Danfoss MCA 123 Operating guide

MAKING MODERN LIVING POSSIBLE
Operating Instructions
MCA 123 POWERLINK
vlt-drives.danfoss.com
Safety Operating Instructions
Safety
This publication contains information proprietary to Danfoss. By accepting and using this manual, the user agrees that the information contained herein is used solely for operating equipment from Danfoss or equipment from other vendors if such equipment is intended for communi­cation with Danfoss equipment over a serial communication link. This publication is protected under the Copyright laws of Denmark and most other countries.
Danfoss does not guarantee that a software program produced according to the guidelines provided in this manual functions properly in every physical, hardware, or software environment.
Although Danfoss has tested and reviewed the documen­tation within this manual, Danfoss gives no warranty or representation, either expressed or implied, with respect to this documentation. This includes its quality, performance, or rness for a particular purpose.
In no event shall Danfoss be liable for direct, indirect, special, incidental, or consequential damages arising out of the use, or the inability to use information contained in this manual, even if advised of the possibility of such damages. In particular, Danfoss is not responsible for any costs including, but not limited to those incurred as a result of lost prots or revenue, loss or damage of equipment, loss of computer programs, loss of data, the costs to substitute these, or any claims by third parties.
1. The frequency converter must be disconnected from mains before carrying out repair work. Check that the mains supply has been discon­nected and that the necessary time has passed before removing motor and mains plugs.
2. The o-command on the serial bus does not disconnect the equipment from mains and should not be used as a safety switch.
3. Correct protective earthing or grounding of the equipment must be established. The user must be protected against supply voltage, and the motor must be protected against overload in accordance with applicable national and local regulations.
4. The earth leakage currents are higher than 3.5 mA.
5. Do not remove the plugs for the motor and mains supply while the frequency converter is connected to mains. Check that the mains supply has been disconnected and that the necessary time has passed before removing motor and mains plugs.
Danfoss reserves the right to revise this publication at any time and to change its contents without prior notice or any obligation to notify previous users of such revisions or changes.
It has been assumed that all devices are sitting behind a rewall that does packet ltering and the environment has implemented restrictions on the software that can run inside the rewall. All nodes are assumed to be "trusted" nodes.
WARNING
HIGH VOLTAGE
The voltage of the frequency converter is dangerous whenever connected to mains. Incorrect installation of the motor, frequency converter, or eldbus may damage the equipment, cause serious personal injury, or death. Consequently, the instructions in this manual, as well as national and local rules and safety regulations, must be complied with.
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved.
Safety MCA 123 POWERLINK
1. The motor can be brought to a stop with bus commands while the frequency converter is connected to mains. These stop functions do NOT provide protection against unintended starts.
2. While parameters are being changed, there is a risk that motor starts.
3. Electronic faults in the frequency converter and cease of
temporary overload
faults in supply mains, or
fault in the motor connection
can cause an unintended start.
WARNING
ELECTRICAL HAZARD
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains.
Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
Contents Operating Instructions
Contents
1 Introduction
1.1 General Information
1.1.1 About this Manual 3
1.1.2 Assumptions 3
1.1.3 Hardware 3
1.1.4 Background Knowledge 3
1.1.5 Available Literature 3
1.1.6 Abbreviations 4
2 How to Install
2.1 Installation
2.1.1 How to Install Option in Frequency Converter 5
2.1.2 Network 5
2.1.3 POWERLINK Cables 6
2.1.4 LED Behaviour 6
2.1.5 Topology 7
2.1.6 EMC Precautions 8
3 3
5 5
3 How to Congure
3.1 Congure the Parameters
3.1.1 IP Settings 10
3.1.2 Ethernet Link Parameters 10
3.2 Congure the Frequency Converter
3.2.1 VLT Parameters 10
3.3 Congure the POWERLINK Network
4 Congure the Master
4.1 Importing the XDD File
4.2 Setting Up the Master
5 How to Control the Frequency Converter
5.1 PDO Communication
5.2 Process Data
5.2.1 Process Control Data 15
5.2.2 Process Status Data 15
5.2.3 Reference Handling 16
10 10
10
10
12 12 12
15 15 15
5.2.5 Inuence of the Digital Input Terminals upon FC Control Mode 17
5.3 Control Prole
5.4 DS 402 Control Prole
5.4.1 Control Word According to DSP 402 Prole (Parameter 8-10=DSP 402 prole) 17
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 1
17 17
Contents MCA 123 POWERLINK
5.4.2 Status Word According to DS 402 Prole 18
5.4.3 DSP 402 State Transitions 21
5.5 Danfoss FC Control Prole
6 Communication Prole Area
6.1 Description - Communication Prole Area
6.2 1000-1FFF Communication Object Area
6.3 2000-5FFF Danfoss Specic Object Area
6.4 6000-Device prole Object Area
7 Parameters
7.1 Parameter Group 8-** Communication and Option
7.2 Parameter Group 12-** Ethernet
7.3 POWERLINK - Specic Parameter List
8 Application Examples
8.1 Example: Process Data with PDO 23
8.2 Example: Simple Control Word, Reference, Status Word and Main Actual Value
9 Troubleshooting
9.1 LED Status
21
25 25 25 31 31
34 34 38 41
44 44 46
48 48
9.2 Communication Problems
9.2.1 No Communication with the Frequency Converter 49
9.2.2 Endless Power-down - Power-up Cycle 52
9.3 Warnings and Alarms
9.3.1 Alarm and Warning Words 52
Index
49
52
55
2 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
Introduction
Operating Instructions
1 Introduction
1.1 General Information
1.1.1 About this Manual
Chapters
chapter 1 Introduction chapter 2 How to Install chapter 3 How to
contain essential information for quick installation and set­up.
For more detailed information, including the full range of set-up options and diagnosis tools, refer to the chapters:
chapter 4 chapter 5 How to Control the Frequency Converter chapter 7 Parameters chapter 8 Application Examples chapter 9 Troubleshooting
Terminology
In this manual the term Ethernet is used to describe the physical layer of the network and does not relate to the application protocol.
Assumptions
1.1.2
These Operating Instructions are under the conditions that the Danfoss POWERLINK option is used with a Danfoss
VLT® AutomationDrive FC 301/FC 302 or FCD 302 frequency converter. The installed controller must support the interfaces described in this manual. Strictly observe all the requirements stipulated in the controller and the frequency converter, along with all limitations herein.
Hardware
1.1.3
This manual relates to the POWERLINK option MCA 123, ordering number 130B5546 (uncoated) and 130B5646 (conformal coated).
