Danfoss MCB 112, FC 202, FC 302, FC 102 Operating guide

MAKING MODERN LIVING POSSIBLE
Operating Instructions
VLT® PTC Thermistor Card MCB 112
VLT® HVAC Drive FC 102 • VLT® AQUA Drive FC 202 VLT® AutomationDrive FC 302
vlt-drives.danfoss.com
Contents Operating Instructions
Contents
1 Introduction
1.1 Purpose of the Manual
1.2 Additional Resources
1.3 Document and Software Version
1.4 Products Covered
1.5 Functional Overview
1.5.1 Intended Use 3
1.5.2 Foreseeable Misuse 4
1.5.3 Thermal Motor Protection 4
1.5.4 ATEX ETR Thermal Monitoring 4
1.5.5 Tripping Function 4
1.5.6 Safe Separation 4
1.5.7 Safe Disconnection Principle 4
1.6 Motor Requirements
1.6.1 Motor Limits and Rules 5
1.6.2 Additional Motor Requirements 5
1.7 Approvals and Certications
3 3 3 3 3 3
5
5
1.8 Symbols, Abbreviations, and Conventions
2 Safety
2.1 Safety Symbols
2.2 Qualied Personnel
2.3 Safety Precautions
3 Installation
3.1 Safety Instructions
3.2 Installation of Sensor Circuit Wires
3.3 Installation of the VLT® PTC Thermistor Card MCB 112
4 Commissioning
4.1 Operation and Maintenance
4.1.1 Monitoring Sensor Resistance 12
4.2 Parameter Set-up
4.2.1 Alarm Handling 13
4.3 Parameter Set-up for Ex-e and Ex-n Motors
6
7 7 7 7
9 9 9
10
12 12
13
14
4.3.1 Maximum Current 14
4.3.2 Maximum Current Limit 14
4.3.3 Minimum Motor Frequency 14
4.3.4 Maximum Motor Frequency 15
4.3.5 Minimum Switching Frequency 15
MG33V302 Danfoss A/S © 01/2015 All rights reserved. 1
Contents
VLT® PTC Thermistor Card MCB 112
4.3.6 Disable Protection Mode 15
4.3.7 Safe Torque O Functionality 15
5 Application Examples
6 Maintenance and Troubleshooting
6.1 Maintenance
6.2 Troubleshooting
6.2.1 Alarm/Warning Code List 19
6.2.2 Description of Alarm Word, Warning Word, and Extended Status Word 19
7 Technical Specications
7.1 Mains Supply
7.2 Control Inputs and Outputs
7.3 Ambient Conditions
7.4 Other Specications
7.5 Safety Characteristics of the Built-in MCB 112
Index
17
19 19 19
21 21 21 21 22 22
23
2 Danfoss A/S © 01/2015 All rights reserved. MG33V302
Introduction Operating Instructions
1 Introduction
1
1
1.1 Purpose of the Manual
This manual provides information for safe installation and commissioning of VLT® PTC Thermistor Card MCB 112 used with a Danfoss VLT® frequency converter with Safe Torque
O (STO). The manual is intended for use by qualied personnel only.
VLT® PTC Thermistor Card MCB 112 is also referred to as MS 220 DA.
The operating instructions are intended for use by qualied personnel. Read and follow the operating instructions to use the frequency converter safely and professionally, and pay particular attention to the safety instructions and general warnings. Keep these operating instructions available with the frequency converter at all times.
VLT® is a registered trademark.
1.2 Additional Resources
This manual is targeted at users already familiar with the VLT® frequency converters. It is intended as a supplement
to the manuals and instructions available for download at vlt-drives.danfoss.com/Support/Technical-Documentation/. Read the instructions shipped with the frequency converter and/or frequency converter option before installing the unit, and observe the instructions for safe installation.
1.3
Document and Software Version
1.4
Products Covered
The VLT® PTC Thermistor Card MCB 112 is available for the following types of frequency converters:
VLT® HVAC Drive FC 102.
