Danfoss MCA 194 Operating guide

MAKING MODERN LIVING POSSIBLE
Operating Instructions
VLT® DeviceNet Converter MCA 194
VLT® AutomationDrive FC 302 • VLT® 5000
www.danfoss.com/drives
Contents Operating Instructions
Contents
1 Introduction
1.1 Purpose of the Manual
1.2 Additional Resources
1.3 Product Overview
1.4 Constraints
1.4.1 Software Versions 3
1.4.2 Relations 3
1.4.3 Hardware 4
1.4.4 Performance 5
1.5 Abbreviations
2 Safety
2.1 Safety Symbols
2.2 Qualified Personnel
2.3 Safety Precautions
3 Installation
3.1 Connecting the Bus Line
3 3 3 3 3
5
6 6 6 6
8 8
3.2 Mechanical Installation
3.3 EMC Precautions
4 Commissioning
4.1 Configure the DeviceNet Network
4.1.1 Setting the DeviceNet Address using the Hardware Switches 11
4.1.2 Setting the DeviceNet Address via 10-02 MAC ID 11
4.1.3 Start-up 12
4.2 LED Behaviour
4.3 Initialisation
5 Parameter Mapping Lists
5.1 VLT® 5000 Parameter Group 0
5.2 VLT® 5000 Parameter Group 1
5.3 VLT® 5000 Parameter Group 2
5.4 VLT® 5000 Parameter Group 3
5.5 VLT® 5000 Parameter Group 4
5.6 VLT® 5000 Parameter Group 5
8
10
11 11
12 13
14
14
16
19
22
30
35
5.7 VLT® 5000 Parameter Group 6
5.8 VLT® 5000 Parameter Group 7
5.9 VLT® 5000 Parameter Group 8
5.10 VLT® 5000 Parameter Group 9
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 1
37
39
40
41
Contents Operating Instructions
6 Troubleshooting
6.1 Step-by-step Troubleshooting
Index
43 43
44
2 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
Introduction
1 Introduction
Operating Instructions
1
1
1.1 Purpose of the Manual
These Operating Instructions provide information for installing and configuring the DeviceNet Converter option MCA 194. The Operating Instructions also contain the parameter mapping lists and troubleshooting information.
First-time users can find the most essential information for quick installation and set-up in:
Chapter 1.3 Product Overview
Chapter 1.4 Constraints
Chapter 3 Installation
For more detailed information including the full range of set-up options and diagnosis tools, refer to:
Chapter 4 Commissioning
Chapter 5 Parameter Mapping Lists
VLT® is a registered trademark.
1.2 Additional Resources
The following literature is available for the FC 300 series:
VLT® AutomationDrive Operating Instructions
VLT® AutomationDrive Design Guide
VLT® AutomationDrive Programming Guide
Supplementary publications and manuals are available for download. See www.danfoss.com/BusinessAreas/DrivesSo-
lutions/Documentations/VLT+Technical+Documentation.htm
for listings.
1.3
Product Overview
The MCA 194 DeviceNet Converter is a DeviceNet option when installed in VLT® AutomationDrive FC 302. It emulates the DeviceNet commands of a VLT® 5000 in a
DeviceNet network.
NOTICE
Some parameters in the VLT® 5000 are not supported in the FC 302 and some FC 302 parameters cannot be accessed via the DeviceNet converter option MCA 194. Refer to chapter 5 Parameter Mapping Lists for more information. If a write request is attempted to a parameter selection not supported, the frequency converter discards the value and issues a positive reply. Only parameters and functions described in this manual are supported.
NOTICE
The replacement frequency converter must match the power size of the motor for optimal performance. In some cases a bigger frequency converter may be needed to replace the VLT® 5000. Make sure that the brake resistor matches the new frequency converter. Make sure that the new frequency converter meets the local regulations concerning the machinery directive, prefuses, and other appropriate regulations.
NOTICE
Observe local rules and regulations when replacing frequency converter in existing installations.
1.4 Constraints
1.4.1 Software Versions
VLT® AutomationDrive FC 302 with firmware
version 6.54 or higher. The MCA 194 DeviceNet Converter firmware is
based on a VLT® 5000 software version 3.9x and DeviceNet software version 2.x.
Relations
1.4.2
This manual relates to the following hardware:
VLT® DeviceNet Converter option MCA 194, type
With this DeviceNet converter option the FC 302 reacts as a VLT® 5000 on the DeviceNet network. Changes to PLC
programming or re-configuration are normally not necessary.
The FC 302 identifies itself as a VLT® 5000 on the DeviceNet network. For example, a write command to
ramp-up time in VLT® 5000 is automatically linked to the corresponding ramp-up time parameter in VLT
AutomationDrive FC 302.
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 3
®
no. 130B5601
VLT® General I/O option MCB 101, type no.
130B1125 (uncoated), 130B1212 (coated)
VLT® External 24 Volt DC Supply MCB 107, type
no. 130B1108 (uncoated), 130B1208 (coated)
130BT310.11
Introduction Operating Instructions
1
1.4.3 Hardware
The VLT® DeviceNet Converter MCA 194 supports
VLT® AutomationDrive FC 302 only. The FC 302 has fewer digital I/Os and analog
output signals than VLT® 5000. The General I/O Option MCB 101 must be mounted in the FC 302 to map these signals and utilise all I/Os.
VLT® 5000
Terminal Function Terminal Function
16 Digital input 17 Digital input 18 Digital input 18 Digital input 19 Digital input 19 Digital input 27 Digital input 27 Digital input 29 Digital input 29 Digital input 32 Digital input 32 Digital input 33 Digital input 33 Digital input 20 GND Digital
input
53 Analog input
voltage
54 Analog input
voltage
60 Analog input
current
55 GND analog/
digital input
voltage
42
39 GND analog/
04-05 Relay 04-06 Relay 01-03 Relay 01-03 Relay
68 RS-485-P 68 RS-485-P 69 RS-485-N 69 RS-485-N 61 GND RS-485 61 GND RS-485 12 24 V out 12 24 V out 13 24 V out 13 24 V out 50 10 V out 50 10 V out
Analog/digital
output
digital output
X30/2
X3/3
20 GND Digital input
53
X30/11
54
55 GND analog/digital
42 Analog output 0/4-20
X30/6 X30/7
39 GND analog /digital
FC 302
1)
1)
3)
1)
1)
Digital input Digital input
Analog input voltage
Analog input voltage
Analog input current
input voltage
Digital output
Pulse output
mA
output
2)
Illustration 1.1 Location of Switches S801, S201, and S202 (Left to Right)
3)
Table 1.1 Terminal Mapping
1) General I/O option MCB 101
2) Switch “S201” must be OFF
3) Switch “S202” must be ON
4 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
Introduction
Operating Instructions
1.4.4 Performance
The dynamic performance on the motor shaft in
the closed loop operation compared with VLT 5000 can be different in certain applications. If necessary, adjust the PID controller manually.
The motor control algorithm of the VLT
AutomationDrive results in a better motor performance compared to VLT® 5000.
®
®
NOTICE
Factory values: After initialisation, most parameters are set to match the factory settings of the VLT® 5000 parameters. For more information about the initialisation, see the VLT AutomationDrive FC 301/FC 302 Programming Guide.
®
NOTICE
Linked Set-ups: To synchronise set-up changes made with running motor, ensure that FC 302 set-ups are linked. This is done in 0-12 This Set-up Linked to.
1
1
1.5 Abbreviations
AOC Application Oriented Control CTW Control Word EMC Electromagnetic Compatibility I/O Input/Output LED Light Emitting Diode LSB Least Significant Bit MAV Main Actual Value (actual output) MOC Motor Oriented Control MSB Most Significant Bit MRV Main Reference Value (Setpoint) N/A Not Applicable PCD Peripherals Communication Data (process data) PCV Parameter Characteristics Value (Parameter
channel) PLC Programmable Logic Controller PNU Parameter Number PU Power Unit REF Reference (= MRV) STW Status Word
Table 1.2 Abbreviations
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 5
Safety
2 Safety
Operating Instructions
22
2.1 Safety Symbols
The following symbols are used in this document:
WARNING
Indicates a potentially hazardous situation which could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which could result in minor or moderate injury. It may also be used to alert against unsafe practices.
NOTICE
Indicates important information, including situations that may result in damage to equipment or property.
2.2 Qualified Personnel
Correct and reliable transport, storage, installation, operation and maintenance are required for the trouble­free and safe operation of the frequency converter. Only qualified personnel is allowed to install or operate this equipment.
Qualified personnel is defined as trained staff, who are authorised to install, commission, and maintain equipment, systems and circuits in accordance with pertinent laws and regulations. Additionally, the personnel must be familiar with the instructions and safety measures described in this document.
2.3
Safety Precautions
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when connected to AC mains input power. Failure to perform installation, start-up, and maintenance by qualified personnel could result in death or serious injury.
Installation, start-up, and maintenance must be
performed by qualified personnel only.
Safety regulations
1. The frequency converter must be disconnected from mains, if repair work is to be carried out. Check that the mains supply has been discon­nected and that the necessary time has passed
NOTICE
The function is initialised at 1.16 x rated motor current and rated motor frequency. For the North American market, the ETR functions provide class 20 motor overload protection in accordance with NEC.
Warning against unintended start
before removing motor and mains plugs, see Table 2.1.
2. The [Off] key does not disconnect the equipment from mains and is thus not to be used as a safety switch.
3. Establish correct protective earthing of the equipment, protect the user against supply voltage, and protect the motor against overload in accordance with applicable national and local regulations.
4. The earth leakage currents are higher than 3.5 mA.
5. Protection against motor overload is not included in the factory setting. If this function is desired, set 1-90 Motor Thermal Protection [4] ETR trip or [3] ETR warning.
6. Do not remove the plugs for the motor and mains supply while the frequency converter is connected to mains. Check that the mains supply has been disconnected and that the necessary time has passed before removing motor and mains plugs, see Table 2.1.
7. The frequency converter has more voltage inputs than L1, L2 and L3, when load sharing (linking of DC intermediate circuit) and external 24 V DC have been installed. Check that all voltage inputs have been disconnected and that the necessary time has passed before commencing repair work, see Table 2.1.
1. The motor can be brought to a stop with digital commands, bus commands, references or a local stop, while the frequency converter is connected to mains. These stop functions are not sufficient to prevent unintended starts.
2. While parameters are being changed, the motor may start. Consequently, always press [Off].
3. A motor that has been stopped may start if faults occur in the electronics of the frequency converter, or if a temporary overload or a fault in the supply mains or the motor connection ceases.
6 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
Safety Operating Instructions
WARNING
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains.
2 2
Voltage [V]
200-240 0.25-3.7 kW 5.5-37 kW 380-480 0.25-7.5 kW 11-75 kW 525-600 0.75-7.5 kW 11-75 kW 525-690 11-75 kW High voltage may be present even when the warning LED indicator lights are off.
Table 2.1 Discharge Time
Also make sure that other voltage inputs have been disconnected, such as external 24 V DC, load sharing (linkage of DC intermediate circuit), as well as the motor connection for kinetic back-up.
Minimum waiting time (minutes)
4 15
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 7
130BD826.10
5 4 23 1
+24V
GND
Drain
CAN_LCAN_H
130BT318.11
Installation Operating Instructions
3 Installation
3.1 Connecting the Bus Line
33
Terminate the bus line at both ends of each segment. A mismatch of impedance may result in reflections on the line resulting in corrupt data transmission.
The DeviceNet Option Card contains a suitable termination. To activate the termination, turn on Switch 1 on the DeviceNet converter option. By default, the switch is turned off.
NOTICE
Notice that pin numbers are colour-coded on the DeviceNet connector.
Unlike the VLT are colour-coded to avoid swapping the bus wires.
®
5000, the FC 302 DeviceNet connectors
Pin no. Terminal Colour Name
1 V- Black GND 2 CAN_L Blue CAN LOW 3 Drain (bare) Screen 4 CAN_H White CAN HIGH 5 V+ Red +24 V
Table 3.1 Correct Colour-Coding
3.2 Mechanical Installation
3.2.1 Mount the Option
Illustration 3.2 Installing Fieldbus Option
Illustration 3.1 Connecting Wires to VLT DeviceNet Converter MCA 194
8 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
Installation Operating Instructions
Illustration 3.3 Cable Holders
1. Remove the LCP from the FC 302.
2. Remove the frame below the LCP.
3. Push the option into place. 2 positions are possible, with cable terminal facing either up or down. The cable up position is often most suitable when several frequency converters are installed side-by-side in a rack, as this position permits shorter cable lengths.
4. Push the fieldbus option adaptor frame for the FC 302 into place.
5. Remount the LCP.
6. Attach the cable.
7. Fasten the cable using cable holders.
3 3
Adapter Plate
3.2.2
To ease the replacement of VLT 5000 with VLT® AutomationDrive, there is a number of adapter plates available. The adapter plates have the same footprints as VLT 5000 and have threaded holes for VLT® AutomationDrive. The adapter plate prevents
damage that can occur from drilling new threaded holes in the backboard of the enclosure. The adapter plate also decreases the time required to exchange a broken frequency converter. The following mechanical adapter plates are available:
Ordering number
130B0183 Bookstyle, IP20 395 90
130B0184 Bookstyle, IP20 395 130
130B0185 Compact, IP20 395 220
Table 3.2 Ordering Numbers for Adapter Plates
Style Height [mm] Width [mm] Type
5001-5003 200-240 V 5001-5005 380-500 V 5004-5006 200-240 V 5006-5011 380-500 V 5001-5003 200-240 V 5001-5005 380-500 V 5004-5006 200-240 V 5006-5011 380-500 V 5001-5011 550-600 V
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 9
Fieldbus cable
Min.200mm
90° crossing
130BA080.11
Installation Operating Instructions
3.3 EMC Precautions
To achieve interference-free operation of the DeviceNet:
Maintain high distance (min. 200 mm [8"])
between the DeviceNet communication cable and
33
the motor and brake resistor cables to avoid coupling of high frequency noise from one cable to the other.