1.1.4
Background Knowledge
The Danfoss POWERLINK option card is designed to communicate with any system complying with the POWERLINK standard. Familiarity with this technology is assumed. Issues regarding hardware or software produced by other manufacturers, including commissioning tools, are
Congure
Congure the Master
beyond the scope of this manual, and not the responsi­bility of Danfoss.
For information regarding commissioning tools, or communication to a non-Danfoss node, consult the appropriate manuals.
1.1.5 Available Literature
-
The VLT® AutomationDrive Operating Instructions provide the necessary information for getting the frequency converter up and running.
-
-
-
-
-
-
-
-
-
-
-
-
Danfoss technical literature is also available online at
www.danfoss.com/BusinessAreas/DrivesSolutions/
®
The VLT technical information about the frequency converter design and applications including encoder, resolver, and relay options.
The VLT® AutomationDrive Probus Operating Instructions provide the information required for controlling, monitoring, and programming the frequency converter via a Probus eldbus.
The VLT Instructions provide the information required for controlling, monitoring, and programming the frequency converter via a DeviceNet eldbus.
The MCT 10 Set-up Software Operating Instructions provide information for installation and use of the software on a PC.
The VLT provides information for installing the IP21/Type 1 option.
The VLT Instruction provides information for installing the 24 V DC Back-up option.
The VLT Instructions.
The VLT Instructions.
The MCA 121 Ethernet/IP Operating Instructions. The MCA 120 PROFINET Operating Instructions. The MCA 124 EtherCAT Operating Instructions. The MCA 122 Modbus TCP Operating Instructions.
AutomationDrive Design Guide entails all
®
AutomationDrive DeviceNet Operating
®
AutomationDrive IP21/Type 1 Instruction
®
AutomationDrive 24 V DC Back-up
®
AutomationDrive CANOpen Operating
®
AutomationDrive Modbus TCP Operating
1
1
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 3
Introduction MCA 123 POWERLINK
1.1.6 Abbreviations
1
Abbre­viation
API Actual Packet Interval ASnd AsynchronousSend CC Control card CTW Control word DCP Discovery and Conguration Protocol DHCP Dynamic Host Conguration Protocol Conguration EMC Electromagnetic Compatibility I/O Input/Output IP Internet Protocol PDO Process Data Object LCP Local Control Panel LED Light Emitting Diode LSB Least Signicant Bit MAV Main Actual Value (actual output) MN Managing Node MSB Most Signicant Bit MRV Main Reference Value N/A Not applicable PC Personal Computer PCD Process Control Data PLC Programmable Logic Controller PNU Parameter Number REF Reference (=MRV) SDO Service Data Object SoC Start Of Cycle Frame SoA Start Of Asynchronous STW Status Word
Denition
Table 1.1 Overview of Abbreviations
4 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
EtherNet Port1
EtherNet Port2
MCA 121 Option A EtherNet/IP 130B1119 MS MS1 MAC-00-1B-08-00-00-22 MS2 SW.ver.
130BT797.10
How to Install
2 How to Install
2.1 Installation
Operating Instructions
2.1.1 How to Install Option in Frequency Converter
Before installing the option, make sure that the installed rmware revision supports the POWERLINK option. Following minimum versions of the frequency converter rmware are required:
POWERLINK option
rmware version
1.01
1.12 FC 301 6.81
Table 2.1 Minimum Firmware Versions
Items required for installing the eldbus option in the frequency converter
Fieldbus option
Fieldbus option adaptor frame for the FC Series.
This frame is deeper than the standard frame to allow space for the eldbus option beneath.
Strain relief (only for A1 and A2 enclosures)
Frequency converter minimum
rmware version
FC 301 6.72 FC 302 6.72
FC 302 6.81 FCD 302 6.81
Illustration 2.2 Strain Relief for A1 and A2 Enclosures
Instructions
1. Remove LCP panel from the FC Series.
2. Remove the frame located beneath and discard it.
3. Push the option into place. The Ethernet connectors must be facing upwards.
4. Remove knock-out on the
eldbus option adaptor
frame.
5. Push the eldbus option adaptor frame for the FC Series into place.
6. Replace the LCP and attach cable.
2 2
Illustration 2.1 Fieldbus Option Adaption Frame
NOTICE
Do not strip and earth the Ethernet cable via the strain relief-plate! The earthing of screened Ethernet cable is done through the RJ-45 connector on the option.
NOTICE
After installing the MCA 123 POWERLINK option, set
parameter 8-01 Control Site to: [2] Control word only or [0] Digital and ctrl. word. parameter 8-02 Control Word Source to: [3] Option A
2.1.2 Network
It is important that the media selected for Ethernet data transmission meets the required properties. Usually CAT 5e and six cables are recommended for industrial applications. Both types are available as unscreened twisted pair and screened twisted pair. Generally, screened cables are recommended for use in industrial environments and with frequency converters. A maximum cable-length of 100 m is allowed between network devices.
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 5
MCA123 POWERLINK
SW. ver. TM. ver.
S/E LED
L/C LED P1
L/C LED P2
Port 1 Port 2
Option A 130B1489
MAC 00-1B-08-00-00-00
Address
8 7 6 5 4 3 2 1
ON OFF
130BD146.11
1
2
3 4 5
6
A
B
A
B
How to Install MCA 123 POWERLINK
2.1.3 POWERLINK Cables
Cable type Specication
S/E LED
Illustration 2.4 S/E LED Status - Power OFF or State
Ethernet standard Standard Ethernet (in accordance with IEEE
802.3), 100Base-TX (Fast Ethernet)
Cable Type S/FTP (screened foiled twisted pair, ISO (IEC
22
Damping 23.2 dB (at 100 MHz and 100 m each) Crosstalk
11801 or EN 50173), CAT 5e
24 dB (at 100 MHz and 100 m each)
Illustration 2.5 S/E LED Status - Green (A)/Red (B) Flash
damping Return loss 10 dB (100 m each) Surge impedance
Table 2.2 Specication of POWERLINK Cables
LED Behaviour
2.1.4
The option has 3 bicolored LEDs that allow a fast and detailed diagnosis. The three LEDs are each linked to its
100 Ω
Illustration 2.6 S/E LED Status - Flickering Green
Illustration 2.7 S/E LED Status - Solid Green
unique part of the POWERLINK option:
LED label Description
Status/Error Module Status, reects the activity on the
POWERLINK slave. Link/Collision Port 1 Link/Collision Port 2
Link/Collision Port 1, reects the activity on the
POWERLINK port 1.
Link/Collision Port 2, reects the activity on the
POWERLINK port 2.