VLT® AQUA Drive FC 202.
VLT® AutomationDrive FC 302.
1.5 Functional Overview
1.5.1 Intended Use
The VLT® PTC Thermistor Card MCB 112 is intended to:
Protect electrical motors against inadmissible
heating due to overload. Protect explosion-protected motors in explosive
atmospheres caused by gases, vapours, or mists, Zone 1 and Zone 2, and/or in explosive atmospheres caused by dust, Zone 21 and Zone
22. Refer to marking G for Zone 1 and Zone 2. Refer to marking D for Zone 21 and Zone 22.
All functions in the MCB 112 serve to protect both non­explosive-protected motors and explosive-protected motors in regular operation and in case of failure.
The VLT® PTC Thermistor Card MCB 112 is designed in accordance with EN 60947-8 (VDE 0660 part 0302). Only connect PTC thermistor sensors according to DIN 44081 and 44082 (EN 60947-8).
This manual is regularly reviewed and updated. All suggestions for improvement are welcome. Please send suggestions via email to techcom_change_request@danfoss.com, including a reference to the document version. Table 1.1 shows the document version and the changes applied.
Edition Remarks
MG33V3xx Replaces MG33V2xx.
Editorial changes.
Now covering the complete system.
Table 1.1 Document Version
MG33V302 Danfoss A/S © 01/2015 All rights reserved. 3
NOTICE
The VLT® PTC Thermistor Card MCB 112 is only functional if it is built into the frequency converter. The option cannot be used as a stand-alone.
MS 220 DA / MCB112
Code no.: 130B1137
Motor protection inside
See manual
for additional instruction
PTB 14 ATEX 3012U
CAUTION:
II (2) D [Ex tb][Ex tc]
II (2) G [Ex e] [Ex d] [Ex n]
ε
130BE103.10
Introduction
VLT® PTC Thermistor Card MCB 112
1
1.5.1.1 Markings of the Frequency Converter
A sticker is delivered with the option as spare part or with the frequency converter to signify ATEX certication. Apply this sticker to the front of the frequency converter in which the ATEX module is integrated. The sticker indicates that the ATEX module is installed in the frequency converter.
Illustration 1.1 Label to Apply to Frequency Converter
Foreseeable Misuse
1.5.2
Any use not expressly approved by Danfoss constitutes misuse. This also applies to failure to comply with the specied operating conditions and applications.
according to DIN 44081 or 44082, the MCB 112 oers ATEX-approved monitoring of the motor temperature. Alternatively, an external ATEX-approved PTC protection device can be used.
1.5.4 ATEX ETR Thermal Monitoring
NOTICE
The ATEX ETR thermal monitoring function only applies to Ex-e and Ex-n motors and is only available for VLT AutomationDrive FC 302 frequency converters.
The FC 302 with equipped with an ATEX ETR thermal monitoring function for operation of Ex-e motors according to EN 60079-7 and Ex-n motors according to EN 60079-15. Combined with an ATEX-approved PTC monitoring device like MCB 112, the installation does not need an individual approval from an approbated organisation, that there is no need for matched pairs.
The feature makes it easier to apply Ex-e and Ex-n motors instead of the more expensive, larger, and heavier Ex-d motors. The use of Ex-e and Ex-n motors is possible by ensuring that the frequency converter limits the motor current to prevent the motor from heating up.
Tripping Function
1.5.5
rmware version V6.3x or higher is
®
Danfoss assumes no liability of any sort for damage attrib­utable to improper use.
Only operate with explosion-protected 3-phase motors which are built, tested and labelled separately for frequency converter use.
WARNING
EXPLOSION DANGER
Zone 0 and Zone 20 are not applicable to electric motors. To avoid explosion, only use motors in:
Zone 1/21.
Zone 2/22.
