These Operating Instructions provide information for
installing and configuring the DeviceNet Converter option
MCA 194. The Operating Instructions also contain the
parameter mapping lists and troubleshooting information.
First-time users can find the most essential information for
quick installation and set-up in:
Chapter 1.3 Product Overview
•
Chapter 1.4 Constraints
•
Chapter 3 Installation
•
For more detailed information including the full range of
set-up options and diagnosis tools, refer to:
Chapter 4 Commissioning
•
Chapter 5 Parameter Mapping Lists
•
VLT® is a registered trademark.
1.2 Additional Resources
The following literature is available for the FC 300 series:
VLT® AutomationDrive Operating Instructions
•
VLT® AutomationDrive Design Guide
•
VLT® AutomationDrive Programming Guide
•
Supplementary publications and manuals are available for
download. See www.danfoss.com/BusinessAreas/DrivesSo-
The MCA 194 DeviceNet Converter is a DeviceNet option
when installed in VLT® AutomationDrive FC 302. It
emulates the DeviceNet commands of a VLT® 5000 in a
DeviceNet network.
NOTICE
Some parameters in the VLT® 5000 are not supported in
the FC 302 and some FC 302 parameters cannot be
accessed via the DeviceNet converter option MCA 194.
Refer to chapter 5 Parameter Mapping Lists for more
information. If a write request is attempted to a
parameter selection not supported, the frequency
converter discards the value and issues a positive reply.
Only parameters and functions described in this manual
are supported.
NOTICE
The replacement frequency converter must match the
power size of the motor for optimal performance. In
some cases a bigger frequency converter may be needed
to replace the VLT® 5000. Make sure that the brake
resistor matches the new frequency converter.
Make sure that the new frequency converter meets the
local regulations concerning the machinery directive,
prefuses, and other appropriate regulations.
NOTICE
Observe local rules and regulations when replacing
frequency converter in existing installations.
1.4 Constraints
1.4.1 Software Versions
VLT® AutomationDrive FC 302 with firmware
•
version 6.54 or higher.
The MCA 194 DeviceNet Converter firmware is
•
based on a VLT® 5000 software version 3.9x and
DeviceNet software version 2.x.
Relations
1.4.2
This manual relates to the following hardware:
VLT® DeviceNet Converter option MCA 194, type
With this DeviceNet converter option the FC 302 reacts as
a VLT® 5000 on the DeviceNet network. Changes to PLC
programming or re-configuration are normally not
necessary.
The FC 302 identifies itself as a VLT® 5000 on the
DeviceNet network. For example, a write command to
ramp-up time in VLT® 5000 is automatically linked to the
corresponding ramp-up time parameter in VLT
the closed loop operation compared with VLT
5000 can be different in certain applications. If
necessary, adjust the PID controller manually.
The motor control algorithm of the VLT
•
AutomationDrive results in a better motor
performance compared to VLT® 5000.
®
®
NOTICE
Factory values:
After initialisation, most parameters are set to match the
factory settings of the VLT® 5000 parameters. For more
information about the initialisation, see the VLTAutomationDrive FC 301/FC 302 Programming Guide.
®
NOTICE
Linked Set-ups:
To synchronise set-up changes made with running
motor, ensure that FC 302 set-ups are linked. This is
done in 0-12 This Set-up Linked to.
1
1
1.5 Abbreviations
AOCApplication Oriented Control
CTWControl Word
EMCElectromagnetic Compatibility
I/OInput/Output
LEDLight Emitting Diode
LSBLeast Significant Bit
MAVMain Actual Value (actual output)
MOCMotor Oriented Control
MSBMost Significant Bit
MRVMain Reference Value (Setpoint)
N/ANot Applicable
PCDPeripherals Communication Data (process data)
PCVParameter Characteristics Value (Parameter
channel)
PLCProgrammable Logic Controller
PNUParameter Number
PUPower Unit
REFReference (= MRV)
STWStatus Word
Indicates a potentially hazardous situation which could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which could
result in minor or moderate injury. It may also be used
to alert against unsafe practices.
