Danfoss MCB 106 Installation guide

Installation Instructions
VLT® 24 V DC Supply MCB 106
®
VLT
Midi Drive FC 280
The instructions provide information about installing the VLT
24 V DC Supply MCB 106 on VLT® Midi Drive FC 280.
®
VLT
24 V DC Supply MCB 106 is a low voltage supply to the control card. The intended use case is to keep the eldbus communication of the control card active at all time during a mains power loss or power cycle. It does not enable full operation of the LCP (including the parameter settings)
®
without connection to mains. The specications of VLT DC Supply MCB 106 are described in Tab l e 1.1.
Input voltage
Reversed voltage input protection Yes
Output voltage 19.9
Output power Minimum 10 W
Input capacitance load
Power up delay <0.6 s
Tab le 1 . 1 V LT® 24 V DC Supply MCB 106 Specications
24 V DC
(Maximum 37 V in 10 s)
<110 uF
+15%
+0.6 V
24 V
®
1
2Cable
3Plug
Illustration 1.1 VLT® 24 V DC Supply MCB 106 Overview
®
24 V DC Supply MCB 106
VLT
NOTICE
VLT® 24 V DC Supply MCB 106 only supports CANopen®, PROFIBUS, PROFINET, and EtherNet/IP variant of VLT
Drive FC 280.
®
CANopen AUTOMATION international users and manufacturers group e. V. EtherNet/IP is a trademark of ODVA, Inc.
Only Danfoss authorized, qualied personnel is allowed to use this equipment. The personnel must be familiar with the instructions and safety measures described in the
®
VLT
is a registered trademark for CAN IN
Midi Drive FC 280 Operating Guide.
®
Midi
Danfoss A/S © 02/2019 All rights reserved. MI07G202
Installation Instructions
®
VLT
24 V DC Supply MCB 106
®
Midi Drive FC 280
VLT
Items Supplied
VLT® 24 V DC Supply MCB 106.
Plug (2 poles).
M3x6 screws (2).
Description Ordering number
®
24 V DC Supply MCB 106
VLT
Table 1.2 Ordering Numbers
132B0368
Tools Required
Torx 10 or slot screwdriver
Safety Instructions
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors which can remain charged even when the frequency converter is not powered. High voltage can be present even when the warning LED indicator lights are o. Failure to wait the specied time after power has been removed before performing service or repair work can result in death or serious injury.
Stop the motor.
Disconnect AC mains and remote DC-link supplies,
including battery back-ups, UPS, and DC-link connections to other frequency converters.
Disconnect or lock PM motor.
Wait for the capacitors to discharge fully. The
minimum waiting time is specied in Ta b l e 1. 3 .
Before performing any service or repair work, use
an appropriate voltage measuring device to make sure that the capacitors are fully discharged.
Voltage [V]
200–240 0.37–3.7 (0.5–5) 4
380–480
Power range
[kW (hp)]
0.37–7.5 (0.5–10) 4
11–22 (15–30) 15
Minimum waiting time
(minutes)
Installation
1. Stop the motor and the frequency converter, and wait until the capacitors discharge completely. The discharge time is specied in Ta b l e 1. 3 .
2.
Mount the VLT
bus decoupling kit (supplied with VLT
280).
3.
Fasten with 2 M3x6 screws (supplied with VLT Drive FC 280).
4. Tighten the screws to 0.5–0.7 Nm (4.4–6.2 in-lb).
1
M3x6 screws supplied with VLT
2 Bus decoupling kit
3
Illustration 1.2 Mounting MCB 106 with Bus Decoupling Kit
®
24 V DC Supply MCB 106
VLT
5.
Mount the VLT bus decoupling kit assembly on the frequency converter.
6.
Fasten with 2 M3x6 screws (supplied with VLT DC Supply MCB 106).
7. Tighten the screws to 0.5–0.7 Nm (4.4–6.2 in-lb).
®
24 V DC Supply MCB 106 with the
®
Midi Drive FC
®
Midi Drive FC 280
®
24 V DC Supply MCB 106 and the
®
Midi
®
24 V
Table 1.3 Discharge Time
2
Danfoss A/S © 02/2019 All rights reserved. MI07G202