When crossing is unavoidable, ensure that the
DeviceNet cable crosses motor and brake resistor cables at an angle of 90°.
NOTICE
Observe relevant national and local regulations, for example regarding protective earth connection.
Illustration 3.4 Correct EMC Installation
10 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
130BD825.10
MCA 194
DeviceNet
Converter
MS
NS
Option A
130B5601
NS
MS
ON
OFF
S600
ON
OFF
ON
S300
ON ON
12345678
Commissioning Operating Instructions
4 Commissioning
4.1 Configure the DeviceNet Network
All DeviceNet stations connected to the same bus network must have a unique station address.
Before a VLT® 5000 can be replaced with an FC 302 with MCA 194, only the station address and baud rate needs to be configured in the FC 302.
The DeviceNet address of the FC 302 can be selected via:
Hardware switches
Parameter 10-02 MAC ID (default 63)
Class code 0X03, Instance 1, Attribute 1
NOTICE
After installing DeviceNet Converter MCA 194, check that 8-02 Control Source is set to [3] Option A.
4.1.1 Setting the DeviceNet Address using the Hardware Switches
Read the hardware switches during power-up. When switches are changed, perform a power down-up immediately to activate the changes.
Using the hardware switches, select an address range from 0 to 63 (factory setting 63) according to Illustration 4.1: ON = 1, OFF = 0
4 4
Illustration 4.1 DeviceNet Converter Option A
NOTICE
The address change comes into effect at the next power­up, and can be read in 10-02 MAC ID.
Switch 1 2 3 4 5 6 7 8 8 7 6 5 4 3 2 1 Address +32 +16 +8 +4 +2 +1 - - - - +32 +16 +8 +4 +2 +1 Example: 1 0 0 0 0 0 1 - - - - 0 0 0 0 0 1 35 1 0 0 0 1 1 - - - - 1 0 0 0 1 1 52 1 1 0 1 0 0 - - - - 1 1 0 1 0 0
Table 4.1 Hardware Switches
VLT® 5000
4.1.2 Setting the DeviceNet Address via
10-02 MAC ID
Setting the address via parameter 10-02 MAC ID or the DeviceNet Class code 0X03, Instance 1, Attribute 1, is possible, if the hardware switches are all set in the "On" position. The new address becomes active at the next power-up.
FC 302
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 11
Commissioning Operating Instructions
4.1.3 Start-up
communication between the master and the frequency converter is established. If the NS LED flashes, the
After setting the station address from VLT® 5000 to VLT
®
master/PLC has not recognised the frequency converter.
AutomationDrive, cycle power on the frequency converter to activate the new address. The master/PLC now
recognises the frequency converter as VLT® 5000. A solid
For more information, refer to chapter 6.1 Step-by-step Troubleshooting.
green NS LED on the MCA 194 option indicates that
44
4.2 LED Behaviour
The option has 2 bi-coloured LEDs, as shown in Table 4.2. The status of the LEDs is shown in Table 4.3 and Table 4.4.
LED label Description
NS Network Status
MS Module Status ( DP-V1 communication)
Table 4.2 Bi Coloured LEDs
State Bi-colour LED Status
No Power Off There is no power applied to the option Device operational
Standby Green The DeviceNet option needs commis-
Minor fault Red Recoverable fault.
Green The DeviceNet option is operating in
normal condition.
sioning due to configuration missing, incomplete or incorrect.
Unrecoverable fault
Self test Green The DeviceNet option is in Self-test
Table 4.3 LED: Module Status (MS)
State Bi-colour LED Status
No Power/Not on­line
On-line, not connected
On-line and connected
Connection time­out
Critical link failure Red
Table 4.4 LED: Network Status (NS)
Red Unrecoverable fault, may need
replacing.
mode.
Red
Off The option has not completed
“Duplicate MAC ID” test yet or may not be powered.
Green The option is on-line, but not allocated
to a master.
Green The DeviceNet option is on-line and
connected to a master.
Red One or more I/O connections are in
time-out state.
NOTICE
The LED status patterns of the MCA 194 are not compatible with the patterns of the VLT® 5000 DeviceNet LEDs.
12 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
Commissioning
Operating Instructions
4.3 Initialisation
To achieve the best performance, initialise the frequency converter after the option is mounted. If the frequency converter is delivered from factory with the option installed, skip this step. The initialisation is done via 14-22 Operation Mode or a 3­finger reset. The parameters of the FC 302 are set to factory values, and a number of FC 302 parameters are set to values
that match the VLT® 5000 initial values.
Factory copy via VLT® 5000 parameter 006 is supported and initialises the FC 302 and also set it to the VLT® 5000 default settings.
Table 4.5 lists the parameter settings created during initialisation.
Parameter Initialisation setting
0-02 Motor Speed Unit [Hz] 1-52 Min Speed Normal Magnetising [Hz] 1.0 Hz 3-16 Reference 2 Source [0] No function 4-12 Motor Speed Low Limit [Hz] 132.0 Hz 3-00 Reference Range min – max 3-01 Reference/Feedback Unit [1] % 3-11 Jog Speed [Hz] 10.0 Hz 4-30 Motor Feedback Loss Function [0] Disabled 4-56 Warning Feedback Low -4000000 4-57 Warning Feedback High 4000000 6-10 Terminal 53 Low Voltage 0.00 Volt 6-20 Terminal 54 Low Voltage 0.00 Volt 6-22 Terminal 54 Low Current 0.00 Volt 5-51 Term. 29 High Frequency 5000 Hz 5-56 Term. 33 High Frequency 25000 Hz 4-32 Motor Feedback Loss Timeout 1.00 s 14-21 Automatic Restart Time 5 s 14-03 Overmodulation [0] Off 20-93 PID Proportional Gain 0.01 8-54 Reversing Select [0] Digital input 8-90 Bus Jog 1 Speed 300 RPM 8-91 Bus Jog 2 Speed 300 RPM 7-04 Speed PID Differentiation Time OFF 2-10 Brake Function [0] Off 2-17 Over-voltage Control [0] Off 5-40 Function Relay [22] Ready, no thermal Warning 5-41 On Delay, Relay [23] Remote, ready, no TW 7-09 Speed PID Error Correction w/ Ramp 100000 (max) 14-11 Mains Voltage at Mains Fault calculated value: VLT5000 level = FC 302 level
* 1,35 / sqrt(2)
MCB 101 option specific parameters
5-16 Terminal X30/2 Digital Input [1] Reset 5-17 Terminal X30/3 Digital Input [19] Freeze reference
PROFIBUS specific parameters
9-71 Profibus Save Data Values [1] Store all setups
4 4
Table 4.5 Parameter Set-up at Initialisation
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 13
Parameter Mapping Lists
5 Parameter Mapping Lists
Operating Instructions
5.1
VLT® 5000 Parameter Group 0
Parameter 001 Language select 0-01 Language Options [0] English [0] English
55
Table 5.1 Conversion of Parameter 001
Parameter 002 Local/remote control Not converted Options [0] Remote
Table 5.2 Conversion of Parameter 002
Parameter 003 Local reference Not converted
Table 5.3 Conversion of Parameter 003
Parameter 004 Active Set-up 0-10 Active Set-up Options [0] Factory Setup [0] Factory Setup
Table 5.4 Conversion of Parameter 004
Parameter 005 Setup Copy 0-51 Set-up Copy Options [0] Factory Set-up [0] Factory Set-up
Table 5.5 Conversion of Parameter 005
VLT 5000 series FC 302 series
[1] Deutsch [1] Deutsch [2] French [2] French [3] Dansk [3] Dansk [4] Spanish [4] Spanish [5] Italian [5] Italian
VLT 5000 series FC 302 series
[1] Local with External Stop [2] Local
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
[1] Setup 1 [1] Setup 1 [2] Setup 2 [2] Setup 2 [3] Setup 3 [3] Setup 3 [4] Setup 4 [4] Setup 4 [5] Multi Setup [9] Multi Setup
VLT 5000 series FC 302 series
[1] Setup 1 [1] Setup 1 [2] Setup 2 [2] Setup 2 [3] Setup 3 [3] Setup 3 [4] Setup 4 [4] Setup 4 [5] Active Setup [9] Active Setup
Parameter 006 Setup Copy 0-51 Set-up Copy Options [0] No Copy [0] No Copy
Table 5.6 Conversion of Parameter 006
Parameter 007 LCP Copy Not converted
Table 5.7 Conversion of Parameter 007
Parameter 008 Display scaling of motor
Table 5.8 Conversion of Parameter 008
Parameter number Parameter number Parameter number Parameter number Options [0] None [0] None
VLT 5000 series FC 302 series
[1] [1] [2] [2] [3] [3] [4] [4]
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
Not converted
frequency
VLT 5000 series FC 302 series
009 Display line 0-23
010 Display line 0-20
011 Display line 0-21
012 Display line 0-22
[1] Reference % [1602] Reference % [2] Reference [Unit] [1601] Reference
[Unit] [3] Feedback [Unit] [1652] Feedback [Unit] [4] Frequency [Hz] [1613] Frequency [Hz] [5] Frequency x scale [1609] Custom
readout [6] Motor current [A] [1614] Motor current
[A] [7] Torque [%] [1622] Torque [%] [8] Power [kW] [1610] Power [kW] [9] Power [HP] [1611] Power [HP] [10] Output energy [kWh] [1502] kWh counter
[kWh] [11] Motor voltage [V] [1612] Motor voltage
[V]
Table 5.9 Conversion of Parameters 009 to 012
14 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
Parameter Mapping Lists
Operating Instructions
Parameter number Parameter number Parameter number Parameter number Options [12] DC link voltage
VLT 5000 series FC 302 series
009 0-09 Performance Monitor
010 0-10 Active Set-up
011 0-11 Programming Set-up
012 0-12 This Set-up Linked to
[V] [13] Thermal load, motor [%] [14] Thermal load, VLT® [%] [15] Running hours [hours] [16] Digital input [1660] Digital input
[17] Analogue input 53 [V] [18] Analogue input 54 [V] [19] Analogue input 60 [mA] [20] Pulse reference [Hz] [21] Ext. reference [%] [22] Status word [hex] [23] Brake effect/2 min [kW] [24] Brake effect/sec [kW] [25] Heat sink temp. [1634] Heat sink temp.
[26] Alarm word [hex] [27] Control word [hex] [28] Warning word 1 [hex] [29] Warning word 2 [hex] [30] Com. Option warning [hex] [31] RPM [min] [1617] Speed RPM [min]
[32] RPM x scaling [min] [33] LCP display text Not possible
[1630] DC link voltage [V]
[1618] Thermal load, motor [%] [1635] Inverter thermal [%]
[1501] Running hours [hours]
[1662] Analogue input 53 [V]
[1664] Analogue input 54 [V]
[1662] Analogue input 53 [mA] [1651] Pulse reference [Hz]
[1650] Ext. reference [%]
[1603] Status word [hex]
[1633] Brake effect/2 min [kW] [1632] Brake effect/sec [kW]
[1600] Control word [hex]
[953] Com. Option warning [hex]
[1609] Custom readout
Parameter 013 Local Ctrl./config Not converted
Table 5.11 Conversion of Parameter 013
Parameter 014 Local Stop key 0-41 [Off] Key on LCP Options [0] Disable [0] Disable
Table 5.12 Conversion of Parameter 014
Parameter 015 Local Jogging Not converted Options [0] Disable
Table 5.13 Conversion of Parameter 015
Parameter 016 Local Reversing Not converted Options [0] Disable
Table 5.14 Conversion of Parameter 016
Parameter 017 Local Stop key 0-43 [Reset] Key on LCP Options [0] Disable [0] Disable
Table 5.15 Conversion of Parameter 017
Parameter 018 Lock for data
Options [0] Not locked [0] Full access
Table 5.16 Conversion of Parameter 018
Parameter 019 Power-Up Mode 0-04 Operating State at
Options [0] Auto Restart, use
Table 5.17 Conversion of Parameter 019
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
[1] Enable [1] Enable [2] Password
VLT 5000 series FC 302 series
[1] Enable
VLT 5000 series FC 302 series
[1] Enable
VLT 5000 series FC 302 series
[1] Enable [1] Enable [2] Password
VLT 5000 series FC 302 series
0-61 Access to Main Menu
change
[1] Lock [1] LCP: Read only
VLT 5000 series FC 302 series
saved ref. [1] Forced stop, use saved ref. [2] Forced stop, set ref = 0.