NOTICE
Indicates important information, including situations that
may result in damage to equipment or property.
2.2 Qualified Personnel
Correct and reliable transport, storage, installation,
operation and maintenance are required for the troublefree and safe operation of the frequency converter. Only
qualified personnel is allowed to install or operate this
equipment.
Qualified personnel is defined as trained staff, who are
authorised to install, commission, and maintain equipment,
systems and circuits in accordance with pertinent laws and
regulations. Additionally, the personnel must be familiar
with the instructions and safety measures described in this
document.
2.3
Safety Precautions
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when
connected to AC mains input power. Failure to perform
installation, start-up, and maintenance by qualified
personnel could result in death or serious injury.
Installation, start-up, and maintenance must be
•
performed by qualified personnel only.
Safety regulations
1.The frequency converter must be disconnected
from mains, if repair work is to be carried out.
Check that the mains supply has been disconnected and that the necessary time has passed
NOTICE
The function is initialised at 1.16 x rated motor current
and rated motor frequency. For the North American
market, the ETR functions provide class 20 motor
overload protection in accordance with NEC.
Warning against unintended start
before removing motor and mains plugs, see
Table 2.1.
2.The [Off] key does not disconnect the equipment
from mains and is thus not to be used as a safety
switch.
3.Establish correct protective earthing of the
equipment, protect the user against supply
voltage, and protect the motor against overload
in accordance with applicable national and local
regulations.
4.The earth leakage currents are higher than 3.5
mA.
5.Protection against motor overload is not included
in the factory setting. If this function is desired,
set 1-90 Motor Thermal Protection[4] ETR trip or
[3] ETR warning.
6.Do not remove the plugs for the motor and
mains supply while the frequency converter is
connected to mains. Check that the mains supply
has been disconnected and that the necessary
time has passed before removing motor and
mains plugs, see Table 2.1.
7.The frequency converter has more voltage inputs
than L1, L2 and L3, when load sharing (linking of
DC intermediate circuit) and external 24 V DC
have been installed. Check that all voltage inputs
have been disconnected and that the necessary
time has passed before commencing repair work,
see Table 2.1.
1.The motor can be brought to a stop with digital
commands, bus commands, references or a local
stop, while the frequency converter is connected
to mains. These stop functions are not sufficient
to prevent unintended starts.
2.While parameters are being changed, the motor
may start. Consequently, always press [Off].
3.A motor that has been stopped may start if faults
occur in the electronics of the frequency
converter, or if a temporary overload or a fault in
the supply mains or the motor connection ceases.
Touching the electrical parts may be fatal - even after
the equipment has been disconnected from mains.
22
Voltage [V]
200-2400.25-3.7 kW5.5-37 kW
380-4800.25-7.5 kW11-75 kW
525-6000.75-7.5 kW11-75 kW
525-69011-75 kW
High voltage may be present even when the warning LED
indicator lights are off.
Table 2.1 Discharge Time
Also make sure that other voltage inputs have been
disconnected, such as external 24 V DC, load sharing
(linkage of DC intermediate circuit), as well as the motor
connection for kinetic back-up.
Terminate the bus line at both ends of each segment. A
mismatch of impedance may result in reflections on the
line resulting in corrupt data transmission.
The DeviceNet Option Card contains a suitable termination.
To activate the termination, turn on Switch 1 on the
DeviceNet converter option. By default, the switch is
turned off.
NOTICE
Notice that pin numbers are colour-coded on the
DeviceNet connector.
Unlike the VLT
are colour-coded to avoid swapping the bus wires.
®
5000, the FC 302 DeviceNet connectors
Pin no.TerminalColourName
1V-BlackGND
2CAN_LBlueCAN LOW
3Drain(bare)Screen
4CAN_HWhiteCAN HIGH
5V+Red+24 V
Table 3.1 Correct Colour-Coding
3.2 Mechanical Installation
3.2.1 Mount the Option
Illustration 3.2 Installing Fieldbus Option
Illustration 3.1 Connecting Wires to VLT DeviceNet Converter
MCA 194
3.Push the option into place. 2 positions are
possible, with cable terminal facing either up or
down. The cable up position is often most
suitable when several frequency converters are
installed side-by-side in a rack, as this position
permits shorter cable lengths.
