Danfoss MCA 123 POWERLINK Operating Instructions Manual

Safety
Copyright, Limitation of Liability and Revision Rights
This publication contains information proprietary to Danfoss. By accepting and using this manual, the user agrees that the information contained herein is used solely for operating equipment from Danfoss or equipment from other vendors if such equipment is intended for communi­cation with Danfoss equipment over a serial communication link. This publication is protected under the Copyright laws of Denmark and most other countries.
Danfoss does not guarantee that a software program produced according to the guidelines provided in this manual functions properly in every physical, hardware, or software environment.
Although Danfoss has tested and reviewed the documen­tation within this manual, Danfoss gives no warranty or representation, either expressed or implied, with respect to this documentation. This includes its quality, performance, or fitness for a particular purpose.
In no event shall Danfoss be liable for direct, indirect, special, incidental, or consequential damages arising out of the use, or the inability to use information contained in this manual, even if advised of the possibility of such damages. In particular, Danfoss is not responsible for any costs including, but not limited to those incurred as a result of lost profits or revenue, loss or damage of equipment, loss of computer programs, loss of data, the costs to substitute these, or any claims by third parties.
Danfoss reserves the right to revise this publication at any time and to change its contents without prior notice or any obligation to notify previous users of such revisions or changes.
It has been assumed that all devices are sitting behind a firewall that does packet filtering and the environment has implemented restrictions on the software that can run inside the firewall. All nodes are assumed to be "trusted" nodes.
Safety Note
WARNING
HIGH VOLTAGE
The voltage of the frequency converter is dangerous whenever connected to mains. Incorrect installation of the motor, frequency converter, or fieldbus may damage the equipment, cause serious personal injury, or death. Consequently, the instructions in this manual, as well as national and local rules and safety regulations, must be complied with.
Safety Regulations
1. The frequency converter must be disconnected from mains before carrying out repair work. Check that the mains supply has been discon­nected and that the necessary time has passed before removing motor and mains plugs.
2. The off-command on the serial bus does not disconnect the equipment from mains and should not be used as a safety switch.
3. Correct protective earthing or grounding of the equipment must be established. The user must be protected against supply voltage, and the motor must be protected against overload in accordance with applicable national and local regulations.
4. The earth leakage currents are higher than 3.5 mA.
5. Do not remove the plugs for the motor and mains supply while the frequency converter is connected to mains. Check that the mains supply has been disconnected and that the necessary time has passed before removing motor and mains plugs.
Warning against Unintended Start
1. The motor can be brought to a stop with bus commands while the frequency converter is connected to mains. If personal safety consider­ations make it necessary to ensure that no unintended start occurs, these stop functions are not sufficient.
2. While parameters are being changed, there is a risk that motor starts.
Safety MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark
3. A motor that has been stopped, can start if faults occur in the electronics of the frequency converter, or if a temporary overload, or a fault in the supply mains, or the motor connection ceases.
WARNING
ELECTRICAL HAZARD
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains.
Safety MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark
Contents
1 Introduction
3
1.1.1 About this Manual 3
1.1.2 Assumptions 3
1.1.3 Hardware 3
1.1.4 Background Knowledge 3
1.1.5 Available Literature 3
1.1.6 Abbreviations 4
2 How to Install
5
2.1 Installation
5
2.1.1 How to Install Option in Frequency Converter 5
2.1.2 Network 5
2.1.3 POWERLINK Cables 6
2.1.4 LED Behaviour 6
2.1.5 Topology 8
2.1.6 EMC Precautions 9
3 How to Configure
10
3.1.1 IP Settings 10
3.1.2 Ethernet Link Parameters 10
3.2 Configure the Frequency Converter
10
3.2.1 VLT Parameters 10
3.3 Configure the POWERLINK Network
10
4 Configure the Master
11
4.1 Importing the XDD File
11
4.2 Setting Up the Master
11
5 How to Control the Frequency Converter
14
5.1 PDO Communication
14
5.2 Process Data
14
5.2.1 Process Control Data 14
5.2.2 Process Status Data 14
5.2.3 Reference Handling 15
5.2.4 Process Control Operation 15
5.2.5 Influence of the Digital Input Terminals upon FC Control Mode 16
5.3 Control Profile
16
5.4 Danfoss FC Control Profile
16
5.5 DS 402 Control Profile
19
5.5.1 Control Word According to DSP 402 Profile (Parameter 8-10=DSP 402 profile) 19
Contents MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 1
5.5.2 Status Word According to DS 402 Profile 20
5.5.3 DSP 402 State Transitions 22
5.5.4 Status Word According to DS 402 Profile 23
6 Communication Profile Area
24
6.1 Description - Communication Profile Area
24
6.2 1000-1FFF Communication Object Area
24
6.3 2000-5FFF Danfoss Specific Object Area
30
6.4 6000-Device profile Object Area
30
7 Parameters
33
7.1 Parameter Group 8-** Communication and Option
33
7.2 Parameter Group 12-** Ethernet
37
7.3 POWERLINK - Specific Parameter List
40
8 Application Examples
42
8.1 Example: Process Data with PDO 23
42
8.2 Example: Simple Control Word, Reference, Status Word and Main Actual Value
44
9 Troubleshooting
45
9.1.1 LED Status 45
9.1.2 No Communication with the Frequency Converter 46
9.1.3 Warning 34 Appears even though Communication is Established 47
9.1.4 Frequency Converter Does Not Respond to Control Signals 47
9.1.5 Alarm and Warning Words 49
Index
51
Contents MCA 123 POWERLINK Operating Instructions
2 MG92C102 - VLT® is a registered Danfoss trademark
1 Introduction
1.1.1 About this Manual
First time users can obtain the most essential information for quick installation and set-up in these chapters:
1 Introduction 2 How to Install 3 How to Configure
For more detailed information, including the full range of set-up options and diagnosis tools, refer to the chapters:
4 Configure the Master 5 How to Control the Frequency Converter 7 Parameters 8 Application Examples 9 Troubleshooting
Terminology In this manual the term Ethernet is used to describe the physical layer of the network and does not relate to the application protocol.
1.1.2
Assumptions
These operating instructions are under the conditions that the Danfoss POWERLINK option is used with a Danfoss VLT® AutomationDrive FC 301/FC 302 frequency converter. The installed controller must support the interfaces described in this document. Strictly observe all the requirements stipulated in the controller and the frequency converter, along with all limitations herein.
1.1.3
Hardware
This manual relates to the POWERLINK option MCA 123, type no. 130B5546 (uncoated) and 130B5646 (conformal coated).
1.1.4
Background Knowledge
The Danfoss POWERLINK Option Card is designed to communicate with any system complying with the POWERLINK standard. Familiarity with this technology is assumed. Issues regarding hardware or software produced by other manufacturers, including commissioning tools, are
beyond the scope of this manual, and not the responsi­bility of Danfoss.
For information regarding commissioning tools, or communication to a non-Danfoss node, consult the appropriate manuals.
1.1.5 Available Literature
Available Literature for FC 301/FC 302
-
The VLT® AutomationDrive Operating Instructions provide the necessary information for getting the frequency converter up and running.
-
The VLT® AutomationDrive Design Guide entails all technical information about the frequency converter design and applications including encoder, resolver, and relay options.
-
The VLT
®
AutomationDrive Profibus Operating
Instructions provide the information required for
controlling, monitoring, and programming the frequency converter via a Profibus fieldbus.
-
The VLT® AutomationDrive DeviceNet Operating Instructions provide the information required for controlling, monitoring, and programming the frequency converter via a DeviceNet fieldbus.
-
The VLT® AutomationDrive MCT 10 Set-up Software Operating Instructions provide information for installation and use of the software on a PC.
-
The VLT® AutomationDrive IP21/Type 1 Instruction provides information for installing the IP21/Type 1 option.
-
The VLT® AutomationDrive 24 V DC Backup Instruction provides information for installing the 24 V DC Backup option.
-
The VLT® AutomationDrive CanOpen Operating Instructions.
-
The VLT® AutomationDrive Modbus TCP Operating Instructions.
-
The MCA 121 EtherNet/IP Operating Instructions.
-
The MCA 120 PROFINET Operation Instructions.
-
The MCA 124 EtherCAT Operation Instructions.
-
The MCA 123 Modbus TCP Operation Instructions.
Danfoss technical literature is also available online at http://www.danfoss.com/BusinessAreas/DrivesSolutions/
Introduction MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 3
1 1
1.1.6 Abbreviations
Abbre­viation
Definition
API Actual Packet Interval ASnd AsynchronousSend CC Control Card CTW Control Word DCP Discovery and Configuration Protocol DHCP Dynamic Host Configuration Protocol Configuration EMC Electromagnetic Compatibility I/O Input/Output IP Internet Protocol PDO Process Data Object LCP Local Control Panel LED Light Emitting Diode LSB Least Significant Bit MAV Main Actual Value (actual output) MN Managing Node MSB Most Significant Bit MRV Main Reference Value N/A Not applicable PC Personal Computer PCD Process Control Data PLC Programmable Logic Controller PNU Parameter Number REF Reference (=MRV) SDO Service Data Object SoC Start Of Cycle Frame SoA Start Of Asynchronous STW Status Word
Table 1.1 Overview of Abbreviations
Introduction MCA 123 POWERLINK Operating Instructions
4 MG92C102 - VLT® is a registered Danfoss trademark
11
2 How to Install
2.1 Installation
2.1.1 How to Install Option in Frequency Converter
Items required for installing a fieldbus option in the frequency converter
The fieldbus option
Fieldbus option adaptor frame for the FC Series. This frame is deeper than the standard frame to allow space for the fieldbus option beneath
Strain relief (only for A1 and A2 enclosures)
EtherNet Port1
EtherNet Port2
MCA 121 Option A EtherNet/IP 130B1119 MS MS1 MAC-00-1B-08-00-00-22 MS2 SW.ver.
130BT797.10
Illustration 2.1 Fieldbus Option Adaption Frame
Illustration 2.2 Strain Relief for A1 and A2 Enclosures
Instructions
1. Remove LCP panel from the FC Series.
2. Remove the frame located beneath and discard it.
3. Push the option into place. The Ethernet connectors must be facing upwards.
4. Remove knock-out on the fieldbus option adaptor frame.
5. Push the fieldbus option adaptor frame for the FC Series into place.
6. Replace the LCP and attach cable.
NOTE
Do not strip and ground the Ethernet cable via the strain relief-plate! The grounding of screened Ethernet cable is done through the RJ-45 connector on the option.
NOTE
After installing the MCA 123 POWERLINK option, set
8-01 Control Site to: [2] Control word only or [0] Digital and ctrl. word. 8-02 Control Word Source to: [3] Option A
2.1.2 Network
It is important that the media chosen for Ethernet data transmission meets the required properties. Usually CAT 5e and six cables are recommended for industrial applications. Both types are available as Unshielded Twisted Pair and Shielded Twisted Pair. Generally, shielded cables are recommended for use in industrial environments and with frequency converters. A maximum cable-length of 100 m is allowed between network devices.
How to Install MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 5
2
2
2.1.3 POWERLINK Cables
Cable type Specification Ethernet standard Standard Ethernet (in accordance with IEEE
802.3), 100Base-TX (Fast Ethernet)
Cable Type S/FTP (Screened Foiled Twisted Pair, ISO (IEC
11801 or EN 50173), CAT 5e Damping 23.2 dB (at 100 MHz and 100 m each) Crosstalk damping 24 dB (at 100 MHz and 100 m each) Return loss 10 dB (100 m each) Surge impedance
100 Ω
Table 2.1 Specification of POWERLINK Cables
2.1.4 LED Behaviour
The option has 3 bicolored LEDs that allow a fast and detailed diagnosis. The three LEDs are each linked to its unique part of the POWERLINK option:
LED label Description Status/Error Module Status, reflects the activity on the
POWERLINK slave. Link/Collision Port 1
Link/Collision Port 1, reflects the activity on the
POWERLINK port 1. Link/Collision Port 2
Link/Collision Port 2, reflects the activity on the
POWERLINK port 2.
Table 2.2 LEDs
MCA123 POWERLINK
SW. ver. TM. ver.
S/E LED
L/C LED P1
L/C LED P2
Port 1 Port 2
Option A 130B1489
MAC 00-1B-08-00-00-00
Address
8 7 6 5 4 3 2 1
ON OFF
Powerlink Port 1 Powerlink Port2
Status/error Link/Collision Port 1
Link/Collision Port 2
130BD146.10
Illustration 2.3 Overview of the Option
How to Install MCA 123 POWERLINK Operating Instructions
6 MG92C102 - VLT® is a registered Danfoss trademark
2
S/E LED
Power OFF or state LED NMT_GS NMT_GS_INITIALISATION NMT_CS_NOT_ACTIVE NMT_MS_NOT_ACTIVE
Green:
Device Operational Green:
Flickering NMT_CS_BASIC_ETHERNET Green:
Blinking NMT_CS_Stopped Green:
Single flash NMT_CS_PRE_OPERATIONAL_1 NMT_MS_PRE_OPERATIONAL_1
Green:
Double flash NMT_CS_PRE_OPERATIONAL_2 NMT_MS_PRE_OPERATIONAL_2
Green:
Triple flash NMT_CS_READY_TO_OPERATE NMT_MS_READY_TO_OPERATE
Green:
Table 2.3 Behaviour of S/E Leds
L/C LED
Power OFF or NO Link Green:
Link Green:
Table 2.4 Behaviour of L/C LEDs
How to Install MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 7
2
2
2.1.5 Topology
The POWERLINK module features a built-in POWERLINK slave controller and a two port HUB. This module enables the possibility for connecting several POWERLINK options in a line topology. If more than eight frequency converters are connected in line, it will require special attention towards the timing in the network.
It is important in a POWERLINK system, that the connection is done correctly. POWERLINK is based on HUB
technology, which means that connecting a none POWERLINK device (for example, personal computer) leads to malfunction of the system.
NOTE
Do not connect any non-POWERLINK device to any free port as this causes malfunction of the complete POWERLINK network.
130BD147.10
Illustration 2.4 Line Topology
Take care that following design rules are followed
1. Do not connect any non POWERLINK device (for example PC) to any free port as this will cause malfunction of the complete POWERLINK network.
2. In a line topology all frequency converters must be powered, either by mains or by a 24 V DC option cards, for the built-in POWERLINK slave controller to work.
3. To achieve interference-free operation of the Ethernet, observe the following EMC precautions. The correct handling of the motor cable shield is vital for the overall performance of the system. If the rules are not followed it will lead to loss of the control and malfunction of the system. The Ethernet communication cable must be kept away from motor and brake resistor cables to avoid coupling of high frequency noise between the cables. Normally, a minimum distance of 200 mm (8 inches) is sufficient, but maintaining the greatest possible distance between the cables is
How to Install MCA 123 POWERLINK Operating Instructions
8 MG92C102 - VLT® is a registered Danfoss trademark
2
recommended, especially where cables run in parallel, over long distances, or if drives with a bigger power size is installed. More information can be found in the norm IEC 61000-5-2:1997.
4. When crossing of cables is unavoidable, the Ethernet cable must cross motor and brake resistor cables at an angle of 90°.
5. Always observe relevant national and local regulations, for example regarding protective earth connection.
NOTE
In a line topology all frequency converters must be powered, either by mains or by their 24 V DC option cards, for the built-in POWERLINK slave controller to work.
2.1.6 EMC Precautions
To achieve interference-free operation of the Ethernet, observe the following EMC precautions. Additional EMC information is available in the VLT
®
AutomationDrive Design
Guide.
NOTE
The correct handling of the shield of the motor cable is vital for the overall performance of the system. If the rules are not followed it can lead to loss of the control and malfunction of the system.
NOTE
Always observe relevant national and local regulations, for example regarding protective earth connection.