Illustration 2.8 S/E LED Status - Blinking Red
Illustration 2.9 S/E LED Status - Single Green Flash
Table 2.3 LEDs
Illustration 2.3 Overview of the Option
Item # Description
1 POWERLINK port 1 2 POWERLINK port 2 3 Status/error 4 Link/collision port 1 5 Link/collision port 2 6 Node ID dip switches
Table 2.4 Legend to Illustration 2.3
Illustration 2.10 S/E LED Status - Red (B)/Green (A) Flash
Illustration 2.11 S/E LED Status - Double Green Flash
Illustration 2.12 S/E LED Status - Tripple Green Flash
Illustration 2.13 S/E LED Status - Yellow Flash
6 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
A
B
A
B
How to Install Operating Instructions
LED ash
pattern
Power OFF or State
Flickering Green
Solid green POWERLINK
Blinking greed Single green
ash
Red/green
ash
Double green ash
Tripple green ash Yellow ash Wink command Node Identication
Table 2.5 S/E LED Pattern
Powerlink option state Description
NMT_GS, NMT_GS_INITIALISATION NMT_CS_NOT_ACTIVE, Basic Ethernet mode POWERLINK
NMT_CS_Stopped PLC has stopped
NMT_CS_PRE_OPERATIONAL_1 POWERLINK
NMT_CS_PRE_OPERATIONAL_1 Communication to
NMT_CS_PRE_OPERATIONAL_2 POWERLINK
NMT_CS_READY_TO_OPERATE POWERLINK
No power supplied to drive or Initialising
interface is in basic Ethernet mode
interface is on operational state
the Network
interface is in Pre­operation mode state 1
PLC lost
interface is in Pre­operation mode state 2
interface is
activated from MCT10
Illustration 2.16 L/C LED Status - Power-up Green (A)/Red (B)
Illustration 2.17 L/C LED Status - Collision Red (B)/Green (A)
Illustration 2.18 L/C LED Status - Yellow Flash
LED ash
pattern
Power OFF or no link
Link NMT_GS_INITIALISATION Only shown once at
Power up Various states Link established Collision Yellow ash Wink command Node Identication
Powerlink option state Description
NMT_GS, NMT_GS_INITIALISATION NMT_CS_NOT_ACTIVE
No power supplied to drive or Initialising
power up
activated from MCT 10 Set-up Software
2 2
L/C LED
Illustration 2.14 L/C LED Status - Power OFF or No Link
Illustration 2.15 L/C LED Status - Link
Topology
2.1.5
Table 2.6 L/C LED Pattern
The POWERLINK module features a built-in POWERLINK controlled node and a two-port hub. This module enables the possibility for connecting several POWERLINK options in a line topology. If more than eight frequency converters are connected in line, it requires special attention towards the timing in the network.
It is important in a POWERLINK system, that the connection is done correctly.
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 7
130BD147.10
How to Install MCA 123 POWERLINK
22
Illustration 2.19 Line Topology
Take care that following design rules are followed
1. Do not connect any non-POWERLINK device (e.g. a PC) to any free port as to avoid malfunction of the complete POWERLINK network.
2. In a line topology, power all frequency converters either by mains or by a 24 V DC option card, for the built-in POWERLINK slave controller to work.
3. To achieve interference-free operation of the Ethernet, observe the following EMC precautions. The correct handling of the motor cable screen is vital for the overall performance of the system. If the rules are not followed, it leads to loss of the control and malfunction of the system. The Ethernet communication cable must be kept away from motor and brake resistor cables to avoid coupling of high frequency noise between the cables. Normally, a minimum distance of 200 mm (8 inches) is sucient, but maintaining the greatest possible distance between the cables is recommended. Especially where cables run in parallel, over long distances, or if frequency converters with a bigger power size are installed. More information can be found in the norm IEC 61000-5-2:1997.
4. When crossing of cables is unavoidable, the Ethernet cable must cross motor and brake resistor cables at an angle of 90°.
5. Always observe relevant national and local regulations, for example regarding protective earth connection.
2.1.6 EMC Precautions
To achieve interference-free operation of the Ethernet, observe the following EMC precautions. Additional EMC
information is available in the VLT® AutomationDrive Design
Guide.
NOTICE
The correct handling of the motor cable screen is vital for the overall performance of the system. If the rules are not followed, it can lead to loss of the control and malfunction of the system.
8 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
min. 200 mm
90 ° crossing
Ethernet Cable
130BA908.11
How to Install Operating Instructions
2 2
Illustration 2.20 Correct Crossing of Ethernet Cable
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 9
How to Congure MCA 123 POWERLINK
3 How to Congure
3.1 Congure the Parameters
3.1.1 IP Settings
All IP-related parameters are located in parameter group
33
12-0* IP Settings: The parameters are all set to POWERLINK standard values, so no setting is needed. In POWERLINK, the parameter 12-00 IP Address Assignment is xed to the option "From node ID". The IP address follows the setting in parameter 12-60 Node ID, so that the IP address is
192.168.100.xxx, where xxx is the node ID. For parameter 12-02 Subnet Mask, the IP addres is
255.255.255.0 and cannot be changed.
The POWERLINK option oers two ways of node ID assignment via parameter or DIP switch.
Ethernet Link Parameters
3.1.2
Parameter group 12-1* Ethernet Link Parameters holds Ethernet Link information:
Parameter 12-10 Link Status Parameter 12-11 Link Duration Parameter 12-12 Auto Negotiation Parameter 12-13 Link Speed Parameter 12-14 Link Duplex
Each port has unique Ethernet link parameters.
Parameter 12-10 Link Status displays Link or No Link according to the status of the present port.
Parameter 12-11 Link Duration displays the duration of the link on the present port. If the link is broken, the counter is reset.
Parameter 12-12 Auto Negotiation is a feature that enables two connected Ethernet devices to select common transmission parameters, such as speed and duplex mode. In POWERLINK, this feature is changed.
xed to OFF and cannot be
xed to
In POWERLINK, the Link Duplex is xed to Half Duplex, and cannot be changed.
3.2 Congure the Frequency Converter
3.2.1 VLT Parameters
Pay particular attention to the following parameters when conguring the frequency converter with a eldbus interface.
Parameter 0-40 [Hand on] Key on LCP. If the [Hand
on] key on the frequency converter is activated, control of the frequency converter via the eldbus interface is disabled.
After an initial power-up, the frequency converter
automatically detects whether a eldbus option is installed in slot A. It then sets parameter 8-02 Control Word Source to [Option A]. Adding, changing, or removing an option from an already commissioned frequency converter does not change parameter 8-02 Control Word Source. However, it causes a trip mode, and the frequency converter displays an error.
