electrical safety codes.
Do not connect power factor correction capacitors to the
output of the VLT® Soft Starter MCD 500. If static power
factor correction is employed, it must be connected to
the supply side of the soft starter.
WARNING
IMMEDIATE START
In auto-on mode, the motor can be controlled remotely
(via remote inputs) while the soft starter is connected to
mains.
MCD5-0021B ~ MCD5-0961B:
Transportation, mechanical shock, or rough handling
may cause the bypass contactor to latch into the On
state.
To prevent the motor from starting immediately on rst
commissioning or operation after transportation:
Always ensure that the control supply is applied
•
before the power.
Applying control supply before power ensures
•
that the contactor state is initialized.
WARNING
UNINTENDED START
When the soft starter is connected to AC mains, DC
supply, or load sharing, the motor can start at any time.
Unintended start during programming, service, or repair
work can result in death, serious injury, or property
damage. The motor can start with an external switch, a
eldbus command, an input reference signal from the
LCP or LOP, via remote operation using MCD PC
Software, or after a cleared fault condition.
To prevent unintended motor start:
Press [O]/[Reset] on the LCP before
•
programming parameters.
Disconnect the soft starter from mains.
•
Completely wire and assemble the soft starter,
•
motor, and any driven equipment before
connecting the soft starter to AC mains, DC
supply, or load sharing.
The soft starter is not a safety device and does not
provide electrical isolation or disconnection from the
supply.
If isolation is required, the soft starter must be
•
installed with a main contactor.
Do not rely on the start and stop functions for
•
safety of personnel. Faults occurring in the
mains supply, the motor connection, or the
electronics of the soft starter can cause
unintended motor starts or stops.
If faults occur in the electronics of the soft
•
starter, a stopped motor may start. A temporary
fault in the supply mains or loss of motor
connection can also cause a stopped motor to
start.
To provide safety of personnel and equipment, control
the isolation device through an external safety system.
NOTICE
Before changing any parameter settings, save the current
parameter to a le using MCD PC Software or the Save
User Set function.
NOTICE
Use the autostart feature with caution. Read all the notes
related to autostart before operation.
The examples and diagrams in this manual are included
solely for illustrative purposes. The information contained
in this manual is subject to change at any time and
without prior notice. Responsibility or liability is never
accepted for direct, indirect, or consequential damage
resulting from the use or application of this equipment.
The soft starter always responds to a local start or stop
command (via the [Hand On] and [O] keys on the LCP).
Pressing the [Auto On] key selects remote control (the soft
starter accepts commands from the remote inputs). In
remote mode, the Auto On LED is on. In hand-on mode,
the Hand On LED is on if the soft starter starts or runs. The
O LED is on if the soft starter is stopped or stops.
NOTICE
SELV oers protection by way of extra low voltage.
Protection against electric shock is ensured when the
electrical supply itself is of the SELV type and the installation follows local/national regulations on SELV supplies.
NOTICE
Galvanic (ensured) isolation is obtained by fullling
requirements for higher isolation and by providing the
relevant creepages/clearance distances. These
requirements are described in the IEC 61140 standard.
The components that make up the electrical isolation
also comply with the requirements for higher isolation
and the relevant test as described in IEC 61140.
4.1.3 Remote Inputs
4.1.2 Control Terminals
Control terminations use 2.5 mm2 (14 AWG) plug-in
terminal blocks. Dierent models require control voltage to
dierent terminals:
CV1 (24 V AC/V DC): A5, A6.
•
CV2 (110–120 V AC): A5, A6.
•
CV2 (220–240 V AC): A4, A6.
•
The soft starter has 3 xed inputs for remote control.
Control these inputs by contacts rated for low voltage, low
current operation (gold ash or similar).
12-wire control
23-wire control
34-wire control
Illustration 4.2 2-, 3-, and 4-wire Control
Illustration 4.1 Wiring to Control Terminals
The reset input can be normally open or normally closed.
NOTICE
Do not short terminals 05 and 06 without using a
thermistor.
To select the conguration, use parameter 3-8 Remote Reset
Logic.
WARNING
All control terminals and relay terminals comply with SELV
(safety extra low voltage). This protection does not apply
to grounded delta leg above 400 V.
To maintain SELV, all connections made to the control
terminals must be PELV (for example thermistor must be
reinforced/double insulated from motor).
Do not apply voltage to the control input terminals.
These terminals are active 24 V DC inputs and must be
controlled with potential-free contacts.
Segregate cables to the control inputs from
•
mains voltage and motor cabling.
177HA646.10
177HA647.10
177HA648.10
177HA649.10
5 mm
15 mm
28 mm
11 mm
(M10)
177HA643.10
6 mm
15 mm
28 mm
11 mm
(M10)
177HA644.10
13 mm
12 mm
32 mm
11 mm
(M10)
177HA645.10
Electrical InstallationOperating Guide
4.1.4 Serial Communication
Control via the serial communication network is always
enabled in hand-on mode and can be enabled or disabled
in remote control mode (see parameter 3-2 Comms inRemote). Control via the serial communication network
requires an optional communication module.
4.1.5 Ground Terminal
Ground terminals are at the back of the soft starter.
MCD5-0021B to MCD5-0105B have 1 terminal on
•
the input side (top).
MCD5-0131B to MCD5-0961B and MCD5-0245C to
•
MCD5-1600C have 2 terminals; 1 on the input
side (top), and 1 on the output side (bottom).
Cable size: 6–50 mm2 (AWG 10-1/0)
Torque: 4 Nm (35.4 in-lb)
MCD5-0021B to MCD5-0105B
38 Nm (336.3 in-lb)
4.1.6 Power Terminations
NOTICE
For personnel safety, snap-o tabs protect the power
terminals on models up to MCD5-0105B. When using
large cables, it may be necessary to break o these tabs.
NOTICE
Some units use aluminum busbars. When connecting
power terminations, clean the surface contact area
thoroughly (using an emery or stainless steel brush), and
use an appropriate jointing compound to prevent
corrosion.
Use only copper stranded or solid conductors, rated for
75 °C (167°F) or higher.
14 mm (0.55 in)
Torx T20 x 150
Flat 7 mm x 150
44
MCD5-0131BMCD5-0141B to MCD5-0215BMCD5-0245B
38 Nm (336.3 in-lb)38 Nm (336 in-lb)
MCD5-0331B to MCD5-0396BMCD5-0469B to MCD5-0961BMCD5-0245C
MCD5-0360C to MCD5-0927CMCD5-1200C to MCD5-1600C
Table 4.1 Measurements and Torques for Power Terminations
When installing IP00 soft starters (MCB5-131B and
above), nger guards are specied for personnel safety.
Finger guards t over the soft starter terminals to
prevent accidental contact with live terminals. Finger
guards provide IP20 protection when correctly installed.
44
MCD5-0131B to MCD5-0215B: 175G5662.
•
MCD5-0245B to MCD5-0396B: 175G5730.
•
MCD5-0469B to MCD5-0961B: 175G5731.
•
MCD5-245C: 175G5663.
•
MCD5-0360C to MCD5-0927C: 175G5664.
•
MCD5-1200C to MCD5-1600C: 175G5665.
•
Illustration 4.3 MCD5-0021B to MCD5-0105B, 21–105 A
NOTICE
To be UL-compliant, the models MCD5-0131B to
MCD5-0396B require nger guards.
4.2 Power Input and Output Congurations
4.2.1 Internally Bypassed Models
(MCD5-0021B to MCD5-0961B)
Models MCD5-0021B to MCD5-0215B have power inputs at
the top of the unit and outputs at the bottom of the unit.
Internally bypassed models MCD5-0245B to MCD5-0396B
have output busbars at the bottom of the unit and input
busbars at both the top and bottom. The AC supply can
be connected:
Top-in/bottom-out.
•
Bottom-in/bottom-out
•
Internally bypassed models MCD5-0469B to MCD5-0961B
have input and output busbars at the top and bottom of
the unit. The AC supply can be connected:
Top-in/bottom-out.
•
Top-in/top-out.
•
Bottom-in/bottom-out.
•
Bottom-in/top-out.
•
Illustration 4.4 MCD5-0131B to MCD5-0215B, 131–215 A
Illustration 4.5 MCD5-0245B to MCD5-0396B, 245–396 A
20.0
2/T1 4/T2 6/T3
1/L1 3/L2 5/L3
2/T1 4/T2 6/T3
1/L1 3/L2 5/L3
177HA650.11
177HA651.10
1/L1 3/L2 5/L3
T1B T2B T3B
2/T1 4/T2 6/T3
(L1B L2B L3B)
1/L1 3/L2 5/L3
2/T1 4/T2 6/T3
1/L1 3/L2 5/L3
(L1B L2B L3B)
2/T1 4/T2 6/T3
(L1B L2B L3B)
1/L1 3/L2 5/L3
2/T1 4/T2 6/T3
1/L1 3/L2 5/L3
(L1B L2B L3B)
2/T1 4/T2 6/T3
177HA652.10
Electrical InstallationOperating Guide
Illustration 4.6 MCD5-0469B to MCD5-0961B, 469–961 A
4.2.3 MCD5-0360C to MCD5-1600C
MCD5-0360C to MCD5-1600C have dedicated bypass
terminals on the input busbars. The bypass terminals are:
L1B.
•
L2B.
•
L3B.
•
The busbars on non-bypassed models MCD5-0360C to
MCD5-1600C can be adjusted for top or bottom input and
output as required. See chapter 12 Busbar AdjustmentProcedure (MCD5-0360C to MCD5-1600C) for step-by-step
instructions. The soft starters are manufactured top-in/
bottom-out.
NOTICE
For models MCD5-0360C to MCD5-1600C to be ULcompliant, mount them top-in/bottom-out, or top-out/bottom-in. See chapter 11.1 UL-compliant Installation for
more information.
44
4.2.2 MCD5-0245C
MCD5-0245C has dedicated bypass terminals at the bottom
of the unit. The bypass terminals are:
T1B.
•
T2B.
•
T3B.
•
Illustration 4.7 Bypass Terminals on MCD5-0245C, 245 A
Illustration 4.8 Location of Bypass Terminals, MCD5-0360C to
MCD5-1600C, 360–1600 A
4.3 Motor Connection
VLT® Soft Starters MCD 500 can be connected to the
motor in-line or inside delta (also called 3-wire and 6-wire
connection). When connecting in inside delta, enter the
motor full load current (FLC) in parameter 1-1 Motor FullLoad Current. The MCD 500 automatically calculates inside
delta current based on this data. Parameter 15-7 MotorConnection is set to Auto Detect as default and can be set
to force the soft starter in inside delta or in-line.
The VLT® Soft Starter MCD 500 can be connected to a
small motor for testing. During this test, the control input
and relay output protection settings can be tested. This
test mode is not suitable for testing soft starting or soft
stopping performance.
44
The minimum FLC of the test motor is 2% of the minimum
FLC of the soft starter (see chapter 4.5 Minimum andMaximum Current Settings).
NOTICE
When testing the soft starter with a small motor, set
parameter 1-1 Motor FLC to the minimum allowable
value.
Models which are internally bypassed do not require an
external bypass contactor.
4.3.2 In-line Installation
4.3.2.1 Internally Bypassed
K1Main contactor (optional)
F1
1) To keep the warranty on the SCRs, use semiconductor fuses.
Non-bypassed models have dedicated bypass terminals,
which allow the soft starter to continue providing
protection and monitoring functions even when bypassed
via an external contactor. Connect the bypass contactor to
the bypass terminals and control it by a programmable
output congured to Run (see parameters 4-1 to 4-9).
NOTICE
The bypass terminals on MCD5-0245C are:
T1B.
•
T2B.
•
T3B.
•
The bypass terminals on MCD5-0360C to MCD5-1600C
are:
L1B.
•
L2B.
•
L3B.
•
If necessary, the fuses can be installed on the input side.
When connecting the VLT® Soft Starter MCD 500 in
inside delta conguration, always install a main
contactor or shunt trip circuit breaker.
NOTICE
When connecting in inside delta, enter the motor full
load current (FLC) in parameter 1-1 Motor FLC. The MCD
500 automatically calculates inside delta currents based
on this data. Parameter 15-7 Motor Connection is set to
Auto detect as default and can be set to force the soft
starter in inside delta or in-line.
44
K1Main contactor
K2Bypass contactor (external)
F1
Semiconductor fuses (optional)
1)
1) To keep the warranty on the SCRs, use semiconductor fuses.
1) To keep the warranty on the SCRs, use semiconductor fuses.
4.3.3.3 Externally Bypassed
Non-bypassed models have dedicated bypass terminals,
which allow the soft starter to continue providing
protection and monitoring functions even when bypassed
via an external bypass contactor. Connect the bypass
contactor to the bypass terminals and control the
contactor by a programmable output congured to Run
(see parameters 4-1 to 4-9).