The Ethernet communication cable must be kept away from motor and brake resistor cables to avoid coupling of high frequency noise between the cables. When crossing is unavoidable, the Ethernet cable must cross motor and brake resistor cables at an angle of 90°.
min. 200 mm
90 ° crossing
Ethernet Cable
130BA908.11
Illustration 2.5 Correct Crossing of Ethernet Cable
How to Install MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 9
2
2
3 How to Configure
3.1.1 IP Settings
All IP-related parameters are located in parameter group 12-0* IP Settings: The parameters are all set to POWERLINK standard values, so no setting is needed. In POWERLINK, the 12-00 IP Address Assignment is fixed to the selection "From node ID". The IP address does follow the setting in 12-60 Node ID, so that the IP address is 192.168.100.xxx, where xxx is the node ID. For 12-02 Subnet Mask, this will be fixed to 255.255.255.0 and can not be changed.
The POWERLINK option offers two ways of IP address assignment via parameter or DIP switch.
3.1.2
Ethernet Link Parameters
Parameter group 12-1* Ethernet Link Parameters holds Ethernet Link information:
12-10 Link Status 12-11 Link Duration 12-12 Auto Negotiation 12-13 Link Speed 12-14 Link Duplex
Each port has unique Ethernet Link Parameters.
12-10 Link Status displays Link or No Link according to the status of the present port.
12-11 Link Duration displays the duration of the link on the present port. If the link is broken, the counter is reset.
12-12 Auto Negotiation is a feature that enables two connected Ethernet devices to choose common transmission parameters, such as speed and duplex mode. In POWERLINK this feature is fixed to OFF and can not be changed.
12-13 Link Speed - displays the link speed for each port. If no link is present, “None” is displayed. In POWERLINK this feature is fixed to 100 MBaud and can not be changed.
12-14 Link Duplex - displays the duplex mode for each port. In POWERLINK, the Link Duplex is fixed to half Duplex, and cannot be changed.
3.2
Configure the Frequency Converter
3.2.1 VLT Parameters
Pay particular attention to the following parameters when configuring the frequency converter with a fieldbus interface.
0-40 [Hand on] Key on LCP. If the [Hand on] key on the frequency converter is activated, control of the frequency converter via the fieldbus interface is disabled.
After an initial power up, the frequency converter automatically detects whether a fieldbus option is installed in slot A, and sets 8-02 Control Word Source to [Option A]. Adding, changing, or removing an option from an already commis­sioned frequency converter does not change 8-02 Control Word Source. However, it causes a Trip Mode, and the frequency converter displays an error.
8-10 Control Word Profile. Choose between the Danfoss FC Profile and the DS 402 profile. The change of 8-10 Control Word Profile will first be active at the next powerup.
8-50 Coasting Select to 8-56 Preset Reference Select. Selection of how to gate fieldbus control commands with digital input command of the control card.
NOTE
When 8-01 Control Site is set to [2] Control word only, the settings in 8-50 Coasting Select to 8-56 Preset Reference Select are overruled, and all act on Bus-control.
8-03 Control Word Timeout Time to 8-05 End-of­Timeout Function. The reaction in the event of a
bus time-out is set via these parameters.
3.3
Configure the POWERLINK Network
All POWERLINK stations that are connected to the same bus network must have a unique Node ID. The Node ID of the frequency converter can be selected via:
Hardware switches (from version 2.00)
12-60 Node ID
How to Configure MCA 123 POWERLINK Operating Instructions
10 MG92C102 - VLT® is a registered Danfoss trademark
33
4 Configure the Master
4.1 Importing the XDD File
To configure a POWERLINK Master, the configuration tool needs an XDD file for each type of slave on the network. The XDD file is a text file containing the necessary communications setup data for a slave. Download the XDD file for the FC Series frequency converters at http:// www.danfoss.com/BusinessAreas/DrivesSolutions/.
15-61 Option SW Version File
1.x FC 301: 0x0200008D_FC301_01.xdd FC 302: 0x0200008D_FC302_01.xdd
Table 4.1 POWERLINK SW Version XDD File
The following steps show how to add a new device to the Automation Studio Tool. For tools from other vendors, consult their relevant manuals.
1. In the Automation Studio, select the menu [Tools] and [Import Fieldbus Device].
130BD136.10
Illustration 4.1 Automation Studio
2. Select the XDD file and the Automation studio, imports it to its library. Use the [Save All] menu or the multiple floppy disc icon to save the new info.
130BD139.10
Illustration 4.2 Selecting the XDD File
4.2 Setting Up the Master
Select the POWERLINK I/O master to open the POWERLINK interface in the Automation Studio Master.
1. Right click and select [Open POWERLINK].
130BD137.10
Illustration 4.3 Open POWERLINK
2. Right click the network icon, and select [Insert].
130BD140.10
Illustration 4.4 Physical View
Configure the Master MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 11
4 4
3. Select [Danfoss FC 302].
130BD145.10
Illustration 4.5 Select Controller Module
Danfoss FC Series is inserted in the POWERLINK master system.
4. Configure the I/O configuration, right click on the Danfoss Icon and select [Open I/O Configuration].
130BD142.10
Illustration 4.6 I/O Configuration
5. By default the POWERLINK option does not have any process data assigned to its I/O mapping. This is done by selecting the channels (FC Parameter) as read or write. By selection the [+] sign in front of the channel menu, the list is expanded and the parameters can be selected. In this example following has been selected:
Object 2690 fieldbus control word 1
Object 2692 fieldbus reference 1
Object 2643 status word
Object 2645 main actual value
130BD141.10
Illustration 4.7 Select Parameters
NOTE
Make sure that maximum ten channels are selected in each direction; or the PLC enters into an endless restart of the network.
6. The POWERLINK configuration does now contain the Danfoss FC Series frequency converter as its slave and communicates with the four words. The final step is to map the I/Os to PLC variables, which is done in the I/O mapping. This is selected via a right click on the [Danfoss FC 302] icon and select [Open I/O Mapping].
130BD142.10
Illustration 4.8 Mapping the I/Os ot the PLC Variables
The mapping can now be done directly to previous defined variables.
Configure the Master MCA 123 POWERLINK Operating Instructions
12 MG92C102 - VLT® is a registered Danfoss trademark
44
130BD143.10
Illustration 4.9 Previous Defined Variables
Variables can also be directly declared, via selecting the Channel Name for each signal and enter the attributes directly.
130BD144.10
Illustration 4.10 Variables Directly Declared
This does insert the Danfoss FC 302 into the B&R system, and the frequency converter can now be controlled and supervised via the POWERLINK.
Configure the Master MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 13
4 4
5 How to Control the Frequency Converter
5.1 PDO Communication
The VLT® AutomationDrive uses the following profiles:
Frequency converter profiles
CANopen DS 402 profile
For each of the two profiles there is a set of SDO objects that is only accessible if the profile is activated in 8-10 Control Word Profile. The change will first be active at the next power up. The PDO communication has to be configured, where a subset of SDOs can be mapped into PDOs for cyclic communication.
PDO communication is reserved for high speed cyclic access to parameters for control and status of the frequency converter. The PLC sends out process control data, and the frequency converter responds with a PDO containing process status data. In the Danfoss POWERLINK interface both PDOs can be freely be configured.
Select the signals for transmission from the master to the frequency converter via the PLCs configuration tool.
12-21 Process Data Config Write, 12-22 Process Data Config Read and 12-23 Process Data Config Write Size will be set
from the PLC and can be used to control if the configu­ration has been sent correctly from the PLC.
The POWERLINK option has only one PDO available: PDO
23. The PDO 23 is flexible in size and is adjustable to fit all needs (max. 10 PCDs). The selection is made in the master configuration and is then automatically downloaded to the frequency converter during the transition from Init to Pre­Op. No manual setting of PPO types in the frequency converter is required.
Selection [1] Standard telegram 1 is equivalent to PDO 23.
Receive PDOs (PLC
Drive)
Transmit PDOs (Drive PLC)
PCD 9
write
PDO 23
PCD 0
CTW
PCD 1
REF
PCD 9
read
PCD 0
STW
PCD 1
MAV
PDO 23
130BC177.10
Illustration 5.1 Standard Telegram
5.2 Process Data
Use the process data part of the PDO for controlling and monitoring the frequency converter via the POWERLINK.
5.2.1 Process Control Data
The example in Table 5.1 shows control and reference sent from the PLC to the frequency converter, and status word and main actual value sent from the frequency converter to the PLC.
Master to slave
0 1 2 ...... 9
CTW MRV PCD ...... PCD
PCD write
Table 5.1 Process Control Data (PCD)
PCD 0 contains a 16-bit control word where each bit controls a specific function of the frequency converter, see
5.3 Control Profile. PCD 1 contains a 16-bit speed set point in percentage format. See 5.2.3 Reference Handling.
The content of PCD 2 to PCD 9 is read only.
5.2.2
Process Status Data
Process data sent from the frequency converter contain information about the current state of the frequency converter.
Slave to master
0 1 2 ...... 9
STW MAV PCD ...... PCD
PCD read
Table 5.2 Process Status Data
PCD 0 contains a 16-bit status word where each bit contains information regarding a possible state of the frequency converter. PCD 1 contains per default the value of the current speed of the frequency converter in percentage format (see
5.2.3 Reference Handling).
How to Control the Frequenc... MCA 123 POWERLINK Operating Instructions
14 MG92C102 - VLT® is a registered Danfoss trademark
5
5.2.3 Reference Handling
The reference handling in FC Series is an advanced mechanism that sums up references from different sources.
For more information on reference handling, refer to the FC Series Design Guide.
Illustration 5.2 Reference Handling
The reference, or speed set point (MRV, sent via POWERLINK), is always transmitted to the frequency converter in percentage format as integers represented in hexadecimal (0-4000 hex).
Depending on the setting of 3-00 Reference Range the reference and MAV are scaled accordingly:
Illustration 5.3 Scaling of MAV and Reference
NOTE
If 3-00 Reference Range is set to [0] Min - Max, a negative reference is handled as 0%.
The speed limit settings are depending on 0-02 Motor
Speed Unit and can be set to RPM or Hz. If 0-02 Motor Speed Unit is set to RPM: The speed limit parameters 4-11 Motor Speed Low Limit [RPM] and 4-13 Motor Speed High Limit [RPM] limit the actual frequency converter
output. If 0-02 Motor Speed Unit set to Hz: The speed limit parameters 4-12 Motor Speed Low Limit [Hz] and 4-14 Motor
Speed High Limit [Hz]
limit the actual frequency converter
output.
4-19 Max Output Frequency limits the maximum output and can also influence the maximum speed of the motor.
For reference and MAV formats, see Table 5.3.
MRV/MAV Integer in hex Integer in decimal
100% 4000 16.384
75% 3000 12.288 50% 2000 8.192 25% 1000 4.096
0% 0 0
-25% F000 -4.096
-50% E000 -8.192
-75% D000 -12.288
-100% C000 -16.384
Table 5.3 Reference and MAV Formats
NOTE
Negative numbers are formed as a complement of two.
NOTE
The data type for MRV and MAV is 16-bit standardised value, which can express a range from -200% to +200% (8001 to 7FFF).
1-00 Configuration Mode set to [0] Speed open loop. 3-00 Reference Range set to [0] Min - Max. 3-02 Minimum Reference set to 100 RPM. 3-03 Maximum Reference set to 3000 RPM.
MRV/MAV
Actual speed 0% 0 hex 100 RPM 25% 1000 hex 825 RPM 50% 2000 hex 1550 RPM 75% 3000 hex 2275 RPM 100% 4000 hex 3000 RPM
Table 5.4
5.2.4
Process Control Operation
In process control operation 1-00 Configuration Mode is set to [3] Process. The reference range in 3-00 Reference Range is always [0]
Min-Max.
- MRV represents the process setpoint.
- MAV expresses the actual process feedback (range ±200%).
How to Control the Frequenc... MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 15
5
5
5.2.5 Influence of the Digital Input Terminals upon FC Control Mode
The influence of the digital input terminals upon control of the frequency converter can be programmed in 8-50 Coasting Select to 8-56 Preset Reference Select.
NOTE
Note the 8-01 Control Site overrules the settings in 8-50 Coasting Select to 8-56 Preset Reference Select, and terminal 37 Coasting Stop (safe) overrules any parameter.
Each digital input signal can be programmed to logic AND, logic OR, or to have no relation to the corresponding bit in the control word. This way, fieldbus only, fieldbus AND Digital Input, or Ether Fieldbus OR Digital input terminal can initiate a specific control command, that is stop/coast.
CAUTION
To control the frequency converter via POWERLINK, set 8-50 Coasting Select to either [1] Bus, or to [2] Logic AND. Then set 8-01 Control Site to [0] Digital and ctrl.word or [2] control word only.
5.3 Control Profile
The frequency converter can be controlled according to the DS 402 profile, or the Danfoss FC profile. Select the desired control profile in 8-10 Control Word Profile. The choice of profile affects the control and status word only. The change of 8-10 Control Word Profile will first be activated at the next power up.
The desired control profile can also be controlled by object 6060 Modes of operation and readout by object 6061 Modes of operation display. Value -1 indicates frequency converter profile. Value 2 indicates DS 402 Velocity mode. If the frequency converter is run in DS 402 profile, the DS 402 profile must be selected (for example, by 8-10 Control Word Profile or object 6060). The four process data Control Word, Reference, Status Word and Main Actual Value will the information in according the specification. Make sure that the profile selected is also the profile used in the PLC.
5.4
Danfoss FC Control Profile
5.4.1 Control Word according to FC Profile (CTW)
To select Danfoss FC protocol in the control word,
8-10 Control Word Profile must be set to [0] frequency converter profile. The control word is used to send
commands from a master (PLC or PC) to a slave (frequency converter).
Bit Bit value=0 Bit value=1 00 Reference value external selection lsb 01 Reference value external selection msb 02 DC brake Ramp 03 Coasting No coasting 04 Quick stop Ramp 05 Hold output frequency Use ramp 06 Ramp stop Start 07 No function Reset 08 No function Jog 09 Ramp 1 Ramp 2 10 Data invalid Data valid 11 No function Relay 01 active 12 No function Relay 04 active 13 Parameter set-up selection lsb 14 Parameter set-up selection msb 15 No function Reverse
Table 5.5 Bit Values for FC Control Word
Explanation of the control bits
Bits 00/01 Reference value Bits 00 and 01 are used to choose between the four reference values, which are pre-programmed in 3-10 Preset Reference according to Table 5.6.
NOTE
In 8-56 Preset Reference Select a selection is made to define how Bit 00/01 gates with the corresponding function on the digital inputs.
Bit 01 Bit 00 Programmed
ref. value
Parameter
0 0 1
[0] 3-10 Preset Reference
0 1 2
[1] 3-10 Preset Reference
1 0 3
[2] 3-10 Preset Reference
1 1 4
[3] 3-10 Preset Reference
Table 5.6 Programmed Reference Values for Bits
Bit 02, DC brake Bit 02=“0” - leads to DC braking and stop. Braking current and duration are set in 2-01 DC Brake Current and 2-02 DC Braking Time. Bit 02=“1” - leads to ramping.
Bit 03, Coasting Bit 03=“0” - causes the frequency converter to immediately coast the motor to a standstill. Bit 03=“1” - enables the frequency converter to start the motor if the other starting conditions have been fulfilled.
How to Control the Frequenc... MCA 123 POWERLINK Operating Instructions
16 MG92C102 - VLT® is a registered Danfoss trademark
5
NOTE
In 8-50 Coasting Select a selection is made to define how Bit 03 gates with the corresponding function on a digital input.
Bit 04, Quick stop Bit 04=“0” - causes a quick stop, ramping the motor speed down to stop via 3-81 Quick Stop Ramp Time. Bit 04=“1” - the frequency converter ramps the motor speed down to stop via 3-81 Quick Stop Ramp Time.
Bit 05, Hold output frequency Bit 05=“0” - causes the present output frequency (in Hz) to freeze. The frozen output frequency can only be changed with the digital inputs (5-10 Terminal 18 Digital Input to 5-15 Terminal 33 Digital Input) programmed to Speed up and Speed down. Bit 05=“1” - use ramp.