Parameter 8-10 Control Word
between the Danfoss FC
prole. The change of parameter 8-10 Control Word Prole is active at the next power-up.
Parameter 8-50 Coasting Select to
parameter 8-56 Preset Reference Select. Selection of how to gate digital input command of the control card.
eldbus control commands with
Prole. Select
Prole and the DS 402
NOTICE
When parameter 8-01 Control Site is set to [2] Control word only, Bus-control overrules the settings in parameter 8-50 Coasting Select to parameter 8-56 Preset Reference Select.
Parameter 8-03 Control Word Timeout Time to
parameter 8-05 End-of-Timeout Function. The reaction in the event of a bus time-out is set via these parameters.
3.3
Congure the POWERLINK Network
Parameter 12-13 Link Speed - displays the link speed for each port. If no link is present, “None” is displayed. In POWERLINK, this feature is xed to 100 MBaud and cannot be changed.
Parameter 12-14 Link Duplex - displays the duplex mode for each port.
Using the hardware switches, it is possible to select an address range 0–239 (factory setting 1) according to
10 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
All POWERLINK stations that are connected to the same bus network must have a unique node address. The node address of the frequency converter can be selected via:
Hardware switches (from version 1.12)
parameter 12-60 Node ID
Setting the NODE Address using the Hardware Switches
Table 3.1:
How to Congure Operating Instructions
Switch 8 7 6 5 4 3 2 1 Address value 128 +64 +32 +16 +8 +4 +2 +1 E.g. address 5 OFF OFF OFF OFF OFF ON OFF ON E.g. address 35 OFF OFF ON OFF OFF OFF ON ON E.g. address 82 OFF ON OFF ON OFF OFF ON OFF E.g. address 157 ON OFF OFF ON ON ON OFF ON
Table 3.1
NOTICE
The switches are only read during power-up. Changes are active after the next power up, and can be read in parameter 12-60 Node ID. Note the location and sequence of the hardware switches as illustrated in Illustration 2.3.
Setting the NODE Address via parameter 12-60 Node ID
Setting the address via parameter 12-60 Node ID, is only possible if the hardware switches are set to 0 or 255 (factory setting). The address change becomes active at the next power-up. The node address has direct in parameter 12-01 IP Address. If the hardware switch is set to an illegal number, the frequency converter immediately issues Warning 34 in the display, and parameter 12-69 Ethernet PowerLink Status is set to 0 (zero).
inuence on the IP address
3 3
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 11
130BD136.10
130BD139.10
130BD137.10
130BD140.10
Congure the Master MCA 123 POWERLINK
4 Congure the Master
4.1 Importing the XDD File
To congure a POWERLINK Master, the conguration tool needs an XDD le for each type of slave on the network. The XDD le is a text le containing the necessary communications set-up data for a slave. Download the
le for the FC Series frequency converters at
XDD www.danfoss.com/BusinessAreas/DrivesSolutions/.
44
parameter 15-61 Option SW Version
1.02 FC 301: 0x0200008D_FC301_01.xdd
1.12 FC 301: 0x0200008D_FC301_08.xdd
Table 4.1 POWERLINK SW Version XDD File
The following steps show how to add a device to the Automation Studio Tool. For tools from other vendors, consult their relevant manuals.
1. In the Automation Studio, select the menu [Tools] and [Import Fieldbus Device].
File
FC 302: 0x0200008D_FC302_01.xdd
FC 302: 0x0200008D_FC302_08.xdd FCD 302: FCD 302: 0x0200008D_FCD302_08.xdd
Illustration 4.2 Selecting the XDD File
4.2 Setting Up the Master
Select the POWERLINK I/O master to open the POWERLINK interface in the Automation Studio Master.
1. Right click and select [Open POWERLINK].
Illustration 4.3 Open POWERLINK
Illustration 4.1 Automation Studio
2. Select the XDD le and the Automation studio, imports it to its library. To save the new info, select the [Save All] menu or the multiple oppy disc icon.
12 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
2. Right click the network icon, and select [Insert].
Illustration 4.4 Physical View
130BD145.11
130BD142.10
130BD141.10
130BD142.10
Congure
the Master Operating Instructions
3. Select [Danfoss FC 302].
Illustration 4.7 Select Parameters
Illustration 4.5 Select Controller Module
Danfoss FC Series is inserted in the POWERLINK master system.
Congure the I/O conguration, right click the
4. Danfoss Icon and select [Open I/O Conguration].
NOTICE
Make sure that maximum ten channels are selected in each direction; or the PLC enters into an endless restart of the network.
6. The POWERLINK the Danfoss FC Series frequency converter as its slave and communicates with the four words. The nal step is to map the I/Os to PLC variables, which is done in the I/O mapping. Select the I/O Mappings by right-clicking the [Danfoss FC 302] icon and selecting [Open I/O Mapping].
conguration does now contain
4 4
Illustration 4.6 I/O Conguration
5. By default the POWERLINK option does not have any process data assigned to its I/O mapping. Assign the process data by selecting the channels (FC Parameter) as read or write. Selecting the [+] sign in front of the channel menu expands the list and the parameters can be selected. In this example following has been selected:
Object 2690 eldbus control word 1
Object 2692 eldbus reference 1
Object 2643 status word
Object 2645 main actual value
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 13
Illustration 4.8 Mapping the I/Os ot the PLC Variables
Now, the mapping can be done directly to previous dened variables.
130BD143.10
130BD144.10
Congure the Master MCA 123 POWERLINK
Illustration 4.9 Previous Dened Variables
44
Variables can also be directly declared, via selecting the Channel Name for each signal and enter the attributes directly.
Illustration 4.10 Variables Directly Declared
This inserts the Danfoss FC 302 into the B&R system, and the frequency converter can now be controlled and supervised via the POWERLINK.
14 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
Receive PDOs (PLC
Drive)
Transmit PDOs (Drive PLC)
PCD 9
write
PDO 23
PCD 0
CTW
PCD 1
REF
PCD 9
read
PCD 0
STW
PCD 1
MAV
PDO 23
130BC177.10
How to Control the Frequenc...
Operating Instructions
5 How to Control the Frequency Converter
5.1 PDO Communication
The frequency converter uses the following proles:
Frequency converter proles
CANOpen DS 402 prole
For each of the two proles there is a set of SDO objects that is only accessible if the prole is activated in parameter 8-10 Control Word Prole. The change is active at the next power-up. Congure the PDO communication, where a subset of SDOs can be mapped into PDOs for cyclic communication.