4.Push the fieldbus option adaptor frame for the FC
302 into place.
5.Remount the LCP.
6.Attach the cable.
7.Fasten the cable using cable holders.
33
Adapter Plate
3.2.2
To ease the replacement of VLT 5000 with VLT® AutomationDrive, there is a number of adapter plates available. The adapter
plates have the same footprints as VLT 5000 and have threaded holes for VLT® AutomationDrive. The adapter plate prevents
damage that can occur from drilling new threaded holes in the backboard of the enclosure. The adapter plate also
decreases the time required to exchange a broken frequency converter.
The following mechanical adapter plates are available:
Ordering
number
130B0183Bookstyle, IP2039590
130B0184Bookstyle, IP20395130
130B0185Compact, IP20395220
Table 3.2 Ordering Numbers for Adapter Plates
StyleHeight [mm]Width [mm]Type
5001-5003 200-240 V
5001-5005 380-500 V
5004-5006 200-240 V
5006-5011 380-500 V
5001-5003 200-240 V
5001-5005 380-500 V
5004-5006 200-240 V
5006-5011 380-500 V
5001-5011 550-600 V
Setting the address via parameter 10-02 MAC ID or the
DeviceNet Class code 0X03, Instance 1, Attribute 1, is
possible, if the hardware switches are all set in the "On"
position. The new address becomes active at the next
power-up.
To achieve the best performance, initialise the frequency converter after the option is mounted. If the frequency converter is
delivered from factory with the option installed, skip this step. The initialisation is done via 14-22 Operation Mode or a 3finger reset. The parameters of the FC 302 are set to factory values, and a number of FC 302 parameters are set to values
that match the VLT® 5000 initial values.
Factory copy via VLT® 5000 parameter 006 is supported and initialises the FC 302 and also set it to the VLT® 5000 default
settings.
Table 4.5 lists the parameter settings created during initialisation.
ParameterInitialisation setting
0-02 Motor Speed Unit[Hz]
1-52 Min Speed Normal Magnetising [Hz]1.0 Hz
3-16 Reference 2 Source[0] No function
4-12 Motor Speed Low Limit [Hz]132.0 Hz
3-00 Reference Rangemin – max
3-01 Reference/Feedback Unit[1] %
3-11 Jog Speed [Hz]10.0 Hz
4-30 Motor Feedback Loss Function[0] Disabled
4-56 Warning Feedback Low-4000000
4-57 Warning Feedback High4000000
6-10 Terminal 53 Low Voltage0.00 Volt
6-20 Terminal 54 Low Voltage0.00 Volt
6-22 Terminal 54 Low Current0.00 Volt
5-51 Term. 29 High Frequency5000 Hz
5-56 Term. 33 High Frequency25000 Hz
4-32 Motor Feedback Loss Timeout1.00 s
14-21 Automatic Restart Time5 s
14-03 Overmodulation[0] Off
20-93 PID Proportional Gain0.01
8-54 Reversing Select[0] Digital input
8-90 Bus Jog 1 Speed300 RPM
8-91 Bus Jog 2 Speed300 RPM
7-04 Speed PID Differentiation TimeOFF
2-10 Brake Function[0] Off
2-17 Over-voltage Control[0] Off
5-40 Function Relay[22] Ready, no thermal Warning
5-41 On Delay, Relay[23] Remote, ready, no TW
7-09 Speed PID Error Correction w/ Ramp100000 (max)
14-11 Mains Voltage at Mains Faultcalculated value: VLT5000 level = FC 302 level
* 1,35 / sqrt(2)
MCB 101 option specific parameters
5-16 Terminal X30/2 Digital Input[1] Reset
5-17 Terminal X30/3 Digital Input[19] Freeze reference
PROFIBUS specific parameters
9-71 Profibus Save Data Values[1] Store all setups
torque with
medium starting
torque
[8] High variable
torque with high
starting torque
[11] Normal
constant torque
[12] Normal
variable torque low
[13] Normal
variable torque
medium
[14] Normal