NOTE
If Freeze output is active, stop the frequency converter with
Bit 03 Coasting stop
Bit 02 DC braking
Digital input (5-10 Terminal 18 Digital Input to
5-15 Terminal 33 Digital Input) programmed to DC braking, Coasting stop, or Reset and coasting stop.
Bit 06, Ramp stop/start Bit 06=“0” - causes a stop, in which the motor speed is ramped down to stop via the selected ramp down parameter. Bit 06=“1" - permits the frequency converter to start the motor, if the other starting conditions have been fulfilled.
NOTE
In 8-53 Start Select a selection is made to define how Bit 06 Ramp stop/start gates with the corresponding function on a digital input.
Bit 07, Reset Bit 07="0" - does not cause a reset. Bit 07="1" - causes the reset of a trip. Reset is activated on the signals leading edge, that is, when changing from logic "0" to logic "1".
Bit 08, Jog Bit 08="0" - no function. Bit 08="1" - 3-19 Jog Speed [RPM] determines the output frequency.
Bit 09, Selection of ramp 1/2 Bit 09="0" - ramp 1 is active (3-40 Ramp 1 Type to 3-47 Ramp 1 S-ramp Ratio at Decel. Start).
Bit 09="1" - ramp 2 (
3-50 Ramp 2 Type to 3-57 Ramp 2 S-
ramp Ratio at Decel. Start) is active.
Bit 10, Data not valid/Data valid Is used to tell the frequency converter whether it should use or ignore the control word. Bit 10="0" - the control word is ignored. Bit 10="1" - the control word is used. This function is relevant, because the control word is always contained in the telegram, regardless of which type of telegram is used. Thus, it is possible to turn off the control word, if it is not wished to use it when updating or reading parameters.
Bit 11, Relay 01 Bit 11="0" - relay 01 not activated. Bit 11="1" - relay 01 activated, provided Control word bit 11 has been chosen in 5-40 Function Relay.
Bit 12, Relay 04 Bit 12="0" - relay 04 has not been activated. Bit 12="1" - relay 04 has been activated, provided Control word bit 12 has been chosen in 5-40 Function Relay.
Bit 13/14, Selection of set-up Bits 13 and 14 are used to choose from the four menu set­ups according to Table 5.7:
The function is only possible when Multi-Set-ups is selected in 0-10 Active Set-up.
Set-up
Bit 14 Bit 13 1 0 0 2 0 1 3 1 0 4 1 1
Table 5.7 Selection of Set-up
NOTE
In 8-55 Set-up Select a selection is made to define how Bit 13/14 gates with the corresponding function on the digital inputs.
Bit 15 Reverse Bit 15="0" - no reversing. Bit 15="1" - reversing.
How to Control the Frequenc... MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 17
5
5
5.4.2 Status Word according to FC Profile (STW)
The status word is used to inform the master (for example, a PC) of the operation mode of the slave (frequency converter).
Refer to 8 Application Examples for an example of a status word telegram using PPO type 3.
Bit Bit=0 Bit=1 00 Control not ready Control ready 01 Frequency converter
not ready
Frequency converter ready
02 Coasting Enable 03 No error Trip 04 No error Error (no trip) 05 Reserved ­06 No error Triplock 07 No warning Warning 08 Speed reference Speed=reference 09 Local operation Bus control 10 Out of frequency limit Frequency limit ok 11 No operation In operation 12 Frequency converter OK Stopped, autostart 13 Voltage OK Voltage exceeded 14 Torque OK Torque exceeded 15 Timer OK Timer exceeded
Table 5.8 Definition of Status Bits
Explanation of the status bits
Bit 00, Control not ready/ready Bit 00="0" - the frequency converter has tripped. Bit 00="1" - the frequency converter controls are ready, but the power component is not necessarily receiving any power supply (in case of external 24 V supply to controls).
Bit 01, frequency converter ready Bit 01="0" - the frequency converter is not ready for operation. Bit 01="1" - the frequency converter is ready for operation, but there is an active coasting command via the digital inputs or via serial communication.
Bit 02, Coasting stop Bit 02="0" - the frequency converter has released the motor. Bit 02="1" - the frequency converter can start the motor when a start command is given.
Bit 03, No error/trip Bit 03="0" - the frequency converter is not in fault mode.
Bit 03="1" - the frequency converter is tripped, and that a reset signal is required to re-establish operation.
Bit 04, No error/error (no trip) Bit 04="0" - the frequency converter is not in fault mode. Bit 04=“1” - there is a frequency converter error but no trip.
Bit 05, Not used Bit 05 is not used in the status word.
Bit 06, No error/triplock Bit 06="0" - the frequency converter is not in fault mode. Bit 06=“1” - the frequency converter is tripped, and locked.
Bit 07, No warning/warning Bit 07="0" - there are no warnings. Bit 07="1" - a warning has occurred.
Bit 08, Speed reference/speed = reference Bit 08="0" - the motor is running, but that the present speed is different from the preset speed reference. It could, for example, be the case while the speed is being ramped up/down during start/stop. Bit 08="1" - the present motor present speed matches the preset speed reference.
Bit 09, Local operation/bus control Bit 09="0" - [Stop/Reset] is activated on the control unit, or that Local control in 3-13 Reference Site is selected. It is not possible to control the frequency converter via serial communication. Bit 09="1" - it is possible to control the frequency converter via the fieldbus/serial communication.
Bit 10, Out of frequency limit Bit 10="0" - the output frequency has reached the value in
4-11 Motor Speed Low Limit [RPM] or 4-13 Motor Speed High Limit [RPM].
Bit 10="1" - the output frequency is within the defined limits.
Bit 11, No operation/in operation Bit 11="0" - the motor is not running. Bit 11="1" - the frequency converter has a start signal or the output frequency is greater than 0 Hz.
Bit 12, frequency converter OK/stopped, autostart Bit 12="0" - there is no temporary over temperature on the frequency converter. Bit 12="1" - the frequency converter has stopped because of over temperature, but the unit has not tripped and resumes operation once the over temperature stops.
How to Control the Frequenc... MCA 123 POWERLINK Operating Instructions
18 MG92C102 - VLT® is a registered Danfoss trademark
5
Bit 13, Voltage OK/limit exceeded Bit 13="0" - there are no voltage warnings. Bit 13="1" - the DC voltage in the frequency converters intermediate circuit is too low or too high.
Bit 14, Torque OK/limit exceeded Bit 14="0" - the motor current is lower than the torque limit selected in 4-16 Torque Limit Motor Mode or 4-17 Torque Limit Generator Mode. Bit 14="1" - the torque limits in 4-16 Torque Limit Motor Mode and 4-17 Torque Limit Generator Mode have been exceeded.
Bit 15, Timer OK/limit exceeded Bit 15="0" - the timers for motor thermal protection and VLT thermal protection, respectively, have not exceeded 100%. Bit 15="1" - one of the timers has exceeded 100%.
5.5 DS 402 Control Profile
5.5.1 Control Word According to DSP 402 Profile (Parameter 8-10=DSP 402 profile)
Speed ref.CTW
Master-slave
130BA274.10
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit no.:
Illustration 5.4 Control Word Profile
Bit Bit value=0 Bit value=1
00 Switch off Switch on 01 Disable voltage Enable voltage 02 Quick stop Run 03 Disable operation Enable operation 04 Disable ramp Enable ramp 05 Freeze Run enable 06 Ramp stop Start 07 No function Reset 08 Reserved 09 Reserved 10 Reserved 11 Jog 1 OFF Jog 1 ON 12 Reserved 13 Setup select (LSB) 14 Setup select (MSB) 15 Forward Reversing
Table 5.9 Definition of Control Bits
Explanation of the control bits
Bit 00, Switch OFF/ON Bits 00, Switch OFF/ON Bit 00=“0” - executes transition 2, 6 or 8. Bit 00=“1” - executes transition 3.
Bit 01, Disable/Enable Voltage Bit 01=“0” - executes transition 9, 10 or 12. Bit 01=“1” - enables voltage.
Bit 02, Quick stop/Run Bit 02="0" - executes transition 7, 10 or 11. Bit 02="1" - quick stop not active.
Bit 03, Disable/enable Operation Bit 03="0" - executes transition 5. Bit 03="1" - enables operation.
Bit 04, Quick-stop/ramp Bit 04="0" - executes transition 7 or 11, Quick stop. Bit 04="1" - enables ramp.
Bit 05, Freeze output frequency/run enable Bit 05="0" - the given output frequency is maintained even if the reference is changed. Bit 05="1" - the frequency converter is again able to regulate, and the given reference is followed.
Bit 06, Ramp stop/start Bit 06="0" - the frequency converter controls the motor down to stop. Bit 01="1" - gives a start command to the frequency converter.
Bit 07, No function/reset Reset of trip. Bit 07="0" - there is no reset. Bit 07="1" - a trip is reset.
Bit 08, 09 and 10 DSP402 reserved.
Bit 11, Jog 1 OFF/ON Activation of pre-programmed speed in 8-90 Bus Jog 1
Speed
JOG 1 is only possible if Bit 04="0", and bit 00-03="1".
Bit 12 Danfoss reserved.
Bits 13/14, Selection of Setup Bits 13 and 14 are used for choosing among the four menu Set-ups in accordance with Table 5.10:
How to Control the Frequenc... MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 19
5
5
Set-up Bit 14 Bit 13
0 0 1 0 1 2 1 0 3 1 1 4
Table 5.10 Set-up Selection Table
Bit 15, Forward/reversing Bit 15="0" - no reversing. Bit 15="1" - reversing.
NOTE
In factory setting reversing is set to [digital] in 8-54 Reversing Select.
5.5.2 Status Word According to DS 402 Profile
Output freq.STW
Bit no.:
Slave-master
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
130BA273.10
Illustration 5.5 Status Word Profile
Bit Bit value=0 Bit value=1 00 Not ready to switch ON Ready to switch ON 01 Switched OFF Switched ON 02 Operation disabled Operation enabled 03 No malfunction Malfunction 04 Voltage disabled Voltage enabled 05 Quick stop Run 06 Switch on disable Switch on enable 07 No warning Warning 08 Not running Running 09 Remote disabled Remote enabled 10 Set point not reached Set point reached 11 Speed limit not active Speed limit active 12 Reserved 13 Reserved 14 Reserved 15 Reserved
Table 5.11 Definition of Status Bits
Explanation of the status bits
Bit 00, Not ready to switch on/Ready to switch on Bit 00="0" - state less than “Ready to switch on”. Bit 00="1" - state at least = “Ready to Switch on”.
Bit 01, Switch off/Switch on Bit 00="0" - state less than “Switched on”. Bit 00="1" - state at least = “Switched on”.
Bit 02, Operation disable/Operation enable Bit 00="0" - state less than “Operation enable”. Bit 00="1" - state at least = “Operation enable”.
Bit 03, No fault/trip Bit 03="0" - the frequency converter is not in a fault condition. Bit 03="1" - the frequency converter has tripped and needs a reset signal to run.
Bit 04, Voltage disable/Voltage enable Bit 04="0" - control word bit 01="1". Bit 04="1" - control word bit 01="0".
Bit 05, Quick stop/Run Bit 05="0" - control word bit 02="1". Bit 05="1" - control word bit 02="0".
Bit 06, Start enable/Start disable Bit 06="0" - state is not “Switch on disable”. Bit 06="1" - state = “Switch on enable”.
Bit 07, No warning/Warning Bit 07="0" - no warning situation. Bit 07="1" - a warning has occurred.
Bit 08, Danfoss reserved
Bit 09, Remote disable/Remote enable Bit 09="0" - the frequency converter has been stopped with the stop key on the LCP, or [Local] has been selected in 3-13 Reference Site. Bit 09="1" - it is possible to control the frequency converter via the serial port.
Bit 10, Set point not reached/Set point reached Bit 10="0" - the actual motor speed is different from the speed reference set. This situation can occur while the speed is ramped up/down during start/stop. Bit 10="1" - the present motor speed equals the speed reference set.
Bit 11, Speed limit not active/speed limit active Bit 11="0" - the output frequency is out of the range set in parameters 4-11/4-12 Motor Speed low Limit RPM/Hz or parameters 4-13/4-14 Motor Speed high Limit RPM/Hz. Bit 11="1" - the output frequency is within the mentioned range.
How to Control the Frequenc... MCA 123 POWERLINK Operating Instructions
20 MG92C102 - VLT® is a registered Danfoss trademark
5
Bit 12, DSP 402 reserved
Bit 13, DSP 402 reserved
Bit 14, Running/Not running Bit 14="0" - the motor is not running. Bit 14="1" - the frequency converter has a valid start signal or that the output frequency is greater than 0 Hz.
Bit 15, Danfoss reserved
8-10 Control Profile
Option: Function:
[0] * FC profile [7] CANopen DSP 402
FC Profile is the default control profile for the frequency converter, whereas CANopen DSP 402 is the CiA standardized control profile, featuring the special DSP 402 transition state machine.
Illustration 5.6 DSP 402 State Machine
How to Control the Frequenc... MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 21
5
5
5.5.3 DSP 402 State Transitions
Transition State Control word Status word Action
- Start condition 0000 0000 ­0
Start-upNot ready to switch on
0000 0200 -
1
Switch On DisabledSwitch On Disabled
0000, 0001 0240 -
2
Not Ready to Switch OnSwitched On
0006 0231 -
3
Ready to Switch OnSwitched On
0007 0233 -
4
Switched OnReady to Switch On
000F 0237 -
5
Operation EnabledSwitched On
0007 0233 Motor ramps to 0 RPM with programmed ramp
down parameter.
6
Switched OnReady to Switch On
0006 0231 -
7
Ready to Switch OnSwitch On Disable
0001, 0000 0240 -
8
Operation EnableReady to Switch On
0006 0231 If the motor is not braked, and the power section is
switched off immediately, the motor is free to rotate.
9
Operation EnableSwitch On Disable
0001, 0000 0240 If the motor is not braked, and the power section is
switched off immediately, the motor is free to rotate.
10
Switched OnSwitched On Disable
0001, 0000 0240 If the motor is not braked, and the power section is
switched off immediately, the motor is free to rotate.
11
Operation EnabledQuick Stop Active
0002 0207 Motor ramps to 0 RPM with programmed quick
ramp parameter.
11
Operation EnabledQuick Stop Active
0003 0217 Motor ramps to 0 RPM with programmed quick
ramp parameter.
12
Quick Stop ActiveSwitch On Disabled
0001, 0000 0240 If the motor is not braked, and the power section is
switched off immediately, the motor is free to rotate.
13
All statesFault Reaction Active
xxxx 023F -
14
Fault Reaction ActiveFault
xxxx 023F -
15
FaultSwitch On Disabled
0000 0240 -
16
Quick Stop ActiveOperation Enable (not supported)
- - -
Table 5.12 DSP 402 State Transitions
How to Control the Frequenc... MCA 123 POWERLINK Operating Instructions
22 MG92C102 - VLT® is a registered Danfoss trademark
5
5.5.4 Status Word According to DS 402 Profile
Output freq.STW
Bit no.:
Slave-master
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
130BA273.10
Illustration 5.7 Status Word Profile
Bit Bit value=0 Bit value=1 00 Not ready to switch ON Ready to switch ON 01 Switched OFF Switched ON 02 Operation disabled Operation enabled 03 No malfunction Malfunction 04 Voltage disabled Voltage enabled 05 Quick stop Run 06 Switch on disable Switch on enable 07 No warning Warning 08 Not running Running 09 Remote disabled Remote enabled 10 Set point not reached Set point reached 11 Speed limit not active Speed limit active 12 Reserved 13 Reserved 14 Reserved 15 Reserved
Table 5.13 Definition of Status Bits
Explanation of the status bits
Bit 00, Not ready to switch on/Ready to switch on Bit 00="0" - state less than “Ready to switch on”. Bit 00="1" - state at least = “Ready to Switch on”.
Bit 01, Switch off/Switch on Bit 00="0" - state less than “Switched on”. Bit 00="1" - state at least = “Switched on”.