PDO communication is reserved for high-speed cyclic access to parameters for control and status of the frequency converter. The PLC sends out process control data, and the frequency converter responds with a PDO containing process status data. In the Danfoss POWERLINK interface, both PDOs can be congured freely.
Select the signals for transmission from the master to the frequency converter via the PLCs PLC sets Parameter 12-21 Process Data
parameter 12-22EN-22 Process Data Cong Read and parameter 12-23 Process Data Cong Write Size, which can
be used to control that the conguration has been sent correctly from the PLC.
conguration tool. The
Cong Write,
5.2 Process Data
Use the process data part of the PDO for controlling and monitoring the frequency converter via the POWERLINK.
5.2.1 Process Control Data
The example in Table 5.1 shows control and reference sent from the PLC to the frequency converter, and status word and Main Actual Value sent from the frequency converter to the PLC.
Master to slave
0 1 2 ...... 9
PCD write
Table 5.1 Process Control Data (PCD)
CTW MRV PCD ...... PCD
PCD 0 contains a 16-bit control word where each bit controls a specic function of the frequency converter, see chapter 5.3 Control Prole. PCD 1 contains a 16-bit speed setpoint in percentage format. See chapter 5.2.3 Reference Handling.
The content of PCD 2 to PCD 9 is read only.
5 5
The POWERLINK option has only one PDO available: PDO
23. The PDO 23 is
exible in size and is adjustable to t all needs (max. 10 PCDs). The selection is made in the master conguration and is then automatically downloaded to the frequency converter during the transition from Init to Pre­Op. No manual setting of PPO types in the frequency converter is required.
Option [1] Standard telegram 1 is equivalent to PDO 23.
Illustration 5.1 Standard Telegram
Process Status Data
5.2.2
Process data sent from the frequency converter contain information about the current state of the frequency converter.
Slave to master
0 1 2 ...... 9
STW MAV PCD ...... PCD
PCD read
Table 5.2 Process Status Data
PCD 0 contains a 16-bit status word where each bit contains information regarding a possible state of the frequency converter. PCD 1 contains per default the value of the current speed of the frequency converter in percentage format (see chapter 5.2.3 Reference Handling).
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 15
How to Control the Frequenc...
MCA 123 POWERLINK
5.2.3 Reference Handling
The reference handling in FC Series is an advanced mechanism that sums up references from dierent sources.
For more information on reference handling, refer to the
VLT® AutomationDrive Design Guide.
Limit [Hz]
limit the actual frequency converter output.
parameter 4-19 Max Output Frequency limits the maximum output and can also inuence the maximum speed of the motor.
For reference and MAV formats, see Table 5.3.
55
Illustration 5.2 Reference Handling
Table 5.3 Reference and MAV Formats
The reference, or speed setpoint (MRV, sent via POWERLINK), is always transmitted to the frequency converter in percentage format as integers represented in hexadecimal (0-4000 hex).
NOTICE
Negative numbers are formed as a complement of two.
and parameter 4-14 Motor Speed High Limit [Hz]
MRV/MAV Integer in hex Integer in decimal
100% 4000 16.384
75% 3000 12.288 50% 2000 8.192 25% 1000 4.096
0% 0 0
-25% F000 -4.096
-50% E000 -8.192
-75% D000 -12.288
-100% C000 -16.384
NOTICE
Depending on the setting of parameter 3-00 Reference Range the reference and MAV are scaled accordingly:
The data type for MRV and MAV is 16-bit standardise value, which can express a range from -200% to +200% (8001 to 7FFF).
Illustration 5.3 Scaling of MAV and Reference
NOTICE
If parameter 3-00 Reference Range is set to [0] Min - Max, a negative reference is handled as 0%.
The speed limit settings depend on parameter 0-02 Motor Speed Unit and can be set to RPM or Hz. If parameter 0-02 Motor Speed Unit is set to RPM, parameter 4-11 Motor Speed Low Limit [RPM] and parameter 4-13 Motor Speed High Limit [RPM] limit the actual frequency converter output. If parameter 0-02 Motor Speed Unit is set to Hz, parameter 4-12 Motor Speed Low
Parameter 1-00 Conguration Mode set to [0] Speed open loop. Parameter 3-00 Reference Range set to [0] Min - Max. Parameter 3-02 Minimum Reference set to 100 RPM. Parameter 3-03 Maximum Reference set to 3000 RPM.
MRV/MAV Actual speed
0% 0 hex 100 RPM 25% 1000 hex 825 RPM 50% 2000 hex 1550 RPM 75% 3000 hex 2275 RPM 100% 4000 hex 3000 RPM
Table 5.4
5.2.4
Process Control Operation
In process control operation parameter 1-00 Conguration Mode is set to [3] Process. The reference range in parameter 3-00 Reference Range is always [0] Min-Max.
- MRV represents the process setpoint.
- MAV expresses the actual process feedback (range ±200%).
16 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
Speed ref.CTW
Master-follower
130BA274.11
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit no.:
How to Control the Frequenc...
Operating Instructions
5.2.5 Inuence of the Digital Input
Terminals upon FC Control Mode
The inuence of the digital input terminals upon control of the frequency converter can be programmed in
parameter 8-50 Coasting Select to parameter 8-56 Preset Reference Select.
NOTICE
The parameter 8-01 Control Site overrules the settings in parameter 8-50 Coasting Select to parameter 8-56 Preset Reference Select, and terminal 37 Coasting Stop (safe)
overrules any parameter.
Each digital input signal can be programmed to logic AND, logic OR, or to have no relation to the corresponding bit in the control word. This way, eldbus only, eldbus AND Digital Input, or Ether Fieldbus OR Digital input terminal can initiate a specic control command, that is stop/coast.
CAUTION
To control the frequency converter via POWERLINK, set
parameter 8-50 Coasting Select to either [1] Bus, or to [2] Logic AND. Then set parameter 8-01 Control Site to [0] Digital and ctrl.word or [2] control word only.
5.3 Control Prole
The frequency converter can be controlled according to the DS 402 prole, or the Danfoss FC prole. Select the desired control Prole. The choice of prole aects the control and status word only. The change of parameter 8-10 Control Word Prole is activated at the next power-up.