variable torque
high
[15] Normal special
motor characteristic
[16] Normal
variable torque
with low constant
starting torque
[17] Normal
variable torque
with medium
constant starting
torque
[18] Normal
variable torque
with high constant
starting torque
Parameter 121 Start function1-72 Start Function
Options[0] DC hold in start delay
Table 5.40 Conversion of Parameter 121
Parameter122 Function at stop1-80 Function at Stop
Options[0] Coasting[0] Coast
VLT 5000 seriesFC 302 series
[0] DC hold/delay time
time
[1] DC brake in start delay
time
[2] Coasting in start delay
time
[3] Start frequency/voltage
clockwise
[4] Start frequency/voltage in
reference direction
[5] VVC+ clockwise[5] VVC+/Flux
VLT 5000 seriesFC 302 series
[1] DC hold[1] DC hold
[2] Motor check[2] Motor check
[3] Pre-magnetizing[3] Pre-magnetizing
[1] DC Brake/delay
time
[2] Coast/delay time
[3] Start speed cw
[4] Horizontal
operation
clockwise
Table 5.36 Conversion of Parameter 117
Parameter 118 Resonance
Range5 – 50 ms5 – 50 ms
Table 5.37 Conversion of Parameter 118
Parameter119 High starting torqueNot converted
Table 5.38 Conversion of Parameters 119
Parameter120 Start delay
Option0.0 – 10.0 s0.0 – 10.0 s
Table 5.39 Conversion of Parameter 120
VLT 5000 seriesFC 302 series
1-65 Resonance
dampening time
constant
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
Dampening Time Constant
1-71 Start Delay
Table 5.41 Conversion of Parameter 122
Parameter 123 Min frequency for
Range0.0 – 10.0 Hz0.0 – 20.0 Hz
Table 5.42 Conversion of Parameter 123
Parameter 124 DC holding
Range0 - 100%0 - 160% (motor depending)
Table 5.43 Conversion of Parameter 124
Parameter 125 DC braking current2-01 DC Brake Current
Range0 - 100%0 – 160% P.U depending
Table 5.44 Conversion of Parameter 125
Parameter126 DC braking time2-02 DC Braking Time
Range0.0 – 60.0 s0.0 – 60.0 s
6-15 Terminal 53 High Ref./Feedb.
Value
6-25 Terminal 54 High Ref./Feedb.
Value
5-53 Term. 29 High Ref./Feedb.
Value
5-58 Term. 33 High Ref./Feedb.
Value
–
Par. 3-02 Ref
min
– 100,000.000
min
55
Table 5.57 Conversion of Parameter 205
Parameter 206 Ramp Type3-40 Ramp 1 Type
Options[0] LinearPar. 3-40 = [0] Linear
Table 5.58 Conversion of Parameter 206
VLT 5000 seriesFC 302 series
3-50 Ramp 2 Type
3-82 Quick Stop Ramp Type
Par. 3-50 = [0] Linear
Par. 3-82 = [0] Linear
[1] Sine shape (S1) Par. 3-40 = [2] S-ramp Const Time
Parameter 307 Terminal 33, input5-15 Terminal 33 Digital
Options[0] No function[0] No operation
55
Table 5.94 Conversion of Parameter 307
VLT 5000 seriesFC 302 series
Input
7-00 Speed PID Feedback
Source
[1] Reset[1] Reset
[2] Stop inverse[6] Stop inverse
[3] Only start
anticlockwise, on
[4] Jog[14] Jog
[5] Preset reference, on[15] Preset reference, on
[6] Preset reference, msb [17] Preset reference bit 1
[7] Freeze reference[19] Freeze reference
[8] Freeze output[20] Freeze output
[9] Speed down[22] Speed down
[10] Choice of Setup,
msb
[11] Choice of Setup,
msb / Speed down
[12] Slow down[29] Slow down
[13] Ramp 2[34] Ramp bit 0
[14] Mains failure
inverted
[24] Pulse feedback[32] Pulse input,
[25] Encoder input 2B[0] No operation
[29] Data change lockNot supported
[13] Enable start reverse
[24] Setup select bit 1
Not supported
Not supported
Parameter 700 = [9]
Frequency input 33
Parameter 700 = [1] 24 V
encoder
Parameter 308 Terminal
Options[0] No
Table 5.95 Conversion of Parameter 308
Parameter 309 Terminal 53, min.
