Danfoss MCB 106 Installation guide

0 (0)

Installation Instructions

VLT® 24 V DC Supply MCB 106

VLT® Midi Drive FC 280

The instructions provide information about installing the VLT® 24 V DC Supply MCB 106 on VLT® Midi Drive FC 280.

VLT® 24 V DC Supply MCB 106 is a low voltage supply to the control card. The intended use case is to keep the fieldbus communication of the control card active at all time during a mains power loss or power cycle. It does not enable full operation of the LCP (including the parameter settings) without connection to mains. The specifications of VLT® 24 V DC Supply MCB 106 are described in Table 1.1.

Input voltage

24 V DC +15%

(Maximum 37 V in 10 s)

 

 

 

Reversed voltage input protection

Yes

 

 

Output voltage

19.9 +0.6 V

 

 

Output power

Minimum 10 W

 

 

Input capacitance load

<110 uF

 

 

Power up delay

<0.6 s

 

 

Table 1.1 VLT® 24 V DC Supply MCB 106 Specifications

1

VLT® 24 V DC Supply MCB 106

2

Cable

 

 

3

Plug

 

 

Illustration 1.1 VLT® 24 V DC Supply MCB 106 Overview

NOTICE

VLT® 24 V DC Supply MCB 106 only supports CANopen®, PROFIBUS, PROFINET, and EtherNet/IPvariant of VLT® Midi

Drive FC 280.

CANopen® is a registered trademark for CAN IN

AUTOMATION international users and manufacturers group e. V.

EtherNet/IPis a trademark of ODVA, Inc.

Only Danfoss authorized, qualified personnel is allowed to use this equipment. The personnel must be familiar with the instructions and safety measures described in the

VLT® Midi Drive FC 280 Operating Guide.

Danfoss A/S © 02/2019 All rights reserved.

MI07G202

Danfoss MCB 106 Installation guide

Installation Instructions

VLT® 24 V DC Supply MCB 106

VLT® Midi Drive FC 280

 

Items Supplied

VLT® 24 V DC Supply MCB 106.

Plug (2 poles).

M3x6 screws (2).

Description

Ordering number

 

 

VLT® 24 V DC Supply MCB 106

132B0368

Table 1.2 Ordering Numbers

 

Tools Required

Torx 10 or slot screwdriver

Safety Instructions

WARNING

DISCHARGE TIME

The frequency converter contains DC-link capacitors which can remain charged even when the frequency converter is not powered. High voltage can be present even when the warning LED indicator lights are off. Failure to wait the specified time after power has been removed before performing service or repair work can result in death or serious injury.

Stop the motor.

Disconnect AC mains and remote DC-link supplies, including battery back-ups, UPS, and DC-link connections to other frequency converters.

Disconnect or lock PM motor.

Wait for the capacitors to discharge fully. The minimum waiting time is specified in Table 1.3.

Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.

Voltage [V]

Power range

Minimum waiting time

[kW (hp)]

(minutes)

 

 

 

 

200–240

0.37–3.7 (0.5–5)

4

 

 

 

380–480

0.37–7.5 (0.5–10)

4

 

 

11–22 (15–30)

15

 

 

 

 

Table 1.3 Discharge Time

Installation

1.Stop the motor and the frequency converter, and wait until the capacitors discharge completely. The discharge time is specified in Table 1.3.

2.Mount the VLT® 24 V DC Supply MCB 106 with the bus decoupling kit (supplied with VLT® Midi Drive FC

280).

3.Fasten with 2 M3x6 screws (supplied with VLT® Midi Drive FC 280).

4.Tighten the screws to 0.5–0.7 Nm (4.4–6.2 in-lb).

1

M3x6 screws supplied with VLT® Midi Drive FC 280

2

Bus decoupling kit

 

 

3

VLT® 24 V DC Supply MCB 106

Illustration 1.2 Mounting MCB 106 with Bus Decoupling Kit

5.Mount the VLT® 24 V DC Supply MCB 106 and the bus decoupling kit assembly on the frequency converter.

6.Fasten with 2 M3x6 screws (supplied with VLT® 24 V DC Supply MCB 106).

7.Tighten the screws to 0.5–0.7 Nm (4.4–6.2 in-lb).