Object 6060 Modes of operation can also control the desired control prole which can be readout by object 6061 Modes of operation display. Value -1 indicates frequency converter prole. Value 2 indicates DS 402 Velocity mode. If the frequency converter is run in DS 402 prole, the DS 402 prole must be selected (for example, by parameter 8-10 Control Word Prole or object 6060). The four process data Control Word, Reference, Status Word and Main Actual Value will the information in according to the specication. Make sure that the prole selected is also the prole used in the PLC.
prole in parameter 8-10 Control Word
5.4
DS 402 Control Prole
5.4.1 Control Word According to DSP 402 Prole (Parameter 8-10=DSP 402 prole)
Illustration 5.4 Control Word Prole
Bit Bit value=0 Bit value=1
00 Switch o Switch on 01 Disable voltage Enable voltage 02 Quick stop Run 03 Disable operation Enable operation 04 Disable ramp Enable ramp 05 Freeze Run enable 06 Ramp stop Start 07 No function Reset 08 Reserved 09 Reserved 10 Reserved 11 Jog 1 OFF Jog 1 ON 12 Reserved 13 Setup select (LSB) 14 Setup select (MSB) 15 Forward Reversing
Table 5.5 Denition of Control Bits
Explanation of the control bits
Bit 00, Switch OFF/ON Bits 00, Switch OFF/ON Bit 00=“0” - executes transition 2, 6 or 8. Bit 00=“1” - executes transition 3.
Bit 01, Disable/Enable Voltage Bit 01=“0” - executes transition 9, 10 or 12. Bit 01=“1” - enables voltage.
Bit 02, Quick stop/Run Bit 02="0" - executes transition 7, 10 or 11. Bit 02="1" - quick stop not active.
5 5
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 17
Bit 03, Disable/enable Operation Bit 03="0" - executes transition 5. Bit 03="1" - enables operation.
Bit 04, Quick-stop/ramp
Output freq.STW
Bit no.:
Follower-master
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
130BA273.11
How to Control the Frequenc...
MCA 123 POWERLINK
Bit 04="0" - executes transition 7 or 11, Quick stop. Bit 04="1" - enables ramp.
5.4.2 Status Word According to DS 402
Prole
Bit 05, Freeze output frequency/run enable Bit 05="0" - the given output frequency is maintained even if the reference is changed. Bit 05="1" - the frequency converter is again able to regulate, and the given reference is followed.
Bit 06, Ramp stop/start
Illustration 5.5 Status Word Prole
Bit 06="0" - the frequency converter controls the motor down to stop. Bit 01="1" - gives a start command to the frequency converter.
55
Bit 07, No function/reset Reset of trip. Bit 07="0" - there is no reset. Bit 07="1" - a trip is reset.
Bit 08, 09 and 10 DSP402 reserved.
Bit 11, Jog 1 OFF/ON Activation of pre-programmed speed in parameter 8-90 Bus
Jog 1 Speed
JOG 1 is only possible if Bit 04="0", and bit 00-03="1".
Bit 12 Danfoss reserved.
Bit Bit value=0 Bit value=1
00 Not ready to switch ON Ready to switch ON 01 Switched OFF Switched ON 02 Operation disabled Operation enabled 03 No malfunction Malfunction 04 Voltage disabled Voltage enabled 05 Quick stop Run 06 Switch on disable Switch on enable 07 No warning Warning 08 Not running Running 09 Remote disabled Remote enabled 10 Set point not reached Set point reached 11 Speed limit not active Speed limit active 12 Reserved 13 Reserved 14 Reserved 15 Reserved
Table 5.7 Denition of Status Bits
Bits 13/14, Selection of Setup Bits 13 and 14 are used for selecting among the four menu
Explanation of the status bits
set-ups in accordance with Table 5.6:
Bit 00, Not ready to switch on/Ready to switch on
Set-up Bit 14 Bit 13
0 0 1 0 1 2 1 0 3 1 1 4
Bit 00="0" - state less than “Ready to switch on”. Bit 00="1" - state at least = “Ready to Switch on”.
Bit 01, Switch o/Switch on Bit 00="0" - state less than “Switched on”. Bit 00="1" - state at least = “Switched on”.
Table 5.6 Set-up Selection Table
Bit 15, Forward/reversing Bit 15="0" - no reversing. Bit 15="1" - reversing.
Bit 02, Operation disable/Operation enable Bit 00="0" - state less than “Operation enable”. Bit 00="1" - state at least = “Operation enable”.
NOTICE
In factory setting reversing is set to [digital] in parameter 8-54 Reversing Select.
18 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
Bit 03, No fault/trip Bit 03="0" - the frequency converter is not in a fault condition. Bit 03="1" - the frequency converter has tripped and needs a reset signal to run.
Bit 04, Voltage disable/Voltage enable Bit 04="0" - control word bit 01="1". Bit 04="1" - control word bit 01="0".
How to Control the Frequenc... Operating Instructions
Bit 05, Quick stop/Run Bit 05="0" - control word bit 02="1". Bit 05="1" - control word bit 02="0".
Bit 06, Start enable/Start disable Bit 06="0" - state is not “Switch on disable”. Bit 06="1" - state = “Switch on enable”.
Bit 07, No warning/Warning Bit 07="0" - no warning situation. Bit 07="1" - a warning has occurred.
Bit 08, Danfoss reserved
Bit 09, Remote disable/Remote enable Bit 09="0" - the frequency converter has been stopped with the stop key on the LCP, or [Local] has been selected in parameter 3-13 Reference Site. Bit 09="1" - it is possible to control the frequency converter via the serial port.
Bit 10, setpoint not reached/Set point reached Bit 10="0" - the actual motor speed is dierent from the speed reference set. This situation can occur while the speed is ramped up/down during start/stop. Bit 10="1" - the present motor speed equals the speed reference set.
Bit 11, Speed limit not active/speed limit active Bit 11="0" - the output frequency is out of the range set in parameters 4-11/4-12 Motor Speed low Limit RPM/Hz or parameters 4-13/4-14 Motor Speed high Limit RPM/Hz. Bit 11="1" - the output frequency is within the mentioned range.
Bit 12, DSP 402 reserved
Bit 13, DSP 402 reserved
Bit 14, Running/Not running Bit 14="0" - the motor is not running. Bit 14="1" - the frequency converter has a valid start signal or that the output frequency is greater than 0 Hz.
Bit 15, Danfoss reserved
8-10 Control
Option: Function:
[0] * FC prole [7] CANOpen DSP 402
FC Prole is the default control prole for the frequency converter, whereas CANOpen DSP 402 is the CiA standardized control transition state machine.