Range0 – 10.0 Volt-10.00 – Par. 6-11
Table 5.96 Conversion of Parameter 309
Parameter 310 Terminal 53, max.
Range0 – 10.0 VoltPar. 6-10 - 10.00 Volt
VLT 5000
series
53, Analogue
Input Voltage
Operation
[1] ReferencePar. 3-15 Reference resource 1 set to
[2] Feedback
signal
[3] Torque
limit
[4] Thermistor Par. 3-15 Reference resource 1 set to
VLT 5000 seriesFC 302 series
scaling
VLT 5000 seriesFC 302 series
scaling
FC 302 series
3-15 Reference 1 Source
7-00 Speed PID Feedback Source
1-93 Thermistor Source
4-20 Torque Limit Factor Source
Par. 3-15 Reference resource 1 set to
[0] No function
[1] Analog input 53
Par. 3-15 Reference resource 1 set to
[1] Analog input 53
Par. 7-00 Speed PID Feedback Source
set to [6] Analog input 53
Par. 3-15 Reference resource 1 set to
[1] Analog input 53
Par. 4-20 Torque Limit Factor Source
set to [2] Analog in 53
[0] No function
Par. 1-93 Thermistor Ressource set to
[1] Analog input 53
frequency
[2] Stop[2] Stop
[3] Jogging[3] Jog
[4] Max Speed, p202[4] Max Speed
[5] Stop and trip[5] Stop and trip
VLT 5000 seriesFC 302 series
Parameter 319 Terminal 42,
Output
Parameter 321 Terminal 45,
Output
Digital = Par. 5-32 DO X30/7
(MCB 101)
Analogue values= Par. 6-50 AO
42
Pulse = Par. 5-66 DO X30/6
Digital = Par. 5-33 DO X30/7
(MCB 101)
Analogue values= Par. 6-60 AO
X30/8
Pulse = Par. 5-66 DO X30/6
Table 5.105 Conversion of Parameter 318
55
Parameter 319 Terminal 42,
VLT 5000 seriesFC 302 series
Digital = Par. 5-32 DO X30/7
Output
(MCB 101)
Options[15] Out of
frequency range
[16] Over f lowPar. 5-32 = [16] Below speed
[17] Under f highPar. 5-32 = [17] Above speed
Analogue values = Par. 6-50 AO
42
Pulse = Par. 5-66 DO X30/6
Parameter 321 Terminal 45,
Output
Digital = Par. 5-33 DO X30/7
(MCB 101)
Analogue values= Par. 6-60 AO
X30/8
Pulse = Par. 5-66 DO X30/6
Options[0] No functionPar. 5-32 = [0] No operation
[1] Control ReadyPar. 5-32 = [1] Control Ready
[2] Ready signalPar. 5-32 = [2] Drive ready
[3] Ready - Remote
Par. 5-32 = [3] Drive rdy/rem ctrl
Control
[4] Enabled, no
warning
[5] Running
[6] Running, no
Warning
[7] Running within
range, no Warning
[8] Run at
reference, no
Par. 5-32 = [4] Enable / no
warning
Par. 5-32 = [5] VLT® running
Par. 5-32 = [6] Running /no
warning
Par. 5-32 = [7] Run in range/no
warning
Par. 5-32 = [8] Run on ref/no
warning
Warning
Table 5.107 Conversion of Parameters 319 to 321
[18] Out of feedback
range
[19] Over feedback
low
[20] Under feedback
high
[21] Thermal
warning
[22] Ready, no
thermal warning
[23] Ready - remote
control - no thermal
warning
[24] Ready – mains
voltage within range
[25] ReversingPar. 5-32 = [25] Reverse
[26] Bus OKPar. 5-32 = [26] Bus OK
[27] Torque limit
and stop
Par. 5-32 = [15] Out of speed
range
1)
low
1)
high
Par. 5-32 = [18] Out of feedb.