NOTICE
The bypass terminals on MCD5-0245C are:
T1B.
•
T2B.
•
T3B.
•
The bypass terminals on MCD5-0360C to MCD5-1600C
are:
L1B.
•
L2B.
•
L3B.
•
If necessary, the fuses can be installed on the input side.
The minimum and maximum full load current settings depend on the model:
In-line connectionInside delta connection
ModelMinimum [A]Maximum [A]Minimum [A]Maximum [A]
MCD5-0021B523734
MCD5-0037B9431364
44
MCD5-0043B10501575
MCD5-0053B11531679
MCD5-0068B157623114
MCD5-0084B199729145
MCD5-0089B2010030150
MCD5-0105B2110532157
MCD5-0131B2914544217
MCD5-0141B3417051255
MCD5-0195B4020060300
MCD5-0215B4422066330
MCD5-0331B7035070525
MCD5-0396B8542585638
MCD5-0469B100500100750
MCD5-0525B116580116870
MCD5-0632B1407001401050
MCD5-0744B1648201641230
MCD5-0825B1849201841380
MCD5-0961B20010002001500
MCD5-0245C5125577382
MCD5-0360C72360108540
MCD5-0380C76380114570
MCD5-0428C86430129645
MCD5-0595C124620186930
MCD5-0619C130650195975
MCD5-0790C1587902371185
MCD5-0927C1869302791395
MCD5-1200C24012003601800
MCD5-1410C28214104232115
MCD5-1600C32016004802400
Table 4.6 Minimum and Maximum Full Load Current
Bypass Contactor
4.6
Some VLT® Soft Starters MCD 500 are internally bypassed
and do not require an external bypass contactor.
4.7 Main Contactor
Install a main contactor if the VLT® Soft Starter MCD 500 is
connected to the motor in inside delta format and is
optional for in-line connection. Select a contactor with an
Non-bypassed soft starters may be installed with an
external bypass contactor. Select a contactor with an AC1
rating greater than or equal to the full load current rating
of the connected motor.
AC3 rating greater than or equal to the full load current
rating of the connected motor.
4.8 Circuit Breaker
A shunt trip circuit breaker may be used instead of a main
contactor to isolate the motor circuit if a soft starter trips.
The shunt trip mechanism must be powered from the
supply side of the circuit breaker or from a separate
control supply.
Connecting power factor correction capacitors to the
output side damages the soft starter.
Connect power factor correction capacitors to
•
the input side of the soft starter.
If power factor correction is used, use a dedicated
contactor to switch in the capacitors.
4.10 Fuses
4.10.1 Power Supply Fuses
NOTICE
WARRANTY
To keep the warranty on the SCRs, all fuses should be
semiconductor fuses.
NOTICE
Use semiconductor fuses for Type 2 coordination
(according to the IEC 60947-4-2 standard) to prevent
damaging the SCRs. VLT® Soft Starter MCD 500 has
integrated SCR protection against overload transient
currents, but if there is a short circuit (for example due
to a defective motor winding) this protection is not
sucient.
For applications using adaptive control to soft stop the
motor with stop times greater than 30 s, select motor
branch protection as follows:
Standard HRC mains fuses: Minimum 150% motor
•
full load current.
Motor rated mains fuses: Minimum rating
•
100/150% motor full load current.
Motor control circuit breaker minimum long time
•
setting: 150% motor full load current.
Motor control circuit breaker minimum short time
•
setting: 400% motor full load current for 30 s.
Fuse recommendations are calculated for 40 °C (104 °F),
and at an altitude of up to 1000 m (3281 ft).
NOTICE
Fuse selection is based on a 400% FLC start for 20 s
with:
Standard published starts per hour.
•
Duty cycle.
•
40 °C (104 °F) ambient temperature.
•
Up to 1000 m (3281 ft) altitude.
•
For installations operating outside these conditions,
consult a local Danfoss supplier.
Table 4.7 to Table 4.13 contain recommendations only. To
conrm the selection for a particular application, always
consult a local supplier.
44
HRC fuses (such as Ferraz AJT fuses) can be used for Type
1 coordination according to the IEC 60947-4-2 standard.
NOTICE
Adaptive control regulates the speed prole of the motor
within the programmed time limit. This control may
result in a higher level of current than traditional control
methods.
4.10.4 UL Fuse Selection and Short Circuit Ratings
Two short-circuit current ratings (SCCR) are available for UL-compliant applications.
Standard fault currents (@600 V AC circuits)
The standard fault currents are determined referring to UL 508, section 1, table 51.2. This standard species the short-circuit
current that the soft starter must withstand based on the horse power rating (or full load current (FLC) rating, or locked
rotor amps (LRA) depending on the model).
If using the standard fault current ratings, the fuse must be in accordance with the information in Table 4.12 (model- and
manufacturer-specic).
High available fault currents (@480 V AC circuits)
It is possible to specify short-circuit current ratings exceeding the minimum ratings set by the standard fault currents when
the soft starter is able to withstand the high available short-circuit current in accordance with the UL 508 test.
If using the high available fault current ratings, select a suitable fuse based on amperage and fuse class (J or L as
applicable).
The thermal model used for motor overload in the soft
starter has 2 components:
Motor windings: The motor windings have a low
•
thermal capacity and aect the short-term
thermal behavior of the motor. The motor
windings are where the current generates heat.
Motor body: The motor body has a large thermal
•
capacity and aects the long-term behavior of
the motor. The thermal model includes considerations for the following:
-Motor current.
-Iron losses.
-Winding resistance losses.
-Motor body and winding thermal
capacities.
-Cooling during run and cooling at
standstill.
-The percentage of the rated capacity of
the motor. This sets the shown value for
the winding model and is aected by
the motor FLC setting among others.
capacity remaining to complete another start
successfully.
The memory function of the model ensures that
•
the motor is fully protected in warm-start
situations. The model uses data from the realtime clock to account for elapsed cooling time,
even if control power has been removed.
The overload protection function provided by this model is
compliant with a NEMA 10 curve, but provides superior
protection at low levels of overload due to the separation
of the winding thermal model.
55
NOTICE
Set parameter 1-1 Motor FLC to the rated motor FLC. Do
not add the overload rating as the soft starter calculates
this rating.
The thermal overload protection used in the soft starter
has several advantages over the thermal relays.
The eect of fan cooling is accounted for when
•
the motor is running.
The actual full load current and locked rotor time
•
can be used to tune the model more accurately.
The thermal characteristics of the windings are
treated separately from the rest of the motor
(that is the model recognizes that the windings
have low thermal mass and high thermal
resistance).
The winding portion of the thermal model
•
responds rapidly compared with the body
portion. Thus, the motor can be run closer to its
safe maximum operating temperature while still
being protected from thermal damage.
The percentage of motor thermal capacity used
•
during each start is stored in memory. The soft
starter can be congured to determine automatically whether the motor has sucient thermal
1
2
3
1) MSTC is the motor start time constant. It is dened as the locked
rotor time (in parameter 1-2 Locked Rotor Time) when the locked
rotor current is 600% of FLC.
Illustration 5.1 Protection Degree Compared to Overload
Adaptive Control
5.2
Adaptive control is motor control based on the
performance characteristics of the motor. With adaptive
control, select the starting or stopping prole that best
matches the load type. The soft starter automatically
controls the motor to match the prole. The VLT® Soft
Starter MCD 500 oers 3 proles:
C u r r e n t ( % m o t o r f u l l l o a d c u r r e n t )
3
1
2
4
Product Features
VLT® Soft Starter MCD 500
Early acceleration and deceleration.
•
Constant acceleration and deceleration.
•
Late acceleration and deceleration.
•
Adaptive control uses 2 algorithms; 1 to measure the
motor characteristics, and 1 to control the motor. The soft
starter uses the rst start to determine the motor characteristics at 0 speed and at maximum speed. During each
subsequent start and stop, the soft starter dynamically
adjusts its control to ensure that the actual motor
performance matches the selected prole throughout the
start. If the actual speed is too low for the prole, the soft
55
starter increases power to the motor. If the speed is too
high, the soft starter decreases power.
•
•
-Set parameter 1-5 Initial Current to a
level that starts the motor with a light
load.
-Set parameter 1-4 Current Limit to a level
that starts the motor with a heavy load.
The load breaks away easily, but starting time
must be extended (for example a centrifugal
pump where pipeline pressure must build up
slowly).
The electricity supply is limited (for example a
generator set), and a slower increase of load
allows more time for the supply to respond.
5.3 Starting Modes
5.3.1 Constant Current
Constant current is the traditional form of soft starting. It
raises the current from 0 to a specied level and keeps the
current stable at that level until the motor has accelerated.
Constant current starting is ideal for applications where the
start current must be kept below a
specic level.
1 Parameter 1-5 Initial current
2 Parameter 1-6 Start ramp time
3 Parameter 1-4 Current limit
4 Full voltage current
Illustration 5.3 Example of a 10 s Current Ramp Time
5.3.3 Adaptive Control
In an adaptive control soft start, the soft starter adjusts the
current to start the motor within a specied time and uses
1 Parameter 1-5 Initial current
2 Parameter 1-4 Current limit
3 Full voltage current
Illustration 5.2 Example of Constant Current
5.3.2 Current Ramp
Current ramp soft starting raises the current from a
specied starting level (1) to a maximum limit (3), over an
extended period (2), see Illustration 5.3.
Current ramp starting can be useful for applications where:
•
The load can vary between starts (for example a
conveyor, which may start loaded or unloaded).
Adaptive control cannot start the motor faster than a
direct on-line (DOL) start. If the time set in parameter 1-6Start ramp time is shorter than the motor DOL start time,
starting current may reach DOL levels.
Every application has a particular starting prole based on
characteristics of the load and the motor. To meet the
requirements of dierent applications, adaptive control
oers 3 dierent starting proles. Selecting a prole that
matches the inherent prole of the application can help
smooth out acceleration across the full start time. Selecting
a dierent adaptive control prole can neutralize the
inherent prole to some extent.
0
1 0 %
2 0 %
3 0 %
4 0 %
5 0 %
T i m e
6 0 %
7 0 %
8 0 %
9 0 %
1 0 0 %
4
1 7 7 H A 5 0 7 . 1 0
S p e e d
1
2
3
7 0 0 %
6 0 0 %
5 0 0 %
3 0 0 %
1 0 0 %
4 0 0 %
2 0 0 %
1 0 % 2 0 % 3 0 % 4 0 % 5 0 %
R o t o r s p e e d ( % f u l l s p e e d )
6 0 % 7 0 % 8 0 % 9 0 % 1 0 0 %
1 7 7 H A 5 0 8 . 1 0
C u r r e n t ( % m o t o r f u l l l o a d c u r r e n t )
1
5
4
6
3
2
Product FeaturesOperating Guide
To use adaptive control to control starting performance:
1.Select Adaptive control in parameter 1-3 StartMode.
2.Set parameter 1-6 Start Ramp Time.
3.Select the wanted prole in parameter 1-13Adaptive Start Prole.
4.Set parameter 1-4 Current Limitsuciently high to
allow a successful start.
The 1st adaptive control start is a constant current start.
This start type allows the soft starter to learn the characteristics of the connected motor. The soft starter uses this
motor data during subsequent adaptive control starts.
5.3.4 Kick-start
Kick-start provides a short boost of extra torque at the
beginning of a start and can be used with current ramp or
constant current starting.
Kick-start can be useful to help start loads that require
high breakaway torque but then accelerate easily once
they are started (for example ywheel loads such as
presses).
Illustration 5.5 Example of Rotor Speed when using Kick-start
NOTICE
Adaptive control regulates the load according to the
programmed prole. Start current varies according to the
selected acceleration prole and the programmed start
time.
The soft starter has to learn the characteristics of a new
motor:
If replacing a motor connected to a soft starter
•
programmed for adaptive control starting or
stopping.
If the soft starter has been tested on a dierent
•
motor before actual installation.
If parameter 1-1 Motor Full Load Current or parameter1-12 Adaptive Control Gain is changed, the soft starter
automatically relearns the motor characteristics.
Coast to stop lets the motor slow at its natural rate, with
no control from the soft starter. The time required to stop
depends on the type of load.
5.4.2 TVR Soft Stop
Timed voltage ramp reduces the voltage to the motor
gradually over a dened time. The load may continue to
run after the stop ramp is complete.
Timed voltage ramp stopping can be useful for
applications where the stop time has to be extended, or to
avoid transients on generator-set supplies.