Bit 02, Operation disable/Operation enable Bit 00="0" - state less than “Operation enable”. Bit 00="1" - state at least = “Operation enable”.
Bit 03, No fault/trip Bit 03="0" - the frequency converter is not in a fault condition. Bit 03="1" - the frequency converter has tripped and needs a reset signal to run.
Bit 04, Voltage disable/Voltage enable Bit 04="0" - control word bit 01="1". Bit 04="1" - control word bit 01="0".
Bit 05, Quick stop/Run Bit 05="0" - control word bit 02="1". Bit 05="1" - control word bit 02="0".
Bit 06, Start enable/Start disable Bit 06="0" - state is not “Switch on disable”. Bit 06="1" - state = “Switch on enable”.
Bit 07, No warning/Warning Bit 07="0" - no warning situation. Bit 07="1" - a warning has occurred.
Bit 08, Danfoss reserved
Bit 09, Remote disable/Remote enable Bit 09="0" - the frequency converter has been stopped with the stop key on the LCP, or [Local] has been selected in 3-13 Reference Site. Bit 09="1" - it is possible to control the frequency converter via the serial port.
Bit 10, Set point not reached/Set point reached Bit 10="0" - the actual motor speed is different from the speed reference set. This situation can occur while the speed is ramped up/down during start/stop. Bit 10="1" - the present motor speed equals the speed reference set.
Bit 11, Speed limit not active/speed limit active Bit 11="0" - the output frequency is out of the range set in parameters 4-11/4-12 Motor Speed low Limit RPM/Hz or parameters 4-13/4-14 Motor Speed high Limit RPM/Hz. Bit 11="1" - the output frequency is within the mentioned range.
Bit 12, DSP 402 reserved
Bit 13, DSP 402 reserved
Bit 14, Running/Not running Bit 14="0" - the motor is not running. Bit 14="1" - the frequency converter has a valid start signal or that the output frequency is greater than 0 Hz.
Bit 15, Danfoss reserved
How to Control the Frequenc... MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 23
5
5
6 Communication Profile Area
6.1 Description - Communication Profile Area
6.1 Description - Communication Profile Area describes the
general layout of the POWERLINK communication area
which is supported. The process data objects are defined in this area.
6.2 1000-1FFF Communication Object Area
Index (hex) Object (symbolic name) Name Type Read/write
1000 VAR Device type UNSIGNED32 ro 1001 VAR Error register UNSIGNED8 ro 1006 VAR Communication cycle period UNSIGNED32 rw
1008 VAR Manufacturer device name VISIBLE_STRING ro 1009 VAR Manufacturer hardware version VISIBLE_STRING ro 100A VAR Manufacturer software version VISIBLE_STRING ro 1010 ARRAY Store parameters UNSIGNED32 rw 1011 ARRAY Restore default parameters UNSIGNED32 rw
0x1C14 VAR DLL_CNLossOfSocTolerance_U32 UNSIGNED32 rw 0x1E40 RECORD NWL_IpAddrTable_1_REC NWL_IpAddrTable_TYPE ro/rw 0x1E4A RECORD RECORD NWL_IpGroup_REC NWL_IpGroup_TYPE ro/rw
1018 RECORD Identity object Identity (23h) ro 1020 RECORD CFM_VerifyConfiguration_REC CFM_VerifyConfiguration_TYPE ro 1030 RECORD NMT_InterfaceGroup_0h_REC NMT_InterfaceGroup_0h_TYPE ro 1031 RECORD NMT_InterfaceGroup_1h_REC NMT_InterfaceGroup_0h_TYPE ro
1300 VAR SDO_SequLayerTimeout_U32 UNSIGNED32 rw 1400 RECORD PDO_RxCommParam_16h_REC UNSIGNED8 ro 1600 ARRAY PDO_RxMappParam_00h_AU64 UNSIGNED64 rw 1800 ARRAY PDO_TxCommParam_16h_REC UNSIGNED8 ro 1A00 ARRAY PDO_TxMappParam_00h_AU64 UNSIGNED64 rw
1C0A RECORD DLL_CNCollision_REC UNSIGNED32 rw 1C0B RECORD DLL_CNLossSoC_REC UNSIGNED32 rw 1C0F RECORD DLL_CNCRCError_REC UNSIGNED32 rw 1C14 1E40 1E4A 1F82 VAR NMT_FeatureFlags_U32 UNSIGNED32 ro 1F83 VAR NMT_EPLVersion_U8 UNSIGNED8 ro 1F8C VAR NMT_CurrNMTState_U8 UNSIGNED8 ro 1F93 RECORD NMT_EPLNodeID_REC UNSIGNED8 ro 1F98 VAR NMT_CycleTiming_REC UNSIGNED32 ro 1F99 VAR NMT_CNBasicEthernetTimeout_U32 UNSIGNED32 rw 1F9A VAR NMT_HostName_VSTR VISIBLE_STRING32 rw 1F9E VAR NMT_ResetCmd_U8 UNSIGNED8 rw
Communication Profile Area MCA 123 POWERLINK Operating Instructions
24 MG92C102 - VLT® is a registered Danfoss trademark
66
Index (hex) Object (symbolic name) Name Type Read/write
2000-5FFF Vendor specific area
See 6.3 2000-5FFF Danfoss Specific Object Area
603F VAR Error Code UNSIGNED16 ro 6040 VAR Control word UNSIGNED16 rw 6041 VAR Status word UNSIGNED16 ro 6042 VAR vl_target_velocity SIGNED16 rw 6043 VAR vl_velocity_demand SIGNED16 ro 6044 VAR vl_velocity_actual_value SIGNED16 ro 6046 ARRAY vl_velocity_min_max_amount UNSIGNED32 ro 6048 RECORD vl_velocity_acceleration See description ro 6049 RECORD vl_velocity_deceleration See description ro 6060 VAR Modes of operation SIGNED8 rw 6061 VAR Modes of operation display SIGNED8 ro 6502 VAR Supported drive mode UNSIGNED32 ro 6504 VAR Drive manufacture VISIBLE_STRING ro
Table 6.1 Communication Object Overview
6.2.1
1000h Device Type
This object describes the type of device and its functionality. It is composed of a 16-bit field describing the device profile used, and a second 16-bit field providing additional information about optional functionality of the device.
Additional information Device profile number Mode bits Type bits Bits
31.. 24 23.. 16 15.. 0 0 1 (frequency converters) 0=FC Profile
402=DS 402
Table 6.2 1000h Device Type
6.2.2
1001h Error Register
This object is the error register of the device. Only bit 0 and bit 5 is supported. The two bits is active (high) if a alarm is active in alarm word 1 or alarm word 2.
Bit Meaning 0 Generic error 1 Current 2 Voltage 3 Temperature 4 Communications error (overrun, error state) 5 Device profile specific 6 Reserved (always zero) 7 Manufacturer specific
Table 6.3 1001h Error Register
6.2.3
1006h Communication Cycle Period
This object defines the communication cycle time interval in μs. This object is reset to its default value by object 1011h. This object is set from the MN.
6.2.4 1008h Manufacturer Device Name
This object contains the device name as defined in 15-40 FC Type.
Index Meaning 1008h for example, FC 302
Table 6.4 1008h Manufacturer Device Name
6.2.5
1009h Manufacturer Hardware Version
This object contains the hardware version for the POWERLINK interface.
6.2.6
100Ah Manufacturer Software Version
This object contains the Danfoss software version as displayed in 15-49 SW ID Control Card.
6.2.7
1010h Store Parameters
In the standard configuration, the contents of parameters written via fieldbus are stored in volatile memory. The changed data will be lost after a power cycle. This index permits non-volatile storage of all frequency converter parameters which have been changed. Writing to one of the indexes will set 12-28 Store Data Values.
Communication Profile Area MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 25
6 6
Index, sub-index Meaning 1010h 0 Number sub-index supported 1010h 1 Save option parameters 1010h 2 Save communication option parameters 1010h 3 Reserved
Table 6.5 1010h Store Parameters
Writing the value “save” (0x65766173) to sub-index 1, stores all frequency converter parameters of all set-ups into non-volatile memory, all other values are rejected.
6.2.8 1011h Restore Default Parameters
To restore factory default settings:
1. Write the value “load” to sub-index 1.
2. Initiate the next power cycle manually.
The default value is restored.
Index, sub-index Meaning 1011h 0 Number of sub-index supported 1011h 1 Restore all default parameters and restart
Table 6.6 1011h Restore Default Parameters
Writing the value “load” (0x64616F6C) restores all frequency converter parameters of all set-ups to factory values, except the communications parameters. All other values are rejected, and abort code 0x08000020 is returned. The frequency converter has to be power cycled before the changes get active and the motor must be in the state coast or stopped.
6.2.9
1018h Identity Object
This object contains general information about the device.
The vendor ID (sub-index 1h) contains a unique value allocated to each manufacturer.
The manufacturer-specific product code (sub-index 2h) identifies a specific device version.
The manufacturer-specific revision number (sub-index 3h) consists of a major revision number and a minor revision number.
Index, sub-index
Meaning 1018h 0 Number of entries 1018h 1 Vendor ID 1018h 2 Product code 1018h 3 Revision number (major revision number and
minor revision number) 1018h 4 Serial number
Table 6.7 1018h Identity Object
6.2.10 1020h CFM_VerifyConfiguration_REC
This object contains the devices local configuration date and time. The object values are set by managing node or configuration tool.
Index, sub-index Meaning 1020h 0 Number of entries 1020h 1 ConfDate_U32, Days since January 1, 1984 1020h 2 ConfTime_U32, milliseconds after midnight 1020h 3 ConfId_U32, assigned by the configuration tool 1020h 4 VerifyConfInvalid_BOOL, Value False indicates
that configuration was not modified since last
storage of ConfId_U32
Table 6.8 1020h CFM_VerifyConfiguration_REC
6.2.11
1030h NMT_InterfaceGroup_0h_REC
This object is used to configure and retrieve parameters of the network interfaces (physical or virtual) via SDO.
Index, sub-index
Meaning 1030h 0 Number of entries 1030h 1 InterfaceIndex_U16 1030h 2 InterfaceDescription_VSTR t 1030h 3 InterfaceType_U8 1030h 4 InterfaceMtu_U16 1030h 5 InterfacePhysAddress_OSTR 1030h 6 InterfaceName_VSTR 1030h 7 InterfaceOperStatus_U8 1030h 8 InterfaceAdminState_U8 1030h 9 Valid_BOOL
Table 6.9 1030h NMT_InterfaceGroup_0h_REC
Communication Profile Area MCA 123 POWERLINK Operating Instructions
26 MG92C102 - VLT® is a registered Danfoss trademark
66
6.2.12 1031h NMT_InterfaceGroup_1h_REC
This object is used to configure and retrieve parameters of the network interfaces (physical or virtual) via SDO.
Index, sub-index Meaning 1031h 0 Number of entries 1031h 1 InterfaceIndex_U16 1031h 2 InterfaceDescription_VSTR t 1031h 3 InterfaceType_U8 1031h 4 InterfaceMtu_U16 1031h 5 InterfacePhysAddress_OSTR 1031h 6 InterfaceName_VSTR 1031h 7 InterfaceOperStatus_U8 1031h 8 InterfaceAdminState_U8 1031h 9 Valid_BOOL
Table 6.10 1031h NMT_InterfaceGroup_1h_REC
6.2.13
1300h SDO_SequLayerTimeout_U32
This object provides a timeout value in [ms] for the connection abort recognition of the SDO sequence Layer. Default value is 30000. This object is linked to 12-62 SDO Timeout.
6.2.14
1400h PDO_RxCommParam_16h_REC
This object describes attributes of PDO Communication for RPDO. Object indices describe the Node ID and PDO Mapping Version. Mapping Version must be set by config­uration tool depending on PDO mapping.
High Nibble
Low Nibble
Main version Sub version
Table 6.11 Mapping Version Structure
PDOs differing main version will be rejected. PDOs differing sub version is accepted. Mapping version 0 indicates that no mapping version is available.
Index, sub-index
Meaning 1400h 0 Number of sub-index supported 1400h 1 NodeID_U8 1400h 2 MappingVersion_U8
Table 6.12 1400h PDO_RxCommParam_16h_REC
6.2.15
1600h PDO_RxCommParam_00h _AU64
This objects indices describe mapping of object contained in RPDO payload to object dictionary entries.
Index, sub-index
Meaning 1600h 0 Number of sub-index supported 1600h 1
12-21 Process Data Config Write, [0] Index 1600h 2
12-21 Process Data Config Write, [1] Index 1600h 3
12-21 Process Data Config Write, [2] Index 1600h 4
12-21 Process Data Config Write, [3] Index 1600h 5
12-21 Process Data Config Write, [4] Index 1600h 6
12-21 Process Data Config Write, [5] Index 1600h 7
12-21 Process Data Config Write, [6] Index 1600h 8
12-21 Process Data Config Write, [7] Index 1600h 9
12-21 Process Data Config Write, [8] Index 1600h 10
12-21 Process Data Config Write, [9] Index
Table 6.13 1600h PDO_RxCommParam_00h _AU64
For every PDO channel up to ten objects can be mapped.
The offset related to the start address of the PDO payload and the length of data is provided for every mapped object.
Octet offset Name Description 0-1 Index Index of the object to be mapped 2 Sub-index Sub-index of the object to be mapped 3 reserved 4-5 Offset Offset related to start of PDO payload
(Bit count)
6-7 Length Length of the mapped object (Bit count)
Table 6.14 Description of Octet Offset
MSB Bits 63 .. 48 47 .. 32 31 .. 24 23 .. 16 Name Length Offset Reserved Sub-index Encoding UNSIGNED16 UNSIGNED16 - UNSIGNED8 LSB Bits 15 .. 0 Name Index Encoding UNSIGNED16
Table 6.15 Internal Mapping of PDO Mapping Entry
Communication Profile Area MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 27
6 6
6.2.16 1800h PDO_TxCommParam_16h_REC
This object describes attributes of PDO Communication for RPDO. Object indices describe the Node ID and PDO Mapping Version. Mapping Version must be set by config­uration tool depending on PDO mapping. Access is read/ write. Mapping version 0 indicates that no mapping version is available.
Index, sub-index Meaning 1400h 0 Number of sub-index supported 1400h 1 NodeID_U8 1400h 2 MappingVersion_U8
Table 6.16 1800h PDO_TxCommParam_16h_REC
6.2.17
1A00h PDO_TxMappParam_00h_AU64
This objects indices describe mapping of object contained in RPDO payload to object dictionary entries.
Index, sub-index
Meaning 1A00h0 Number of sub-index supported 1A00h1 12-22 Process Data Config Read, [0] Index 1A00h2 12-22 Process Data Config Read, [1] Index 1A00h3 12-22 Process Data Config Read, [2] Index 1A00h4 12-22 Process Data Config Read, [3] Index 1A00h5 12-22 Process Data Config Read, [4] Index 1A00h6 12-22 Process Data Config Read, [5] Index 1A00h7 12-22 Process Data Config Read, [6] Index 1A00h8 12-22 Process Data Config Read, [7] Index 1A00h9 12-22 Process Data Config Read, [8] Index 1A00h10 12-22 Process Data Config Read, [9] Index
Table 6.17 1A00h PDO_TxMappParam_00h_AU64
For every PDO channel up to ten objects is be mapped.
The offset related to the start address of the PDO payload and the length of data is provided for every mapped object.
Octet offset
Name Description 0-1 Index Index of the object to be mapped 2 Sub-index Sub-index of the object to be mapped 3 Reserved 4-5 Offset Offset related to start of PDO payload
(Bit count)
6-7 Length Length of the mapped object (Bit count)
Table 6.18 Description of Octet Offset
Table 6.19 shows.
MSB Bits 63 .. 48 47 .. 32 31 .. 24 23 .. 16 Name Length Offset Reserved Sub-index Encoding UNSIGNED16 UNSIGNED16 - UNSIGNED8 LSB 15 .. 0 Index UNSIGNED16
Table 6.19 Internal Mapping of PDO Mapping Entry
6.2.18 1C0Ah DLL_CNCollision_REC
This object contains information regarding collisions on the network.