Range
Par. 5-32 = [19] Below
feedback low
Parameter 319 Terminal 42, Output Digital = Par. 5-32 DO
Parameter 321 Terminal 45, Output Digital = Par. 5-33 DO
Options[28] Brake, no brake
Table 5.108 Conversion of Parameters 319 to 321
VLT 5000 seriesFC 302 series
X30/7 (MCB 101)
Analogue values= Par. 6-50
AO 42
Pulse = Par. 5-66 DO X30/6
X30/7 (MCB 101)
Analogue values= Par. 6-60
AO X30/8
Pulse = Par. 5-66 DO X30/6
Par. 5-32 = [28] Brake, no
warning
[29] Brake ready, no
fault
[30] Brake faultPar. 5-32 = [30] Brake fault
[31] Relay 123Par. 5-32 = [31] Relay 123
[32] Mechanical brake
control
[34] Extended
mechanical brake
control
[35] Safety InterlockNot supported
[36] 0 – 100 Hz ⇒ 0 – 20
mA
[37] 0 – 100 Hz ⇒ 4 – 20
mA
[38] 0 – 100 Hz ⇒ 0 –
32000 p
[39] 0 – f max ⇒ 0 – 20
mA
[40] 0 – f max ⇒ 4 – 20
mA
[41] 0 – f max ⇒ 0 –
32000 p
[42] Ref min – Ref max
⇒ 0 – 20 mA
brake warning
Par. 5-32 = [29] Brake
ready, no fault
(IGBT)
Par. 5-32 = [32] Mech
brake ctrl
Par. 5-32 = [32] Mech
brake ctrl
Not supported
Not supported
Not supported
Par. 6-50 = [109] Max Out
freq. 0 – 20 mA
Par. 6-50 = [130] Max Out
freq. 4 – 20 mA
Par. 5-66 = [109] Max Out
freq. 0 – 32000p Par. 568 =
32000
Par. 6-50 = [101] Reference
0 -20 mA
Parameter 319 Terminal 42,
Parameter 321 Terminal 45,
Options[43] Ref min – Ref max
VLT 5000 seriesFC 302 series
Output
Output
⇒ 4 – 20 mA
[44] Ref min – Ref max
⇒ 0 - 32000 p
[45] FB min – FB max
⇒ 0 – 20 mA
[46] FB min – FB max
⇒ 4 – 20 mA
[47] FB min – FB max
⇒ 0 - 32000 p
[48] 0 – I max ⇒ 0 – 20
mA
[49] 0 – I max ⇒ 4 – 20
mA
[50] 0 – I max ⇒ 0 –
32000 p
[51] 0 – T lim ⇒ 0 – 20
mA
[52] 0 – T lim ⇒ 4 – 20
mA
[53] 0 – T lim ⇒ 0 –
32000 p
[54] 0 – T nom ⇒ 0 –
20 mA
[55] 0 – T nom ⇒ 4 –
20 mA
[56] 0 – T nom ⇒ 0 –
32000 p
[57] 0 – P nom ⇒ 0 –
20 mA
[58] 0 – P nom ⇒ 4 –
20 mA
[59] 0 – P nom ⇒ 0 –
32000 p
Digital = Par. 5-32 DO X30/7
(MCB 101)
Analogue values= Par. 6-50
AO 42
Pulse = Par. 5-66 DO X30/6
Digital = Par. 5-33 DO X30/7
(MCB 101)
Analogue values= Par. 6-60
AO X30/8
Pulse = Par. 5-66 DO X30/6
Par. 6-50 = [131] Reference 4
Parameter405 Reset14-20 Reset Mode
Options[0] Manual reset[0] Off
Table 5.133 Conversion of Parameter 405
Parameter 406 Automatic restart
Range0 – 10 s0 – 600 s
Table 5.134 Conversion of Parameter 406
Parameter 407 Mains failure14-10 Mains Failure
Data range [0] No function[0] No function
Table 5.135 Conversion of Parameter 407
VLT 5000 seriesFC 302 series
time
VLT 5000 seriesFC 302 series
[1] Automatic reset
x 1
[2] Automatic reset
x 2
[3] Automatic reset
x 3
[4] Automatic reset
x 4
[5] Automatic reset
x 5
[6] Automatic reset
x 6
[7] Automatic reset
x 7
[8] Automatic reset
x 8
[9] Automatic reset
x 9
[10] Automatic reset
x 10
5000 seriesFC 302 series
[1] Controlled ramp
down
[2] Controlled ramp
down and trip
[3] Coast[3] Coast
[4] Kinetic back-up[4] Kinetic back-up
[5] Controlled alarm
suppression
[1] Automatic reset x
1
[2] Automatic reset x
2
[3] Automatic reset x
3
[4] Automatic reset x
4