1.5.3 Thermal Motor Protection
According to ATEX Directive 94/9/EC and Standard EN 60079-14, motor overload protection is a requirement. The MCB 112 monitors the temperature in the motor windings with an ATEX-approved motor overload protection device. If there is a critical temperature level or a malfunction, switch o the motor. If the frequency converter is equipped with 3–6 PTC thermistors in series
The MCB 112 includes a tripping stage for PTC thermistor sensors with safe potential separation of supply voltage from ground. The tripping function switches o the +24 V DC directly at terminal 37 on the frequency converter.
The PNP logic output terminal X44/10 signals the status in case of failure. The MCB 112 works according to the closed-circuit principle. The device trips in case of short circuit or line interruption.
Safe Separation
1.5.6
The PTC thermistor circuit (T1, T2) has a safe separation of low-voltage electric circuits PELV, see chapter 3.2 Instal- lation of Sensor Circuit Wires.
1.5.7
Safe Disconnection Principle
The Safe Torque O function disables the control voltage of the power semiconductors or the frequency converter output stage. Disabling the control voltage prevents the inverter from generating the voltage required to rotate the motor.
4 Danfoss A/S © 01/2015 All rights reserved. MG33V302
Frequency Converter
Logic Out
Control Card
Potentially explosive
atmosphere
PTC-Sensors
3~ Ex-Motor
Safe Channel T37
Safe Stop T37
T1
TP TP
T2
+24 V
PTC Thermistor Card MCB 112
Non-explosive hazard zone
91 92 93
96 97 98
Converter module
130BE102.10
DI
Introduction
Illustration 1.2 Block Diagram of the System
Operating Instructions
1.6 Motor Requirements
1.6.1 Motor Limits and Rules
For every certied motor with increased safety, the manufacturer supplies a data list including limits and rules. During planning, installation, commissioning, operation, and service, respect the limits for:
Minimum switching frequency.
Maximum current.
Minimum motor frequency.
Maximum motor frequency.
Furthermore, respect the following:
1.6.2
Additional Motor Requirements
The Ex-e motor must be approved for operation in hazardous zones (ATEX Zone 1/21, ATEX Zone 2/22) in combination with frequency converters. The motor must be certied for the particular hazardous zone.
The Ex-n motor must be approved for operation in hazardous zones (ATEX Zone 2/22) in combination with frequency conveters. The motor must be certied for the particular harzardous zone.
NOTICE
The motor can be placed in Zone 1/21 or 2/22 according to motor approval. The frequency converter must always be installed outside of the hazardous zone.
Only operate explosion-protected 3-phase motors
with frequency converters, if the motors are built, tested, approved, and labelled separately for this mode.
When the usage of the motor and its thermal
protective device are approved for frequency converter operation, use the MCB 112 for each ignition protection system for all motor types. For motors of Ex-e and Ex-n-type ignition protection, which are OEM-approved for frequency converter operation in Ex-harzardous areas, consider and use the requested limitations in the frequency converter’s ATEX ETR thermal monitoring settings.
The necessary parameters and conditions can be
found on the nameplate or the documentation of the motor. To prevent prohibited temperatures, the motors are equipped as standard with thermal winding protection, which has to be evaluated by a suitable device like MCB 112. The motors must not be operated as a group drive.
1.7
Approvals and Certications
1
1
MG33V302 Danfoss A/S © 01/2015 All rights reserved. 5
Do not exceed the maximum allowable ratio
between frequency converter size and motor size. The typical value is I
Consider all voltage drops from the frequency
converter to the motor. If the motor is running with lower voltage than listed in the U/f charac­teristics, current might increase and cause an alarm.
Multi-motor applications are not allowed. Only
connect 1 motor to the frequency converter.
2xI
VLT, n
m,n
.
Certication number: PTB 14 ATEX 3012U
Certicates and declarations of conformity are available. Contact a local Danfoss partner.
Introduction
VLT® PTC Thermistor Card MCB 112
1
1.8 Symbols, Abbreviations, and
Conventions
Abbreviation Description
ETR Electronic thermal relay. LCP Local control panel. NC Not connected. PNP Positive negative positive (transistor). TNF Nominal response temperature.