w/o Password
Power-up [0] Resume
[1] Forced stop, use saved ref. [2] Forced stop, set ref = 0
5 5
Table 5.10 Conversion of Parameters 009 to 012
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 15
Parameter Mapping Lists Operating Instructions
Parameter 027 Warning readout line Not converted Options [0] Warning in line 1/2
Table 5.18 Conversion of Parameter 027
55
VLT 5000 series FC 302 series
[1] Warning in line 3/4
5.2
VLT® 5000 Parameter Group 1
Parameter 100 Configuration 0-02
Options [0] Speed control,
Table 5.19 Conversion of Parameter 100
Parameter 101 Torque charac-
Options [1] High constant
VLT 5000 series FC 302 series
1-01 Motor Control Principle Par. 1-00 = [0] Speed open loop
open loop [1] Speed control,
closed loop [3] Process control, closed loop [4] Torque control, open loop [5] Torque control, speed feedback
VLT 5000 series FC 302 series
teristic
torque [2] High variable torque low
[3] High variable torque medium
[4] High variable torque high
[5] High special motor characteristic [6] High variable torque with low starting torque
Par. 1-01 = [1] VVC Par. 0-02 = [0] RPM Par. 1-00 = [1] Speed closed loop Par. 1-00 = [3] Process Par. 1-01 = [1] VVC
Par. 1-00 = [4] Torque open loop Par.1-01 = [1] VVC Par. 1-00 = [2] Torque close loop Par. 1-01 = [3] Flux with motor fb Par. 5-71 = [1] Counter clockwise
1-03 Torque Characteristics 1-04 Overload Mode 14-40 VT Level Par. 1-03 = [0] Constant torque Par. 1-04 Over load = [0] High Par. 1-03 = [1] Variable torque Par. 14-40 VT level = 45% Par. 1-04 Over load = [0] High Par. 1-03 = [1] Variable torque Par. 14-40 VT level = 66% Par. 1-04 Over load = [0] High Par. 1-03 = [1] Variable torque Par. 14-40 VT level = 85% Par. 1-04 Over load = [0] High Par. 1-01 = [0] U/f Par. 1-04 Over load = [0] High Par. 1-03 = [1] Variable torque Par. 14-40 VT level = 45% Par. 1-04 Over load = [0] High
+
+
+
Table 5.20 Conversion of Parameter 101
16 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
Parameter Mapping Lists
Operating Instructions
Parameter 101 Torque charac-
Options [7] High variable
VLT 5000 series FC 302 series
teristic
torque with medium starting torque [8] High variable torque with high starting torque [11] Normal constant torque [12] Normal variable torque low
[13] Normal variable torque medium [14] Normal variable torque high [15] Normal special motor characteristic [16] Normal variable torque with low constant starting torque [17] Normal variable torque with medium constant starting torque [18] Normal variable torque with high constant starting torque
1-03 Torque Characteristics 1-04 Overload Mode 14-40 VT Level Par. 1-03 = [1] Variable torque Par. 14-40 VT level = 66% Par. 1-04 Over load = [0] High
Par. 1-03 = [1] Variable torque Par. 14-40 VT level = 85% Par. 1-04 Over load = [0] High Par. 1-03 = [0] Constant torque Par. 1-04 Over load = [1] Normal Par. 1-03 = [1] Variable torque Par. 14-40 VT level = 45% Par. 1-04 Over load = [1] Normal Par. 1-03 = [1] Variable torque Par. 14-40 VT level = 66% Par. 1-04 Over load = [1] Normal Par. 1-03 = [1] Variable torque Par. 14-40 VT level = 85% Par. 1-04 Over load = [1] Normal Par. 1-01 = [0] U/f Par. 1-04 Over load = [1] Normal Par. 1-03 = [1] Variable torque Par. 14-40 VT level = 45% Par. 1-04 Over load = [1] Normal
Par. 1-03 = [1] Variable torque Par. 14-40 VT level = 66% Par. 1-04 Over load = [1] Normal
Par. 1-03 = [1] Variable torque Par. 14-40 VT level = 85% Par. 1-04 Over load = [1] Normal
Parameter 105 Motor Current 1-24 Motor Current Range Power Unit dependable Power Unit dependable
Table 5.25 Conversion of Parameter 105
Parameter 106 Rated motor speed 1-25 Motor Nominal Speed Range 100 – 60000 10 – 60000
Table 5.26 Conversion of Parameter 106
Parameter 107 Automatic motor
Options [0] Adaptation off [0] Off
Table 5.27 Conversion of Parameter 107
Parameter 108 Stator resistor 1-30 Stator Resistance (Rs) Range Power Unit dependable 0.0140 – 140.0000
Table 5.28 Conversion of Parameter 108
Parameter 109 Stator reactance 1-35 Main Reactance (Xh) Range Power Unit dependable 1.0000 – 10000.0000
Table 5.29 Conversion of Parameter 109
Parameter 110 Motor magnetizing at
Range 0 – 300% 0 – 300%
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
1-29 Automatic Motor
adaptation
[1] Adaptation on, Rs and Xs [2] Adaptation on, RS [2] Enable reduce AMA
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
0 RPM
Adaptation (AMA)
[1] Enable complete AMA
1-50 Motor Magneti­sation at Zero Speed
5 5
Table 5.21 Conversion of Parameter 101
Parameter 102 Motor Power 1-20 Motor Power [kW] Range 0.18 – 600 kW 0.09 – 3000 kW
Table 5.22 Conversion of Parameter 102
Parameter 103 Motor Voltage 1-22 Motor Voltage Range 200 – 600 Volt 50 – 1000 V
Table 5.23 Conversion of Parameter 103
Parameter 104 Motor frequency 1-23 Motor Frequency Range 20 -1000 Hz 20-1000 Hz
Table 5.24 Conversion of Parameter 104
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 17
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
Table 5.30 Conversion of Parameter 110
Parameter 111 Min. frequency
Range 0.1 – 10.0 Hz 0.3 – 10.0 Hz
Table 5.31 Conversion of Parameter 111
Parameter 113 Load compensation at
Range 0 – 300% 0 – 300%
Table 5.32 Conversion of Parameter 113
VLT 5000 series FC 302 series
low speed
VLT 5000 series FC 302 series
1-52 Min Speed
normal magnetizing
Normal Magnetising [Hz]
1-60 Low Speed Load Compensation
Parameter Mapping Lists
Operating Instructions
Parameter 114 Load compensation at
Range 0 – 300% 0 – 300%
Table 5.33 Conversion of Parameter 114
Parameter 115 Slip Compensation 1-62 Slip Compensation Range -500 - 500% -500 - 500%
Table 5.34 Conversion of Parameter 115
55
Parameter 116 Slip Compensation
Range 0.05 – 1.00 s 0.05 – 5.00 s
Table 5.35 Conversion of Parameter 116
Parameter 117 Resonance
Range 0 - 500% 0 - 500%
VLT 5000 series FC 302 series
1-61 High Speed Load
high speed
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
Time constant
VLT 5000 series FC 302 series
dampening
Compensation
1-63 Slip Compensation Time Constant
1-64 Resonance Dampening
Parameter 121 Start function 1-72 Start Function Options [0] DC hold in start delay
Table 5.40 Conversion of Parameter 121
Parameter 122 Function at stop 1-80 Function at Stop Options [0] Coasting [0] Coast
VLT 5000 series FC 302 series
[0] DC hold/delay time
time [1] DC brake in start delay time [2] Coasting in start delay time [3] Start frequency/voltage clockwise [4] Start frequency/voltage in reference direction [5] VVC+ clockwise [5] VVC+/Flux
VLT 5000 series FC 302 series
[1] DC hold [1] DC hold [2] Motor check [2] Motor check [3] Pre-magnetizing [3] Pre-magnetizing
[1] DC Brake/delay
time
[2] Coast/delay time
[3] Start speed cw
[4] Horizontal
operation
clockwise
Table 5.36 Conversion of Parameter 117
Parameter 118 Resonance
Range 5 – 50 ms 5 – 50 ms
Table 5.37 Conversion of Parameter 118
Parameter 119 High starting torque Not converted
Table 5.38 Conversion of Parameters 119
Parameter 120 Start delay Option 0.0 – 10.0 s 0.0 – 10.0 s
Table 5.39 Conversion of Parameter 120
VLT 5000 series FC 302 series
1-65 Resonance dampening time constant
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
Dampening Time Constant
1-71 Start Delay
Table 5.41 Conversion of Parameter 122
Parameter 123 Min frequency for
Range 0.0 – 10.0 Hz 0.0 – 20.0 Hz
Table 5.42 Conversion of Parameter 123
Parameter 124 DC holding
Range 0 - 100% 0 - 160% (motor depending)
Table 5.43 Conversion of Parameter 124
Parameter 125 DC braking current 2-01 DC Brake Current Range 0 - 100% 0 – 160% P.U depending
Table 5.44 Conversion of Parameter 125
Parameter 126 DC braking time 2-02 DC Braking Time Range 0.0 – 60.0 s 0.0 – 60.0 s
VLT 5000 series FC 302 series
1-82 Min Speed for
function at stop
VLT 5000 series FC 302 series
current
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
Function at Stop [Hz]
2-00 DC Hold/Preheat Current
Table 5.45 Conversion of Parameter 126
18 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
Parameter Mapping Lists
Operating Instructions
Parameter 127 DC brake cut-in
Range 0.0 (Off) – f
Table 5.46 Conversion of Parameter 127
Parameter 128 Motor thermal
Options [0] No protection [0] No protection [1] Thermistor warning [1] Thermistor warning [2] Thermistor trip [2] Thermistor trip [3] ETR warning 1 [3] ETR warning 1 [4] ETR trip 1 [4] ETR trip 1 [5] ETR warning 2 [5] ETR warning 2 [6] ETR trip 2 [6] ETR trip 2 [7] ETR warning 3 [7] ETR warning 3 [8] ETR trip 3 [8] ETR trip 3 [9] ETR warning 4 [9] ETR warning 4 [10] ETR trip 4 [10] ETR trip 4
Table 5.47 Conversion of Parameter 128
VLT 5000 series FC 302 series
2-04 DC Brake Cut In
frequency
(par. 202) 0.0 (Off) – f
max
VLT 5000 series FC 302 series
protection
Speed [Hz]
1-90 Motor Thermal Protection
max
(par. 414)
5.3
VLT® 5000 Parameter Group 2
Parameter 200 Output Frequency Range/
Options [0] Only clockwise, 0 – 132 Hz [0] Clockwise [1] Both directions, 0 – 132 Hz [2] Both directions [2] Only clockwise, 0 – 1000 Hz [0] Clockwise [3] Both directions, 0 – 1000 Hz [2] Both directions [4] Only counter clockwise, 0 –
[5] Only counter clockwise, 0 –
Table 5.52 Conversion of Parameter 200
Parameter 201 Output frequency
Range 0.0 – par. 202 F
Table 5.53 Conversion of Parameter 201
VLT 5000 series FC 302 series
4-10 Motor Speed
Direction
132 Hz
1000 Hz
VLT 5000 series FC 302 series
low limit
max
Direction
[1] Counter clockwise [1] Counter clockwise
4-12 Motor Speed Low Limit [Hz] 0 – par. 414 F
max
[Hz]
5 5
Parameter 129 External motor fan 1-91 Motor External Fan Options [0] No [0] No [1] Yes [1] Yes
Table 5.48 Conversion of Parameter 129
Parameter 130 Start frequency 1-75 Start Speed [Hz] Range 0.0 – 10.0 Hz 0.0 – 500 Hz P.U depending
Table 5.49 Conversion of Parameter 130
Parameter 131 Initial voltage Not converted
Table 5.50 Conversion of Parameter 131
Parameter 145 Minimum DC brake time Not converted
Table 5.51 Conversion of Parameter 132
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
Parameter 202 Output frequency
Range 0.0 – 132/1000 Hz 0 – 1000 Hz
Table 5.54 Conversion of Parameter 202
Parameter 203 Reference/feedback area 3-00 Reference Range Options [0] Min – Max [0] Min – Max
Table 5.55 Conversion of Parameter 203
Parameter 204 Minimum
Range -100,000.000 – par.
Table 5.56 Conversion of Parameter 204
VLT 5000 series FC 302 series
4-14 Motor Speed High
high limit
VLT 5000 series FC 302 series
[1] - Max - +Max [1] - Max - +Max
VLT 5000 series FC 302 series
reference
205 Ref
Limit [Hz] 4-19 Max Output Frequency
3-02 Minimum Reference
-100,000.000 – par.
max
3-03 Ref
max
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 19
Parameter Mapping Lists
Operating Instructions
Parameter 205 Maximum
Range Par. 204 Ref
VLT 5000 series FC 302 series
3-03 Maximum Reference
reference
100,000.000
6-15 Terminal 53 High Ref./Feedb. Value 6-25 Terminal 54 High Ref./Feedb. Value 5-53 Term. 29 High Ref./Feedb. Value 5-58 Term. 33 High Ref./Feedb. Value
Par. 3-02 Ref
min
– 100,000.000
min
55
Table 5.57 Conversion of Parameter 205
Parameter 206 Ramp Type 3-40 Ramp 1 Type
Options [0] Linear Par. 3-40 = [0] Linear
Table 5.58 Conversion of Parameter 206
VLT 5000 series FC 302 series
3-50 Ramp 2 Type 3-82 Quick Stop Ramp Type
Par. 3-50 = [0] Linear Par. 3-82 = [0] Linear
[1] Sine shape (S1) Par. 3-40 = [2] S-ramp Const Time
Par. 3-45 = 1% Par. 3-46 = 25% Par. 3-47 = 1% Par. 3-48 = 25% Par. 3-50 = [2] S-ramp Const Time Par. 3-55 = 1% Par. 3-56 = 25% Par. 3-57 = 1% Par. 3-58 = 25% Par. 3-82 = [2] S-ramp Const Time Par. 3-83 = 1%
Par. 3-84 = 25% [2] Sin2 Shape (S2)
Par. 3-40 = [2] S-ramp Const Time
Par. 3-45 = 25%
Par. 3-46 = 25%
Par. 3-47 = 25%
Par. 3-48 = 25%
Par. 3-50 = [2] S-ramp Const Time
Par. 3-55 = 25%
Par. 3-56 = 25%
Par. 3-57 = 25%
Par. 3-58 = 25%
Par. 3-82 = [2] S-ramp Const Time
Par. 3-83 = 25%
Par. 3-84 = 25%
Parameter 206
Options [0]
Table 5.59 Conversion of Parameter 206
Parameter 207 Ramp up Time 1 3-41 Ramp 1 Ramp Up Time Range 0.05 – 3600.00 s 0.01 – 3600.00 s
Table 5.60 Conversion of Parameter 207
Parameter 208 Ramp down Time 1 3-42 Ramp 1 Ramp Down
Range 0.05 – 3600.00 s 0.01 – 3600.00 s
Table 5.61 Conversion of Parameter 208
Parameter 209 Ramp up Time 2 3-51 Ramp 2 Ramp Up Time Range 0.05 – 3600.00 s 0.01 – 3600.00 s
VLT 5000 series
Ramp Type
Linear [3] Sin3 Shape (S3)
[4] Sin2 filter
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
FC 302 series
3-40 Ramp 1 Type3-50 Ramp 2 Type3-82 Quick Stop Ramp Type
[0] Linear. Write to p.340, 350 and 382
Par. 3-40 = [2] S-ramp Const Time Par. 3-45 = 50% Par. 3-46 = 50% Par. 3-47 = 50% Par. 3-48 = 50% Par. 3-50 = [2] S-ramp Const Time Par. 3-55 = 50% Par. 3-56 = 50% Par. 3-57 = 50% Par. 3-58 = 50% Par. 3-82 = [2] S-ramp Const Time Par. 3-83 = 50% Par. 3-84 = 50% Par. 3-40 = [2] S-ramp Const Time Par. 3-45 = 25% Par. 3-46 = 25% Par. 3-47 = 25% Par. 3-48 = 25% Par. 3-50 = [2] S-ramp Const Time Par. 3-55 = 25% Par. 3-56 = 25% Par. 3-57 = 25% Par. 3-48 = 25% Par. 3-82 = [2] S-ramp Const Time Par. 3-83 = 25% Par. 3-84 = 25%
Time
Table 5.62 Conversion of Parameter 209
Parameter 210 Ramp down Time 2 3-52 Ramp 2 Ramp Down
Range 0.05 – 3600.00 s 0.01 – 3600.00 s
Table 5.63 Conversion of Parameter 210
20 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
VLT 5000 series FC 302 series
Time
Parameter Mapping Lists
Operating Instructions
Parameter 211 Jog ramp time 3-80 Jog Ramp Time Range 0.05 – 3600.00 s 0.01 – 3600.00 s
Table 5.64 Conversion of Parameter 211
Parameter 212 Quick stop ramp
Range 0.05 – 3600.00 s 0.01 – 3600.00 s
Table 5.65 Conversion of Parameter 212
Parameter 213 Jog Frequency 3-11 Jog Speed [Hz] Range 0.0 – par. 202 0.0 – par. 4-14
Table 5.66 Conversion of Parameter 213
Parameter 214 Reference function 3-04 Reference Function Options [0] Sum [0] Sum
Table 5.67 Conversion of Parameter 214
*= Relative reference is added to the MRV from PROFIBUS.