[5] Automatic reset x
5
[6] Automatic reset x
6
[7] Automatic reset x
7
[8] Automatic reset x
8
[9] Automatic reset x
9
[10] Automatic reset x
10
14-21 Automatic Restart
Time
[1] Controlled ramp down
[2] Controlled ramp down
and trip
[5] Kinetic back-up, trip
Parameter 409 Trip delay torque 14-25 Trip Delay at Torque
Range0 – 60 s (60=OFF)0 – 60 s (60=OFF)
Table 5.137 Conversion of Parameter 409
Parameter 410 Trip delay inverter 14-26 Trip Delay at Inverter
Range0 – 35 s0 – 35 s
Table 5.138 Conversion of Parameter 410
Parameter 411 Switching frequency 14-01 Switching Frequency
RangeUnsigned 16 (6)Unsigned 8 (5)
Parameter710 - 77919-10 -19-79
OptionsUser definedUser defined
Table 5.265 Conversion of Parameters 710 to 779
Parameter780 Dead time compensationNot supported
Options[0] Off
Table 5.266 Conversion of Parameter 780
Parameter781 Program IDNot supported
Options0 – 65000
Table 5.267 Conversion of Parameter 781
Parameter 795 - 799 User defined
OptionsUser definedUser defined
Table 5.268 Conversion of Parameters 795 to 799
VLT 5000 seriesFC 302 series
32-65 Velocity Feed-
forward
VLT 5000 seriesFC 302 series
Feed-forward
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
[1] On
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
(read only)
Forward
32-66 Acceleration FeedForward
19-95 -19-99 User
defined (read only)
5.9
VLT® 5000 Parameter Group 8
Parameter801 Baud rate selectionNot converted
Table 5.269 Conversion of Parameter 801
Parameter802 Minimum station delayNot converted
Table 5.270 Conversion of Parameter 802
Parameter 803 Time out after bus
Range1 – 990.1 – 18000.0
Table 5.271 Conversion of Parameter 803
Parameter 804 Response after bus
Range[0] Off[0] Off
Table 5.272 Conversion of Parameter 804
Parameter 805 Function of control word
Range[0] No function[0] None
[1] Bit 10 = 1 => CTW active [1] Profile default
[2] Bit 10 = 0 => CTW active [2] CTW Valid, active
[3] Bit 10 = 1 => Time out[1] Profile default
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
8-03 Control Timeout
error
VLT 5000 seriesFC 302 series
time out
[1] Freeze output
frequency
[2] Stop[2] Stop
[3] Jogging[3] Jogging
[4] Max speed[4] Max speed
[5] Stop and trip[5] Stop and trip
[6] No com. option
control
[7] Select set up 4[10] Select set up 4
VLT 5000 seriesFC 302 series
bit 10
Time
8-04 Control Timeout
Function
8-02 Control Word Source
[204] Minimum Reference [302] Minimum Reference
[205] Maximum
Reference
[219] Catch up/slow
Down Value
[207] Ramp 1 Ramp up
Time
[208] Ramp 1 Ramp
Down Time
[209] Ramp 2 Ramp up
Time
[210] Ramp 2 Ramp
down Time
[211] Jog Ramp Time[380] Jog Ramp Time
[212] Quick Stop Ramp
Time
[201] Motor Low Limit
[Hz]
[202] Motor High Limit
[Hz]
[221] Torque Limit Motor
Mode
[222] Torque Limit
Generator Mode
[509] Bus Jog 1 Speed[890] Bus Jog 1 Speed
[510] Bus Jog 2 Speed[891] Bus Jog 2 Speed
VLT® 5000 supports more write signals. If a notsupported signal is written then the corresponding
signal is set to [0] None.