Index, sub-index Meaning 1C0Ah 0 Number of entries 1C0Ah 1 CumulativeCnt_U32 1C0Ah 2 ThresholdCnt_U32 1C0Ah 3 Threshold_U32
Table 6.20 1C0Ah DLL_CNCollision_REC
6.2.19
1C0Bh DLL_CNLossSoC_REC
This object contains information regarding loss of SoC on the network.
Index, sub-index
Meaning 1C0Bh 0 Number of entries 1C0Bh 1
CumulativeCnt_U32, [0] 12-68 Cumulative
Counters
1C0Bh 2
ThresholdCnt_U32, [0] 12-67 Threshold Counters 1C0Bh 3
Threshold_U32, [0] 12-66 Threshold
Table 6.21 1C0Bh DLL_CNLossSoC_REC
6.2.20
1C0Fh DLL_CNCRCError_REC.
This object contains information regarding “CRC Errors” on the network. CumulativeCnt_U32 increases with one each time a CRC error occurs. CumulativeCnt_U32 decrements with one for each cycle without an error. When Cumula­tiveCnt_U32 is equal or larger than ThresholdCnt_U32, the drive issues Warning 34 in the display.
Index, sub-index
Meaning 1C0Fh 0 Number of entries 1C0Fh 1
CumulativeCnt_U32, [5] 12-68 Cumulative
Counters
1C0Fh 2
ThresholdCnt_U32, [5] 12-67 Threshold Counters 1C0Fh 3
Threshold_U32, [5] 12-66 Threshold
Table 6.22 1C0Fh DLL_CNCRCError_REC.
Communication Profile Area MCA 123 POWERLINK Operating Instructions
28 MG92C102 - VLT® is a registered Danfoss trademark
66
6.2.21 1F82 NMT_FeatureFlags_U32
Feature flags indicate communication profile specific properties of the frequency converter.
Bit Name Remark 0 Isochronous 1 SDO by UDP/IP Not supported 2 SDO by ASnd 3 SDO by PDO Not supported 4 NMT Info Services Not supported 5 Extended NMT State Commands Not supported 6 Dynamic PDO Mapping 7 NMT Service by UDP/IP Not supported 8 Configuration Manager Not supported 9 Multiplexed Access 10 NodeID setup by SW Not supported 11 MN Basic Ethernet Mode Not supported 12 Routing Type 1 Support Not supported 13 Routing Type 2 Support Not supported 14 SDO Read/Write All by Index Not supported 15 SDO Read/Write Multiple Parameter by
Index
Not supported
16..31 Reserved
Table 6.23 Bit Description
6.2.22
1F83h NMT_ EPLVersion_U8
The object holds the POWERLINK communication profile version that is implemented.
High nibble
Low nibble
POWERLINK Main Version POWERLINK Sub Version
Table 6.24 Implemented Communication Profile
6.2.23
1F8C NMT_CurrNMTState_U8
This object holds the node‘s current NMT state.
Binary value
NMT state 0001 1100 NMT_CS_NOT_ACTIVE (Default) 0001 1101 NMT_CS_PRE_OPERATIONAL_1 0101 1101 NMT_CS_PRE_OPERATIONAL_2 0110 1101 NMT_CS_READY_TO_OPERATE 1111 1101 NMT_CS_OPERATIONAL 0100 1101 NMT_CS_STOPPED 0001 1110 NMT_CS_BASIC_ETHERNET
Table 6.25 NMS State
6.2.24
1F93h NMT_EPLNodeID_REC
This object contains drives POWERLINK NodeID.
Index, sub-index Meaning 1F93h 0 Number of entries 1F93h 1
NodeID_U8, [5] 12-68 Cumulative Counters
1F93h 2 NodeIDByHW_BOOL, DIP switch reading
Table 6.26 1F93h NMT_EPLNodeID_REC.
6.2.25 1F98h NMT_CycleTiming_REC
This object contains node-specific timing parameters which influence the POWERLINK cycle timing.
Index, sub­index
Meaning Remark
1F98h 0 Number of entries 1F98h 1 IsochrTxMax-
Payload_U16
Number of transmit bits, 320=10 signals, 32 bit each
1F98h 2 IsochrRxMax-
Payload_U16
Number of receive bits, 320=10 signals, 32 bit
each 1F98h 3 PResMaxLatency_U32 Latency, fixed to 10 (nS) 1F98h 4 PReqActPayloa-
dLimit_U16
Set by MN during config-
uration 1F98h 5 PResActPayloa-
dLimit_U16
Set by MN during config-
uration 1F98h 6 ASndMaxLatency_U32 Latency, fixed to 10 (nS) 1F98h 7 MultiplCycleCnt_U8 Set by MN during config-
uration 1F98h 8 AsyncMTU_U16 Configurable in the range
of 300 to 1500
Table 6.27 Node-specific Timing Parameters
6.2.26
1F99h NMT_CNBasicEthernetTimeout_U32
This object specifies the time in µs for which the option must wait for SoC before switching to basic Ethernet mode.
Index, sub­index
Meaning Remark
1F99 NMT_CNBasicEthernet-
Timeout_U32
Time in microseconds before switching to basic Ethernet mode. Default 5000000 (5 s) Mapped to
12-63 Basic Ethernet Timeout
Table 6.28 Basic Ethernet Timeout
Communication Profile Area MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 29
6 6
6.2.27 1F9Ah NMT_HostName_VSTR _U32
Index, sub-index Meaning Meaning 1F9A NMT_HostName_VSTR
Mapped to 12-08 Host
Name
Table 6.29 DNS Host Name
6.2.28 1F9E NMT_ResetCmd_U8
This object is used to reset the frequency converter, communication or configuration.
Hex value NMT service FFh NMTInvalidService 2Bh NMTSwReset 28h NMTResetNode 2Ah NMTResetConfiguration 29h NMTResetCommunication
Table 6.30 Reset Command
6.3 2000-5FFF Danfoss Specific Object Area
6.3.1 2000h–5FFFh Vendor Specific Object Area
The area 2000h to 5FFFh holds the indexes for accessing the Danfoss frequency converter parameters. All parameters in the frequency converter are linked to indexes in this area. The first index available is index 2001h. This index is linked to the frequency converters 0-01 Language. The rest of the POWERLINK index follows the same rule, where the frequency converters parameter number plus 2000h gives the POWERLINK index. For example, reading the running hours in 15-01 Running Hours, is calculated by 2000h + parameter number in hex number=2000h+5DD=index 25DDh. The XDD file only contains a subset of the frequency converters parameters. This subset has the indexes that are required for setting up the PDO communication. All parameters can be read or written via SDO communication from the PLC. Table 6.31 shows a few indexes and their mapping.
Index
Parameter 2001h 0-01 Language 2002h 0-02 Motor Speed Unit 2003h 0-03 Regional Settings .. 2078h 1-20 Motor Power [kW] 2079h 1-22 Motor Voltage .. 24B1h 12-01 IP Address 24B2h 12-02 Subnet Mask
Table 6.31 2000h-5FFFh Vendor Specific Object Area
6.4 6000-Device profile Object Area
6.4.1 6000h–9FFFh Standardised Device Profile Area
The area 6000h to 9FFFh holds the indexes specified by the IEC for various device profiles. The Danfoss POWERLINK does support three profiles, FC Profile, MCO, and the DS 402 profile, velocity mode. The profile is selected via 8-10 Control Word Profile, Control Word Profile, or via Index 6060h Modes of operation. The profile area has up to 13 indexes depending on the selection made in 8-10 Control
Word Profile.
Table 6.32 shows the support of indexes, depending on
setting of 8-10 Control Word Profile (Index 6060h)
Communication Profile Area MCA 123 POWERLINK Operating Instructions
30 MG92C102 - VLT® is a registered Danfoss trademark
66
Index Name 8-10 Control Word Profile
=FC Profile
8-10 Control Word Profile= MCO
8-10 Control Word Profile=
DS 402 603Fh Error code - - √ 6040h Control word - - √ 6041h Status word - - √ 6042h Vl_target_velocity - - √ 6043h Vl_velocity_demand - - √ 6044h Vl_velocity_actual_value - - √ 6046h Vl_velocity_min_max_amount - - √ 6048h Vl_velocity_acceleration - - √ 6049h Vl_velocity_deceleration - - √ 6060h Modes of operation √ 6061h Modes of operation display √ 6502h Supported frequency converter mode √ 6504h Frequency converter manufacture
Table 6.32 6000h-9FFFh Standardised Device Profile Area
6.4.2
603Fh Error Code
Error signaling mechanism is used to signal alarms and events generated on the frequency converter to the MN. The error code consist of 8 byte of data, where: Byte 0 (zero) is a copy of object 1001h. Byte 1 & 2, not used. Byte 3 contains: Bit 0=1, Alarmword 1 has an active Alarm (16-90 Alarm Word). Bit 1=1, Alarmword 2 has an active Alarm (Future ext. 16-91 Alarm Word 2). Bit 2=0, Reserved. Bit 3=1, Warningword 1 has an active Warning (16-92 Warning Word). Bit 4=1, Warningword 2 has an active Warning (Future ext. 16-93 Warning Word 2). Bit 5-7=0, Reserved. Byte 4 and 5, Profile specific. Byte 6 and 7, reserved.
6.4.3
6040h Control Word
This object contains the control word in accordance with DS 402. The control word consists of 16 bit, these 16 bit are used for controlling the frequency converter (for example, start, stop, reset). The control word is described in 5.5 DS 402 Control Profile.
6.4.4
6041h Status Word
This object contains the Status word in accordance to DS
402. The status word consists of 16 bit. The 16 bits show the state and status of the frequency converter (for example, running, ramping, on speed). The Status word is described in 5.5 DS 402 Control Profile.
6.4.5
6042h vl_target_velocity
The vl_target_velocity is the required velocity of the system. The velocity is in RPM.
6.4.6
6043h vl_velocity_demand
The vl_velocity_demand is the velocity of the system after the ramp controller. The velocity is in RPM.
6.4.7 6044h vl_actual_velocity_value
The vl_actual_velocity_value is the velocity at the motor shaft. The velocity is in RPM, and is obtained from 16-17 Speed [RPM]. The velocity is in RPM.
6.4.8 6046h vl_velocity_min_max_amount
The vl_ velocity_min_max_amount is the minimum and maximum RPM at the motor shaft. The two values are obtained from 3-02 Minimum Reference and 3-03 Maximum Reference. The readout values in 3-02 Minimum Reference and 3-03 Maximum Reference will be truncated.
Index, sub-index Meaning 1046h 0 Number of sub-index supported 1046h 1 vl_velocity_min_max_amount 1046h 2 vl_velocity_min_amount
Table 6.33 Minimum/Maximum RPM at Motor Shaft
Communication Profile Area MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 31
6 6
6.4.9 6048h vl_velocity_acceleration
The vl_ velocity_acceleration index specifies the slope of the acceleration ramp. It is generated as the quotient of the delta_speed and delta_time. The Delta time is stored in 3-41 Ramp 1 Ramp Up Time, and the Delta speed is store locally in the options non volatile memory. After a power down the delta speed will be generated from the frequency converter 1-25 Motor Nominal Speed. This can give a different readout from the frequency converter, but the slope value is maintained.
Index, sub-index Meaning 1048h 0 Number of sub-index supported 1048h 1 Delta speed 1048h 2 Delta time
Table 6.34 6048h vl_velocity_acceleration
6.4.10
6049h vl_velocity_deceleration
The vl_ velocity_deceleration index specifies the slope of the deceleration ramp. It is generated as the quotient of the delta_speed and delta_time. The Delta time is stored in 3-42 Ramp 1 Ramp Down Time, and the Delta speed is stored locally in the options non volatile memory. After a power down, the delta speed is generated from the frequency converter 1-25 Motor Nominal Speed. This can give a different readout from the frequency converter, but the slope value is maintained.
Index, sub-index
Meaning 1049h 0 Number of sub-index supported 1049h 1 Delta speed 1049h 2 Delta time
Table 6.35 6049h vl_velocity_deceleration
6.4.11
6060h Modes of Operation
This index is used for selection the Danfoss FC profile, MCO profile, or the DS 402 profile. The index links directly to 8-10 Control Word Profile. If this value is changed while in operation, the option enters the “Error PREOP” state.
Index, 6060h value
Meaning
-2 MCO profile (only possible if MCO305 is
mounted)
-1 FC Profile 2 DS 402 profile
Table 6.36 6060h Modes of Operation
6.4.12
6061h Modes of Operation Display
This index is used to display which mode the frequency converter is in. The mode can be changed via index 6060. The values are the same as used for index 6060.
Index, 6061h value Meaning
-2 MCO profile (only possible if MCO305 is mounted)
-1 FC Profile
2 DS 402 profile
Table 6.37 6061h Modes of Operation Display
6.4.13
6502h Supported Frequency Converter Mode
This index informs the user of which operating mode the frequency converter is capable of. Bit 1 is set, indicating that the frequency converter can run DS 402 velocity mode, bit 16 FC profile and 17 indicates MCO profile.
6.4.14
6504h Frequency Converter Manufacturer
This index does readout the name of the frequency converter manufacturer. Data is coded as a string.
Index, sub-index
Meaning
6504Ch 0 Manufacturer “DANFOSS DRIVES”
Table 6.38 6504h Drive Manufacturer (read only)
Communication Profile Area MCA 123 POWERLINK Operating Instructions
32 MG92C102 - VLT® is a registered Danfoss trademark
66
7 Parameters
7.1 Parameter Group 8-** Communication and Option
8-01 Control Site
Option: Function:
The setting in this parameter overrides the settings in 8-50 Coasting Select to 8-56 Preset Reference Select.
[0] Digital and
ctrl.word
Control by using both digital input and control word.
[1] Digital only Control by using digital inputs only.
[2] Controlword only Control by using control word only.
8-02 Control Word Source
Select the source of the control word: one of two serial interfaces or four installed options. During initial power-up, the frequency converter automatically sets this parameter to [3] Option A if it detects a valid fieldbus option installed in slot A. If the option is removed, the frequency converter detects a change in the configuration, sets 8-02 Control Word Source back to default setting RS-485, and the frequency converter trips. If an option is installed after initial power-up, the setting of 8-02 Control Word Source does not change, but the frequency converter trips and displays: Alarm 67 Option Changed. When retrofitting a bus option into a frequency converter, that did not have a bus option installed to begin with, take an ACTIVE decision to move the control to Bus based. This is done for safety reasons to avoid an accidental change.
Option: Function:
[0] None [1] FC RS485 [2] FC USB [3] Option A [4] Option B [5] Option C0 [6] Option C1 [30] External Can
NOTE
This parameter cannot be adjusted while the motor is running.
8-03 Control Word Timeout Time
Range: Function:
1 s* [ 0.1 -
18000 s]
Enter the maximum time expected to pass between the reception of two consecutive telegrams. If this time is exceeded, it indicates that the serial communication has stopped. The function selected in 8-04 Control Word
8-03 Control Word Timeout Time
Range: Function:
Timeout Functionis then carried out. A valid control word triggers the time-out counter.
8-04 Control Word Timeout Function
Select the time-out function. The time-out function activates when the control word fails to be updated within the time period specified in 8-03 Control Word Timeout Time.
Option: Function:
[0] Off Resumes control via serial bus (fieldbus or
standard) using the most recent control word.
[1] Freeze output Freezes output frequency until communi-
cation resumes.
[2] Stop Stops with auto restart when communi-
cation resumes.
[3] Jogging Runs the motor at JOG frequency until
communication resumes.
[4] Max. speed Runs the motor at maximum frequency until
communication resumes.
[5] Stop and trip Stops the motor, then resets the frequency
converter to restart: via the fieldbus, via [Reset], or via a digital input.
[7] Select setup 1 Changes the set-up upon reestablishment of
communication following a control word time-out. If communication resumes after a time-out, 8-05 End-of-Timeout Function defines whether to resume the set-up used before the time-out, or to retain the set-up endorsed by the time-out function.