7 0 %
6 0 %
5 0 %
3 0 %
1 0 %
4 0 %
T i m e
V o l t a g e ( % f u l l v o l t a g e )
2 0 %
8 0 %
9 0 %
1 0 0 %
1 7 7 H A 5 0 9 . 1 0
1
0
1 0 %
2 0 %
3 0 %
4 0 %
5 0 %
T i m e
S p e e d
6 0 %
7 0 %
8 0 %
9 0 %
1 0 0 %
1 7 7 H A 5 1 0 . 1 0
1 2
4
3
Product Features
VLT® Soft Starter MCD 500
of the connected motor. The soft starter uses this motor
data during subsequent adaptive control stops.
NOTICE
Adaptive control regulates the load according to the
programmed prole. Stopping current varies according
to the selected deceleration prole and stop time.
The soft starter has to learn the characteristics of a new
motor:
If replacing a motor connected to a soft starter
•
programmed for adaptive control starting or
55
1 Parameter 1-11 Stop Time
Illustration 5.6 TVR Soft Stop
5.4.3 Adaptive Control
To use adaptive control to control stopping performance:
1.Select Adaptive control from the Stop Mode menu.
2.Set parameter 1-11 Stop Time.
3.Select the required prole in parameter 1-14Adaptive Stop Prole.
Adaptive control does not actively slow the motor down
and does not stop the motor faster than a coast to stop.
To shorten the stopping time of high-inertia loads, use a
brake function, see chapter 5.4.5 Brake.
The rst adaptive control stop is a normal soft stop. This
stop type allows the soft starter to learn the characteristics
If parameter 1-1 Motor Full Load Current or parameter
1-12 Adaptive Control Gain is changed, the soft starter
automatically relearns the motor characteristics.
5.4.4 Pump Stopping
The hydraulic characteristics of pump systems vary considerably. This variation means that the ideal deceleration
prole and stop time vary from application to application.
Table 5.1 provides guidelines on selecting between
adaptive control proles. For identication of the best
prole for the application, test all 3 proles.
Adaptive stop
prole
Late decelerationHigh-head systems, where even a small
Constant
deceleration
Early decelerationOpen pump systems, where uid must drain
Table 5.1 Selection of Adaptive Control Deceleration Proles
5.4.5 Brake
A brake reduces the required stop time of the motor.
During braking, an increased noise level from the motor
may be audible. This noise is a normal part of motor
braking.
stopping.
If the soft starter has been tested on a dierent
•
motor before actual installation.
Application
decrease in motor/pump speed results in a
rapid transition between forward ow and
reverse ow.
Low to medium head, high-ow
applications, where the uid has high
momentum.
back through the pump without driving the
pump in reverse.
1 0 0 %
7 0 %
0 %
3 0 %
1
2
3
1 7 7 H A 5 1 1 . 1 0
T i m e
S p e e d
Product FeaturesOperating Guide
CAUTION
EQUIPMENT DAMAGE
If the brake torque is set too high, the motor stops
before the end of the brake time. The motor suers
unnecessary heating, which could result in damage.
Careful conguration is required to ensure safe operation
of the soft starter and the motor.
A high brake torque setting can result in peak currents
up to motor DOL being drawn while the motor is
stopping. Ensure that protection fuses installed in the
motor branch circuit are selected appropriately.
CAUTION
RISK OF OVERHEATING
Brake operation causes the motor to heat faster than the
rate calculated by the motor thermal model. If using
brake functionality, install a motor thermistor or allow
sucient restart delay (parameter 2-11 Restart Delay).
When brake is selected, the soft starter uses DC injection
to slow the motor.
too low, the motor does not stop completely and
coasts to stop by the end of the braking period.
55
1 Parameter 1-11 Stop Time
2 Parameter 1-16 Brake Time
3 Coast to stop time
Illustration 5.8 Brake Time
Braking
Does not require the use of a DC brake contactor.
•
Controls all 3 phases so that the braking currents
•
and associated heating are evenly distributed
through the motor.
Braking has 2 stages:
1.Prebrake: Provides an intermediate level of
braking to slow motor speed to a point where
full brake can be operated successfully (approximately 70% speed).
2.Full brake: Provides maximum braking torque but
is ineective at speeds greater than approximately 70%.
To congure the VLT® Soft Starter MCD 500 for brake
operation:
1.Set parameter 1-11 Stop Time for the wanted
stopping time duration (1), see Illustration 5.8. The
stop time is the total brake time. Set the stop
time suciently longer than the brake time
(parameter 1-16 Brake Time) to allow the
prebraking stage to reduce motor speed to
approximately 70%. If the stop time is too short,
braking is not successful and the motor coasts to
stop.
2.Set parameter 1-16 Brake Time to approximately
25% of the programmed stop time. The brake
time sets the time for the full brake-stage (2), see
Illustration 5.8.
3.Adjust parameter 1-15 Brake Torque so that the
wanted stopping performance is achieved. If set
NOTICE
When using DC brake:
1.Connect the mains supply to the soft starter
(input terminals L1, L2, L3) in positive phase
sequence.
2.Set parameter 2-1 Phase Sequence to Positive
only.
NOTICE
For loads which may vary between braking cycles, install
a zero-speed sensor to ensure that the soft starter ends
DC braking when the motor stops. This installation
avoids unnecessary heating of the motor.
For more information on using the MCD 500 with an
external speed sensor (for example for applications with
variable load during the braking cycle), see chapter 5.12 DCBrake with External Zero-speed Sensor.
Jog Operation
5.5
Jog runs the motor at reduced speed to allow alignment
of the load or to assist servicing. The motor can be jogged
in either forward or reverse direction.
The maximum available torque for jog forward is approximately 50–75% of motor full load torque (FLT) depending
on the motor. When the motor is jogged in reverse, the
torque is approximately 25–50% of FLT. Parameter 15-8 JogTorque controls how much of the maximum available jog
torque the soft starter applies to the motor.
Setting parameter 15-8 Jog Torque above 50% may cause
increased shaft vibration.
55
1 Jog forward
2 Jog reverse
3 Normal operation
CAUTION
REDUCED MOTOR COOLING
Slow speed running is not intended for continuous
operation due to reduced motor cooling. Jog operation
causes the motor to heat faster than the rate calculated
by the motor thermal model.
If using jog, install a motor thermistor, or allow
Adaptive control, jog, and brake functions are not
supported in inside delta (6-wire) operation. If these
functions are programmed when the soft starter is
connected inside delta, the behavior is as in Table 5.2:
Adaptive
control
start
Adaptive
control
stop
JogThe soft starter issues a warning with the error
BrakeThe starter performs a coast to stop.
The soft starter performs a constant current start.
If stop time is >0 s, the starter performs a TVR soft
stop. If stop time is set to 9 s, the starter performs a
coast to stop.
message Unsupported Option.
Illustration 5.9 Jog Operation
To activate jog operation, use a programmable input
(parameter 3-3 Input A Function).
To stop a jog operation, perform either of the following:
Remove the jog command.
•
Press [O] on the LCP.
•
Activate Starter disable using the LCP
•
programmable inputs.
If the jog command is still present, jog recommences at
the end of a restart delay. All other commands except the
ones listed are ignored during jog operation.
Table 5.2 Inside Delta Behavior at Adaptive Control, Jog,
and Brake
NOTICE
When connected in inside delta, current imbalance is the
only phase loss protection that is active during run. Do
not disable parameter 2-2 Current Imbalance during
inside delta operation.
NOTICE
Inside delta operation is only possible with mains
voltage ≤600 V AC.
NOTICE
Soft start and soft stop are not available during jog
operation. Jog is only available for the primary motor.
To determine the typical start current for an application,
use this information.
NOTICE
These start current requirements are appropriate and
typical in most circumstances. However, the performance
and start torque requirements of motors and machines
do vary. For further assistance, contact the local Danfoss
supplier.
General and water
Agitator4.0 x FLC
Centrifugal pump3.5 x FLC
Compressor (screw, unloaded)3.0 x FLC
Compressor (reciprocating, unloaded)4.0 x FLC
Conveyor4.0 x FLC
Fan (damped)3.5 x FLC
Fan (undamped)4.5 x FLC
Mixer4.5 x FLC
Positive displacement pump4.0 x FLC
Submersible pump3.0 x FLC
Table 5.3 Typical Start Currents for General and Water
Applications
Pulp and paper
Dryer4.5 x FLC
Repulper4.5 x FLC
Shredder4.5 x FLC
Table 5.6 Typical Start Currents for Pulp and Paper Applications
Petrochemical
Ball mill4.5 x FLC
Centrifuge4.0 x FLC
Extruder5.0 x FLC
Screw conveyor4.0 x FLC
Table 5.7 Typical Start Currents for Petrochemical Applications
Transport and machine tool
Ball mill4.5 x FLC
Grinder3.5 x FLC
Material conveyor4.0 x FLC
Palletizer4.5 x FLC
Press3.5 x FLC
Roller mill4.5 x FLC
Rotary table4.0 x FLC
Table 5.8 Typical Start Currents for Transport and Machine
Tool Applications
55
Metals and mining
Belt conveyor4.5 x FLC
Dust collector3.5 x FLC
Grinder3.0 x FLC
Hammer mill4.5 x FLC
Rock crusher4.0 x FLC
Roller conveyor3.5 x FLC
Roller mill4.5 x FLC
Tumbler4.0 x FLC
Wire draw-machine5.0 x FLC
Table 5.4 Typical Start Currents for Metals and Mining
Applications
Food processing
Bottle washer3.0 x FLC
Centrifuge4.0 x FLC
Dryer4.5 x FLC
Mill4.5 x FLC
Palletizer4.5 x FLC
Separator4.5 x FLC
Slicer3.0 x FLC
Lumber and wood products
Bandsaw4.5 x FLC
Chipper4.5 x FLC
Circular saw3.5 x FLC
Debarker3.5 x FLC
Edger3.5 x FLC
Hydraulic power pack3.5 x FLC
Planer3.5 x FLC
Sander4.0 x FLC
Table 5.9 Typical Start Currents for Lumber and Wood
Products Applications
Table 5.5 Typical Start Currents for Food Processing
The VLT® Soft Starter MCD 500 is installed with a main contactor (AC3 rated). Supply control voltage from the input side of
the contactor.
The soft starter main contactor output controls the main contactor. The main contactor output is by default assigned to
output relay A (terminals 13, 14).
55
1Control voltage (model dependent)K1Main contactor
224 V DC outputF1Semiconductor fuses (optional)
3Remote control inputsS1Start/stop
4Motor thermistor input (PTC only)S2Reset contact
5Relay outputs13, 14Relay output A
63-phase supply21, 22, 24Relay output B
7Motor terminals33, 34Relay output C
Illustration 5.10 Installation with Main Contactor
Parameter settings:
Parameter 4-1 Relay A Function
•
-Select Main contactor - assigns the main contactor function to relay output A (default value).
The VLT® Soft Starter MCD 500 is installed with a bypass contactor (AC1 rated). The soft starter run output controls the
bypass contactor. The run output is by default assigned to output relay B (terminals 21, 22, 24).
55
1Control voltage (model dependent)K1Bypass contactor
224 V DC outputF1Semiconductor fuses (optional)
3Remote control inputsS1Start contact
4Motor thermistor input (PTC only)S2Stop contact
5Relay outputsS3Reset contact
63-phase supply13, 14Relay output A
7Motor terminals21, 22, 24Relay output B
33, 34Relay output C
Illustration 5.11 Installation with Bypass Contactor
Parameter settings:
•
Parameter 4-4 Relay B Function.
-Select Run - assigns the run output function to output relay B (default value).
In normal operation, the VLT® Soft Starter MCD 500 is controlled via a remote 2-wire signal (terminals 17, 18).
A 2-wire circuit connected to input A (terminals 11, 16) controls emergency run. Closing input A causes the soft starter to
run the motor and ignore all trip conditions.
55
1Control voltage (model dependent)S1Start/stop contact
224 V DC outputS2Reset contact
3Remote control inputsS3Emergency run contact
4Motor thermistor input (PTC only)13, 14Relay output A
5Relay outputs21, 22, 24Relay output B
63-phase supply33, 34Relay output C
7Motor terminals
Illustration 5.12 Emergency Run Operation
Parameter settings:
•
•
Parameter 3-3 Input A Function.
-Select Emergency Run - assigns input A to emergency run function.
Although Emergency run fullls the functionality requirements of re mode, Danfoss does not recommend its use in
situations that require testing and/or compliance with specic standards as it is not certied.
5.11 Auxiliary Trip Circuit
In normal operation, the VLT
®
Soft Starter MCD 500 is controlled via a remote 2-wire signal (terminals 17, 18).
Input A (terminals 11, 16) is connected to an external trip circuit (such as a low-pressure alarm switch for a pumping
system). When the external circuit activates, the soft starter trips and stops the motor.