Parameter 215 Preset Reference 1 3-10 Preset Reference Range -100.00 – 100.00% -100.00 – 100.00%
Table 5.68 Conversion of Parameter 215
Parameter 216 Preset Reference 2 3-10 Preset Reference Range -100.00 – 100.00% -100.00 – 100.00%
Table 5.69 Conversion of Parameter 216
Parameter 217 Preset Reference 3 3-10 Preset Reference Range -100.00 – 100.00% -100.00 – 100.00%
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
3-81 Quick Stop Ramp
time
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
[1] Relative See comment below* [2] External/Preset [2] External/Preset
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
Time
Parameter 221 Torque limit for
Range 0.0 – Max. torque % 0.0 – Max. torque %
Table 5.73 Conversion of Parameter 221
Parameter 222 Torque limit for
Range 0.0 – Max. torque % 0.0 – Max. torque %
Table 5.74 Conversion of Parameter 222
Parameter 223 Warning: Current
Range 0.0 – par. 2-24 Current
Table 5.75 Conversion of Parameter 223
Parameter 224 Warning: Current
Range Power Unit dependable Power Unit dependable
Table 5.76 Conversion of Parameter 224
Parameter 225 Warning Low
Range 0,0 – par. 226 0,0 – Par. 4-53
Table 5.77 Conversion of Parameter 225
Parameter 226 Warning High
Range par. 2-25 – par. 202 Par. 4-52 – par. 4-13
Table 5.78 Conversion of Parameter 226
VLT 5000 series FC 302 series
4-16 Torque Limit Motor
motor mode
VLT 5000 series FC 302 series
generating mode
VLT 5000 series FC 302 series
Low
High
VLT 5000 series FC 302 series
High
VLT 5000 series FC 302 series
Frequency
VLT 5000 series FC 302 series
Frequency
Mode
4-17 Torque Limit Generator Mode
4-50 Warning Current Low 2-20 Release Brake Current
0.00 – par. 4-51
4-51 Warning Current High
4-52 Warning Speed Low 2-22 Activate Brake Speed [Hz]
4-53 Warning Speed High
5 5
Table 5.70 Conversion of Parameter 217
Parameter 218 Preset Reference 4 3-10 Preset Reference Range -100,00 - 100,00% -100,00 - 100,00%
Table 5.71 Conversion of Parameter 218
Parameter 219 Catch up/slow
Range 0.00 – 100% 0.00 – 100%
Table 5.72 Conversion of Parameter 219
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 21
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
3-12 Catch up/slow Down
down value
Value
Parameter 227 Warning Low
Range -100,000.000 – par. 228 -999,999.999 – par. 4-57
Table 5.79 Conversion of Parameter 227
Parameter 228 Warning High
Range par. 227 – 100,000.000 Par. 4-56 – 999,999.999
Table 5.80 Conversion of Parameter 228
VLT 5000 series FC 302 series
4-56 Warning Feedback
Feedback
VLT 5000 series FC 302 series
Feedback
Low
4-57 Warning Feedback High
Parameter Mapping Lists
Operating Instructions
Parameter 229 Frequency bypass,
Range 0 - 100%
Table 5.81 Conversion of Parameter 229
Parameter 230 Frequency Bypass14-61 Bypass Speed From [Hz]
Range 0 – par. 200 0 – par. 4-14
55
Table 5.82 Conversion of Parameter 230
Parameter 2-31 Frequency Bypass24-61 Bypass Speed From [Hz]
Range 0 – par. 200 0 – par. 4-14
Table 5.83 Conversion of Parameter 231
Parameter 232 Frequency Bypass34-61 Bypass Speed From [Hz]
Range 0 – par. 200 0 – par. 4-14
Table 5.84 Conversion of Parameter 232
Parameter 233 Frequency Bypass44-61 Bypass Speed From [Hz]
Range 0 – par. 200 0 – par. 4-14
Table 5.85 Conversion of Parameter 233
Parameter 234 Motor phase
Range [0] Enable [2] Trip 1000 ms
Table 5.86 Conversion of Parameter 234
VLT 5000 series FC 302 series
Stored in EEprom only
bandwidth
VLT 5000 series FC 302 series
4-63 Bypass Speed To [Hz]
VLT 5000 series FC 302 series
4-63 Bypass Speed To [Hz]
VLT 5000 series FC 302 series
4-63 Bypass Speed To [Hz]
VLT 5000 series FC 302 series
4-63 Bypass Speed To [Hz]
VLT 5000 series FC 302 series
4-58 Missing Motor Phase
monitor
[1] Disable [0] Disable
Function
5.4
VLT® 5000 Parameter Group 3
Parameter 300 Terminal 16, input 5-16 Terminal X30/2 Digital
Options [0] No function [0] No function
Comments FC 302 does not have a digital input 16, so this is
Table 5.87 Conversion of Parameter 300
Parameter 301 Terminal 17, input 5-17 Terminal X30/3
Options [0] No function [0] No operation
Comments FC 302 does not have a digital input 17, so this is
VLT 5000 series FC 302 series
Input
[1] Reset [1] Reset [2] Stop inverse [6] Stop inverse [3] Only start clockwise,on[12] Enable start forward
[4] Jog [14] Jog [5] Preset reference, on [15] Preset reference, on [6] Preset reference, lsb [16] Preset reference bit 0
[7] Freeze reference [17] Freeze reference [8] Freeze output [20] Freeze output [9] Speed up [21] Speed up [10] Choice of setup, lsb [23] Setup select bit 0 [11] Catch-up [28] Catch-up [12] Ramp 2 [34] Ramp bit 0 [13] Mains failure inverted [29] Data change lock Not supported
linked to 5-16 Terminal X30/2 Digital Input
VLT 5000 series FC 302 series
[1] Reset [1] Reset [2] Stop inverse [6] Stop inverse [3] Only start anticlockwise, on [4] Jog [14] Jog [5] Preset reference, on [15] Preset reference, on [6] Preset reference, msb [17] Preset reference bit
[7] Freeze reference [19] Freeze reference [8] Freeze output [20] Freeze output [9] Speed down [22] Speed down [10] Choice of setup, msb [24] Setup select bit 1 [11] Slow down [29] Slow down [12] Ramp 2 [34] Ramp bit 0 [13] Mains failure inverted Not supported [23] Pulse reference [32] Pulse input [24] Safety interlock Not supported [29] Data change lock Not supported
linked to 5-16 Terminal X30/2 Digital Input
Not supported
Digital Input
[13] Enable start reverse
1
Table 5.88 Conversion of Parameter 301
22 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
Parameter Mapping Lists
Operating Instructions
Parameter 302 Terminal 18, input 5-10 Terminal 18 Digital
Options [0] No function [0] No operation
Table 5.89 Conversion of Parameter 302
Parameter 303 Terminal 19, input 5-11 Terminal 19 Digital
Options [0] No function [0] No operation
Table 5.90 Conversion of Parameter 303
Parameter 304 Terminal 27, input 5-12 Terminal 27 Digital
Options [0] Coasting stop,
Table 5.91 Conversion of Parameter 304
VLT 5000 series FC 302 series
Input
[1] Start [8] Start [2] Latched start [9] Latched start [3] Only start clockwise,on[12] Enable start forward
VLT 5000 series FC 302 series
Input
[1] Reversing [10] Reversing [2] Start reversing [11] Start reversing [3] Only start anticlockwise, on
VLT 5000 series FC 302 series
inverse [1] Reset and Coasting stop, inv. [2] Quick-stop, inverse [4] Quick-stop, inverse [3] DC-braking, inverse [5] DC-brake inverse [4] Stop inverse [6] Stop inverse
[13] Enable start reverse
Input [2] Coast inverse
[3] Coast and reset inv
Parameter 305 Terminal 29, input 5-13 Terminal 29 Digital
Options [0] No function [0] No operation
Table 5.92 Conversion of Parameter 305
Parameter 306 Terminal 32, input 5-14 Terminal 32 Digital
Options [0] No function [0] No operation
VLT 5000 series FC 302 series
Input
[1] Reset [1] Reset [2] Stop inverse [6] Stop inverse [3] Only start clockwise,on[12] Enable start forward
[4] Only start anticlockwise, on [5] Jog [14] Jog [6] Preset reference, on [15] Preset reference, on [7] Preset reference, lsb [16] Preset reference bit 0 [8] Preset reference, msb [17] Preset reference bit 1 [9] Freeze reference [19] Freeze reference [10] Freeze output [20] Freeze output [11] Speed up [21] Speed up [12] Speed down [22] Speed down [13] Choice of Setup, lsb [23] Setup select bit 0 [14] Choice of Setup, msb [24] Setup select bit 1 [15] Catch up [28] Catch up [16] Slow down [29] Slow down [17] Ramp 2 [34] Ramp bit 0 [18] Mains failure inverted Not supported [28] Pulse reference [32] Pulse input [29] Data change lock Not supported
VLT 5000 series FC 302 series
[1] Reset [1] Reset [2] Stop inverse [6] Stop inverse [3] Only start clockwise,on[12] Enable start forward
[13] Enable start reverse
Input
5 5
[4] Jog [14] Jog [5] Preset reference, on [15] Preset reference, on [6] Preset reference, lsb [16] Preset reference bit 0 [7] Freeze reference [19] Freeze reference [8] Freeze output [20] Freeze output [9] Speed up [21] Speed up [10] Choice of Setup, lsb [23] Setup select bit 0 [11] Choice of Setup, msb / Speed up [12] Catch up [28] Catch up [13] Ramp 2 [34] Ramp bit 0 [14] Mains failure inverted [24] Encoder input 2A [0] No operation [29] Data change lock Not supported
Table 5.93 Conversion of Parameter 306
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 23
Not supported
Not supported
Parameter Mapping Lists Operating Instructions
Parameter 307 Terminal 33, input 5-15 Terminal 33 Digital
Options [0] No function [0] No operation
55
Table 5.94 Conversion of Parameter 307
VLT 5000 series FC 302 series
Input 7-00 Speed PID Feedback Source
[1] Reset [1] Reset [2] Stop inverse [6] Stop inverse [3] Only start anticlockwise, on [4] Jog [14] Jog [5] Preset reference, on [15] Preset reference, on [6] Preset reference, msb [17] Preset reference bit 1 [7] Freeze reference [19] Freeze reference [8] Freeze output [20] Freeze output [9] Speed down [22] Speed down [10] Choice of Setup, msb [11] Choice of Setup, msb / Speed down [12] Slow down [29] Slow down [13] Ramp 2 [34] Ramp bit 0 [14] Mains failure inverted [24] Pulse feedback [32] Pulse input,
[25] Encoder input 2B [0] No operation
[29] Data change lock Not supported
[13] Enable start reverse
[24] Setup select bit 1
Not supported
Not supported
Parameter 700 = [9] Frequency input 33
Parameter 700 = [1] 24 V encoder
Parameter 308 Terminal
Options [0] No
Table 5.95 Conversion of Parameter 308
Parameter 309 Terminal 53, min.
Range 0 – 10.0 Volt -10.00 – Par. 6-11
Table 5.96 Conversion of Parameter 309
Parameter 310 Terminal 53, max.