[8] Select setup 2
See [7] Select setup 1
[9] Select setup 3
See [7] Select setup 1
[10] Select setup 4
See [7] Select setup 1
[26] Trip
NOTE
To change the set-up after a time-out, the following configuration is required: Set 0-10 Active Set-up to [9] Multi set-up and select the relevant link in 0-12 This Set-up Linked to.
8-05 End-of-Timeout Function
Option: Function:
Select the action after receiving a valid control word following a time-out. This parameter is active only when 8-04 Control Timeout Function
Parameters MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 33
7 7
8-05 End-of-Timeout Function
Option: Function:
is set to [7] Set-up 1, [8] Set-up 2, [9] Set-up 3 or [10] Set-up 4.
[0] Hold set-up
Retains the set-up selected in 8-04 Control
Timeout Function and displays a warning, until 8-06 Reset Control Timeout toggles. Then the
frequency converter resumes its original set-up.
[1] Resume set-upResumes the set-up active before the time-out.
8-06 Reset Control Word Timeout
This parameter is active only when [0] Hold set-up has been selected in 8-05 End-of-Timeout Function.
Option: Function:
[0] Do not reset
Retains the set-up specified in 8-04 Control Word Timeout Function, following a control word time-out.
[1] Do reset Returns the frequency converter to the original
set-up following a control word time-out. The frequency converter performs the reset and then immediately reverts to the [0] Do not reset setting
8-07 Diagnosis Trigger
This parameter enables and controls the frequency converter diagnosis/Emergency function. In Profibus, it expands the diagnosis data to 24 byte. In EtherCAT, it activates the transmission of the Emergency object. In POWERLINK, it enables the Error signaling. The Emergency/Error signaling object consists of 8 byte of data, where byte 3 indicates an active alarm or warning. Bit 0=1 Alarmword 1 has an active Alarm. Bit 1=1 Alarmword 2 has an active Alarm. Bit 2, reserved, Bit 3=1 Warningword 1 has an active warning. Bit 4=1 Warningword 2 has an active warning. Bits 5-7, reserved.
Option: Function:
[0] Disable [1] Trigger on alarms [2] Trigger alarm/warn.
NOTE
The following is only valid for Profibus and EtherCAT.
-
[0] Disable: Do not send extended diagnosis/ emergency data even if they appear in the frequency converter.
-
[1] Trigger on alarms: Send extended diagnosis/ emergency data when one or more alarms appear in alarm 16-90 Alarm Word or 9-53 Profibus Warning Word.
-
[2] Trigger alarms/warn.: Send extended diagnosis/ emergency data if one or more alarms or warnings appear in alarm 16-90 Alarm Word,
9-53 Profibus Warning Word
, or warning
16-92 Warning Word.
Enabling diagnosis can cause increased bus traffic. Not all fieldbus types support Diagnosis functions.
8-08 Readout Filtering
If the speed feedback value readouts on fieldbus are fluctuating, this function is used. Select filtered if the function is required. A power-cycle is required for changes to take effect.
Option: Function:
[0] Motor Data Std-
Filt.
Select [0] for normal bus readouts.
[1] Motor Data LP-
Filter
Select [1] for filtered bus readouts of the following parameters:
16-10 Power [kW] 16-11 Power [hp] 16-12 Motor Voltage 16-14 Motor current 16-16 Torque [Nm] 16-17 Speed [RPM] 16-22 Torque [%] 16-25 Torque [Nm] High
8-10 Control Word Profile
Select the interpretation of the control and status words corresponding to the installed fieldbus. Only the selections valid for the fieldbus installed in slot A are visible in the LCP display. If the parameter is changed while the frequency converter is in operation mode, the frequency converter goes to error state, and the control of the frequency converter is lost. This parameter should not be changed while the motor is running, since it can lead to a unknown state of the profile.
Option: Function:
[0] * FC Profile [7] CANopen DSP 402
8-13 Configurable Status Word STW
Option: Function:
This parameter enables configuration of bits
12–15 in the status word. [0] No function [1] * Profile
Default
Function corresponds to the profile default
selected in 8-10 Control Profile. [2] Alarm 68
Only
Only set in case of an Alarm 68.
[3] Trip excl.
Alarm 68
Set in case of a trip, except if Alarm 68
executes the trip. [10] T18 DI
status.
The bit indicates the status of terminal 18.
“0” indicates that the terminal is low
“1” indicates that the terminal is high [11] T19 DI
status.
The bit indicates the status of terminal 19.
“0” indicates that the terminal is low
“1” indicates that the terminal is high [12] T27 DI
status.
The bit indicates the status of terminal 27.
“0” indicates that the terminal is low
Parameters MCA 123 POWERLINK Operating Instructions
34 MG92C102 - VLT® is a registered Danfoss trademark
77
8-13 Configurable Status Word STW
Option: Function:
“1” indicates that the terminal is high
[13] T29 DI
status.
The bit indicates the status of terminal 29. “0” indicates that the terminal is low “1” indicates that the terminal is high
[14] T32 DI
status.
The bit indicates the status of terminal 32. “0” indicates that the terminal is low “1” indicates that the terminal is high
[15] T33 DI
status.
The bit indicates the status of terminal 33. “0” indicates that the terminal is low “1” indicates that the terminal is high
[16] T37 DI
status
The bit indicates the status of terminal 37. 0” indicates T37 is low (safe stop) “1” indicates T37 is high (normal)
[21] Thermal
warning
The thermal warning turns on when the temperature exceeds the limit in the motor, the frequency converter, the brake resistor, or the thermistor.
[30] Brake fault
(IGBT)
Output is Logic ‘1’ when the brake IGBT is short-circuited. Use this function to protect the frequency converter if there is a fault on the brake modules. Use the output/relay to cut out the main voltage from the frequency converter.
[40] Out of ref.
range
[60] Comtor 0
See parameter group 13-1* ComparatorsCom- parators. If Comtor 0 is evaluated as TRUE, the output goes high. Otherwise, it is low.
[61] Comtor 1
See parameter group 13-1* ComparatorsCom- parators. If Comtor 1 is evaluated as TRUE, the output goes high. Otherwise, it is low.
[62] Comtor 2
See parameter group 13-1* ComparatorsCom- parators. If Comtor 2 is evaluated as TRUE, the output goes high. Otherwise, it is low.
[63] Comtor 3
See parameter group 13-1* ComparatorsCom- parators. If Comtor 3 is evaluated as TRUE, the output goes high. Otherwise, it is low.
[64] Comtor 4
See parameter group 13-1* ComparatorsCom- parators. If Comtor 4 is evaluated as TRUE, the output goes high. Otherwise, it is low.
[65] Comtor 5
See parameter group 13-1* ComparatorsCom- parators. If Comtor 5 is evaluated as TRUE, the output goes high. Otherwise, it is low.
[70] Logic Rule
0
See parameter group 13-4* LC-4# Logic RulesLogic Rules. If Logic Rule 0 is evaluated as TRUE, the output goes high. Otherwise, it is low.
[71] Logic Rule
1
See parameter group 13-4* LC-4# Logic RulesLogic Rules. If Logic Rule 1 is evaluated as TRUE, the output goes high. Otherwise, it is low.
[72] Logic Rule
2
See parameter group 13-4* LC-4# Logic RulesLogic Rules. If Logic Rule 2 is evaluated as
8-13 Configurable Status Word STW
Option: Function:
TRUE, the output goes high. Otherwise, it is
low. [73] Logic Rule3See parameter group 13-4*. If Logic Rule 3 is
evaluated as TRUE, the output goes high.
Otherwise, it is low. [74] Logic Rule
4
See parameter group 13-4* LC-4# Logic
RulesLogic Rules. If Logic Rule 4 is evaluated as
TRUE, the output goes high. Otherwise, it is
low. [75] Logic Rule
5
See parameter group 13-4* LC-4# Logic
RulesLogic Rules. If Logic Rule 5 is evaluated as
TRUE, the output goes high. Otherwise, it is
low. [80] SL Digital
Output A
See 13-52 SL Controller Action. The output
goes high whenever the Smart Logic Action
[38] Set digital out A high is executed. The
output goes low whenever the Smart Logic
Action [32] Set digital out A low is executed. [81] SL Digital
Output B
See 13-52 SL Controller Action. The input goes
high whenever the Smart Logic Action [39]
Set digital out B high is executed. The input
goes low whenever the Smart Logic Action
[33] Set digital out B low is executed. [82] SL Digital
Output C
See 13-52 SL Controller Action. The input goes
high whenever the Smart Logic Action [40]
Set digital out C high is executed. The input
goes low whenever the Smart Logic Action
[34] Set digital out C low is executed. [83] SL Digital
Output D
See 13-52 SL Controller Action. The input goes
high whenever the Smart Logic Action [41]
Set digital out D high is executed. The input
goes low whenever the Smart Logic Action
[35] Set digital out D low is executed. [84] SL Digital
Output E
See 13-52 SL Controller Action. The input goes
high whenever the Smart Logic Action [42]
Set digital out E high is executed. The input
goes low whenever the Smart Logic Action
[36] Set digital out E low is executed. [85] SL Digital
Output F
See 13-52 SL Controller Action. The input goes
high whenever the Smart Logic Action [43]
Set digital out F high is executed. The input
goes low whenever the Smart Logic Action
[37] Set digital out F low is executed.
8-14 Configurable Control Word CTW
Option: Function:
Selection of control word bit 10 if it is active low or active high.
[0] None [1] Profile default [2] CTW Valid,
active low
[3] Safe Option
Reset
Parameters MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 35
7 7
8-14 Configurable Control Word CTW
Option: Function:
[4] PID error
inverse
When enabled, it inverts the resulting error from the process PID controller. Available only if "Configuration Mode" is set to "Surface Winder", "Extended PID Speed OL" or "Extended PID Speed CL".
[5] PID reset I
part
When enabled, resets the I-part of the Process PID controller. Equivalent to 7-40 Process PID I-part Reset. Available only if "Configuration Mode" is set to "Surface Winder", "Extended PID Speed OL" or "Extended PID Speed CL".
[6] PID enable When enabled, enables the extended process
PID controller. Equivalent to 7-50 Process PID Extended PID. Available only if "Configuration Mode" is set "Extended PID Speed OL" or "Extended PID Speed CL".
8-50 Coasting Select
Option: Function:
Select control of the coasting function via the terminals (digital input) and/or via the bus.
[0] Digital
input
Activates Start command via a digital input.
[1] Bus Activates Start command via the serial
communication port or fieldbus option.
[2] Logic AND Activates Start command via the fieldbus/serial
communication port, AND additionally via one of the digital inputs.
[3] Logic OR Activates Start command via the fieldbus/serial
communication port OR via one of the digital inputs.
8-51 Quick Stop Select
Select control of the Quick Stop function via the terminals (digital input) and/or via the bus.
Option: Function:
[0] Digital input [1] Bus [2] Logic AND [3] Logic OR
8-52 DC Brake Select
Option: Function:
Select control of the DC brake via the terminals (digital input) and/or via the fieldbus.
NOTE
Only selection [0] Digital input is available when 1-10 Motor Construction is set to [1] PM non-salient SPM.
[0] Digital
input
Activates Start command via a digital input.
8-52 DC Brake Select
Option: Function:
[1] Bus Activates Start command via the serial communi-
cation port or fieldbus option.
[2] Logic AND Activates Start command via the fieldbus/serial
communication port, AND additionally via one of the digital inputs.
[3] Logic OR Activates Start command via the fieldbus/serial
communication port OR via one of the digital inputs.
8-53 Start Select
Option: Function:
Select control of the frequency converter start function via the terminals (digital input) and/or via the fieldbus.
[0] Digital
input
Activates Start command via a digital input.
[1] Bus Activates Start command via the serial
communication port or fieldbus option.
[2] Logic AND Activates Start command via the fieldbus/serial
communication port, AND additionally via one of the digital inputs.
[3] Logic OR Activates Start command via the fieldbus/serial
communication port OR via one of the digital inputs.
8-54 Reversing Select
Option: Function:
[0] Digital
input
Select control of the frequency converter reverse function via the terminals (digital input) and/or via the fieldbus.
[1] Bus Activates the Reverse command via the serial
communication port or fieldbus option.
[2] Logic AND Activates the Reverse command via the
fieldbus/serial communication port, AND additionally via one of the digital inputs.
[3] Logic OR Activates the Reverse command via the
fieldbus/serial communication port OR via one of the digital inputs.
8-55 Set-up Select
Option: Function:
Select control of the frequency converter set-up selection via the terminals (digital input) and/or via the fieldbus.
[0] Digital
input
Activates the set-up selection via a digital input.
[1] Bus Activates the set-up selection via the serial
communication port or fieldbus option.
Parameters MCA 123 POWERLINK Operating Instructions
36 MG92C102 - VLT® is a registered Danfoss trademark
77
8-55 Set-up Select
Option: Function:
[2] Logic AND Activates the set-up selection via the fieldbus/
serial communication port, AND additionally via one of the digital inputs.
[3] Logic OR Activate the set-up selection via the fieldbus/
serial communication port OR via one of the digital inputs.
8-90 Bus Jog 1 Speed
Range: Function:
100 RPM* [ 0 - par. 4-13
RPM]
Enter the jog speed. Activate this fixed jog speed via the serial port or fieldbus option.
8-91 Bus Jog 2 Speed
Range: Function:
200 RPM* [ 0 - par. 4-13
RPM]
Enter the jog speed. Activate this fixed jog speed via the serial port or fieldbus option.
7.2 Parameter Group 12-** Ethernet
7.2.1 12-0* IP Settings
12-00 IP Address Assignment
Option: Function:
Selects the IP Address assignment method.
[0] MANUAL
IP-address can be set in 12-01 IP Address IP Address.
[1] DHCP IP-address is assigned via DHCP server.
[2] BOOTP IP-address is assigned via BOOTP server.
[10] DCP DCP Assigned via the DCP protocol. [20] *From
Node ID address is set from 12-60 Node ID.
12-01 IP Address
Range: Function:
0 * [0 -
2147483647 ]
Configure the IP address of the option. Read-only if 12-00 IP Address Assignment set to DHCP or BOOTP. In POWERLINK the IP address follows the 12-60 Node ID last byte and the first part is fixed to
192.168.100 (Node ID).
12-02 Subnet Mask
Range: Function:
0 * [0 - 4244635647 ] Configure the IP subnet mask of the
option. Read-only if 12-00 IP Address Assignment set to DHCP or BOOTP. In POWERLINK it is fixed to 255.255.255.0.
12-03 Default Gateway
Range: Function:
0 * [0 -
2147483647 ]
Configure the IP default gateway of the option. Read-only if 12-00 IP Address Assignment set to DHCP or BOOTP. In a non-routed network this address is set to the IP address of the IO Device
12-08 Host Name
Range: Function:
0 * [0 -
2147483647 ]
Logical (given) name of option. The display of the frequency converter only shows the first 19 characters, but the remaining characters are stored in the frequency converter. The frequency converter can accept longer text than 19 characters, but it is recommended to limit the length to 19 characters.
12-09 Physical Address
Range: Function:
0 * [0 - 0 ] Read only. Displays the Physical (MAC) address of
the option.
7.2.2 12-1* Ethernet Link Parameters
12-1* Ethernet Link parameters
Option: Function:
Applies for whole parameter group.
[0] Port 1 Index [0] goes for Port 1. For EtherCAT it goes for In
Port.
[1] Port 2 Index [1] goes for Port 2. For EtherCAT it goes for out
Port.
12-10 Link Status
Option: Function:
Read only. Displays the link status of the Ethernet ports.
[0] No Link [1] Link
12-11 Link Duration
Range: Function:
Size related* [ 0 - 0 ] Read only. Displays the duration of the
present link on each port in dd:hh:mm:ss.
12-12 Auto Negotiation
Option: Function:
Configures Auto Negotiation of Ethernet link parameters, for each port: ON or OFF.