55
1Control voltage (model dependent)S1Start/stop contact
224 V DC outputS2Reset contact
3Remote control inputsS3Auxiliary trip contact
4Motor thermistor input (PTC only)13, 14Relay output A
-Select Input Trip (N/O) - assigns input A to auxiliary trip (N/O) function.
Parameter 3-4 Input A Name.
•
-Select a name, for example Low Pressure - assigns a name to input A.
Parameter 3-8 Remote Reset Logic.
•
-Select as required, for example Normally Closed - the input behaves like a normally closed contact.
5.12 DC Brake with External Zero-speed
Sensor
55
For loads varying between braking cycles, there are
benets in using an external zero-speed sensor to interface
with the VLT® Soft Starter MCD 500 for brake shut-o. This
control method ensures that the MCD 500 braking always
shuts o when the motor has reached a standstill, thus
avoiding unnecessary motor heating.
Illustration 5.14 shows how to use a zero-speed sensor with
the MCD 500 to turn o the brake function at motor
standstill. The zero-speed sensor (-A2) is often referred to
as an underspeed detector. Its internal contact is open at 0
speed and closed at any speed above 0 speed. Once the
motor has reached a standstill, terminals 11 and 16 open,
and the soft starter is disabled. When the next start
command is given, that is next application of K10,
terminals 11 and 16 close, and the soft starter is enabled.
Operate the MCD 500 in auto-on mode and set parameter3-3 Input A Function to Starter disable.
1Control voltage15, 16 Start
2Motor terminals17, 18 Stop
33-phase supply25, 18 Reset
4Starter disable
AO (ready)
(shown on soft
starter display)
5Start signal (2-, 3-,
BStart
or 4-wire)
6Zero-speed detectCRun
7Zero-speed sensorDStop
EZero speed
Illustration 5.14 Turning O Brake Function at Standstill with
For details on conguring DC Brake, see chapter 5.4.5 Brake.
NOTICE
When using DC brake, connect the mains supply to the
soft starter (input terminals L1, L2, L3) in positive phase
sequence. Then set parameter 2-1 Phase Sequence to
Positive only.
3
177HA526.12
6
5
6
4
2
3
1
K3T
K2
K10K11K12K13K1
M1
54 55585756
F1
K2K1
K12
S2K13
A2
K1T
K1TK2T K3T
K1K2
K1 K2S1 K10K10
Y1
Y2
Y1
Y2
K10
K2T
4/T2
6/T3
E
1/L1
3/L2
5/L3
2/T1
33
34
A4 A5 A6
05
06
K12
K11S3
53
Product FeaturesOperating Guide
5.13 Soft Braking
For high inertia loads, the VLT® Soft Starter MCD 500 can be congured for soft braking.
In this application, the MCD 500 is employed with forward run and braking contactors. When the soft starter receives a start
signal (push-button S1), it closes the forward run contactor (K1) and controls the motor according to the programmed
primary motor settings.
When the soft starter receives a stop signal (push-button S2), it opens the forward run contactor (K1) and closes the braking
contactor (K2) after a delay of approximately 2–3 s (KT1). K12 is also closed to activate the secondary motor settings, which
are user-programmed for the wanted stopping performance characteristics.
When motor speed approaches 0, the external zero-speed sensor (A2) stops the soft starter and opens the braking contactor
(K2).
1Control voltage (model dependent)K10Run relay
2Remote control inputsK11Start relay
3Motor thermistor input (PTC only)K12Brake relay
4Relay outputsK13Zero-speed detector relay
53-phase supplyK1Line contactor (run)
6Motor terminalsK2Line contactor (brake)
A2Zero-speed sensorK1TRun delay timer
S1Start contactK2TBrake delay timer
S2Stop contactK3TZero-speed detector delay timer
S3Reset contact
55
Illustration 5.15 Soft Braking Conguration
Parameter settings:
•
Parameter 3-3 Input A Function.
-Select Motor Set Select - assigns input A for motor set selection.
-Set starting performance characteristics using the primary motor set (parameter group 1 Primary Motor
-Set braking performance characteristics using the secondary motor settings (parameter group 7 Secondary
Parameter 4-7 Relay C Function.
•
-Select Trip - assigns trip function to output relay C.
Motor Set).
VLT® Soft Starter MCD 500
NOTICE
If the soft starter trips on supply frequency (parameter 16-5 Frequency) when the braking contactor K2 opens, modify
the settings of parameters 2-8 to 2-10.
5.14 Two-speed Motor
55
The VLT® Soft Starter MCD 500 can be congured for control of 2-speed Dahlander type motors, using a high-speed
contactor (K1), low-speed contactor (K2), and a star contactor (K3).
NOTICE
Pole amplitude modulated (PAM) motors alter the speed by eectively changing the stator frequency using external
winding conguration. Soft starters are not suitable for use with this type of 2-speed motor.
When the soft starter receives a high-speed start signal, it closes the high-speed contactor (K1) and star contactor (K3). Then
it controls the motor according to the primary motor settings (parameters 1-1 to 1-16).
When the soft starter receives a low-speed start signal, it closes the low-speed contactor (K2). This action closes input A and
the soft starter controls the motor according to the secondary motor settings (parameters 7-1 to 7-16).
NOTICE
If the soft starter trips on supply frequency (16-5 Frequency) when the high-speed start signal (7) is removed, modify the
settings of parameters 2-8 to 2-10.
Contactors K2 and K3 must be mechanically interlocked.
Parameter settings:
Parameter 3-3 Input A Function.
•
-Select Motor Set Select - assigns input A for motor set selection.
•
NOTICE
If the soft starter trips on supply frequency (parameter 16-5 Frequency) when the high-speed signal (7) is removed,
modify the settings of parameters 2-9 to 2-10.
-Set high-speed performance characteristics using parameters 1-1 to 2-9.
-Set low-speed performance characteristics using parameters 7-1 to 7-16.
Parameter 4-4 Relay B Function.
-Select Trip - assigns trip function to relay output B.
6
Operation
VLT® Soft Starter MCD 500
6 Operation
6.1 Control Methods
The VLT® Soft Starter MCD 500 can be controlled:
Via the control keys on the LCP (local control).
•
Via the remote inputs (remote control).
•
Via the serial communication network.
•
Control functions
Local control is only available in hand-on mode.
•
Remote control is only available in auto-on mode.
•
Control via the serial communication network is always disabled in hand-on mode. Enable or disable start/stop
•
commands via the serial network in auto-on mode by changing the setting of parameter 3-2 Comms in Remote.
The MCD 500 can also be congured to autostart or autostop. Autostart/stop operation is only available in auto-on mode. In
hand-on mode, the soft starter ignores any autostart/stop setting. To congure autostart/stop operation, set parameters 5-1
to 5-4.
To switch between hand-on mode and auto-on mode, press the keys on the LCP.
[Hand On]: Start the motor and enter hand-on mode.
•
[O]: Stop the motor and enter hand-on mode.
•
[Auto On]: Set the soft starter to auto-on mode.
•
[Reset]: Reset a trip (hand-on mode only).
•
The MCD 500 can also be set to allow local control only or remote control only, using parameter 3-1 Local/Remote.
If parameter 3-1 Local/Remote is set to Remote Control Only, the
the serial communication network.
Hand-on modeAuto-on mode
To soft start the motor.Press [Hand On] on the LCP.Activate the Start remote input.
To stop the motor.Press [O] on the LCP.Activate the Stop remote input.
To reset a trip on the soft starter.Press [Reset] on the LCP.Activate the Reset remote input.
Autostart/stop operation.Disabled.Enabled.
Table 6.1 Start, Stop, and Reset in Hand-on Mode and Auto-on Mode
To stop the motor with a coast to stop, regardless of the setting in parameter 1-10 Stop Mode, press
same time. The soft starter removes power from the motor and opens the main contactor, and the motor coasts to stop.
[O] key is disabled. Stop the motor by remote control or via
[O] and [Reset] at the
NOTICE
Brake and jog functions operate only with in-line connected motors (see chapter 5.6 Inside Delta Operation).
To reset a trip on the soft starter, press [Reset] on
•
the LCP.
To stop the motor with a coast to stop, regardless
•
of the setting of parameter 1-10 Stop mode, press
[O] and [Reset] at the same time. The soft
starter removes power from the motor and opens
the main contactor, and then the motor coasts to
stop.
In auto-on mode:
To soft start the motor, activate the Start remote
•
input.
To stop the motor, activate the Stop remote input.
•
To reset a trip on the soft starter, activate the
•
Reset remote input.
NOTICE
Brake and jog functions operate only with in-line
connected motors (see chapter 4.3.3 Inside Delta Instal-lation).
6.2.2 The LCP
14-line display for status and programming details.
A remote-mounted LCP can be installed with the VLT® Soft
Starter MCD 500. The control panel LCP 501 can be
mounted up to 3 m (9.8 ft) away from the soft starter, for
control and monitoring.
The soft starter can be controlled and programmed from
either the remote LCP or the LCP on the soft starter. Both
displays show the same information.
The remote LCP also allows parameter settings to be
copied between soft starters.
6.3.1 Synchronizing the LCP and the Soft
Starter
The DB9 cable can be connected/disconnected from the
LCP while the soft starter runs.
The rst time an LCP is plugged into a soft starter, the soft
starter copies its parameter settings to the LCP.
New display detected
If the LCP has previously been used with a VLT® Soft
Starter MCD 500, select whether to copy the parameters
from the LCP to the soft starter, or from the soft starter to
the LCP.
NOTICE
While the LCP synchronizes, only the [▲], [▼], [OK], and
[O] keys are enabled.
NOTICE
The LCP can be removed or replaced while the soft
starter is running. It is not necessary to remove mains or
control voltage.
6.4 Welcome Screen
When control power is applied, the soft starter shows the
welcome screen.
ReadyS1
Welcome
1.05/2.0/1.13
MCD5-0053-T5-G1-
CV2
Third display line: Software versions for remote LCP, control software,
model software.
Fourth display line: Product model number.
NOTICE
The LCP version is only shown if a remote LCP 501 is
connected when control power is applied. If no remote
LCP is present, only the control software and model
software versions are shown.
6.5 Local Control Keys
To select the required option:
1.
Press the [▲] and [▼] keys.
A dotted line surrounds the selected option.
2.Press [OK] to proceed with the Copy Parameters
selection.
2aDisplay to soft starter.
2bSoft starter to display.
Copy parameters
Display to soft starter
Soft starter to display
NOTICE
If the parameter software version in the LCP is dierent
from the software version of the soft starter, only Starterto Display is available.
If parameter 3-1 Local/Remote is set to LCL/RMT Anytime or
LCL/RMT When OFF, the [Hand On] and [Auto On] keys are
always active. If the soft starter is in auto-on mode,
pressing [Hand On] enters hand-on mode and starts the
motor.
If parameter 3-1 Local/Remote is set to Remote Control Only,
the [O] key is disabled. Stop the motor by remote control
or via the serial communication network.
Displays
6.6
The LCP shows a wide range of performance information
about the soft starter. Press [Status] to access the status
display screens, then press [▲] and [▼] to select the
information to be shown. To return to the status screens
from within a menu, press [Back] repeatedly, or press
[Status]. Available status information:
The temperature screen shows the temperature of the
motor as a percentage of total thermal capacity. It also
shows which motor data set is in use.
The temperature monitoring screen is the default status
screen.
ReadyS1
MS1000.0A000.0kW
Primary Motor Set
M1 000%
6.6.2 Programmable Screen (S2)
The user-programmable screen of the soft starter can be
congured to show the most important information for the
particular application. Use parameters 8-2 to 8-5 to select
which information to show.
ReadyS2
MS1000.0A000.0kW
-.-- pf
00000 hrs
6.6.5 Frequency Monitoring Screen (S5)
The frequency screen shows the mains frequency as
measured by the soft starter.
ReadyS5
MS1000.0A000.0kW
00.0Hz
6.6.6 Motor Power Screen (S6)
The motor power screen shows motor power (kW, hp, and
kVA) and power factor.
ReadyS6
MS1000.0A000.0kW
000.0kW0000HP
0000kVA-. - - pf
6.6.7 Last Start Information (S7)
The last start information screen shows details of the most
recent successful start:
Start duration, (s).
•
Maximum start current drawn (as a percentage of
•
motor full load current).
Calculated rise in motor temperature.
•
ReadyS7
MS1000.0A000.0kW
Last start000 s
000% FLC
ΔTemp 0%
6.6.8 Date and Time (S8)
6
6
6.6.3 Average Current (S3)
The average current screen shows the average current of
all 3 phases.