Prole
prole, featuring the special DSP 402
5 5
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 19
How to Control the Frequenc... MCA 123 POWERLINK
55
Illustration 5.6 DSP 402 State Machine
20 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
How to Control the Frequenc... Operating Instructions
5.4.3 DSP 402 State Transitions
Transition State Control
word
- Start condition 0000 0000 ­0 1 2 3 4 5
6 7 8
9
10
11
11
12
13 14 15 16
Start-upNot ready to switch on Switch On DisabledSwitch On Disabled Not Ready to Switch OnSwitched On Ready to Switch OnSwitched On Switched OnReady to Switch On Operation EnabledSwitched On
Switched OnReady to Switch On Ready to Switch OnSwitch On Disable Operation EnableReady to Switch On
Operation EnableSwitch On Disable
Switched OnSwitched On Disable
Operation EnabledQuick Stop Active
Operation EnabledQuick Stop Active
Quick Stop ActiveSwitch On Disabled
All statesFault Reaction Active Fault Reaction ActiveFault FaultSwitch On Disabled Quick Stop ActiveOperation Enable (not
supported)
0000 0200 ­0000, 0001 0240 ­0006 0231 ­0007 0233 ­000F 0237 ­0007 0233 Motor ramps to 0 RPM with programmed ramp down
0006 0231 ­0001, 0000 0240 ­0006 0231 If the motor is not braked, and the power section is
0001, 0000 0240 If the motor is not braked, and the power section is
0001, 0000 0240 If the motor is not braked, and the power section is
0002 0207 Motor ramps to 0 RPM with programmed quick ramp
0003 0217 Motor ramps to 0 RPM with programmed quick ramp
0001, 0000 0240 If the motor is not braked, and the power section is
xxxx 023F ­xxxx 023F ­0000 0240 -
- - -
Status word
Action
parameter.
5 5
switched o immediately, the motor is free to rotate.
switched o immediately, the motor is free to rotate.
switched o immediately, the motor is free to rotate.
parameter.
parameter.
switched o immediately, the motor is free to rotate.
Table 5.8 DSP 402 State Transitions
5.5
Danfoss FC Control Prole
5.5.1 Control Word according to FC Prole (CTW)
To select Danfoss FC protocol in the control word,
parameter 8-10 Control Word Prole must be set to [0] frequency converter prole. The control word is used to
send commands from a master (PLC or PC) to a slave (frequency converter).
Bit Bit value=0 Bit value=1
00 Reference value external selection lsb 01 Reference value external selection msb 02 DC brake Ramp 03 Coasting No coasting 04 Quick stop Ramp 05 Hold output frequency Use ramp 06 Ramp stop Start 07 No function Reset 08 No function Jog 09 Ramp 1 Ramp 2 10 Data invalid Data valid 11 No function Relay 01 active 12 No function Relay 04 active 13 Parameter set-up selection lsb 14 Parameter set-up selection msb 15 No function Reverse
Table 5.9 Bit Values for FC Control Word
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 21
How to Control the Frequenc...
MCA 123 POWERLINK
Explanation of the control bits Bits 00/01 Reference value
Bits 00 and 01 are used to choose between the four reference values, which are pre-programmed in parameter 3-10 Preset Reference according to Table 5.10.
NOTICE
In parameter 8-56 Preset Reference Select a selection is made to dene how Bit 00/01 gates with the corresponding function on the digital inputs.
Bit 01 Bit 00 Programmed
ref. value
0 0 1 [0]
55
0 1 2 [1]
1 0 3 [2]
1 1 4 [3]
Table 5.10 Programmed Reference Values for Bits
Bit 02, DC brake
Bit 02=“0” - leads to DC braking and stop. Braking current and duration are set in parameter 2-01 DC Brake Current and parameter 2-02 DC Braking Time. Bit 02=“1” - leads to ramping.
Bit 03, Coasting
Bit 03=“0” - causes the frequency converter to immediately coast the motor to a standstill. Bit 03=“1” - enables the frequency converter to start the motor if the other starting conditions have been fullled.
Parameter
Parameter 3-10 Preset
Reference
Parameter 3-10 Preset
Reference
Parameter 3-10 Preset
Reference
Parameter 3-10 Preset
Reference
NOTICE
In parameter 8-50 Coasting Select a selection is made to
dene how Bit 03 gates with the corresponding function on a digital input.
Bit 04, Quick stop
Bit 04=“0” - causes a quick stop, ramping the motor speed down to stop via parameter 3-81 Quick Stop Ramp Time. Bit 04=“1” - the frequency converter ramps the motor speed down to stop via parameter 3-81 Quick Stop Ramp Time.
Bit 05, Hold output frequency
Bit 05=“0” - causes the present output frequency (in Hz) to freeze. The frozen output frequency can only be changed with the digital inputs (parameter 5-10 Terminal 18 Digital Input to parameter 5-15 Terminal 33 Digital Input) programmed to Speed up and Speed down. Bit 05=“1” - use ramp.
NOTICE
If Freeze output is active, stop the frequency converter with
Bit 03 Coasting stop
Bit 02 DC braking
Digital input (parameter 5-10 Terminal 18 Digital
Input to parameter 5-15 Terminal 33 Digital Input) programmed to DC braking, Coasting stop, or Reset and coasting stop.
Bit 06, Ramp stop/start
Bit 06=“0” - causes a stop, in which the motor speed is ramped down to stop via the selected ramp down parameter. Bit 06=“1" - permits the frequency converter to start the motor, if the other starting conditions have been
fullled.
NOTICE
In parameter 8-53 Start Select a selection is made to
dene how Bit 06 Ramp stop/start gates with the corresponding function on a digital input.
Bit 07, Reset
Bit 07="0" - does not cause a reset. Bit 07="1" - causes the reset of a trip. Reset is activated on the signals leading edge, that is, when changing from logic "0" to logic "1".
Bit 08, Jog
Bit 08="0" - no function. Bit 08="1" - parameter 3-19 Jog Speed [RPM] determines the output frequency.
Bit 09, Selection of ramp 1/2
Bit 09="0" - ramp 1 is active (parameter 3-40 Ramp 1 Type to parameter 3-47 Ramp 1 S-ramp Ratio at Decel. Start). Bit 09="1" - ramp 2 (parameter 3-50 Ramp 2 Type to parameter 3-57 Ramp 2 S-ramp Ratio at Decel. Start) is active.
Bit 10, Data not valid/Data valid
Is used to tell the frequency converter whether it should use or ignore the control word. Bit 10="0" - the control word is ignored. Bit 10="1" - the control word is used. This function is relevant, because the control word is always contained in the telegram, regardless of which type of telegram is used. Thus, it is possible to turn wished to use it when updating or reading parameters.
Bit 11, Relay 01
Bit 11="0" - relay 01 not activated. Bit 11="1" - relay 01 activated, provided Control word bit 11 has been chosen in parameter 5-40 Function Relay.