[0] Off
Link Speed and Link Duplex can be configured in 12-13 Link Speed and 12-14 Link Duplex.
Parameters MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 37
7 7
12-12 Auto Negotiation
Option: Function:
[1] On
NOTE
In POWERLINK this parameter is fixed to OFF setting.
12-13 Link Speed
Option: Function:
Forces the link speed for each port in 10 Mbps or 100 Mbps. If 12-12 Auto Negotiation is set to: ON, this parameter is read only and displays the actual link speed. If no link is present, “None” is displayed.
[0] None [1] 10 Mbps [2] 100 Mbps
NOTE
In POWERLINK this parameter is locked to 100 Mbs.
12-14 Link Duplex
Option: Function:
Forces the duplex for each port to Full or Half duplex. If 12-12 Auto Negotiation is set to: [ON], this parameter is read only.
[0] Half Duplex [1] Full Duplex
NOTE
In POWERLINK this parameter is locked to half duplex.
7.2.3 12-2* Process Data
12-20 Control Instance
Range: Function:
[None, 20, 21, 23, 100, 101, 103]
Read only. Displays the connection to the master. In Ethernet/IP: If no CIP connection is present, “None” is displayed. In EtherCAT: If no connection is active "None" is displayed, else it displays the active PDO. In POWERLINK: If no connection is active “None” is displayed, else it displays the active PDO (23).
12-21 Process Data Config Write
Range: Function:
[[0 - 9] PCD read 0 - 9] Configuration of readable process
data.
In POWERLINK this parameter is read only. Same applies for 12-22 Process Data Config Read, 12-23 Process Data Config Write Size and 12-24 Process Data Config Read Size.
12-22 Process Data Config Read
Range: Function:
[[0 - 9] PCD read 0 - 9] Configuration of readable process
data.
12-23 Process Data Config Write Size
Range: Function:
16 * [8 - 32 ] Sets the number of bits being sent from the
frequency converter as process data. The setting counts from right (LSB). The value 1 means that only the least significant bit of the signal is transferred from the frequency converter.
12-24 Process Data Config Read Size
Range: Function:
16 * [8 - 32 ] Sets the number of bits being sent to the
frequency converter as process data. The setting counts from right (LSB). The value 1 means that only the least significant bit of the signal is transferred to the frequency converter. The preceding bits are set to zero.
12-28 Store Data Values
Option: Function:
[0] Off [1] Store all setups [2] Store all setups
12-29 Store Always
Option: Function:
Activates function that always stores received
parameter data in non-volatile memory (EEPROM). [0] * Off [1] On
7.2.4 12-6* Ethernet PowerLink
12-60 Node ID
Range: Function:
1 * [1 -
239 ]
Enter the Node ID in this parameter or alterna­tively in the hardware switch. In order to adjust the Node ID in 12-60 Node ID, the hardware switch must be set to o or 254 (i.e. all switches set to [ON] or to [OFF]). Otherwise this parameter displays the actual setting of the switch. Setting this parameter will first be active at the next power up cycle.
12-62 SDO Timeout
Range: Function:
30000 ms*
[0 - 2000000000 ms]
12-62 SDO Timeout is the SDO Timeout in milliseconds. Value of this parameter is read during
Parameters MCA 123 POWERLINK Operating Instructions
38 MG92C102 - VLT® is a registered Danfoss trademark
77
12-62 SDO Timeout
Range: Function:
communication initialization into Object 1300h
12-63 Basic Ethernet Timeout
Range: Function:
5000.000 ms*
[0 ­2100000 ms]
12-63 Basic Ethernet Timeout in microseconds. This parameter is mapped to Object 1F99h. If the POWERLINK interface does not receive a SoC frame within the specified period of time, the interface shifts to standard Ethernet mode. This feature is first available from version 2.00 of the POWERLINK Interface.
12-66 Threshold
Range: Function:
15 * [0 -
99999 ]
12-66 Threshold holds six threshold values. If one of these thresholds are exceeded, the POWERLINK Interface exits operational mode. The parameters are set to optimal settings and should not be changed. The actual value of the counters can be read out via 12-67 Threshold Counters.
12-67 Threshold Counters
Range: Function:
0 * [0 -
65538 ]
12-67 Threshold Counters hold 6 counters. The counter reflects the actual value in the POWERLINK interface. Counters increases with a count of eight at detection of an error and decreases with a count of one when no errors are detected. The values are read only.
12-68 Cumulative Counters
Range: Function:
0 * [0 - 65535 ] Loss off SoC Cumulative. This parameter
reflects the value in object 1C0Bh, subindex 1.
12-69 Ethernet PowerLink Status
Range: Function:
0 * [0 - 4294967295 ]
7.2.5 12-8* Other Ethernet Services
12-80 FTP Server
Option: Function:
[0] Disabled Disables the built-in FTP server.
[1] Enabled Enables the built-in FTP server.
12-81 HTTP Server
Option: Function:
[0] Disabled [1] Enabled Enables the built-in HTTP (web) server.
12-82 SMTP Service
Option: Function:
[0] Disabled [1] Enabled Enables the SMTP (e-mail) service on the option.
12-89 Transparent Socket Channel Port
Range: Function:
Size related*
[ 0 -
0. ]
Configures the TCP port number for the transparent socket channel. This configu­ration enables FC telegrams to be sent transparently on Ethernet via TCP. Default value is 4000, 0 means disabled. The MCT 10 Set-up Software uses this port.
7.2.6 12-9* Advanced Ethernet Settings
12-90 Cable Diagnostic
Option: Function:
Enables/disables advanced Cable diagnosis function. If enabled, the distance to cable errors can be read out in 12-93 Cable Error Length. The parameter resumes to the default setting of Disable after the diagnostics have finished.
[0] Disabled [1] Enabled
NOTE
The cable diagnostics function is only issued on ports where there is no link (see 12-10 Link Status, Link Status)
12-91 Auto Cross Over
Option: Function:
[0] Disabled Disables the auto cross-over function.
[1] Enabled Enables the auto cross-over function.
12-93 Cable Error Length
Range: Function:
0 * [0 -
65535 ]
If Cable Diagnostics is enabled in 12-90 Cable Diagnostic, the built-in switch is possible via Time Domain Reflectometry (TDR). This measurement technique detects common cabling problems such as open circuits, short circuits, and impedance mismatches or breaks in transmission cables. The distance from the option to the error is displayed in meters with an accuracy of ±2 m. The value 0 means that no errors detected.
Parameters MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 39
7 7
7.3 POWERLINK - Specific Parameter List
Parameter Default value Range Conversion index Data type
8-01 Control Site [0] Dig. & ctrl. word [0-2] - Uint8 8-02 Control Word Source [0] FC RS485 [0-4] - Uint8 8-03 Control Word Timeout Time 1 0.1-18000 -1 Uint32 8-04 Control Word Timeout Function [0] Off [0-10] - Uint8 8-05 End-of-Timeout Function [0] Hold set-up [0-1] - Uint8 8-06 Reset Control Word Timeout [0] Do not reset [0-1] - Uint8 8-07 Diagnosis Trigger [0] Disable [0-3] - Uint8 8-10 Control Word Profile [0] FC profile [0-x] - Uint8 8-13 Configurable Status Word STW 8-50 Coasting Select [3] *Logic OR [0-3] - Uint8 8-51 Quick Stop Select [3] *Logic OR [0-3] - Uint8 8-52 DC Brake Select [3] *Logic OR [0-3] - Uint8 8-53 Start Select [3] *Logic OR [0-3] - Uint8 8-54 Reversing Select [3] *Logic OR [0-3] - Uint8 8-55 Set-up Select [3] *Logic OR [0-3] - Uint8 8-56 Preset Reference Select [3] *Logic OR [0-3] - Uint8
8-90 Bus Jog 1 Speed 100 rpm
0-4-13 Motor Speed
High Limit [RPM]
67 Uint16
8-91 Bus Jog 2 Speed 200 rpm
0-4-13 Motor Speed
High Limit [RPM]
67 Uint16 12-00 IP Address Assignment [20] *From node ID - - Unsigned 8 12-01 IP Address 192.168.100.xxx - - Unsigned 32 12-02 Subnet Mask 255.255.255.0 - - Unsigned 32 12-03 Default Gateway 0.0.0.0 - - Unsigned 32 12-08 Host Name - - String 12-09 Physical Address 00:1B:08:00:00:00 - - Visible string 17 12-10 Link Status [0] No Link [0-1] - Unsigned 8 12-11 Link Duration 00:00:00:00 - - Time diff. w/date 12-12 Auto Negotiation [1] On [0-1] - Unsigned 8 12-13 Link Speed [0] None [0-2] - Unsigned 8 12-14 Link Duplex [1] Full Duplex [0-1] - Unsigned 8[ 12-20 Control Instance Application Dependent 0-255 12-21 Process Data Config Write Application Dependent 12-22 Process Data Config Read 16 1-32 12-23 Process Data Config Write Size 16 1-32 12-24 Process Data Config Read Size 0 0-4294967295 12-28 Store Data Values 12-29 Store Always [0] Off 12-60 Node ID [0] [0-240] Unsigned 8 12-80 FTP Server [0] Disable [0–1] - Unsigned 8 12-81 HTTP Server [0] Disable [0–1] - Unsigned 8 12-82 SMTP Service [0] Disable [0–1] - Unsigned 8 12-89 Transparent Socket Channel Port [0] Disable [0–1] - Unsigned 8 12-90 Cable Diagnostic [0] Disable [0-1] - Unsigned 8 12-91 Auto Cross Over [0] Enable [0-1] - Unsigned 8 12-93 Cable Error Length 0 0-200 0 Unsigned 16 12-98 Interface Counters 0 0-65535 - Unsigned 16 12-99 Media Counters 0 0-65535 - Unsigned 16 16-84 Comm. Option STW 0 0-FFFF 0 V2 16-90 Alarm Word 0 0-FFFF 0 Uint32
Parameters MCA 123 POWERLINK Operating Instructions
40 MG92C102 - VLT® is a registered Danfoss trademark
77
Parameter Default value Range Conversion index Data type
16-92 Warning Word 0 0-FFFF 0 Uint32
Table 7.1 Specific Parameters
Refer to the relevant Operating Instructions for a comprehensive parameter list.
Parameters MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 41
7 7
8 Application Examples
8.1 Example: Process Data with PDO 23
This example shows how to work with PDO 23, which consists of Control Word/Status Word and Reference/Main Actual Value. In the example the frequency converter is set
to FC profile in 8-10 Control Word Profile. The PDO contains up to ten objects, which can be programmed to monitor process signals.
PCD
0 1 2 3
CTW MRV PCD[2] PCD
From controller
04 7C 20 00 00 00 00 00
STW MAV PCD[2] PCD[3]
From frequency
converter
0F
07
20
00
3F A6 00 08
Byte # 1 2 3 4 5 6 7 8
Table 8.1 Example of FC Profile
The application requires monitoring of the motor torque and digital input, so PCD 2 is set up to read the current motor torque. PCD 3 is set up to monitor the state of an external sensor via the process signal digital input. The sensor is connected to digital input 18.
An external device is also controlled via control word bit 11 and the built-in relay of the frequency converter. Reversing is permitted only when the reversing bit 15 in the control word and the digital input 19 are set to high.
For safety reasons, the frequency converter stops the motor if the POWERLINK cable is broken, the master has a system failure, or the PLC is in stop mode.
Recieve PDO’s (PLC Drive)
Transmit PDO’s (Drive
PLC )
PCD 0
CTW
PCD 1
REF
PCD 3
Digital Inputs
PCD 0
STW
PCD 1
MAV
PCD 2
Torque [Nm]
Sensor
Reversing
18
Ext. Device
Relay 04-05
230 VAC
12
20
19
+
-
13
20
­+
130BD148.10
Illustration 8.1 Application Example
Application Examples MCA 123 POWERLINK Operating Instructions
42 MG92C102 - VLT® is a registered Danfoss trademark
88
Program the frequency converter as shown in Table 8.2.
Parameter Setting 4-10 Motor Speed Direction [2] Both directions 5-10 Terminal 18 Digital Input [0] No operation 5-11 Terminal 19 Digital Input [10] Reversing 5-40 Function Relay [36/37] Control word bit 11/12 8-03 Control Word Timeout Time 1 s 8-04 Control Word Timeout Function [2] Stop 8-10 Control Word Profile [0] FC Profile 8-50 Coasting Select [1] Bus 8-51 Quick Stop Select [1] Bus 8-52 DC Brake Select [1] Bus 8-53 Start Select [1] Bus 8-54 Reversing Select [2] Logic AND 8-55 Set-up Select [1] Bus 8-56 Preset Reference Select [1] Bus
Table 8.2 Programming of Frequency Converter
Application Examples MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 43
8 8
8.2 Example: Simple Control Word, Reference, Status Word and Main Actual Value
This example shows how the control word telegram relates to the controller and the frequency converter, using FC Control Profile.
The control word telegram is sent from the PLC to the frequency converter. Standard Telegram 1 is used in the
example to demonstrate the full range of modules. All the values shown are arbitrary, and are provided for demonstration purposes only.
PCD
0 1 2 3
CTW MRV PCD PCD
04 7C 20 00
PQW:
256 258
260 262
CTW MRV
Bit no.:
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 0 0 0 0 1 0 0 0 1 1 1 1 1 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0
0 4 7 C 2 0 0 0
Table 8.3 Standard Telegram 1 Example
Table 8.3 indicates the bits contained within the control word, and how they are presented as process data in Standard Telegram 1 for this example.
Table 8.4 indicates which bit functions, and which corresponding bit values are active for this example.
Bit Bit value=0 Bit value=1 Bit value 00 Reference value External selection lsb 0
C
01 Reference value External selection msb 0 02 DC brake Ramp 1 03 Coasting Enable 1 04 Quick stop Ramp 1
7
05 Freeze output Ramp enable 1 06 Ramp stop Start 1 07 No function Reset 0 08 No function Jog 0
4
09 Ramp 1 Ramp 2 0 10 Data not valid Valid 1 11 No function Relay 01 active 0 12 No function Relay 02 active 0
0
13 Parameter set-up Selection lsb 0 14 Parameter set-up Selection msb 0 15 No function Reversing 0
Function active
Function inactive
Table 8.4 Bit Functions
Application Examples MCA 123 POWERLINK Operating Instructions
44 MG92C102 - VLT® is a registered Danfoss trademark
88
9 Troubleshooting
9.1.1 LED Status
MCA123 POWERLINK
SW. ver. TM. ver.
S/E LED
L/C LED P1
L/C LED P2
Port 1 Port 2
Option A 130B1489
MAC 00-1B-08-00-00-00
Address
8 7 6 5 4 3 2 1
ON OFF
Powerlink Port 1 Powerlink Port2
Status/error Link/Collision Port 1
Link/Collision Port 2
130BD146.10
Illustration 9.1 LED Status
Power OFF or state LED NMT_GS NMT_GS_INITIALISATION NMT_CS_NOT_ACTIVE NMT_MS_NOT_ACTIVE
Green:
Device Operational Green:
Flickering NMT_CS_BASIC_ETHERNET Green:
Blinking NMT_CS_Stopped Green:
Single flash NMT_CS_PRE_OPERATIONAL_1 NMT_MS_PRE_OPERATIONAL_1
Green:
Double flash NMT_CS_PRE_OPERATIONAL_2 NMT_MS_PRE_OPERATIONAL_2
Green:
Triple flash NMT_CS_READY_TO_OPERATE NMT_MS_READY_TO_OPERATE
Green:
Table 9.1 S/E LED
Power OFF or NO Link
Green:
Link Green:
Table 9.2 L/C LED
Troubleshooting MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 45
9
9
9.1.2 No Communication with the Frequency Converter
If there is no communication with the frequency converter, proceed with the following checks:
Check 1: Is the cabling correct? Check that the cable is mounted correctly. Check if the corresponding XDD files L/C LED shows link activity.