ReadyS3
MS1000.0A000.0kW
0.0A
The date and time screen shows the current system date
and time (24-hour format). For details on setting the date
and time, see chapter 9.1 Set Date and Time.
ReadyS8
MS1000.0A000.0kW
YYYY MMM DD
HH:MM:SS
6.6.4 Current Monitoring Screen (S4)
The current screen shows real-time line current on each
phase.
The SCR conduction bar graph shows the level of
conduction on each phase.
Illustration 6.2 Bar Graph
6.6.10 Performance Graphs
The VLT® Soft Starter MCD 500 can show real-time
performance information for:
Current.
•
Motor temperature.
•
Motor kW.
•
Motor kVA.
•
Motor power factor.
•
The newest information is shown at the right side of the
screen. Older data is not stored. To allow past performance
to be analyzed, the graph can also be paused. To pause or
unpause the graph, press and hold [OK] for more than
0.5 s.
NOTICE
The soft starter does not collect data while the graph is
paused. When graphing resumes, a small gap is shown
between the old data and the new data.
It is possible to access the programming menus at any
time, including while the soft starter is running. All
changes take eect immediately.
7.1 Access Control
A 4-digit security access code protects critical parameters
(parameter group 15 Restricted Parameters and higher),
preventing unauthorized users from viewing or modifying
parameter settings.
If attempts are made to enter a restricted parameter group,
the LCP prompts for an access code. The access code is
requested once for the programming session, and authorization continues until the menu is closed.
To enter the access code:
1.Press [Back] and [OK] to select a digit.
2.
Press [▲] and [▼] to change the value.
3.When all 4 digits match the access code, press
[OK].
The LCP shows an acknowledgement message before
continuing.
Enter Access Code
####
OK
Access Allowed
SUPERVISOR
To change the access code, use parameter 15-1 Access Code.
NOTICE
The security access code also protects the protection
simulation and output simulation. The counters and
thermal model reset can be viewed without entering an
access code, but an access code must be entered to
reset.
The default access code is 0000.
To prevent users from altering parameter settings, lock the
menus. The adjustment lock can be set to allow Read &
Write, Read Only, or No Access in parameter 15-2 Adjustment
Lock.
If attempting to change a parameter value or access the
Main Menu when the adjustment lock is active, an error
message is shown:
Access Denied
Adj Lock is On
7.2 Quick Menu
[Quick Menu] provides access to the menus for setting up
the soft starter for simple applications.
7.2.1 Quick Set-up
Quick set-up provides access to commonly used
parameters, allowing conguration of the soft starter as
required for the application. For details of individual
parameters, see chapter 8 Parameter Descriptions.
Table 7.5 Suggested Values for Undamped Fan Applications
Compressor screw
7.2.2 Application Set-up Examples
Motor full load current
The application set-ups menu makes it easy to congure
the soft starter for common applications. The soft starter
selects the parameters relevant to the application and
Start modeConstant current
Start ramp time5 s
Current limit400%
suggests a typical setting. Each parameter can be adjusted
to suit the exact requirements.
Table 7.6 Suggested Values for Compressor Screw Applications
77
On the display, the highlighted values are suggested
values. The values indicated by ▶ are the loaded values.
Always set parameter 1-1 Motor FLC to match the motor
nameplate full load current. The suggested value for motor
FLC is the minimum FLC of the soft starter.
Centrifugal pump
Motor full load current
Start modeAdaptive control
Adaptive start proleEarly acceleration
Start ramp time10 s
Stop modeAdaptive control
Adaptive stop proleLate deceleration
Stop time15 s
Table 7.2 Suggested Values for Centrifugal Pump Applications
Submersible pump
Motor full load current
Start modeAdaptive control
Adaptive start proleEarly acceleration
Start ramp time5 s
Stop modeAdaptive control
Adaptive stop proleLate deceleration
Stop time5 s
Compressor recip
Motor full load current
Start modeConstant current
Start ramp time10 s
Current limit450%
Table 7.7 Suggested Values for Compressor Recip Applications
Conveyor
Motor full load current
Start modeConstant current
Start ramp time5 s
Current limit400%
Stop modeAdaptive control
Adaptive stop proleConstant deceleration
Stop time10 s
Table 7.8 Suggested Values for Conveyor Applications
Crusher rotary
Motor full load current
Start modeConstant current
Start ramp time10 s
Current limit400%
Excess start time30 s
Locked rotor time20 s
Table 7.3 Suggested Values for Submersible Pump Applications
Table 7.9 Suggested Values for Crusher Rotary Applications
Damped fan
Motor full load current
Start modeConstant current
Current limit350%
Table 7.4 Suggested Values for Damped Fan Applications
Table 7.10 Suggested Values for Crusher Jaw Applications
7.2.3 Loggings
To view performance information in real-time graphs, enter
the Loggings menu.
Current (%FLC).
•
Motor Temp (%).
•
Motor kW (%).
•
Motor kVA (%).
•
Motor pf.
•
The newest information is shown at the right side of the
screen. The graph can be paused to analyze data by
pressing and holding the [OK] key. To restart the graph,
press and hold [OK].
7.3.1 Parameters
Parameters allow viewing and changing all programmable
parameters that control how the soft starter operates.
To open Parameters, press [Main Menu] then select
Parameters.
Navigating through parameters
To scroll through parameter groups, press [▲] or
•
[▼].
To view the parameters in a group, press [OK].
•
To return to the previous level, press [Back].
•
To close Parameters, press the [Back].
•
Changing a parameter value
Scroll to the appropriate parameter and press
•
[OK] to enter edit mode.
To alter the parameter setting, press [▲] and [▼].
•
To save changes, press [OK]. The setting shown
•
on the display is saved and the LCP returns to the
parameter list.
To cancel changes, press [Back]. The LCP returns
•
to the parameter list without saving changes.
77
Main Menu
7.3
[Main Menu] provides access to menus for setting up the
soft starter for advanced applications and for monitoring
performance.
7.3.2 Parameter Shortcut
The VLT® Soft Starter MCD 500 also includes a parameter
shortcut, which gives direct access to a parameter within
the Parameters menu.
The parameters in Primary Motors Settingscongure the
soft starter to match the connected motor. These
parameters describe the operating characteristics of the
motor and allow the soft starter to model the motor
temperature.
NOTICE
Parameter 1-2 Locked Rotor Time determines the trip
current for motor overload protection. Its default setting
provides motor overload protection:
Class 10.
•
Trip current 105% of FLA, or equivalent.
•
1-1 Motor FLC
Option:Function:
Model
dependent
Matches the soft starter to the connected
motor full load current. Set to the full load
current (FLC) rating shown on the motor
nameplate.
NOTICE
The setting for this parameter sets the
basis for calculation of all current-based
protection settings.
1-2 Locked Rotor Time
Range:Function:
10 s* [0:01–2:00
(min:s)]
Sets the maximum length of the time the
motor can sustain locked rotor current from
cold before reaching its maximum
temperature. Set according to the motor
datasheet.
1-5 Initial Current
Range:Function:
350%* [100–
600%
FLC]
1-6 Start Ramp Time
Range:Function:
10 s* [1–
180 s]
1-7 Kick-start Level
Range:Function:
500%* [100–
700% FLC]
Sets the initial start current level for current
ramp starting as a percentage of motor full load
current. Set so that the motor begins to
accelerate immediately after a start is initiated.
If current ramp starting is not required, set the
initial current equal to the current limit. See
chapter 5.3 Starting Modes for more details.
Sets the total start time for an adaptive control
start or the ramp time for current ramp
starting (from the initial current to the current
limit). See chapter 5.3 Starting Modes for more
details.
CAUTION
INCREASED TORQUE LEVEL
Kick-start subjects the mechanical
equipment to increased torque levels.
•
Sets the level of the kick-start current.
88
Ensure that the motor, load,
and couplings can handle the
additional torque before
using this feature.
Kick-start subjects the mechanical
equipment to increased torque
levels.
•
Ensure that the motor,
load, and couplings can
handle the additional
torque before using this
1-12 Adaptive Control Gain
Range:Function:
NOTICE
Leave the gain setting at the default
level unless adaptive control
performance is not satisfactory. If the
motor accelerates or decelerates too
quickly at the end of a start or stop,
increase the gain setting by 5–10%. If
the motor speed uctuates during
starting or stopping, decrease the gain
setting slightly.
feature.
1-13 Adaptive Start Prole
Sets the kick-start duration. A setting of 0
disables kick-start. See chapter 5.3 Starting
Modes for more details.
1-9 Excess Start Time
Range:Function:
Excess start time is the maximum time the soft
88
20 s* [0:00–
4:00
(min:s)]
starter attempts to start the motor. If the
motor does not reach full speed within the
programmed limit, the soft starter trips. Set for
a period slightly longer than required for a
normal healthy start. A setting of 0 disables
excess start time protection.
Set as required.
1-10 Stop Mode
Option:Function:
Selects the stop mode. See
chapter 5.4 Stopping Modes for more details.
Coast to stop*
TVR soft stop
Adaptive control
Brake
1-11 Stop Time
Range:Function:
0s* [0:00–
4:00
(min:s)]
Sets the time for soft stopping the motor using
timed voltage ramp or adaptive control. If a main
contactor is installed, the contactor must remain
closed until the end of the stop time. To control
the main contactor, use a programmable output
congured to Run. Sets the total stopping time
when using brake. See chapter 5.4 Stopping
Modes for more details.
1-12 Adaptive Control Gain
Range:Function:
75%* [1–200%] Adjusts the performance of adaptive control.
This setting aects both starting and stopping
control.
Option:Function:
Selects which prole the soft starter uses
for an adaptive control soft start. See
chapter 5.4 Stopping Modes for more
details.
Early acceleration
Constant
acceleration*
Late acceleration
1-14 Adaptive Stop Prole
Option:Function:
Selects which prole the soft starter uses
for an adaptive control soft stop. See
chapter 5.4 Stopping Modes for more
details.
Early deceleration
Constant
deceleration*
Late acceleration
8.1.1 Brake
Brake uses DC injection to slow the motor actively. See
chapter 5.4 Stopping Modes for more details.
1-15 Brake Torque
Range:Function:
20%* [20–100%] Sets the amount of brake torque the soft
starter uses to slow the motor.
1-16 Brake Time
Range:Function:
1 s* [1–30 s] Sets the duration for DC injection during a
braking stop.
NOTICE
This parameter is used with parameter
1-11 Stop Time. See chapter 5.4 Stopping
Modes for details.
allows at a start. During its prestart checks, the
soft starter examines the sequence of the
phases at its input terminals. If the actual
sequence does not match the selected option,
the soft starter trips.
Any sequence*
Positive only
Negative only
8.2.1 Current Imbalance
If the currents on the 3 phases vary by more than a
specied amount, the soft starter can be congured to trip.
The imbalance is calculated as the dierence between the
highest and lowest currents on all 3 phases, as a
percentage of the highest current.
Current imbalance detection is desensitized by 50% during
starting and soft stopping.
2-2 Current Imbalance
Range:Function:
30%* [10–50%] Sets the trip point for current imbalance
protection.
2-3 Current Imbalance Delay
Range:Function:
3 s* [0:00–4:00
(min:s)]
Slows the response of the soft starter to
current imbalance, avoiding trips due to
momentary uctuations.
8.2.2 Undercurrent
If the average current of all 3 phases drops below a
specied level while the motor is running, the soft starter
can be congured to trip.
2-4 Undercurrent
Range:Function:
20%* [0–
100%]
2-5 Undercurrent Delay
Range:Function:
5 s* [0:00–4:00
(min:s)]
Sets the trip point for undercurrent protection,
as a percentage of motor full load current. Set to
a level between the normal motor working
range and the motor magnetizing (no load)
current (typically 25–35% of full load current). A
setting of 0% disables undercurrent protection.
Slows the response of the soft starter to
undercurrent, avoiding trips due to
momentary uctuations.
8.2.3 Instant Overcurrent
If the average current of all 3 phases exceeds a specied
level while the motor is running, the soft starter can be
congured to trip.
2-6 Instantaneous Overcurrent
Range:Function:
400%* [80–600%
FLC]
Sets the trip point for instant overcurrent
protection as a percentage of motor full
load current.
2-7 Instantaneous Overcurrent Delay
Range:Function:
0 s* [0:00–1:00
(min:s)]
Slows the response of the soft starter to
overcurrent, avoiding trips due to
momentary overcurrent events.
8.2.4 Frequency Trip
The soft starter monitors mains frequency throughout
operation and can be congured to trip if the frequency
varies beyond a specied tolerance.
2-8 Frequency Check
Option:Function:
Determines when the soft starter monitors for a
frequency trip.
Do not check
Start only
Start/run*
Run only
2-9 Frequency Variation
Option: Function:
Selects the soft starter tolerance for frequency
variation.