Range 0 – 10.0 Volt Par. 6-10 - 10.00 Volt
VLT 5000 series
53, Analogue Input Voltage
Operation [1] Reference Par. 3-15 Reference resource 1 set to
[2] Feedback signal
[3] Torque limit
[4] Thermistor Par. 3-15 Reference resource 1 set to
VLT 5000 series FC 302 series
scaling
VLT 5000 series FC 302 series
scaling
FC 302 series
3-15 Reference 1 Source 7-00 Speed PID Feedback Source 1-93 Thermistor Source 4-20 Torque Limit Factor Source Par. 3-15 Reference resource 1 set to [0] No function
[1] Analog input 53 Par. 3-15 Reference resource 1 set to [1] Analog input 53 Par. 7-00 Speed PID Feedback Source set to [6] Analog input 53 Par. 3-15 Reference resource 1 set to [1] Analog input 53 Par. 4-20 Torque Limit Factor Source set to [2] Analog in 53
[0] No function Par. 1-93 Thermistor Ressource set to [1] Analog input 53
6-10 Terminal 53 Low Voltage
6-11 Terminal 53 High Voltage
Table 5.97 Conversion of Parameter 310
24 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
Parameter Mapping Lists
Operating Instructions
Parameter 311 Terminal 54,
Options [0] No Operation Par. 3-16 Reference
VLT 5000 series FC 302 series
3-16 Reference 2 Analogue Input Voltage
[1] Reference Par. 3-16 Reference
[2] Torque limit Par. 4-20 Torque
[3] Thermistor Par. 1-93 Thermistor
[4] Relative reference [5] Max. torque frequency
Source
7-00 Speed PID
Feedback Source
4-20 Torque Limit
Factor Source
1-93 Thermistor
Source
4-21 Speed Limit
Factor Source
resource 2 set to [0]
No function
resource 1 set to [2]
Analog input 53
Limit Factor Source
set to [6] Analog in
54
Ressource set to [2]
Analog input 54
Not supported
Par. 4-21 Speed
Limit Factor Source
set to [6] Analog in
54
Parameter 314 Terminal 60,
Options [0] No
Comments The HW switch S202 for analogue input 54 must be
Table 5.101 Conversion of Parameter 314
Parameter 315 Terminal 60, min.
Range 0.0 – 20.0 mA 0.00 – Par. 6-23
VLT 5000 series FC 302 series
3-17 Reference 3 Source Analogue Input current
Operation [1] Reference Par. 3-17 Reference resource 3 set
[2] Feedback signal [3] Torque limit Par. 3-17 Reference resource 3 set
[4] Relative reference
set to current (ON).
VLT 5000 series FC 302 series
scaling
7-00 Speed PID Feedback Source
1-93 Thermistor Source
4-20 Torque Limit Factor Source
Par. 3-17 Reference resource 3 set
to [0] No function
to [2] Analog input 54 Par. 7-00
Speed PID
Feedback Source set to [7] Analog
input 54
Par. 7-00 Speed PID Feedback
Source set to [7] Analog input 54
to [2] Analog input 54 Par. 4-20
Torque Limit
Factor Source set to [6] Analog in
54
Not supported
6-22 Terminal 54 Low Current
5 5
Table 5.98 Conversion of Parameter 311
Parameter 312 Terminal 54, min.
Range 0 – 10.0 Volt -10.00 – Par. 6-21
Table 5.99 Conversion of Parameter 312
Parameter 313 Terminal 54, max.
Range 0 – 10.0 Volt Par. 6-20 - 10.00 Volt
Table 5.100 Conversion of Parameter 313
VLT 5000 series FC 302 series
6-20 Terminal 54 Low
scaling
VLT 5000 series FC 302 series
scaling
Voltage
6-21 Terminal 54 High Voltage
Table 5.102 Conversion of Parameter 315
Parameter 316 Terminal 60, max.
Range 0.0 – 20.0 mA Par. 6-22 - 20.00 mA
Table 5.103 Conversion of Parameter 316
Parameter 317 Time Out 6-00 Live Zero Timeout Time Range 0 – 99 sec 0 – 99 sec
Table 5.104 Conversion of Parameter 317
VLT 5000 series FC 302 series
6-23 Teminal 54 High
scaling
VLT 5000 series FC 302 series
Current
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 25
Parameter Mapping Lists Operating Instructions
Parameter 318 Function after time
VLT 5000 series FC 302 series
6-01 Live Zero Timeout
out
Function
Options [0] Off [0] Off
[1] Freeze output frequency
[1] Freeze output
frequency [2] Stop [2] Stop [3] Jogging [3] Jog [4] Max Speed, p202 [4] Max Speed [5] Stop and trip [5] Stop and trip
VLT 5000 series FC 302 series
Parameter 319 Terminal 42,
Output
Parameter 321 Terminal 45,
Output
Digital = Par. 5-32 DO X30/7 (MCB 101) Analogue values= Par. 6-50 AO 42 Pulse = Par. 5-66 DO X30/6 Digital = Par. 5-33 DO X30/7 (MCB 101) Analogue values= Par. 6-60 AO X30/8 Pulse = Par. 5-66 DO X30/6
Table 5.105 Conversion of Parameter 318
55
Parameter 319 Terminal 42,
VLT 5000 series FC 302 series
Digital = Par. 5-32 DO X30/7
Output
(MCB 101)
Options [15] Out of
frequency range [16] Over f low Par. 5-32 = [16] Below speed
[17] Under f high Par. 5-32 = [17] Above speed
Analogue values = Par. 6-50 AO 42 Pulse = Par. 5-66 DO X30/6
Parameter 321 Terminal 45,
Output
Digital = Par. 5-33 DO X30/7 (MCB 101) Analogue values= Par. 6-60 AO X30/8 Pulse = Par. 5-66 DO X30/6
Options [0] No function Par. 5-32 = [0] No operation
[1] Control Ready Par. 5-32 = [1] Control Ready [2] Ready signal Par. 5-32 = [2] Drive ready [3] Ready - Remote
Par. 5-32 = [3] Drive rdy/rem ctrl Control [4] Enabled, no warning [5] Running
[6] Running, no Warning [7] Running within range, no Warning [8] Run at reference, no
Par. 5-32 = [4] Enable / no
warning
Par. 5-32 = [5] VLT® running
Par. 5-32 = [6] Running /no
warning
Par. 5-32 = [7] Run in range/no
warning
Par. 5-32 = [8] Run on ref/no
warning Warning
Table 5.107 Conversion of Parameters 319 to 321
[18] Out of feedback range [19] Over feedback low
[20] Under feedback high
[21] Thermal warning [22] Ready, no thermal warning [23] Ready - remote control - no thermal warning [24] Ready – mains voltage within range [25] Reversing Par. 5-32 = [25] Reverse [26] Bus OK Par. 5-32 = [26] Bus OK
[27] Torque limit and stop
Par. 5-32 = [15] Out of speed range
1)
low
1)
high Par. 5-32 = [18] Out of feedb. Range Par. 5-32 = [19] Below feedback low
1)
Par. 5-32 = [20] Above feedback high
1)
Par. 5-32 = [21] Thermal warning Par. 5-32 = [12] Ready,no thermal W Par. 5-32 = [23] Remote, ready, no TW
Par. 5-32 = [24] Ready, Voltage OK
Par. 5-32 = [27] Torque limit & stop
[9] Alarm Par. 5-32 = [9] Alarm [10] Alarm or Warning
Par. 5-32 = [10] Alarm or
Warning [11] Torque limit Par. 5-32 = [11] At torque limit [12] Out of current range
Par. 5-32 = [12] Out of current
range [13] Above I low Par. 5-32 = [13] Below current,
1)
low [14] Under I high Par. 5-32 = [14] Above current,
1)
high
Table 5.106 Conversion of Parameters 319 to 321
26 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
Parameter Mapping Lists
Operating Instructions
Parameter 319 Terminal 42, Output Digital = Par. 5-32 DO
Parameter 321 Terminal 45, Output Digital = Par. 5-33 DO
Options [28] Brake, no brake
Table 5.108 Conversion of Parameters 319 to 321
VLT 5000 series FC 302 series
X30/7 (MCB 101) Analogue values= Par. 6-50 AO 42 Pulse = Par. 5-66 DO X30/6
X30/7 (MCB 101) Analogue values= Par. 6-60 AO X30/8 Pulse = Par. 5-66 DO X30/6
Par. 5-32 = [28] Brake, no warning [29] Brake ready, no fault [30] Brake fault Par. 5-32 = [30] Brake fault
[31] Relay 123 Par. 5-32 = [31] Relay 123 [32] Mechanical brake control [34] Extended mechanical brake control [35] Safety Interlock Not supported [36] 0 – 100 Hz 0 – 20 mA [37] 0 – 100 Hz 4 – 20 mA [38] 0 – 100 Hz 0 – 32000 p [39] 0 – f max 0 – 20 mA [40] 0 – f max 4 – 20 mA [41] 0 – f max 0 – 32000 p
[42] Ref min – Ref max 0 – 20 mA
brake warning
Par. 5-32 = [29] Brake
ready, no fault
(IGBT)
Par. 5-32 = [32] Mech
brake ctrl
Par. 5-32 = [32] Mech
brake ctrl
Not supported
Not supported
Not supported
Par. 6-50 = [109] Max Out
freq. 0 – 20 mA
Par. 6-50 = [130] Max Out
freq. 4 – 20 mA
Par. 5-66 = [109] Max Out
freq. 0 – 32000p Par. 568 =
32000
Par. 6-50 = [101] Reference
0 -20 mA
Parameter 319 Terminal 42,
Parameter 321 Terminal 45,
Options [43] Ref min – Ref max
VLT 5000 series FC 302 series
Output
Output
4 – 20 mA [44] Ref min – Ref max 0 - 32000 p [45] FB min – FB max 0 – 20 mA [46] FB min – FB max 4 – 20 mA [47] FB min – FB max 0 - 32000 p [48] 0 – I max 0 – 20 mA [49] 0 – I max 4 – 20 mA [50] 0 – I max 0 – 32000 p
[51] 0 – T lim 0 – 20 mA
[52] 0 – T lim 4 – 20 mA
[53] 0 – T lim 0 – 32000 p
[54] 0 – T nom 0 – 20 mA
[55] 0 – T nom 4 – 20 mA
[56] 0 – T nom 0 – 32000 p
[57] 0 – P nom 0 – 20 mA
[58] 0 – P nom 4 – 20 mA
[59] 0 – P nom 0 – 32000 p
Digital = Par. 5-32 DO X30/7 (MCB 101) Analogue values= Par. 6-50 AO 42 Pulse = Par. 5-66 DO X30/6 Digital = Par. 5-33 DO X30/7 (MCB 101) Analogue values= Par. 6-60 AO X30/8 Pulse = Par. 5-66 DO X30/6 Par. 6-50 = [131] Reference 4
-20 mA Par. 5-66 = [101] Reference 0
– 32000p Par. 5-68 = 32000 Par. 6-50 = [102] Feedback 0
-20 mA Par. 6-50 = [132] Feedback 4
-20 mA Par. 5-66 = [102] Feedback 0
– 32000p Par. 5-68 = 32000 Par. 6-50 = [103] Motor
current 0 -20 mA Par. 6-50 = [133] Motor
current 4 -20 mA Par. 5-66 = [103] Motor
current 0 - 32000p Par. 5-68 = 32000 Par. 6-50 = [104] Torque related to limit 0 - 20 mA
Par. 6-50 = [134] Torque related to limit 4 - 20 mA
Par. 5-66 = [104] Torque related to limit 0 – 32000p Par. 5-68 = 32000 Par. 6-50 = [105] Torque related to norm 0 - 20 mA
Par. 6-50 = [135] Torque related to norm 4 - 20 mA
Par. 5-66 = [105] Torque related to norm 0 – 32000p Par. 5-68 = 32000 Par. 6-50 = [106] Power related to norm 0 - 20 mA
Par. 6-50 = [136] Power related to norm 4 - 20 mA
Par. 5-66 = [106] Power related to norm 0 – 32000p Par. 5-68 = 32000
5 5
Table 5.109 Conversion of Parameters 319 to 321
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 27
Parameter Mapping Lists
Operating Instructions
Parameter 319 Terminal 42,
VLT 5000 series FC 302 series
Digital = Par. 5-32 DO X30/7
Output
(MCB 101) Analogue values= Par. 6-50 AO 42 Pulse = Par. 5-66 DO X30/6
Parameter 321 Terminal 45,
Output
Digital = Par. 5-33 DO X30/7 (MCB 101) Analogue values= Par. 6-60 AO X30/8 Pulse = Par. 5-66 DO X30/6
Options
55
[60] 0 – SyncRPM 0 – 20 mA
[61] 0 – SyncRPM 4
Not supported
Not supported – 20 mA [62] 0 – SyncRPM 0
Not supported – 32000 p [63] RPM at F max 0 – 20 mA [64] RPM at F max 4 – 20 mA [65] RPM at F max 0 – 32000 p
Par. 6-50 = [107] Speed
related to norm 0 - 20 mA
Par. 6-50 = [137] Speed
related to norm 4 - 20 mA
Par. 5-66 = [107] Speed
related to norm 0 – 32000p
Par. 5-68 = 32000
Table 5.110 Conversion of Parameters 319 to 321
Parameter 320 Terminal 42 Output,
VLT 5000 series FC 302 series
5-68 Pulse Output Max
pulse scaling
Freq #X30/6
Range 1 – 32000 Hz 0 – 32000 Hz
Table 5.111 Conversion of Parameter 320
Parameter 322 Terminal 45 Output,
VLT 5000 series FC 302 series
5-68 Pulse Output Max
pulse scaling
Freq #X30/6
Range 1 – 32000 Hz 0– 32000 Hz
Table 5.112 Conversion of Parameter 322
VLT 5000 series FC 302 series
Parameter 323, 326 5-40 Function Relay Range 01 Relay
04 Relay
Relay 1
Relay 2 [0] No function Par. 5-40 = [0] No operation [1] Control Ready Par. 5-40 = [1] Control Ready [2] Ready signal Par. 5-40 = [2] Drive ready [3] Ready - Remote
Par. 5-40 = [3] Drive rdy/rem ctrl Control [4] Enabled, no warning
Par. 5-40 = [4] Enable / no
warning [5] Running Par. 5-40 = [5] VLT running [6] Running, no Warning [7] Running within range, no warning [8] Run at reference, no
Par. 5-40 = [6] Running / no
warning
Par. 5-40 = [7] Run in range/no
warn
Par. 5-40 = [8] Run on ref/no
warn Warning [9] Alarm Par. 5-40 = [9] Alarm [10] Alarm or Warning
Par. 5-40 = [10] Alarm or
Warning [11] Torque limit Par. 5-40 = [11] At torque limit [12] Out of current range
Par. 5-40 = [12] Out of current
range [13] Above I low Par. 5-40 = [13] Below current,
1)
low [14] Under I high Par. 5-40 = [14] Above current,
1)
high [15] Out of frequency range
Par. 5-40 = [15] Out of speed
range [16] Over f low Par. 5-40 = [16] Below speed
1)
low [17] Under f high Par.5-40 = [17] Above speed
1)
high [18] Out of feedback range [19] Over feedback low [20] Under feedback high [21] Thermal warning
Par. 5-40 = [18] Out of feedb.