Check 2: Does the hardware configuration match? Check that the 12-60 Node ID in the master matches the value in 12-50 Configured Station Alias
Check 3: Is the correct XDD file installed? Download the correct XDD file from
http://www.danfoss.com/BusinessAreas/DrivesSolutions/.
Check that the process data matches the active profile in the drive.
Check 4: What is the value of 12-69 Ethernet PowerLink Status? The 12-69 Ethernet PowerLink Status contains 32 bits, which each is linked to internal information. The different bits give an overview over possible errors.
Bit no.
Description Value=[0]Value=[1] Comment
0 Initialisation
State
NMT_GS_INITIL
ASATION
Mapped to Object 1F8Ch (WHAT79188)
1 Not Active
State
NMT_CS_NOT_
ACTIVE
Mapped to Object 1F8Ch (WHAT79188)
2 Basic
Ethernet State
NMT_CS_BASIC
_ETHERNET
Mapped to Object 1F8Ch (WHAT79188)
3 Pre-
Operational 1 State
NMT_CS_PRE_
OPERATIONAL_ 1
Mapped to Object 1F8Ch (WHAT79188)
4 Pre-
Operational 2 State
NMT_CS_PRE_
OPERATIONAL_ 2
Mapped to Object 1F8Ch (WHAT79188)
5 Ready to
Operate State
NMT_CS_OPER
ATIONAL
Mapped to Object 1F8Ch (WHAT79188)
6 Operational
State
NMT_CS_STOP
PED
Mapped to Object 1F8Ch (WHAT79188)
7 Stopped
State
Value shall be
read as 0
8 Reserved Value shall be
read as 0
Bit no.
Description Value=[0]Value=[1] Comment
9 Reserved Value shall be
read as 0
10 Reserved Value shall be
read as 0
11 Reserved Value shall be
read as 0
12 Reserved Value shall be
read as 0
13 Reserved Value shall be
read as 0
14 Reserved Value shall be
read as 0
15 Reserved Value shall be
read as 0
16 Reserved Value shall be
read as 0
17 Reserved Value shall be
read as 0
18 Reserved Value shall be
read as 0
19 Reserved Value shall be
read as 0
20 Physical link
on Port 1
No link present on Port 1
Link present on Port 1
Mapped to object 1030h subindex 7
21 Physical link
on Port 2
No link present on Port 2
Link present on Port 2
Mapped to object 1030h subindex 7
22 Reserved Value shall be
read as 0
23 Reserved Value shall be
read as 0
24 W34 source
No Op State
Mapped to
object 178Ch (WHAT79188)
25 W34 source
Alarm
Mapped to
Alarm Word and Alarm Word 1
26 W34 source
IP Address Conflict
IP address
conflict detection in Basic Ethernet mode
27 W34 source
Invalid Node ID
Value read from
DIP switch
28 W34 source
Incorrect PDO mapping
Set on incorrect
Tx or Rx PDO mapping
29 Reserved Value shall be
read as 0
Troubleshooting MCA 123 POWERLINK Operating Instructions
46 MG92C102 - VLT® is a registered Danfoss trademark
9
Bit no.
Description Value=[0]Value=[1] Comment
30 Reserved Value shall be
read as 0
31 Reserved Value shall be
read as 0
Table 9.3 POWERLINK Bits
9.1.3 Warning 34 Appears even though Communication is Established
If the master is in stop mode, Warning 34 appears. Check that the master is in run mode. If the frequency converter is not in operational state Warning 34 will appear (60 s after power up or immediately if the frequency converter has been in operational state).
9.1.4
Frequency Converter Does Not Respond to Control Signals
Check 1: Is the Control word valid? If bit 10=0 in the Control word, the frequency converter does not accept the Control word.
Check 2: Is the relationship between bits in the Control word and the terminal I/Os correct? Check the logical relationship in the frequency converter.
Define the desired logical relationship in 8-50 Coasting Select to 8-56 Preset Reference Select according to the following range of options. Select the FC control mode, digital input and/or serial communication, using 8-50 Coasting Select to 8-56 Preset Reference Select.
If 8-01 Control Site is set to digital only, then the frequency converter will not react on commands send via the control word.
Table 9.4 to Table 9.11 show a coast command's effect upon the frequency converter for the full range of 8-50 Coasting Select settings.
The effect of control mode upon the function of
8-50 Coasting Select, 8-51 Quick Stop Select, and 8-52 DC Brake Select is as follows:
If [0] Digital input is selected, the terminals control the Coast and DC Brake functions.
NOTE
Coasting, Quick Stop, and DC brake functions are active for logic 0.
Terminal Bit 02/03/04 Function 0 0 Coast/DC brake/Q-Stop 0 1 Coast/DC brake/Q-Stop 1 0 No Coast/DC brake/Q-Stop 1 1 No Coast/DC brake/Q-Stop
Table 9.4 [0] Digital Input
If [1] Serial communication is selected, commands are activated only when given via serial communication.
Terminal Bit 02/03/04 Function 0 0 Coast/DC brake/Q-Stop 0 1 No Coast/DC brake/Q-Stop 1 0 Coast/DC brake/Q-Stop 1 1 No Coast/DC brake/Q-Stop
Table 9.5 [1] Serial Communication
If [2] Logic AND is selected, both signals must be activated to perform the function.
Terminal Bit 02/03/04 Function 0 0 Coast/DC brake/Q-Stop 0 1 No Coast/DC brake/Q-Stop 1 0 No Coast/DC brake/Q-Stop 1 1 No Coast/DC brake/Q-Stop
Table 9.6 [2] Logic AND
If [3] Logic OR is selected, activation of one signal activates the function.
Terminal
Bit 02/03/04 Function 0 0 Coast/DC brake/Q-Stop 0 1 Coast/DC brake/Q-Stop 1 0 Coast/DC brake/Q-Stop 1 1 No Coast/DC brake/Q-Stop
Table 9.7 [3] Logic OR
The effect of control mode upon the function of 8-53 Start Select and 8-54 Reversing Select:
If [0] Digital input is selected, the terminals control the start and reversing functions
Terminal
Bit 06/15 Function 0 0 Stop/Anti-clockwise 0 1 Stop/Anti-clockwise 1 0 Start/Clockwise 1 1 Start/Clockwise
Table 9.8 [0] Digital input
Troubleshooting MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 47
9
9
If [1] Serial communication is selected, commands are activated only when given via serial communication.
Terminal Bit 02/03/04 Function 0 0 Stop/Anti-clockwise 0 1 Start/Clockwise 1 0 Stop/Anti-clockwise 1 1 Start/Clockwise
Table 9.9 [1] Serial Communication
If [2] Logic AND is selected, both signals must be activated to perform the function.
Terminal Bit 02/03/04 Function 0 0 Stop/Anti-clockwise 0 1 Stop/Anti-clockwise 1 0 Stop/Anti-clockwise 1 1 Start/Clockwise
Table 9.10 [2] Logic AND
If [3] Logic OR is selected, activation of one signal activates the function.
Terminal
Bit 02/03/04 Function 0 0 Stop/Anti-clockwise 0 1 Start/Clockwise 1 0 Start/Clockwise 1 1 Start/Clockwise
Table 9.11 [3] Logic OR
The effect of control mode upon the function of 8-55 Set- up Select and 8-56 Preset Reference Select:
If [0] Digital input is selected, the terminals control the set­up and preset reference functions.
Terminal
Bit 00/01, 13/14 Function Msb Lsb Msb Lsb Preset ref. Set-up no. 0 0 0 0 1 0 0 0 1 1 0 0 1 0 1 0 0 1 1 1 0 1 0 0 2 0 1 0 1 2 0 1 1 0 2 0 1 1 1 2 1 0 0 0 3 1 0 0 1 3 1 0 1 0 3 1 0 1 1 3 1 1 0 0 4 1 1 0 1 4 1 1 1 0 4 1 1 1 1 4
Table 9.12 [0] Digital Input
If [1] Serial communication is selected, commands are activated only when given via serial communication.
Terminal
Bit 00/01, 13/14 Function Msb Lsb Msb Lsb Preset ref. Set-up no. 0 0 0 0 1 0 0 0 1 2 0 0 1 0 3 0 0 1 1 4 0 1 0 0 1 0 1 0 1 2 0 1 1 0 3 0 1 1 1 4 1 0 0 0 1 1 0 0 1 2 1 0 1 0 3 1 0 1 1 4 1 1 0 0 1 1 1 0 1 2 1 1 1 0 3 1 1 1 1 4
Table 9.13 [1] Serial Communication
If [2] Logic AND is selected, both signals must be activated to perform the function.
Troubleshooting MCA 123 POWERLINK Operating Instructions
48 MG92C102 - VLT® is a registered Danfoss trademark
9
Terminal Bit 00/01, 13/14 Function Msb Lsb Msb Lsb Preset ref. Set-up no. 0 0 0 0 1 0 0 0 1 1 0 0 1 0 1 0 0 1 1 1 0 1 0 0 1 0 1 0 1 2 0 1 1 0 1 0 1 1 1 2 1 0 0 0 1 1 0 0 1 1 1 0 1 0 3 1 0 1 1 3 1 1 0 0 1 1 1 0 1 2 1 1 1 0 3 1 1 1 1 4
Table 9.14 [2] Logic AND
If [3] Logic OR is selected, activation of one signal activates the function.
Terminal
Bit 00/01, 13/14 Function Msb Lsb Msb Lsb Preset ref, Set-up no. 0 0 0 0 1 0 0 0 1 2 0 0 1 0 3 0 0 1 1 4 0 1 0 0 2 0 1 0 1 2 0 1 1 0 4 0 1 1 1 4 1 0 0 0 3 1 0 0 1 4 1 0 1 0 3 1 0 1 1 4 1 1 0 0 4 1 1 0 1 4 1 1 1 0 4
Table 9.15 [3] Logic OR
9.1.5
Alarm and Warning Words
Alarm word, Warning word, and POWERLINK Status word are shown in the display in Hex format. If there is more than one warning or alarm, a sum of all warnings or alarms is shown. Alarm word, warning word, and POWERLINK Status word can also be displayed using the serial bus in
16-90 Alarm Word, 16-92 Warning Word, and 12-69 Ethernet PowerLink Status.
Bit (Hex)
Unit diagnose bit
Alarm word (16-90 Alarm Word)
Alarm no.
00000001 48 Brake check 28 00000002 49 Power card over
temperature
29
00000004 50 Earth fault 14 00000008 51 Control card over
temperature
65
00000010 52 Control word timeout 18 00000020 53 Over current 13 00000040 54 Torque limit 12 00000080 55 Motor thermistor over
temp.
11
00000100 40 Motor ETR over
temperature
10
00000200 41 Inverter overloaded 9 00000400 42 DC link under voltage 8 00000800 43 DC link over voltage 7 00001000 44 Short circuit 16 00002000 45 Inrush fault 33 00004000 46 Mains phase loss 4 00008000 47 AMA not OK 50 00010000 32 Live zero error 2 00020000 33 Internal fault 38 00040000 34 Brake overload 26 00080000 35 Motor phase U is missing 30 00100000 36 Motor phase V is missing 31 00200000 37 Motor phase W is missing 32 00400000 38 Fieldbus comm. fault 34 00800000 39 24 V supply fault 47 01000000 24 Mains failure 36 02000000 25 1.8 V supply fault 48 04000000 26 Brake resistor short circuit 25 08000000 27 Brake chopper fault 27 10000000 28 Option change 67 20000000 29 Drive initialisation 80 40000000 30 Safe stop 68 80000000 31 Mechanical brake low 63
Table 9.16 FC 301/FC 302
Troubleshooting MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 49
9
9
Bit (Hex) Unit
diagnose bit
Warning word (16-92 Warning Word)
Alarm no.
00000001 112 Brake check 28 00000002 113 Power card over
temperature
29
00000004 114 Earth fault 14 00000008 115 Control card 65 00000010 116 Control word timeout 18 00000020 117 Over current 13 00000040 118 Torque limit 12 00000080 119 Motor thermistor over
temp.
11
00000100 104 Motor ETR over
temperature
10
00000200 105 Inverter overloaded 9 00000400 106 DC link under voltage 8 00000800 107 DC link over voltage 7 00001000 108 DC link voltage low 6 00002000 109 DC link voltage high 5 00004000 110 Mains phase loss 4 00008000 111 No motor 3 00010000 96 Live zero error 2 00020000 97 10 V low 1 00040000 98 Brake overload 26 00080000 99 Brake resistor short circuit 25 00100000 100 Brake chopper fault 27 00200000 101 Speed limit 49 00400000 102 Fieldbus comm. fault 34 00800000 103 24 V supply fault 47 01000000 88 Mains failure 36 02000000 89 Current limit 59 04000000 90 Low temperature 66 08000000 91 Voltage limit 64 10000000 92 Encoder loss 61 20000000 93 Output frequency limit 62 40000000 94 Unused ­80000000 95 Warning word 2 (ext. stat.
word)
-
Table 9.17 FC 301/FC 302
Bit (Hex)
Comm. option STW (16-84 Comm. Option STW)
00000001 parameterization ok 00000002 configuration ok 00000004 clearmode active 00000008 baudrate search 00000010 waiting for parameterization 00000020 waiting for configuration 00000040 in data exchange 00000080 not used 00000100 not used 00000200 not used 00000400 not used 00000800 MCL2/1 connected 00001000 MCL2/2 connected 00002000 MCL2/3 connected 00004000 data transport active 00008000 not used
Table 9.18 FC 301/FC 302
NOTE
16-84 Comm. Option STW is not part of extended diagnosis.
9.1.6 Warning and Alarm Messages
There is a clear distinction between alarms and warnings. When there is an alarm, the frequency converter enters a fault condition. After the cause for the alarm has been cleared, the master will have to acknowledge the alarm message before the frequency converter can start operating again. A warning, on the other hand, may come when a warning condition appears, then disappear when conditions return to normal, without interfering with the process.
Warnings A single bit within a warning word represents warnings within the frequency converter. Bit status [0] False means no warning, while bit status [1] True means warning. Any bit change in the warning word is notified by a change of bit 7 in the status word.
Alarms Following an alarm message, the frequency converter enters fault condition. When the fault has been removed and the controller has acknowledged the alarm message by setting bit 7 in the control word, the frequency converter resumes operation. A single bit within an alarm word represents alarms within the frequency converter. Bit status [0] False means no fault, while bit status [1] True means fault.
Troubleshooting MCA 123 POWERLINK Operating Instructions
50 MG92C102 - VLT® is a registered Danfoss trademark
9
Index
A
Abbreviations........................................................................................... 4
Alarm Word............................................................................................. 49
Assumptions............................................................................................. 3
B
Background Knowledge....................................................................... 3
C
Cabling..................................................................................................... 39
Configuration...................................................................... 33, 34, 38, 4
Control Profile........................................................................................ 16
D
DC Backup................................................................................................. 3
DeviecNet.................................................................................................. 3
E
EMC Precautions..................................................................................... 9
EtherCAT.................................................................................................... 3
Ethernet........................................................................................ 9, 37, 39
H
Hardware.............................................................................................. iii, 3
I
I/O................................................................................................................. 4
Installation....................................................................................... iii, 3, 5
IP Settings................................................................................................ 10
IP21/Type 1................................................................................................ 3
L
LED
LED........................................................................................................... 4
Status.................................................................................................... 45
Literature.................................................................................................... 3
N
Network............................................................................................. 3, 9, 5
No
Communication................................................................................ 46
Respose To Control Signals.......................................................... 47
O
Overview.................................................................................................... 6
P
Parameters......................................................................................... iii, 10
PDO Communication.......................................................................... 14
Process
Control Data....................................................................................... 14
Control Operation............................................................................ 15
Status Data......................................................................................... 14
Profibus....................................................................................................... 3
R
Reference................................................................................................... 4
S
Safety.......................................................................................................... iii
T
Topology.................................................................................................... 8
V
VLT Parameters...................................................................................... 10
W
Warning Word........................................................................................ 49
Index MCA 123 POWERLINK Operating Instructions
MG92C102 - VLT® is a registered Danfoss trademark 51
Loading...