±2 Hz
±5 Hz*
±10 Hz
±15 Hz
2-10 Frequency Delay
Range:Function:
1 s* [0:01–4:00
(min:s)]
Slows the response of the soft starter to
frequency disturbances, avoiding trips due to
momentary uctuations.
NOTICE
If the mains frequency drops below
35 Hz or rises above 75 Hz, the soft
starter trips immediately.
Always active* A trip can occur at any time when the soft
starter is receiving power.
Operating only A trip can occur while the soft starter is
running, stopping, or starting.
Run onlyA trip can only occur while the soft starter is
running.
3-6 Input A Trip Delay
Range:Function:
0 s* [0:00–4:00 (min:s)] Sets delay between the input
activating and soft starter tripping.
3-7 Input A Initial Delay
Range:Function:
0 s* [00:00–
30:00 (min:s)]
Sets a delay before an input trip can occur.
The initial delay is counted from the time a
start signal is received. The state of the input
is ignored until the initial delay has elapsed.
3-8 Remote Reset Logic
Option:Function:
Selects whether the remote reset input of the
soft starter (terminals 25 and 18) is normally
open or normally closed.
Normally closed*
Normally open
8.4 Outputs
4-1 Relay A Function
Option:Function:
Selects the function of relay A (normally open).
ORelay A is not used
Main
contactor*
The relay closes when the soft starter receives
a start command and remains closed as long
as the motor receives voltage.
4-1 Relay A Function
Option:Function:
RunThe relay closes when the starter changes to
run state.
TripThe relay closes when the starter trips.
WarningThe relay closes when the starter issues a
warning.
Low current
ag
High current
ag
Motor temp
ag
The relay closes when the low current ag
activates (parameter 4-10 Low Current Flag).
The relay closes when the high current ag
activates (parameter 4-11 High Current Flag).
The relay closes when the motor temperature
ag activates (parameter 4-12 Motor
Temperature Flag).
8.4.1 Relay A Delays
The soft starter can be congured to wait before opening
or closing relay A.
4-2 Relay A On Delay
Range:Function:
0 s* [0:00–5:00 (min:s)]Sets the delay for closing relay A.
4-3 Relay A O Delay
Range:Function:
0 s* [0:00–5:00 (min:s)]Sets the delay for reopening relay A.
8.4.2 Relays B and C
Parameters 4-4 to 4-9congure the operation of relays B
and C in the same way as parameters 4-1 to 4-3congure
relay A. See parameter 4-2 Relay A On Delay and parameter4-3 Relay A O Delay for details.
Relay B is a changeover relay.
•
Relay C is normally open.
•
4-4 Relay B Function
Option:Function:
Selects the function of relay B (changeover).
ORelay B is not used.
Main
contactor
Run*The relay closes when the soft starter changes
TripThe relay closes when the soft starter trips.
WarningThe relay closes when the soft starter issues a
0 s* [0:00–5:00 (min:s)]Sets the delay for closing relay B.
4-6 Relay B O Delay
4-10 Low Current Flag
Range:Function:
50%* [1–100%
FLC]
Sets the level at which the low current
ag operates, as a percentage of motor
full load current.
4-11 High Current Flag
Range:Function:
100%* [50–600%
FLC]
Sets the level at which the high current
ag operates, as a percentage of motor
full load current.
Range:Function:
0 s* [0:00–5:00 (min:s)]Sets the delay for reopening relay B.
8.4.4 Motor Temperature Flag
4-7 Relay C Function
Option:Function:
Selects the function of relay C (normally open).
ORelay C is not used.
Main
contactor
88
RunThe relay closes when the soft starter changes
Trip*The relay closes when the soft starter trips.
WarningThe relay closes when the soft starter issues a
Low current
ag
High current
ag
Motor temp
ag
The relay closes when the soft starter receives a
start command and remains closed as long as
the motor is receiving voltage.
to run state.
warning.
The relay closes when the low current ag
activates (parameter 4-10 Low Current Flag).
The relay closes when the high current ag
activates (parameter 4-11 High Current Flag).
The relay closes when the motor temperature
ag activates (parameter 4-12 Motor Temperature
Flag).
4-8 Relay C On Delay
Range:Function:
0 s* [0:00–5:00 (min:s)]Sets the delay for closing relay C.
4-9 Relay C O Delay
Range:Function:
0 s* [0:00–5:00 (min:s)]Sets the delay for reopening relay C.
8.4.3 Low Current Flag and High Current
Flag
The soft starter has low and high current ags to give early
warning of abnormal operation. The current ags can be
congured to indicate an abnormal current level during
operation between the normal operating level and the
undercurrent or instant overcurrent trip levels. The ags
can signal the situation to external equipment via 1 of the
programmable outputs. The ags clear when the current
returns within the normal operating range by 10% of the
programmed ag value.
The soft starter has a motor temperature ag to give early
warning of abnormal operation. The ag can indicate that
the motor is operating above its normal operating
temperature, but lower than the overload limit. The ag
can signal the situation to external equipment via 1 of the
programmable outputs.
4-12 Motor Temperature Flag
Range:Function:
80%* [0–160%] Sets the level at which the motor temperature
ag operates, as a percentage of the motor
thermal capacity.
8.4.5 Analog Output A
The soft starter has an analog output, which can be
connected to associated equipment to monitor motor
performance.
4-13 Analog Output A
Option:Function:
Selects which information is reported via analog
output A.
Current (%
FLC)*
Motor
temp (%)
Motor kW
(%)
Motor kVA
(%)
Motor pfMotor power factor, measured by the soft starter.
Current as a percentage of motor full load current.
100%* [0–600%] Calibrates the upper limit of the analog
output to match the signal measured on an
external current measuring device.
4-16 Analog A Minimum Adjustment
Range:Function:
0%* [0–600%] Calibrates the lower limit of the analog output
to match the signal measured on an external
current measuring device.
8.5 Start/Stop Timers
5-4 Auto-Stop Time
Range:Function:
1 min* [00:01–
24:00
(hrs:min)]
Sets the time for the soft starter to
autostop in 24-hour clock format.
NOTICE
Do not use this function with
remote 2-wire control. The soft
starter still accepts start and stop
commands from the remote inputs
or serial communication network. To
disable local or remote control, use
parameter 3-1 Local/Remote. If
autostart is enabled and the user is
in the menu system, autostart
becomes active if the menu times
out (if no LCP activity is detected for
5 minutes).
8.6 Auto-reset
The soft starter can be programmed to reset certain trips
automatically, which can help minimize operating
downtime. Trips are divided into 3 categories for autoreset, depending on the risk to the soft starter:
88
CAUTION
UNINTENDED START
The autostart timer overrides any other form of control.
The motor may start without warning.
5-1 Auto-Start Type
Option: Function:
Selects whether the soft starter autostarts after a
specied delay or at a specic time of day.
O*The soft starter does not autostart.
Timer The soft starter does autostart after a delay from the
next stop, as specied in parameter 5-2 Auto-start Time.
Clock The soft starter autostarts at the time programmed in
parameter 5-2 Auto-start Time.
5-2 Auto-Start Time
Range:Function:
1 min* [00:01–24:00
(hrs:min)]
5-3 Auto-Stop Type
Option: Function:
Selects whether the soft starter autostops after a
specied delay or at a specic time of day.
O*The soft starter does not autostop.
TimeThe soft starter autostops after a delay from the next
start, as specied in parameter 5-4 Auto-stop Time.
Clock The soft starter autostops at the time programmed in
parameter 5-4 Auto-stop Time.
Sets the time for the soft starter to
autostart in 24-hour clock format.
Group
Current imbalance
Phase loss
A
Power loss
Frequency
Undercurrent
B
Instant overcurrent
Input A trip
Motor overload
C
Motor thermistor
Heat overtemperature
Table 8.1 Trip Categories for Auto-reset
Other trips cannot be automatically reset.
This function is ideal for remote installations using 2-wire
control in auto-on mode. If the 2-wire start signal is
present after an auto-reset, the soft starter restarts.
75%* [1–200%] Adjusts the performance of adaptive control.
The setting aects both starting and stopping
control.
NOTICE
Leave the gain setting at the default
level unless adaptive control
performance is not satisfactory.
If the motor accelerates or decelerates
quickly at the end of a start or stop,
increase the gain setting by 5–10%. If
the motor speed uctuates during
starting or stopping, decrease the gain
setting slightly.
7-13 Adaptive Start Prole-2
Option:Function:
Selects which prole the soft starter
uses for an adaptive control soft start.
Early acceleration
Constant acceleration*
Late acceleration
7-14 Adaptive Stop Prole-2
Option:Function:
Selects which prole the soft starter
uses for an adaptive control soft stop.
Early deceleration
Constant deceleration*
Late acceleration
7-15 Brake Torque-2
Range:Function:
20%* [20–100%] Sets the amount of brake torque the soft
starter uses to slow the motor.
7-16 Brake Time-2
Range:Function:
1 s* [1–30 s]
8.8 Display
8-1 Language
Option:Function:
English*
Chinese (中丈)
Spanish (Español)
German (Deutsch)
Portuguese (Português)
NOTICE
This parameter is used with parameter
7-11 Stop Time-2.
Sets the duration for DC injection during a
braking stop.
Selects in which language the LCP
shows messages and feedback.
8-1 Language
Option:Function:
French (Français)
Italian (Italiano)
Russian (Русский)
8.8.1 User-programmable Screen
Selects which 4 items to show on the programmable
monitoring screen.
8-2 User Screen - Top Left
Option:Function:
Selects the item shown in the top left part of
the screen.
BlankShows no data in the selected area, allowing
long messages to be shown without
overlapping.
Starter stateThe operating state of the soft starter (starting,
running, stopping, or tripped). Only available
for Top L and Btm L.
Motor currentThe average current measured on 3 phases.
Motor pf*The motor power factor measured by the soft
starter.
Mains
frequency
Motor kWThe motor running power in kW.
Motor hpThe motor running power in horse power.
Motor tempThe motor temperature, calculated by the
kWhThe number of kWh the motor has run via the
Hours runThe number of hours the motor has run via
8-3 User Screen - Top Right
Option:Function:
Blank*Shows no data in the selected area, allowing
Starter stateThe operating state of the soft starter (starting,
Motor currentThe average current measured on 3 phases.
Motor pfThe motor power factor measured by the soft
Mains
frequency
Motor kWThe motor running power in kW.
Motor hpThe motor running power in horse power.
Motor tempThe motor temperature, calculated by the
Read only Prevents users altering parameter values in the
No accessPrevents users adjusting parameters in the
Allows altering parameter values in the
programming menu.
programming menu. Parameter values can still be
viewed.
programming menu unless an access code is
entered.
NOTICE
Changes to the adjustment lock setting take
eect only after the programming menu
has been closed.
15-3 Emergency Run
Option: Function:
CAUTION
EQUIPMENT DAMAGE
Continued use of emergency run is not
recommended. Emergency run may compromise
the soft starter life as all protections and trips
are disabled.
Using the soft starter in Emergency run mode
voids the product warranty.
Selects whether the soft starter allows emergency run
operation. In emergency run, the soft starter starts (if
not already running) and continues to operate until
emergency run ends, ignoring stop commands and
trips.
Emergency run is controlled using a programmable
input.
When emergency run is activated in internally bypassed
models which are not running, the soft starter attempts
a normal start while ignoring all trips. If a normal start
is not possible, a DOL start via the internal bypass
contactors is attempted. For non-bypassed models, an
external emergency run bypass contactor may be used.
15-5 Main Contactor Time
Range:Function:
400 ms* [100–
2000 ms]
Sets the delay period between the soft
starter switching the main contactor
output (terminals 13 and 14) and
beginning the prestart checks (before
start) or entering the not ready state
(after a stop). Set according to the speci-
cations of the main contactor used.
15-6 Bypass Contactor Time
Range:Function:
150 ms* [100–
2000 ms]
Sets the soft starter to match the bypass
contactor closing/opening time. Set
according to the specications of the
bypass contactor used. If the time is too
short, the soft starter trips.
15-7 Motor Connection
Option:Function:
The soft starter automatically detects the format
of the connection to the motor.
Auto-Detect*
In-line
Inside Delta
15-8 Jog Torque
Range:Function:
50%* [20–100%]
NOTICE
Setting this parameter above 50% may
cause increased shaft vibration.
Sets the torque level for jog operation. See
chapter 5.5 Jog Operation for more details.
88
15-4 Current Calibration
Range:Function:
100%* [85–
115%]
Motor current calibration calibrates the soft
starter's current monitoring circuits to match an
external current metering device.