Range
Par. 5-40 = [16] Below feedback
1)
low
Par. 5-40 = [17] Above feedback
1)
high
Par. 5-40 = [21] Thermal
warning
Table 5.113 Conversion of Parameters 323 to 326
28 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
Parameter Mapping Lists
Operating Instructions
Parameter 323, 326 5-40 Function Relay Range [22] Ready, no
Table 5.114 Conversion of Parameters 323 to 326
Parameter 324 Relay 01, ON delay 5-41 On Delay, Relay Range 0.00 – 600.00 sec 0.01 – 600.00 sec
Table 5.115 Conversion of Parameter 324
Parameter 325 Relay 01, OFF delay 5-42 Off Delay, Relay Range 0.00 – 600.00 s 0.01 – 600.00 s
VLT 5000 series FC 302 series
Par. 5-40 = [22] Ready,no thermal warning [23] Ready - remote control - no thermal warning [24] Ready – mains voltage within range [25] Reversing Par. 5-40 = [25] Reverse [26] Bus OK Par. 5-40 = [26] Bus OK [27] Torque limit and stop [28] Brake, no brake warning [29] Brake ready, no fault [30] Brake fault Par. 5-40 = [30] Brake fault
[31] Relay 123 Par. 5-40 = [31] Relay 123 [32] Mechanical brake control
[33] Control word bit 11/12
[34] Extended mechanical brake control [35] Safety Interlock Not supported
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
thermal W
Par. 5-40 = [23] Remote, ready,
no TW
Par. 5-40 = [24] Ready, Voltage
OK
Par. 5-40 = [27] Torque limit &
stop
Par. 5-40 = [28] Brake, no
brake warning
Par. 5-40 = [29] Brake ready,
no fault
(IGBT)
Par. 5-40.0 = [32] Mech brake
ctrl
Par. 1-72 = [5] VVC+/Flux
Par. 5-40 = [36] Control word
bit 11
Par. 5-40.1 = [37] Control word
bit 12
Par. 5-40.0 = [32] Mech brake
ctrl
Par. 1-72 = [5] VVC+/Flux
Parameter 328 Pulse feedback, max. freq 5-56, 5-50, 5-55 Range 100 – 65000 Hz 0 – 110000 Hz
Table 5.118 Conversion of Parameter 328
Parameter 329 Encoder feedback
Range 1 – 4096 pulses 1 – 4096 pulses
Table 5.119 Conversion of Parameter 329
Parameter 330 Freeze ref. /output function Not converted
Table 5.120 Conversion of Parameter 330
Parameter 345 Encoder loss
Range 0.0 – 60.0 s 0.00 – 60.00 s
Table 5.121 Conversion of Parameter 345
Parameter 346 Encoder loss
Range [0] Off [0] Disable
Table 5.122 Conversion of Parameter 346
Parameter 357 Term. 42, Output
Range 0 – 100% 0 – 200%
Table 5.123 Conversion of Parameter 357
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
5-70 Term 32/33 Pulses Per
pulse/rev.
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
timeout
VLT 5000 series FC 302 series
function
[1] Freeze output frequency [3] Jog [3] Jog [4] Max speed [5] Max speed [5] Stop and trip [11] Stop and trip [7] Select setup 4 [10] Select setup 4
VLT 5000 series FC 302 series
min. scale
Revolution
4-32 Motor Feedback Loss Timeout
4-30 Motor Feedback Loss Function
[4] Freeze output frequency
6-51 Terminal 42 Output Min Scale
5 5
Table 5.116 Conversion of Parameter 325
Parameter 327 Pulse reference, max.
Range 100 – 65000 Hz 0 – 110000 Hz
Table 5.117 Conversion of Parameter 327
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 29
VLT 5000 series FC 302 series
5-51 Term. 29 High
freq
Frequency
Parameter 358 Term. 42, Output
Range 0 – 500% 0 – 200%
Table 5.124 Conversion of Parameter 358
Parameter 359 Term. 45, Output
Range 0 – 100% 0 – 200%
Table 5.125 Conversion of Parameter 359
VLT 5000 series FC 302 series
6-52 Terminal 42 Output
max. scale
VLT 5000 series FC 302 series
min. scale
Max Scale
6-61 Terminal X30/8 Min. Scale
Parameter Mapping Lists Operating Instructions
Parameter 360 Term. 45, Output
Range 0 – 500% 0 – 200%
Table 5.126 Conversion of Parameter 360
Parameter 361 Encoder loss threshold Not converted Range 0 – 600%
Table 5.127 Conversion of Parameter 361
55
VLT 5000 series FC 302 series
6-62 Terminal X30/8 Max.
max. scale
VLT 5000 series FC 302 series
Scale
5.5
VLT® 5000 Parameter Group 4
Parameter 400 Brake function/
Options [0] Off [0] Off
Table 5.128 Conversion of Parameter 400
Parameter Options Power unit dependable Power unit dependable
Table 5.129 Conversion of Parameter 401
Parameter 402 Brake power limit,
Range Depends on unit Depends on unit
VLT 5000 series FC 302 series
2-10 Brake Function
over voltage cont.
[1] Resistor brake Par. 2-10 = *1* Resistor brake
[2] Over voltage control [3] Over voltage control and stop
VLT 5000 series FC 302 series
401 Brake resistor, [Ω]
VLT 5000 series FC 302 series
[kW]
2-17 Over-voltage Control
Par. 2-17 = [0] Off Par. 2-10 = [0] Off Par. 2-17 = [2] Enabled Par- 2-10 = [0] Off Par. 2-17 = [1] Enabled (not at stop)
30-81 Brake Resistor (ohm)
2-12 Brake Power Limit (kW)
Table 5.130 Conversion of Parameter 402
Parameter 403 Power monitoring 2-13 Brake Power Monitoring Options [0] Off [0] Off
Table 5.131 Conversion of Parameter 403
Parameter 404 Brake check 2-15 Brake Check Options [0] Off [0] Off
Table 5.132 Conversion of Parameter 404
VLT 5000 series FC 302 series
[1] Warning [1] Warning [2] Trip [2] Trip
VLT 5000 series FC 302 series
[1] Warning [1] Warning [2] Trip [2] Trip
30 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
Parameter Mapping Lists
Operating Instructions
Parameter 405 Reset 14-20 Reset Mode Options [0] Manual reset [0] Off
Table 5.133 Conversion of Parameter 405
Parameter 406 Automatic restart
Range 0 – 10 s 0 – 600 s
Table 5.134 Conversion of Parameter 406
Parameter 407 Mains failure 14-10 Mains Failure Data range [0] No function [0] No function
Table 5.135 Conversion of Parameter 407
VLT 5000 series FC 302 series
time
VLT 5000 series FC 302 series
[1] Automatic reset x 1 [2] Automatic reset x 2 [3] Automatic reset x 3 [4] Automatic reset x 4 [5] Automatic reset x 5 [6] Automatic reset x 6 [7] Automatic reset x 7 [8] Automatic reset x 8 [9] Automatic reset x 9 [10] Automatic reset x 10
5000 series FC 302 series
[1] Controlled ramp down [2] Controlled ramp down and trip [3] Coast [3] Coast [4] Kinetic back-up [4] Kinetic back-up [5] Controlled alarm suppression
[1] Automatic reset x 1 [2] Automatic reset x 2 [3] Automatic reset x 3 [4] Automatic reset x 4 [5] Automatic reset x 5 [6] Automatic reset x 6 [7] Automatic reset x 7 [8] Automatic reset x 8 [9] Automatic reset x 9 [10] Automatic reset x 10
14-21 Automatic Restart Time
[1] Controlled ramp down
[2] Controlled ramp down and trip
[5] Kinetic back-up, trip
Parameter 409 Trip delay torque 14-25 Trip Delay at Torque
Range 0 – 60 s (60=OFF) 0 – 60 s (60=OFF)
Table 5.137 Conversion of Parameter 409
Parameter 410 Trip delay inverter 14-26 Trip Delay at Inverter
Range 0 – 35 s 0 – 35 s
Table 5.138 Conversion of Parameter 410
Parameter 411 Switching frequency 14-01 Switching Frequency Range Unsigned 16 (6) Unsigned 8 (5)
Table 5.139 Conversion of Parameter 411
Parameter 412 Output frequency dependent
Table 5.140 Conversion of Parameter 412
Parameter 413 Overmodulation
Options [0] Off [0] Off
Table 5.141 Conversion of Parameter 413
Parameter 414 Minimum feedback Not converted
VLT 5000 series FC 302 series
Limit
VLT 5000 series FC 302 series
Fault
VLT 5000 series FC 302 series
1.5 – 14 kHz
VLT 5000 series FC 302 series
switching frequency
VLT 5000 series FC 302 series
function
[1] On [1] On
VLT 5000 series FC 302 series
< 2.3 2.0 kHz [2]
2.3 > 2.7 2.5 kHz [3]
2.8 > 3.2 3.0 kHz [4]
3.3 > 3.7 3.5 kHz [5]
3.8 > 4.5 4.0 kHz [6]
4.6 > 5.5 5.0 kHz [7]
5.6 > 6.5 6.0 kHz [8]
6.6 > 7.5 7.0 kHz [9]
7.6 > 9.0 8.0 kHz [10]
9.1 > 10.0 kHz [11]
Not converted
14-03 Overmodulation function
5 5
Parameter 408 Quick discharge Not converted
Table 5.136 Conversion of Parameter 408
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 31
VLT 5000 series FC 302 series
Table 5.142 Conversion of Parameter 414
Parameter 415 Maximum feedback Not converted
Table 5.143 Conversion of Parameter 415
VLT 5000 series FC 302 series
Parameter Mapping Lists
Operating Instructions
Parameter 416 Feedback Unit 3-01 Reference/
Options
55
VLT 5000 series FC 302 series
feedback Unit
[0] None [0] None
[1] % [1] %
[2] PPM [5] PPM
[3] rpm [2] RPM
[4] bar [71] bar
[5] Cycle/min Not supported
[6] Pulse/s [12] Pulse/s
[7] Unit s/s Not supported
[8] Unit s/min Not supported
[9] Unit s/h Not supported
[10] °C [60] °C
[11] Pa [72] Pa
[12] l/s [20] l/s
Parameter 416 Feedback Unit 3-01 Reference/
[26] m/min [41] m/min
Table 5.145 Conversion of Parameter 416 Part 2
Parameter 417 Speed PID propor-
Data range 0.000 – 0.150 0.000 – 1.000
VLT 5000 series FC 302 series
tional gain
VLT 5000 series FC 302 series
feedback Unit
[27] °F [160] °F [28] in wg [172] in wg [29] gal/s [121] gal/s [30] ft3/s [125] ft3/s [31] gal/min [122] gal/min [32] ft3/min [126] ft3/min [33] gal/h [123] gal/h [34] ft3/h [127] ft3/h [35] lb/s [130] lb/s [36] lb/min [131] lb/min [37] lb/h [132] lb/h [38] lb ft [150] lb ft [39] ft/s [140] ft/s [40] ft/min [141] ft/min
7-02 Speed PID propor­tional gain
[13] m3/s [23] m3/s
[14] l/min [21] l/min
[15] m3/min [24] m3/min
[16] l/h [22] l/h
[17] m3/h [25] m3/h
[18] kg/s [30] kg/s
[19] kg/min [31] kg/min
[20] kg/h [32] kg/h
[21] t/min [33] t/min
[22] t/h [34] t/h
[23] m [45] m
[24] Nm [4] Nm
[25] m/s [40] m/s
Table 5.144 Conversion of Parameter 416 Part 1
Table 5.146 Conversion of Parameter 417
Parameter 418 Speed PID Integral
Data range 2.0 – 999.9 2.0 – 20000.0
Table 5.147 Conversion of Parameter 418
Parameter 419 Speed PID Differen-
Data range 0.0 – 200.0 0.0 – 200.0
Table 5.148 Conversion of Parameter 419
Parameter 420 Speed PID D-gain
Data range 5.0 – 50.0 1.0 – 20.0
Table 5.149 Conversion of Parameter 420
Parameter 421 Speed PID low-pass
Data range 5.0 – 200.0 ms 1.0 – 100.0
VLT 5000 series FC 302 series
7-03 Speed PID propor-
Time
VLT 5000 series FC 302 series
tiation Time
VLT 5000 series FC 302 series
limit
VLT 5000 series FC 302 series
filter
tional gain
7-04 Speed PID Differen­tiation Time
7-05 Speed PID Diff. Gain Limit
7-06 Speed PID Lowpass Filter Time
Table 5.150 Conversion of Parameter 421
32 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
Parameter Mapping Lists
Operating Instructions
Parameter 422 U0 voltage at 0 Hz 1-55 U0 voltage Data range 0.0 – par. 103 0.0 – 1000.0 V
Table 5.151 Conversion of Parameter 422
Parameter 423 U1 voltage 1-55 U1 voltage Data range 0.0 – par. 103 0.0 – 1000.0 V
Table 5.152 Conversion of Parameter 423
Parameter 424 F1 frequency 1-56 F1 frequency Data range 0.0 – par. 104 0.0 – 1000.0 Hz
Table 5.153 Conversion of Parameter 424
Parameter 425 U2 voltage 1-55 U2 voltage Data range 0.0 – par. 103 0.0 – 1000.0 V
Table 5.154 Conversion of Parameter 425
Parameter 426 F2 frequency 1-56 F2 frequency Data range 0.0 – par. 104 0.0 – 1000.0 Hz
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
Parameter 431 U5 voltage 1-55 U5 voltage Data range 0.0 – par. 103 0.0 – 1000.0 V
Table 5.160 Conversion of Parameter 431
Parameter 432 F5 frequency 1-56 F5 frequency Data range 0.0 – par. 104 0.0 – 1000.0 Hz
Table 5.161 Conversion of Parameter 432
Parameter 433 Torque control,
Data range 0 (Off) – 500% 0 (Off) – 500%
Table 5.162 Conversion of Parameter 433
Parameter 434 Torque control,
Data range 0.002 – 2.000 sec 0.002 – 2.000 sec
Table 5.163 Conversion of Parameter 434
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
7-12 Torque PI open loop propor­tional gain
VLT 5000 series FC 302 series
open loop integral time
Integration Time
7-13 Torque PI
Integration Time
5 5
Table 5.155 Conversion of Parameter 426
Parameter 427 U3 voltage 1-55 U3 voltage Data range 0.0 – par. 103 0.0 – 1000.0 V
Table 5.156 Conversion of Parameter 427
Parameter 428 F3 frequency 1-56 F3 frequency Data range 0.0 – par. 104 0.0 – 1000.0 Hz
Table 5.157 Conversion of Parameter 428
Parameter 429 U4 voltage 1-55 U4 voltage Data range 0.0 – par. 103 0.0 – 1000.0 V
Table 5.158 Conversion of Parameter 429
Parameter 430 F4 frequency 1-56 F4 frequency Data range 0.0 – par. 104 0.0 – 1000.0 Hz
Table 5.159 Conversion of Parameter 430
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
Parameter 437 Process PID
Options [0] Normal [0] Normal
Table 5.164 Conversion of Parameter 437
Parameter 438 Process PID Anti
Options [0] Off [0] Off
Table 5.165 Conversion of Parameter 438
Parameter 439 Process PID
Data range Fmin – fmax 0 – 6000 rpm
Table 5.166 Conversion of Parameter 439
VLT 5000 series FC 302 series
7-30 Process PID Normal/Inverse contr
[1] Inverse [1] Inverse
VLT 5000 series FC 302 series
windup
[1] On [1] On
VLT 5000 series FC 302 series
start frequency
Normal/ Inverse
Control
7-31 Process PID
Anti Windup
7-32 Process PID
Start Speed
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 33
Parameter Mapping Lists
Operating Instructions
Parameter 440 Process PID
Data range 0.00 – 10.00 0.00 – 10.00
Table 5.167 Conversion of Parameter 440
Parameter 441 Process PID
Data range 0.01 – 9999.99 0.01 – 10000.00
55
Table 5.168 Conversion of Parameter 441
Parameter 442 Process PID
Data range 0.00 – 10.00 0.00 – 10.00
Table 5.169 Conversion of Parameter 442
Parameter 443 Process PID diff.