[203] Maximum Reference
[312] Catch up/slow
Down Value
[341] Ramp 1 Ramp up
Time
[342] Ramp 1 Ramp
Down Time
[351] Ramp 2 Ramp up
Time
[352] Ramp 2 Ramp
down Time
[381] Quick Stop Ramp
Time
[412] Motor Speed Low
Limit [Hz]
[414] Motor Speed High
Limit [Hz]
[416] Torque Limit Motor
Mode
[417] Torque Limit
Generator Mode
Parameter918 Station address10-02 MAC ID
Range0 - 630 - 63
VLT 5000 seriesFC 302 series
ration
[538] Alarm word[1472] VLT Alarm Word
[540] Warning word[1473] VLT Warning Word
[541] Ext. status word[1474] VLT Ext. status
Word
[600] Operating hours[1500] Operating hours
[601] Running hours[1501] Running hours
[602] kWh Counter[1502] kWh Counter
[539] Control word[1600] Control word
[516] Reference [Unit][1601] Reference [Unit]
[515] Reference %[1602] Reference %
[534] Status word[1603] Status word
[522] Power [kW][1610] Power [kW]
[523] Power [HP][1611] Power [HP]
[524] Motor voltage[1612] Motor voltage
[518] Motor frequency[1613] Motor frequency
[520] Motor current[1614] Motor current
[557] Motor RPM[1617] Motor speed
[526] Motor thermal[1618] Motor thermal
[521] Torque[1622] Torque %
[525] DC link voltage[1630] DC link voltage
[536] Brake energy/s[1632] Brake energy/s
[535] Brake energy/2 min [1633] Brake energy/2 min
[537] Heat sink temp.[1634] Heat sink temp.
[527] Inverter Thermal[1635] Inverter Thermal
[533] External reference[1650] External reference
[532] Pulse reference[1651] Pulse reference
[517] Feedback [Unit][1652] Feedback [Unit]
[528] Digital input[1660] Digital input
[529] Analog input 53[1662] Analog input 53
[530] Analog input 54[1664] Analog input 54
[531] Analog input 60[1664] Analog input 54
Copy the station address from the VLT® 5000 to
the VLT® AutomationDrive.
2.Cycle power to the FC 302.
3.
The master/PLC now recognises FC 302 as a VLT
5000.
4.The NS LED on the MCA 194 option is now solid
green indicating that communication between
master and slave is established.
If the NS LED flashes, the master/PLC has not recognised
the FC 302 action:
Check if station address is the same in the FC 302
•
as the replaced VLT® 5000.
Check 10-01 Baud Rate Select. If the frequency
•
converter has no connection to the master, this
parameter may be set to the wrong baudrate.
Check 10-13 Warning Parameter.
•
®
66
Bit
Table 6.1 Warning Word
Warn. Word
[Hex]
00001Bus not active
10002Explicit connection timeout
20004I/O connection
30008Retry limit reached
40010Actual value is not updated
50020CAN bus off
60040I/O send error
70080Initialisation error
80100No bus supply
90200Bus off
100400Error passive
110800Error warning
121000Duplicate MAC ID Error
132000RX queue overrun
144000TX queue overrun
158000CAN overrun
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to
products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property
of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.