Use the following formula to determine the
necessary adjustment:
Calibration( % ) =
e . g . 102 % =
CurrentshownonMCD500display
Currentmeasuredbyexternaldevice
66A
65A
NOTICE
This adjustment aects all current-based
functions.
The security access code also protects simulation tools
and counter-resets. The default access code is 0000.
9.1 Set Date and Time
To set the date and time:
1.Open the Tools Menu.
2.Scroll to Set Date & Time.
3.Press [OK] to enter edit mode.
4.Press [OK] to select which part of the date or
time to edit.
5.
Use [▲] and [▼] to change the value.
To save changes, press [OK] repeatedly. The soft starter
conrms the changes. To cancel changes, press [Back]
repeatedly.
Load/Save Settings
9.2
The VLT® Soft Starter MCD 500 includes options to:
Load defaults: Load the soft starter parameters
•
with default values.
Load User Set 1: Reload previously saved
•
parameter settings from an internal le.
Save User Set 1: Save the current parameter
•
settings to an internal le.
In addition to the factory default values le, the soft starter
can store a user-dened parameter le. This le contains
default values until a user le is saved.
Load Defaults
No
Yes
Table 9.2 Load Defaults Menu
When the action has been completed, the screen briey
shows a conrmation message and then returns to the
status screens.
9.3 Reset Thermal Model
NOTICE
The security access code protects the reset thermal
model.
The advanced thermal modeling software in the soft
starter constantly monitors the motor performance. This
monitoring allows the soft starter to calculate the motor
temperature and ability to start successfully at any time.
If necessary, reset the thermal model.
NOTICE
Resetting the motor thermal model may compromise
motor life and should only be done in the case of
emergency.
1.Open Tools.
2.Scroll to Reset Thermal Model and press [OK].
3.At the conrmation prompt, press [OK] to
conrm, then enter the access code, or press
[Back] to cancel the action.
4.Select Reset or Do Not Reset, then press [OK].
When the thermal model has been reset, the soft
starter returns to the previous screen.
99
To load or save parameter settings:
1.Open the Tools Menu.
2.
Use [▼] to select the required function, then press
[OK].
3.At the
4.Press [OK] to load/save the selection or exit the
Protection simulation is protected by the security access
code.
To test the operation and control circuits of the soft starter
without connecting it to mains voltage, use the software
simulation functions.
The protection simulation feature enables the soft starter
to conrm that it responds correctly and reports the
situation on the display and across the communication
network.
To use the protection simulation:
1.Open the Main Menu.
2.Scroll to Protection Sim and press [OK].
3.
To select the protection to simulate, press [▲] and
[▼].
4.To simulate the selected protection, press [OK].
5.The screen is shown while [OK] is pressed. The
99
MS1000.0A0000.0kW
Tripped
Selected Protection
Table 9.5 Protection Simulation Menu
soft starter response depends on the protection
action setting (parameter group 16 ProtectionActions).
6.To return to the simulation list, press [Back].
7.
To select another simulation, press [▲] or [▼], or
press [Back] to return to the Main Menu.
NOTICE
To test operation of the ags (motor temperature and
low/high current), set an output relay to the appropriate
function and monitor the relay behavior.
To use the output signal simulation:
1.Open the Main Menu.
2.Scroll to Output Signal Sim and press [OK], then
enter the access code.
3.
To select a simulation, press [▲] and [▼], then
press [OK].
4.
To turn the signal on and o, press [▲] and [▼].
To conrm correct operation, monitor the state of
the output.
5.To return to the simulation list, press [Back].
Prog Relay A
O
On
Table 9.6 Output Signal Simulation Menu
Digital I/O State
9.6
This screen shows the status of the digital I/O in order.
The top line of the screen shows:
Start.
•
Stop.
•
Reset.
•
Programmable input.
•
The bottom line of the screen shows programmable
outputs A, B, and C.
NOTICE
If the protection trips the soft starter, reset before
simulating another protection. If the protection action is
set to Warn or Log, no reset is required.
If the protection is set to Warn & Log, the warning
message can be viewed only while [OK] is pressed.
If the protection is set to Log only, nothing appears on
the screen, but an entry appears in the log.
Inputs: 0100
Outputs: 100
Table 9.7 Digital I/O Status Screen
Temp Sensors State
9.7
Digital I/O State
9.5 Output Signal Simulation
NOTICE
The security access code protects the output signal
simulation.
The LCP allows simulation of output signaling to conrm
that the output relays are operating correctly.
This screen shows the state of the motor thermistor.
The screenshot shows the thermistor state as O (open).
Temp Sensors State
Thermistor: O
S = shrt H=hot C=cld O=opn
Table 9.8 Motor Thermistor Status Screen
ToolsOperating Guide
9.8 Alarm Log
The [Alarm Log] key opens the alarm logs, which contain:
Trip log.
•
Event log.
•
Counters which store information on the soft
•
starter operating history.
9.8.1 Trip Log
The trip log stores details of the 8 most recent trips,
including the date and time the trip happened. Trip 1 is
the most recent and trip 8 is the oldest stored trip.
To open the trip log:
1.Press [Alarm Log].
2.Scroll to Trip Log and press [OK].
3.
To select a trip to view, press [▲] and [▼], then
press [OK] to show details.
To close the log and return to the main display, press
[Back].
The resettable counters (hours run, starts, and motor kWh)
can only be reset if the correct access code is entered.
To view the counters:
1.Press [Alarm Log].
2.Scroll to Counters and press [OK].
3.
To scroll through the counters, press [▲] and [▼].
Press [OK] to view details.
4.To reset a counter, press [OK], then enter the
access code. Select Reset, then press [OK] to
conrm.
To close the counter and return to the alarm logs, press
[Back].
9.8.2 Event Log
The event log stores time-stamped details of the 99 most
recent events (actions, warnings, and trips), including the
date and time of the event. Event 1 is the most recent and
event 99 is the oldest stored event.
To open the event log:
1.Press [Alarm Log].
2.Scroll to Event Log and press [OK].
3.
To select an event to view, press [▲] and [▼], then
press [OK] to show details.
To close the log and return to the main display, press
[Back].
9.8.3 Counters
NOTICE
The security access code protects the counters function.
The performance counters store statistics on the soft
starter operation:
Hours run (lifetime and time since the last reset
•
of the counter).
Number of starts (lifetime and time since the last
When a protection condition is detected, the VLT® Soft
Starter MCD 500 writes this condition to the event log and
may also trip or issue a warning. The soft starter response
depends on the protection action settings (parametergroup 16 Protection Actions).
Some protection responses cannot be adjusted. Usually,
external events (for example phase loss) or a fault within
the soft starter cause these trips. These trips do not have
associated parameters and cannot be set to Warn or Log.
If the soft starter trips:
1.Identify and clear the condition that triggered the
trip.
2.Reset the soft starter.
3.Restart the soft starter.
To reset the soft starter, press [Reset] or activate the Resetremote input.
If the soft starter has issued a warning, it resets itself when
the cause of the warning has been resolved.
10.1 Trip Messages
Table 10.1 lists the protection mechanisms in the soft starter and the probable cause of the trip. Some of these protection
mechanisms can be adjusted using parameter group 2 Protection and parameter group 16 Protection Action. Other settings are
built-in system protections and cannot be set or adjusted.
DisplayPossible cause/suggested solution
Awaiting dataThe LCP does not receive data from the control PCB. Check the cable connection and the tting of
the display on the soft starter.
Battery/clockA verication error has occurred on the real-time clock, or the back-up battery voltage is low. If the
1010
ControllerName selected for a programmable input. Refer to Input A trip.
Current imbalance Problems with the motor, the environment, or the installation can cause current imbalance, such as:
Current read err lxWhere X is 1, 2, or 3.
battery is low and the power is o, date/time settings are lost. Reprogram the date and time.
Related parameter:
Parameter 16-12 Battery Clock.
•
An imbalance in the incoming mains voltage.
•
A problem with the motor windings.
•
A light load on the motor.
•
A phase loss on mains terminals L1, L2, or L3 during run mode.
•
An SCR that has failed open circuit. A failed SCR can only be diagnosed accurately by replacing the
SCR and checking the soft starter performance.
Related parameters:
Parameter 2-2 Current Imbalance.
•
Parameter 2-3 Current Imbalance Delay.
•
Parameter 16-2 Current Imbalance.
•
Internal fault (PCB fault). The output from the current transformer circuit is not close enough to 0
when the SCRs are turned o. Contact the local Danfoss supplier for advice.
Excess start timeExcess start time trip can occur under the following conditions:
Parameter 1-1 Motor FLC is not appropriate for the motor.
•
Parameter 1-4 Current Limit has been set too low.
•
Parameter 1-6 Start Ramp Time has been set higher than the setting in parameter 1-9 Excess Start
•
Time Setting.
Parameter 1-6 Start Ramp Time is set too short for a high inertia load when using adaptive
•
control.
Related parameters:
Parameter 1-1 Motor FLC.
•
Parameter 1-4 Current Limit.
•
Parameter 1-6 Start Ramp Time.
•
Parameter 1-9 Excess Start Time.
•
Parameter 7-1 Motor FLC-2.
•
Parameter 7-4 Current Limit-2.
•
Parameter 7-6 Start Ramp-2.
•
Parameter 7-9 Excess Strt Time-2.
•
Parameter 16-7 Excess Start Time.
•
Firing fail pxWhere X is phase 1, 2, or 3.
The SCR did not re as expected. Check for faulty SCRs and internal wiring faults.
This trip is not adjustable.
Related parameters: None.
FLC too highThe soft starter can support higher motor full load current values when connected to the motor
using inside delta conguration rather than in-line connection. If the soft starter is connected in-
line, but the programmed setting for parameter 1-1 Motor FLC exceeds the in-line maximum, the
soft starter trips at start (see chapter 4.5 Minimum and Maximum Current Settings).
If the soft starter is connected to the motor using inside delta conguration, check that the soft
starter detects the connection correctly. Contact the local Danfoss supplier for advice.
Related parameters:
Parameter 1-1 Motor FLC.
•
Parameter 7-1 Motor FLC-2.
•
FrequencyThe mains frequency is outside of the specied range.
Check for other equipment in the area that could be aecting the mains supply, particularly
frequency converters and switch mode power supplies (SMPS).
If the soft starter is connected to a generator-set supply, the generator may be too small or could
have a speed control problem.
Related parameters:
Parameter 2-8 Frequency Check.
•
Parameter 2-9 Frequency Variation.
•
Parameter 2-10 Frequency Delay.
•
Parameter 16-5 Frequency.
•
Heat sink overtempCheck that cooling fans are operating. If mounted in an enclosure, check if ventilation is adequate.
Fans operate during start, run, and for 10 minutes after the soft starter exits the stop state.
NOTICE
Models MCD5-0021B ~ MCD4-0053B and MCD5-0141B do not have a cooling fan.
Models with fans operate the cooling fans from a start until 10 minutes after a stop.
If the start current is too low, the motor does not produce enough torque to
•
accelerate to full speed. The soft starter may trip on excess start time.
NOTICE
Make sure that the motor starting parameters are appropriate for the
application and that the intended motor starting prole is used. If
parameter 3-3 Input A Function is set to Motor Set Select, check that the
corresponding input is in the expected state.
Check if the load is jammed. Check the load for severe overloading or a locked
•
rotor situation.
Erratic motor operation.
Erratic and noisy motor operation.If the soft starter is connected to the motor using inside delta conguration, the soft
Soft stop ends too quickly.
1010
Adaptive control, DC brake, and jog functions not
working.
A reset does not occur after an auto-reset when
using a remote 2-wire control.
Remote start/stop command overrides autostart/
stop settings when using remote 2-wire control.
After selecting adaptive control, the motor used an
ordinary start and/or the 2nd start was dierent
from the 1st start.
Non-resettable Thermistor Cct trip, when there is a
link between thermistor inputs 05 and 06, or when
the motor thermistor connected between 05 and
06 is permanently removed.
Parameter settings cannot be stored.
The LCP shows message Awaiting data.The LCP does not receive data from the control PCB. Check the cable connection.
The SCRs in the soft starter require at least 5 A of current to latch. If testing the
•
soft starter on a motor with full load current less than 5 A, the SCRs may not
latch correctly.
starter may not be detecting the connection correctly. Contact the local Danfoss
supplier for advice.
The soft stop settings may not be appropriate for the motor and load. Review the
•
settings of:
-Parameter 1-10 Stop Mode.
-Parameter 1-11 Stop Time.
-Parameter 7-10 Stop Mode-2.
-Parameter 7-11 Stop Time-2.
If the motor is lightly loaded, soft stop has limited eect.
•
These features are only available with in-line installation. If the soft starter is
•
installed inside delta, these features do not operate.
Remove and reapply the remote 2-wire start signal for a restart.