Data range 5.0 – 50.0 0.00 – 10.00
Table 5.170 Conversion of Parameter 443
VLT 5000 series FC 302 series
7-33 Process PID
proportional gain
VLT 5000 series FC 302 series
integral time
VLT 5000 series FC 302 series
differentiation time
VLT 5000 series FC 302 series
gain limit
proportional gain
7-34 Process PID integral time
7-35 Process PID Differentiation Time
7-36 Process PID Diff. Gain Limit
Parameter 448 Gear ratio Not supported
Table 5.175 Conversion of Parameter 448
Parameter 449 Friction loss Not supported
Table 5.176 Conversion of Parameter 449
Parameter 450 Mains voltage
Range 180 – 690 V 100 – 800 V
Table 5.177 Conversion of Parameter 450
Parameter 453 Gear ratio,
Range 0.01 – 100.00 0.0001 – 32.0000
Table 5.178 Conversion of Parameter 453
Parameter 454 Dead time
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
14-11 Mains Voltage at mains fault
VLT 5000 series FC 302 series
speed close loop
VLT 5000 series FC 302 series
compensation
at Mains Fault
7-07 Speed PID
Feedback Gear Ratio
Not supported
Parameter 444 Process PID
Table 5.171 Conversion of Parameter 444
Parameter 445 Flying start 1-73 Flying Start
Options [0] Off [0] Disable
Table 5.172 Conversion of Parameter 445
Parameter 446 Switching
Options [0] 60 AVM [0] 60 AVM
Table 5.173 Conversion of Parameter 446
Parameter 447 Torque
VLT 5000 series FC 302 series
Not supported
lowpass filter time
VLT 5000 series FC 302 series
[1] On [1] Enable
VLT 5000 series FC 302 series
14-00 Switching
pattern
[1] SFAVM [1] SFAVM
VLT 5000 series FC 302 series
compensation
Pattern
Not supported
Table 5.179 Conversion of Parameter 454
Parameter 455 Frequency
Table 5.180 Conversion of Parameter 455
Parameter 457 Phase loss
Options [0] Trip [0] Trip
Table 5.181 Conversion of Parameter 457
Parameter 483 Dynamic DC
Table 5.182 Conversion of Parameter 483
VLT 5000 series FC 302 series
Not supported range monitor
VLT 5000 series FC 302 series
14-12 Function at functions
[1] Warning [1] Warning
VLT 5000 series FC 302 series
link compensation
Mains Imbalance
Not supported
Table 5.174 Conversion of Parameter 447
34 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
Parameter Mapping Lists
Operating Instructions
5.6
VLT® 5000 Parameter Group 5
Parameter 500 Address 8-31 Address Range 0-126 0-126
Table 5.183 Conversion of Parameter 500
Parameter 501 Baud rate 8-32 Baud Rate Options [0] 300 Not supported
Table 5.184 Conversion of Parameter 501
VLT 5000 series FC 302 series
Parameter 502 Coasting 8-50 Coasting Select Parameter 503 Quick - Stop 8-51 Quick Stop Select Parameter 504 DC brake 8-52 DC Brake Select Parameter 505 Start 8-53 Start Select Parameter 506 Reversing 8-54 Reversing Select Parameter 507 Setup select 8-55 Set-up Select Parameter 508 Preset reference
Parameter type Options [0] Digital input [0] Digital input
Table 5.185 Conversion of Parameter 502-508
Parameter 509 Bus Jog 1 8-90 Bus Jog 1 Speed Range 0.0 – par. 202 0.0 – par. 4-13
Table 5.186 Conversion of Parameter 509
Parameter 510 Bus Jog 2 8-91 Bus Jog 2 Speed Range 0.0 – par. 202 0.0 – par. 4-13
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
[1] 600 Not supported [2] 1200 Not supported [3] 2400 [0] 2400 [4] 4800 [1] 4800 [5] 9600 [2] 9600
8-56 Preset Reference select Unsigned 8 (5) Unsigned 8 (5)
[1] Bus [1] Bus [2] Logic AND [2] Logic AND [3] Logic OR [3] Logic OR
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
Select
Parameter 513 Bus time interval Not Converted
Table 5.189 Conversion of Parameter 513
Parameter 514 Bus time interval function Not Converted
Table 5.190 Conversion of Parameter 514
Parameter 515 Reference % 16-02 Reference [%]
Table 5.191 Conversion of Parameter 515
Parameter 516 Reference Unit 16-01 Reference [Unit]
Table 5.192 Conversion of Parameter 516
Parameter 517 Feedback 16-52 Feedback[Unit]
Table 5.193 Conversion of Parameter 517
Parameter 518 Frequency 16-13 Frequency
Table 5.194 Conversion of Parameter 518
Parameter 519 Frequency x scaling Not converted
Table 5.195 Conversion of Parameter 519
Parameter 520 Current 16-14 Motor current
Table 5.196 Conversion of Parameter 520
Parameter 521 Torque 16-22 Torque [%]
Table 5.197 Conversion of Parameter 521
Parameter 522 Power, kW 16-10 Input Power [kW]
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
16-21 Torque [%] high resolution
VLT 5000 series FC 302 series
5 5
Table 5.187 Conversion of Parameter 510
Parameter 512 Telegram Profile 8-10 Control Profile Range [0] Fieldbus profile [1] ProfiDrive profile
Table 5.188 Conversion of Parameter 512
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 35
VLT 5000 series FC 302 series
[1] FC profile [0] FC profile
Table 5.198 Conversion of Parameter 522
Parameter 523 Power, HP 16-11 Input Power [hp]
Table 5.199 Conversion of Parameter 523
VLT 5000 series FC 302 series
Parameter Mapping Lists
Operating Instructions
Parameter 524 Motor voltage 16-12 Motor Voltage
Table 5.200 Conversion of Parameter 524
Parameter 525 DC link voltage 16-30 DC Link Voltage
Table 5.201 Conversion of Parameter 525
Parameter 526 Motor temp. 16-18 Motor Thermal
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
55
Table 5.202 Conversion of Parameter 526
Parameter
Table 5.203 Conversion of Parameter 527
Parameter 528 Digital input 16-60 Digital Input Options Term. 16 (binary 0000 0001) Term. X30/2 (binary)
Table 5.204 Conversion of Parameter 528
VLT 5000 series FC 302 series
527 VLT® temp.
VLT 5000 series FC 302 series
Term. 17 (binary 0000 0010) Term. X30/3 (binary) Term. 18 (binary 0000 0100) Term. 18 (binary) Term. 19 (binary 0000 1000) Term. 19 (binary) Term. 27 (binary 0001 0000) Term. 27 (binary) Term. 32 (binary 0010 0000) Term. 32 (binary) Term. 33 (binary 0100 0000) Term. 33 (binary)
16-35 Inverter Thermal
Parameter 534 Status word, binary 16-03 Status Word
Table 5.210 Conversion of Parameter 534
Parameter 535 Brake power/2 min 16-33 Brake Energy /2 min
Table 5.211 Conversion of Parameter 535
Parameter 536 Brake power/s 16-32 Brake Energy /s
Table 5.212 Conversion of Parameter 536
Parameter 537 Heat sink temp 16-34 Heatsink Temp.
Table 5.213 Conversion of Parameter 537
Parameter 538 Alarm word 14-72 Legacy Alarm Word
Table 5.214 Conversion of Parameter 538
Parameter
Table 5.215 Conversion of Parameter 539
Parameter 540 Warning word 14-73 Legacy Warning Word
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
539 VLT® Control word
VLT 5000 series FC 302 series
16-00 Control Word
Parameter 529 Analogue input 53 16-62 Analog Input 53
Table 5.205 Conversion of Parameter 529
Parameter 530 Analogue input 54 16-64 Analog Input 54
Table 5.206 Conversion of Parameter 530
Parameter 531 Analogue input 60 16-64 Analog Input 54
Table 5.207 Conversion of Parameter 531
Parameter 532 Pulse reference 16-51 Pulse Reference
Table 5.208 Conversion of Parameter 532
Parameter 533 External reference % 16-50 External Reference
Table 5.209 Conversion of Parameter 533
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
Table 5.216 Conversion of Parameter 540
Parameter 541 Extended status
Table 5.217 Conversion of Parameter 541
Parameter 553 Display text 1 Not converted
Table 5.218 Conversion of Parameter 553
Parameter 554 Display text 2 Not converted
Table 5.219 Conversion of Parameter 554
Parameter 557 Motor RPM 16-17 Speed [RPM]
Table 5.220 Conversion of Parameter 557
VLT 5000 series FC 302 series
14-74 Leg. Ext. Status
word
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
Word
36 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
Parameter Mapping Lists
Operating Instructions
Parameter 558 Motor RPM x scaling Not converted
Table 5.221 Conversion of Parameter 558
Parameter number
Table 5.222 Conversion of Parameter 580-582
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
580, 581, 582 Define parameter Not converted
5.7
VLT® 5000 Parameter Group 6
Parameter 600 Operating hours 15-00 Operating hours
Table 5.223 Conversion of Parameter 600
Parameter 601 Hours run 15-01 Running Hours
Table 5.224 Conversion of Parameter 601
Parameter 602 kWh counter 15-02 Input kWh Counter
Table 5.225 Conversion of Parameter 602
Parameter 603 Numbers of power up 15-03 Power Up's
Table 5.226 Conversion of Parameter 603
Parameter 604 Numbers of over temp. 15-04 Over Temp's
Table 5.227 Conversion of Parameter 604
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
5 5
Parameter 605 Numbers of over voltage 15-05 Over Volt's
Table 5.228 Conversion of Parameter 605
Parameter 606 Data log: Digital input Not converted
Table 5.229 Conversion of Parameter 606
Parameter 607 Data log: Bus commands Not converted
Table 5.230 Conversion of Parameter 607
Parameter 608 Data log: Status word Not converted
Table 5.231 Conversion of Parameter 608
Parameter 609 Data log: Reference Not converted
Table 5.232 Conversion of Parameter 609
Parameter 610 Data log: Feedback Not converted
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
Table 5.233 Conversion of Parameter 610
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 37
Parameter Mapping Lists
Operating Instructions
Parameter 611 Data log: Motor frequency Not converted
Table 5.234 Conversion of Parameter 611
Parameter 612 Data log: Motor voltage Not converted
Table 5.235 Conversion of Parameter 612
Parameter 613 Data log: Motor current Not converted
55
Table 5.236 Conversion of Parameter 613
Parameter 614 Data log: DC link voltage Not converted
Table 5.237 Conversion of Parameter 614
Parameter 615 Fault log: Error
Table 5.238 Conversion of Parameter 615
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
15-30 Alarm Log: Error
code
Code
Parameter 620 Operation mode 14-22 Operation Mode Options [0] Normal operation [0] Normal operation
Table 5.243 Conversion of Parameter 620
Parameter
Table 5.244 Conversion of Parameter 621
Parameter 622 Name plate: Power section Not converted
Table 5.245 Conversion of Parameter 622
Parameter
Table 5.246 Conversion of Parameter 623
VLT 5000 series FC 302 series
[1] Function with deactivated inverter [2] Control card test [2] Control card test [3] Initialisation [3] Initialisation