Table 1.2 Abbreviations
AbbreviationReference Description
ATEX ATEX Directive
94/9/EC
HFT EN IEC 61508 Hardware fault tolerance: HFT=n
PDS/SR EN IEC
61800-5-2
PFD EN IEC 61508 Average probability of failure on
SFF EN IEC 61508 Safe failure fraction [%]; percentage
SIL EN IEC 61508
EN IEC 62061
STO EN IEC
61800-5-2
SRECS EN IEC 62061 Safety-related electrical control
ATmosphere EXplosibles
means that n+1 faults could cause a loss of the safety function. Power drive system (safety-related).
demand, value used for low­demand operation.
of safe failures and dangerous detected failures of a safety function or a subsystem related to all failures. Safety integrity level.
Safe Torque O.
system.
Table 1.3 Abbreviations Related to Functional Safety
Conventions
Numbered lists indicate procedures. Bullet lists indicate other information and description of illustrations. Italicised text indicates:
Cross-reference.
Link.
Parameter name.
6 Danfoss A/S © 01/2015 All rights reserved. MG33V302
Safety Operating Instructions
2 Safety
2.1 Safety Symbols
The following symbols are used in this manual:
WARNING
Indicates a potentially hazardous situation that could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could result in minor or moderate injury. It can also be used to alert against unsafe practices.
NOTICE
Indicates important information, including situations that can result in damage to equipment or property.
2.2 Qualied Personnel
The products must only be assembled, installed, programmed, commissioned, maintained, and decommis­sioned by persons with proven skills. Persons with proven skills:
Are qualied electrical engineers, or persons who
have received training from qualied electrical engineers and are suitably experienced to operate devices, systems, plant, and machinery in accordance with the general standards and guidelines for safety technology.
Are familiar with the basic regulations concerning
health and safety/accident prevention. Have read and understood the safety guidelines
given in this manual and also the instructions given in the operating instructions of the frequency converter.
Have a good knowledge of the generic and
specialist standards applicable to the specic application.
Users of PDS(SR) are responsible for:
Hazard and risk analysis of the application. In EN
ISO 12100, risk assessment is dened as an overall process comprising a risk analysis and a risk evaluation.
Ensuring that the qualied personnel has
experience with working in ATEX areas according to Directive 99/92/EC (also known as the ATEX Workplace Directive).
Identifying safety functions required, and
allocating SIL to each of the functions. Other subsystems and the validity of signals and
commands from those subsystems. Designing appropriate safety-related control
systems (hardware, software, parameterisation, and so on).
Protective measures
Safety engineering systems must only be installed
and commissioned by qualied and skilled personnel.
Install the frequency converter in an IP54 cabinet
as per IEC 60529, or in an equivalent environment. In special applications, a higher IP degree may be necessary.
Ensure short-circuit protection of the cable
between terminal 37 and the external safety device according to ISO 13849-2 table D.4.
When external forces inuence the motor axis (for
example suspended loads), additional measures (for example a safety holding brake) are required to eliminate hazards.
2.3
Safety Precautions
WARNING
EXPLOSION HAZARD
Using the VLT® PTC Thermistor Card MCB 112 in areas with explosive gas and/or dust atmosphere may lead to death, personal injury, or property damage. To avoid the risk, adhere to the following:
Always provide the MCB 112 with a pressurised
enclosure according to EN 60079-1 (Explosive atmospheres - Part 1: Equipment protection by ameproof enclosures “d”).
Observe national safety rules and regulations
for prevention of accidents, as well as the European Standard EN 60079-14 (Explosive atmospheres - Part 14: Electrical installations design, selection, and erection).
Only
qualied personnel (see chapter 2.2 Qualied Personnel) is allowed to install, connect, and commission the MCB 112.
Ensure that the motor thermal protection switches o the motor directly, via the STO function, or by using the ATEX ETR thermal monitoring function.
2 2
MG33V302 Danfoss A/S © 01/2015 All rights reserved. 7
Loading...
+ 19 hidden pages