•
Only use autostart/stop in auto-on mode with 3-wire or 4-wire control.
•
The 1st adaptive control start is Current limit. The soft starter then learns from the
•
motor characteristics. Subsequent starts use adaptive control.
The thermistor input is enabled once a link is tted and short-circuit protection
•
has activated.
Remove the link, then load the default parameter set. This disables the thermistor
input and clears the trip.
Place a 1.2 kΩ resistor across the thermistor input.
Turn thermistor protection to Log only (parameter 16-9 Motor Thermistor).
Make sure to save the new value by pressing [OK] after adjusting a parameter
•
setting. If pressing [Back], the change is not saved.
Check that the adjustment lock (parameter 15-2 Adjustment Lock) is set to Read/
•
Write. If the adjustment lock is on, settings can be viewed, but not changed.
Knowing the security access code is necessary to change the adjustment lock
setting.
The EEPROM may be faulty on the main control PCB. A faulty EEPROM also trips
•
the soft starter, and the LCP shows the message Par. Out of Range. Contact the
Supply
Mains voltage (L1, L2, L3)
MCD5-xxxx-T5200–525 V AC (±10%)
MCD5-xxxx-T7380–690 V AC (±10%) (in-line connection)
MCD5-xxxx-T7380–690 V AC (±10%) (inside delta connection)
Control voltage (A4, A5, A6)
CV1 (A5, A6)24 V AC/V DC (±20%)
CV2 (A5, A6)110–120 V AC (+10%/-15%)
CV2 (A4, A6)220–240 V AC (+10%/-15%)
Current consumption (maximum)
CV12.8 A
CV2 (110–120 V AC)1 A
CV2 (220–240 V AC)500 mA
Mains frequency45–66 Hz
Rated insulation voltage to ground690 V AC
Rated impulse withstand voltage4 kV
Form designationBypassed or continuous, semiconductor motor starter form 1
Short-circuit capability (IEC)
Coordination with semiconductor fusesType 2
Coordination with HRC fuses Type 1
MCD5-0021B to MCD5-0215BProspective current 65 kA
MCD5-0245B to MCD5-0961BProspective current 85 kA
MCD5-0245C to MCD5-0927BProspective current 85 kA
MCD5-1200C to MCD5-1600CProspective current 100 kA
For UL short-circuit current ratings, see Table 4.12.
Electromagnetic capability (compliant with EU Directive 2014/30/EU)
EMC emissionsIEC 60947-4-2 Class B and Lloyds Marine No 1 Specication
EMC immunityIEC 60947-4-2
Inputs
Input ratingActive 24 V DC, 8 mA approximately
Start (15, 16)Normally open
Stop (17, 18)Normally closed
Reset (25, 18)Normally closed
Programmable input (11, 16)Normally open
Motor thermistor (05, 06)Trip >3.6 kΩ, reset <1.6 kΩ
Outputs
Relay outputs10 A @ 250 V AC resistive, 5 A @ 250 V AC AC15 pf 0.3
Programmable outputs
Relay A (13, 14)Normally open
Relay B (21, 22, 24)Changeover
Relay C (33, 34)Normally open
Analog output (07, 08)0–20 mA or 4–20 mA (selectable)
Maximum load600 Ω (12 V DC @ 20 mA)
Accuracy±5%
24 V DC output (16, 08) maximum load200 mA
Accuracy±10%
Environmental
Protection
MCD5-0021B to MCD5-0105BIP20 & NEMA, UL Indoor Type 1
MCD5-0131B to MCD5-1600CIP00, UL Indoor Open Type
Operating temperature-10 °C (14 °F) to +60 °C (140 °F), above 40 °C (104 °F) with derating
Storage temperature-25 °C (-13 °F) to +60 °C
Operating altitude (using MCD PC software)0–1000 m (0–3281 ft), above 1000 m (3281 ft) with derating
Humidity5–95% relative humidity
Pollution degreePollution degree 3
VibrationIEC 60068-2-6
Heat dissipation
During start4.5 W per ampere
During run
MCD5-0021B to MCD5-0053B≤39 W approximately
MCD5-0068B to MCD5-0105B≤51 W approximately
MCD5-0131B to MCD5-0215B≤120 W approximately
MCD5-0245B to MCD5-0469B≤140 W approximately
MCD5-0525B to MCD5-0961B≤357 W approximately
MCD5-0245C to MCD5-0927C4.5 W per ampere approximately
MCD5-1200C to MCD5-1600C4.5 W per ampere approximately
VLT® Soft Starter MCD 500
Certication
C✓IEC 60947-4-2
UL/C-UL
MCD5-0021B to MCD5-0396B, MCD5-0245C to MCD5-1600C
MCD5-0469B to MCD5-0961B
MCD5-0021B to MCD5-105B
MCD5-0131B to MCD5-1600C
CEIEC 60947-4-2
1111
CCCGB 14048-6
Marine
(MCD5-0021B to MCD5-0961B)Lloyds Marine No 1 Specication
RoHSCompliant with EU Directive 2002/95/EC
1) For UL certication extra requirements may apply, depending on the models. For details, see chapter 11.1 UL-compliant Installation.
UL-compliant Installation
11.1
11.1.3 Models MCD5-0245B to
IP20, when tted with optional nger guard kit
UL recognized
UL 508
UL listed
1)
MCD5-0396B
This section details more requirements and conguration
settings for the VLT® Soft Starter MCD 500 to be ULcompliant. See also Table 4.12.
11.1.1 Models MCD5-0021B to
MCD5-0105B
Use with nger guard kit, ordering number
•
175G5730.
Use the recommended pressure terminal/
•
connector kit. See Table 11.1 for more
information.
There are no additional requirements for these models.
11.1.2 Models MCD5-0131B to
MCD5-0215B
Use with nger guard kit, ordering number
•
175G5662.
Use the recommended pressure terminal/
•
connector kit. See Table 11.1 for more
information.
connector kit. See Table 11.1 for more
information.
SpecicationsOperating Guide
11.1.5 Models MCD5-0360C to
MCD5-1600C
Congure the busbars for line/load terminals at
•
opposite ends of the soft starter (that is Top in/
Bottom out, or Top out/Bottom in.
Use the recommended pressure terminal/
•
connector kit. See Table 11.1 for more
information.
11.1.6 Models MCD5-0469B to
MCD5-0961B
These models are UL recognized components. Separate
cable landing busbars may be required within the electrical
cabinet when terminating cables sized according to the
National Wiring Code (NEC) regulations.
11.1.7 Pressure Terminal/Connector Kits
For models MCD50131B to MCD5-0396B and MCD5-0245C
to MCD5-1600C to be UL-compliant, use the recommended
pressure terminal/connector as detailed in Table 11.1.
ModelFLC (A)
MCD5-0131B1451 OPHD 95-16
MCD5-0141B1701 OPHD 120-16
MCD5-0195B2001 OPHD 150-16
MCD5-0215B2201 OPHD 185-16
MCD5-0245B2551 OPHD 240-20
MCD5-0331B3501OPHD 400-16
MCD5-0396B4252OPHD 185-16
MCD5-0245C2551OPHD 240-20
MCD5-0360C360
MCD5-0380C380
MCD5-0428C430
MCD5-0595C620
MCD5-0619C650
MCD5-0790C79042 x 600T-2
MCD5-0927C93032 x 600T-2
MCD5-1200C1200
MCD5-1410C1410
MCD5-1600C16005
Number of
wires
21 x 600T-2
4 1 x 750T-4
Recommended
lugs ordering
numbers
1 x 750T-4 and
1 x 600T-3
Accessories
11.2
11.2.1 LCP Remote Mounting Kit
The VLT® Soft Starter MCD 500 LCP can be mounted up to
3 m (9.8 ft) away from the soft starter, allowing remote
control and monitoring. The remote LCP also allows
parameter settings to be copied between soft starters.
175G0096 Control Panel LCP 501.
•
11.2.2 Communication Modules
VLT® Soft Starter MCD 500 supports network communication via easy-to-install communication modules. Each
soft starter can support 1 communication module at a
time.
Available protocols:
Ethernet (PROFINET, Modbus TCP, EtherNet/IP).
•
PROFIBUS.
•
DeviceNet.
•
Modbus RTU.
•
USB.
•
Ordering numbers for communication modules
175G9000 Modbus module.
•
175G9001 PROFIBUS module.
•
175G9002 DeviceNet module.
•
175G9009 MCD USB module.
•
175G9904 Modbus TCP module.
•
175G9905 PROFINET module.
•
175G9906 EtherNet/IP module.
•
11.2.3 PC Software
WinMaster PC software provides:
Monitoring.
•
Programming.
•
Control of up to 99 soft starters.
•
A Modbus or USB communication module is required for
each soft starter to use WinMaster.
Finger guards may be specied for personnel safety. Finger
guards t over the soft starter terminals to prevent
accidental contact with live terminals. Finger guards
provide IP20 protection when correctly installed.
MCD5-0131B to MCD5-0215B: 175G5662.
•
MCD5-0245B to MCD5-0396B: 175G5730.
•
MCD5-0469B to MCD5-0961B: 175G5731.
•
MCD5-245C: 175G5663.
•
MCD5-0360C to MCD5-0927C: 175G5664.
•
MCD5-1200C to MCD5-1600C: 175G5665.
•
NOTICE
To be UL-compliant, the models MCD5-0131B to
MCD5-0396B require nger guards.
As standard, VLT® Soft Starter MCD 500 rated impulse
withstand voltage is limited to 4 kV. The surge protection
kits protect the system and make the soft starter immune
to high-voltage impulses.
6 kV
175G0100 SPD Surge protection kit for G1.
•
1111
12 kV
175G0101 SPD Surge protection kit, G2-G5.
•
175G0102 SPD Surge protection kit for G1.
•
175G0103 SPD Surge protection kit, G1-G5.
•
Illustration 11.1 System with Surge Protection Kit
12 Busbar Adjustment Procedure (MCD5-0360C to MCD5-1600C)
The busbars on non-bypassed models MCD5-0360C to
MCD5-1600C can be adjusted for top or bottom input and
output as required.
NOTICE
Many electronic components are sensitive to static
electricity. Voltages so low that they cannot be felt, seen,
or heard can reduce the life, aect performance, or
completely destroy sensitive electronic components.
When performing service, use proper ESD equipment to
prevent possible damage from occurring.
All units are manufactured with input and output busbars
at the bottom of the unit as standard. If necessary, the
input and/or output busbars can be moved to the top of
the unit.
1.Remove all wiring and links from the soft starter
before dismantling the unit.
2.Remove the unit cover (4 screws).
3.Remove the LCP front cover, then gently remove
the LCP (2 screws).
4.Remove the control card terminal plugs.
5.Gently fold the main plastic away from the soft
starter (12 screws).
6.Unplug the LCP loom from CON 1 (see Notice).
7.Label each SCR ring loom with the number of
the corresponding terminal on the main control
PCB, then unplug the looms.
8.Unplug the thermistor, fan, and current
transformer wires from the main control PCB.
9.Remove the plastic tray from the soft starter (4
screws).
NOTICE
Remove the main plastic slowly to avoid damaging the
LCP wiring loom (wiring harness), which runs between
the main plastic and the backplane PCB.
Illustration 12.1 Removing Front Cover and LCP
10.Unscrew and remove the magnetic bypass plates
(models MCD5-0620C to MCD5-1600C only).
11.Remove the current transformer assembly (3
screws).
12.Identify which busbars to remove. Remove the
bolts holding these busbars in place, then slide
out the busbars through the bottom of the soft
starter (4 bolts per busbar).
13.Slide the busbars in through the top of the soft
starter. For input busbars, place the short curved
end outside the soft starter. For output busbars,
place the unthreaded hole outside the soft
starter.
14.Replace the dome washers with the at face
towards the busbar.
15.Tighten the bolts holding the busbars in place to
1212
20 Nm (177 in-lb).
16.Place the current transformer assembly over the
input busbars and screw the assembly to the
body of the soft starter (see Notice).
17.Run all wiring to the side of the soft starter and
secure with cable ties.
Illustration 12.3 Busbars with Cable Ties
NOTICE
If moving the input busbars, the current transformers
must also be recongured.
1.Label the current transformers L1, L2, and L3
(L1 is leftmost when working from the front of
the soft starter). Remove the cable ties and
unscrew the current transformers from the
bracket.
2.Move the current transformer bracket to the top
of the soft starter. Position the current
transformers for the correct phases, then screw
the current transformers to the bracket. For
models MCD5-0360C to MCD5-0930, place the
current transformers on an angle. The left-hand
legs of each current transformer are on the top
row of holes and the right-hand legs are on the
bottom tabs.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to
products already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed. All trademarks in this material are property
of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.