VLT 5000 series FC 302 series
621 Name plate: VLT® type
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
623 Name plate: VLT® ordering no.
Not supported
Not converted
Not converted
Parameter 616 Fault log: Time 15-32 Alarm Log: Time
Table 5.239 Conversion of Parameter 616
Parameter 617 Fault log: Value 15-31 Alarm Log: Value
Table 5.240 Conversion of Parameter 617
Parameter 618 Reset of kWh counter 15-06 Reset kWh Counter Options [0] No reset [0] Do not reset
Table 5.241 Conversion of Parameter 618
Parameter 619 Reset of Hours
Options [0] No reset [0] Do not reset
Table 5.242 Conversion of Parameter 619
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
[1] Reset [1] Reset counter
VLT 5000 series FC 302 series
15-07 Reset Running Hours
run
[1] Reset [1] Reset counter
Counter
Parameter 624 Name plate: Software version no. Not converted
Table 5.247 Conversion of Parameter 624
Parameter 625 Name plate: LCP ID no. Not converted
Table 5.248 Conversion of Parameter 625
Parameter 626 Name plate: Data base ID Not converted
Table 5.249 Conversion of Parameter 626
Parameter 627 Name plate: Power ID no. Not converted
Table 5.250 Conversion of Parameter 627
Parameter 628 Name plate: Application type Not converted
Table 5.251 Conversion of Parameter 628
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
Parameter 629 Name plate: Application type no. Not converted
Table 5.252 Conversion of Parameter 629
38 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
VLT 5000 series FC 302 series
Parameter Mapping Lists
Operating Instructions
Parameter 630 Name plate: Com. type Not converted
Table 5.253 Conversion of Parameter 630
Parameter 631 Name plate: Com. Type no. Not converted
Table 5.254 Conversion of Parameter 631
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
5.8
VLT® 5000 Parameter Group 7
Parameter 700 System control 8-02 Control Source
Options [0] Enable SyncPos Par. 8-02: [5] Option C0
Table 5.255 Conversion of Parameter 700
Parameter 701 Program
Options -1 – 127 -1 – 127
Table 5.256 Conversion of Parameter 701
Parameter 702 PID Proportional factor 32-60 Proportional factor Options 0 – 65000 0 – 100000
VLT 5000 series FC 302 series
33-82 Drive Status Monitoring
Par. 33-82: [1] On [1] Disable SyncPos Par. 8-02: [1] FC RS-485 [2] Enable SyncPos without VLT monitoring
VLT 5000 series FC 302 series
number
VLT 5000 series FC 302 series
Par. 8-02: [5] Option C0
Par. 33-82: [0] Off
33-80 Activated Program Number
5 5
Table 5.257 Conversion of Parameter 702
Parameter 703 PID Derivative
Options 0 – 65000 0 – 100000
Table 5.258 Conversion of Parameter 703
Parameter 704 PID Integral factor 32-62 Integral factor Options 0 – 65000 0 – 100000
Table 5.259 Conversion of Parameter 704
Parameter 705 PID Integral
Options 0 – 1000 0 – 1000
Table 5.260 Conversion of Parameter 705
Parameter 706 PID Active bandwidth 32-64 PID Bandwidth Options 0 – 65000 0 – 1000
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
bandwidth
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
32-61 Derivative
factor
factor
32-63 Limit Value for Integral Sum
Table 5.261 Conversion of Parameter 706
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 39
Parameter Mapping Lists
Operating Instructions
Parameter 707 PID Velocity Feed-
Options 0 – 65000 0 – 100000
Table 5.262 Conversion of Parameter 707
Parameter 708 PID Acceleration
Options 0 – 65000 0 – 100000
55
Table 5.263 Conversion of Parameter 708
Parameter 709 PID Velocity filter 33-26 Velocity Filter Options -500000 – 500000 -1073741824 – 107374203
Table 5.264 Conversion of Parameter 709
Parameter 710 - 779 19-10 -19-79 Options User defined User defined
Table 5.265 Conversion of Parameters 710 to 779
Parameter 780 Dead time compensation Not supported Options [0] Off
Table 5.266 Conversion of Parameter 780
Parameter 781 Program ID Not supported Options 0 – 65000
Table 5.267 Conversion of Parameter 781
Parameter 795 - 799 User defined
Options User defined User defined
Table 5.268 Conversion of Parameters 795 to 799
VLT 5000 series FC 302 series
32-65 Velocity Feed-
forward
VLT 5000 series FC 302 series
Feed-forward
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
[1] On
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
(read only)
Forward
32-66 Acceleration Feed­Forward
19-95 -19-99 User defined (read only)
5.9
VLT® 5000 Parameter Group 8
Parameter 801 Baud rate selection Not converted
Table 5.269 Conversion of Parameter 801
Parameter 802 Minimum station delay Not converted
Table 5.270 Conversion of Parameter 802
Parameter 803 Time out after bus
Range 1 – 99 0.1 – 18000.0
Table 5.271 Conversion of Parameter 803
Parameter 804 Response after bus
Range [0] Off [0] Off
Table 5.272 Conversion of Parameter 804
Parameter 805 Function of control word
Range [0] No function [0] None [1] Bit 10 = 1 => CTW active [1] Profile default [2] Bit 10 = 0 => CTW active [2] CTW Valid, active
[3] Bit 10 = 1 => Time out [1] Profile default
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
8-03 Control Timeout
error
VLT 5000 series FC 302 series
time out
[1] Freeze output frequency [2] Stop [2] Stop [3] Jogging [3] Jogging [4] Max speed [4] Max speed [5] Stop and trip [5] Stop and trip [6] No com. option control [7] Select set up 4 [10] Select set up 4
VLT 5000 series FC 302 series
bit 10
Time
8-04 Control Timeout Function 8-02 Control Word Source
[1] Freeze output frequency
Par. 802 to RS485
8-14 Configurable Control Word CTW
low
Table 5.273 Conversion of Parameter 805
40 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
Parameter Mapping Lists
Operating Instructions
5.10
VLT® 5000 Parameter Group 9
Parameter 904 PPO type select for DP Not converted
Table 5.274 Conversion of Parameter 904
Parameter 915 PCD config write 9-15 PCD Write Configu-
Options [0] None [0] None
Comments
Table 5.275 Conversion of Parameter 915
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
ration
[204] Minimum Reference [302] Minimum Reference [205] Maximum Reference [219] Catch up/slow Down Value [207] Ramp 1 Ramp up Time [208] Ramp 1 Ramp Down Time [209] Ramp 2 Ramp up Time [210] Ramp 2 Ramp down Time [211] Jog Ramp Time [380] Jog Ramp Time [212] Quick Stop Ramp Time [201] Motor Low Limit [Hz] [202] Motor High Limit [Hz] [221] Torque Limit Motor Mode [222] Torque Limit Generator Mode [509] Bus Jog 1 Speed [890] Bus Jog 1 Speed [510] Bus Jog 2 Speed [891] Bus Jog 2 Speed VLT® 5000 supports more write signals. If a not­supported signal is written then the corresponding signal is set to [0] None.
[203] Maximum Reference
[312] Catch up/slow Down Value [341] Ramp 1 Ramp up Time [342] Ramp 1 Ramp Down Time [351] Ramp 2 Ramp up Time [352] Ramp 2 Ramp down Time
[381] Quick Stop Ramp Time [412] Motor Speed Low Limit [Hz] [414] Motor Speed High Limit [Hz] [416] Torque Limit Motor Mode [417] Torque Limit Generator Mode
Parameter 916 PCD config read 9-16 PCD Read Configu-
Options [0] None [0] None
Table 5.276 Conversion of Parameter 916
Parameter 918 Station address 10-02 MAC ID Range 0 - 63 0 - 63
VLT 5000 series FC 302 series
ration
[538] Alarm word [1472] VLT Alarm Word [540] Warning word [1473] VLT Warning Word [541] Ext. status word [1474] VLT Ext. status
Word [600] Operating hours [1500] Operating hours [601] Running hours [1501] Running hours [602] kWh Counter [1502] kWh Counter [539] Control word [1600] Control word [516] Reference [Unit] [1601] Reference [Unit] [515] Reference % [1602] Reference % [534] Status word [1603] Status word [522] Power [kW] [1610] Power [kW] [523] Power [HP] [1611] Power [HP] [524] Motor voltage [1612] Motor voltage [518] Motor frequency [1613] Motor frequency [520] Motor current [1614] Motor current [557] Motor RPM [1617] Motor speed [526] Motor thermal [1618] Motor thermal [521] Torque [1622] Torque % [525] DC link voltage [1630] DC link voltage [536] Brake energy/s [1632] Brake energy/s [535] Brake energy/2 min [1633] Brake energy/2 min [537] Heat sink temp. [1634] Heat sink temp. [527] Inverter Thermal [1635] Inverter Thermal [533] External reference [1650] External reference [532] Pulse reference [1651] Pulse reference [517] Feedback [Unit] [1652] Feedback [Unit] [528] Digital input [1660] Digital input [529] Analog input 53 [1662] Analog input 53 [530] Analog input 54 [1664] Analog input 54 [531] Analog input 60 [1664] Analog input 54
VLT 5000 series FC 302 series
5 5
Table 5.277 Conversion of Parameter 918
Parameter 927 Parameter edit 9-27 Parameter Edit Options [0] Disable [0] Disable
Table 5.278 Conversion of Parameter 927
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 41
VLT 5000 series FC 302 series
[1] Enable [1] Enable
Parameter Mapping Lists
Operating Instructions
Parameter 928 Control authority 9-28 Process Control Options [0] Disable [0] Disable
Table 5.279 Conversion of Parameter 928
Parameter 953 Warning parameter 9-53 Profibus Warning Word
Table 5.280 Conversion of Parameter 953
55
Parameter 967 Control word Not converted
Table 5.281 Conversion of Parameter 967
Parameter 968 Status word Not converted
Table 5.282 Conversion of Parameter 968
Parameter 970 Parameter set-up selection 9-70 Edit Set-up Options [0] Factory setting [0] Factory setting
VLT 5000 series FC 302 series
[1] Enable [1] Enable cyclic master
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
[1] Parameter setup 1 [1] Parameter setup 1 [2] Parameter setup 2 [2] Parameter setup 2 [3] Parameter setup 3 [3] Parameter setup 3 [4] Parameter setup 4 [4] Parameter setup 4 [5] Active setup [9] Active setup
Table 5.283 Conversion of Parameter 970
Parameter 971 Save data values 9-71 Profibus Save Data Values Options Unsigned 8 (5) Unsigned 8 (5)
Table 5.284 Conversion of Parameter 971
Parameter 980, 981, 982, 990 Modified
Table 5.285 Conversion of Parameter 980-990
VLT 5000 series FC 302 series
[0] Not active [0] Off [1] Save active setup [1] Store all setups [2] Save edit setup [1] Store all setups [3] Save all setups [1] Store all setups
VLT 5000 series FC 302 series
Not converted
parameters
42 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
Troubleshooting
Operating Instructions
6 Troubleshooting
6.1 Step-by-step Troubleshooting
1.
Copy the station address from the VLT® 5000 to the VLT® AutomationDrive.
2. Cycle power to the FC 302.
3.
The master/PLC now recognises FC 302 as a VLT
5000.
4. The NS LED on the MCA 194 option is now solid green indicating that communication between master and slave is established.
If the NS LED flashes, the master/PLC has not recognised the FC 302 action:
Check if station address is the same in the FC 302
as the replaced VLT® 5000. Check 10-01 Baud Rate Select. If the frequency
converter has no connection to the master, this parameter may be set to the wrong baudrate.
Check 10-13 Warning Parameter.
®
6 6
Bit
Table 6.1 Warning Word
Warn. Word
[Hex]
0 0001 Bus not active 1 0002 Explicit connection timeout 2 0004 I/O connection 3 0008 Retry limit reached 4 0010 Actual value is not updated 5 0020 CAN bus off 6 0040 I/O send error 7 0080 Initialisation error 8 0100 No bus supply
9 0200 Bus off 10 0400 Error passive 11 0800 Error warning 12 1000 Duplicate MAC ID Error 13 2000 RX queue overrun 14 4000 TX queue overrun 15 8000 CAN overrun
Check chapter 1.4 Constraints for more
information on limitations.
Description
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 43
Index Operating Instructions
Index
A
Abbreviation............................................................................................. 5
Additional resources.............................................................................. 3
B
Brake resistor............................................................................................ 3
C
Commissioning..................................................................................... 12
Configuration........................................................................................... 3
Constraint.................................................................................................. 3
D
DIP switch................................................................................................ 11
T
Terminal...................................................................................................... 4
Troubleshooting................................................................................... 43
W
Warning word........................................................................................ 43
E
EMC precautions................................................................................... 10
H
Hardware.................................................................................................... 4
High voltage............................................................................................. 6
I
Installation................................................................................................. 8
L
LED............................................................................................................. 12
Linked set-up............................................................................................ 5
Literature.................................................................................................... 3
M
MCA 194................................................................................................... 43
Mechanical installation......................................................................... 9
P
Parameter (mapping list)................................................................... 14
Performance............................................................................................. 5
Power size.................................................................................................. 3
Product overview.................................................................................... 3
Q
Qualified personnel................................................................................ 6
S
Set-up, linked............................................................................................ 5
44 Danfoss A/S © Rev. 2014-03-06 All rights reserved. MG37E102
Index Operating Instructions
MG37E102 Danfoss A/S © Rev. 2014-03-06 All rights reserved. 45
www.danfoss.com/drives
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss A/S Ulsnaes 1 DK-6300 Graasten www.danfoss.com/drives
130R0577 MG37E102 Rev. 2014-03-06
*MG37E102*
Loading...