Bit 12, Relay 04
Bit 12="0" - relay 04 has not been activated.
o the control word, if it is not
22 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
How to Control the Frequenc...
Operating Instructions
Bit 12="1" - relay 04 has been activated, provided Control word bit 12 has been chosen in parameter 5-40 Function Relay.
Bit 13/14, Selection of set-up
Bits 13 and 14 are used to choose from the four menu set­ups according to Table 5.11:
The function is only possible when [9] Multi-Set-up is selected in parameter 0-10 Active Set-up.
Set-up Bit 14 Bit 13
1 0 0 2 0 1 3 1 0 4 1 1
Table 5.11 Selection of Set-up
NOTICE
In parameter 8-55 Set-up Select a selection is made to
dene how Bit 13/14 gates with the corresponding function on the digital inputs.
Bit 15 Reverse
Bit 15="0" - no reversing. Bit 15="1" - reversing.
Status Word according to FC Prole
5.5.2 (STW)
The status word is used to inform the master (for example, a PC) of the operation mode of the slave (frequency converter).
Refer to chapter 8 Application Examples for an example of a status word telegram using PPO type 3.
Bit Bit=0 Bit=1
00 Control not ready Control ready 01 Frequency converter not
ready 02 Coasting Enable 03 No error Trip 04 No error Error (no trip) 05 Reserved ­06 No error Triplock 07 No warning Warning 08 Speed reference Speed=reference 09 Local operation Bus control 10 Out of frequency limit Frequency limit ok 11 No operation In operation 12 Frequency converter OK Stopped, autostart 13 Voltage OK Voltage exceeded 14 Torque OK Torque exceeded 15 Timer OK Timer exceeded
Table 5.12 Denition of Status Bits
Frequency converter ready
Explanation of the status bits Bit 00, Control not ready/ready
Bit 00="0" - the frequency converter has tripped. Bit 00="1" - the frequency converter controls are ready, but the power component is not necessarily receiving any power supply (in case of 24 V external supply to controls).
Bit 01, frequency converter ready
Bit 01="0" - the frequency converter is not ready for operation. Bit 01="1" - the frequency converter is ready for operation, but there is an active coasting command via the digital inputs or via serial communication.
Bit 02, Coasting stop
Bit 02="0" - the frequency converter has released the motor. Bit 02="1" - the frequency converter can start the motor when a start command is given.
Bit 03, No error/trip
Bit 03="0" - the frequency converter is not in fault mode. Bit 03="1" - the frequency converter is tripped, and that a reset signal is required to re-establish operation.
Bit 04, No error/error (no trip)
Bit 04="0" - the frequency converter is not in fault mode. Bit 04=“1” - there is a frequency converter error but no trip.
Bit 05, Not used
Bit 05 is not used in the status word.
Bit 06, No error/triplock
Bit 06="0" - the frequency converter is not in fault mode. Bit 06=“1” - the frequency converter is tripped, and locked.
Bit 07, No warning/warning
Bit 07="0" - there are no warnings. Bit 07="1" - a warning has occurred.
5 5
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 23
How to Control the Frequenc...
Bit 08, Speed reference/speed = reference
Bit 08="0" - the motor is running, but that the present speed is dierent from the preset speed reference. It could, for example, be the case while the speed is being ramped up/down during start/stop. Bit 08="1" - the present motor present speed matches the preset speed reference.
Bit 09, Local operation/bus control
Bit 09="0" - [Stop/Reset] is activated on the control unit, or that Local control in parameter 3-13 Reference Site is selected. It is not possible to control the frequency converter via serial communication. Bit 09="1" - it is possible to control the frequency converter via the eldbus/serial communication.
55
Bit 10, Out of frequency limit
Bit 10="0" - the output frequency has reached the value in
parameter 4-11 Motor Speed Low Limit [RPM] or parameter 4-13 Motor Speed High Limit [RPM].
Bit 10="1" - the output frequency is within the dened limits.
Bit 11, No operation/in operation
Bit 11="0" - the motor is not running. Bit 11="1" - the frequency converter has a start signal or the output frequency is greater than 0 Hz.
Bit 12, frequency converter OK/stopped, auto start
Bit 12="0" - there is no temporary over temperature on the frequency converter. Bit 12="1" - the frequency converter has stopped because of over temperature, but the unit has not tripped and resumes operation once the over temperature stops.
Bit 13, Voltage OK/limit exceeded
Bit 13="0" - there are no voltage warnings. Bit 13="1" - the DC voltage in the frequency converters intermediate circuit is too low or too high.
Bit 14, Torque OK/limit exceeded
Bit 14="0" - the motor current is lower than the torque limit selected in parameter 4-16 Torque Limit Motor Mode or parameter 4-17 Torque Limit Generator Mode. Bit 14="1" - the torque limits in parameter 4-16 Torque Limit
Motor Mode and parameter 4-17 Torque Limit Generator Mode have been exceeded.
Bit 15, Timer OK/limit exceeded
Bit 15="0" - the timers for motor thermal protection and VLT thermal protection, respectively, have not exceeded 100%. Bit 15="1" - one of the timers has exceeded 100%.
MCA 123 POWERLINK
24 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
Communication Prole Area Operating Instructions
6 Communication Prole Area
6.1 Description - Communication Prole Area
This chapter describes the general layout of the supported POWERLINK communication area. The process data objects are dened in this area.
6.2 1000-1FFF Communication Object Area
Index [hex] Object (symbolic name) Name Type Read/write
1000 VAR Device type UNSIGNED32 ro 1001 VAR Error register UNSIGNED8 ro 1006 VAR Communication cycle period UNSIGNED32 rw
1008 VAR Manufacturer device name VISIBLE_STRING ro 1009 VAR Manufacturer hardware version VISIBLE_STRING ro 100A VAR Manufacturer software version VISIBLE_STRING ro 1010 ARRAY Store parameters UNSIGNED32 rw 1011 ARRAY Restore default parameters UNSIGNED32 rw
0x1C14 VAR DLL_CNLossOfSocTolerance_U32 UNSIGNED32 rw 0x1E40 RECORD NWL_IpAddrTable_1_REC NWL_IpAddrTable_TYPE ro/rw 0x1E4A RECORD RECORD NWL_IpGroup_REC NWL_IpGroup_TYPE ro/rw
1018 RECORD Identity object Identity (23h) ro 1020 RECORD CFM_VerifyConguration_REC CFM_VerifyConguration_TYPE ro 1030 RECORD NMT_InterfaceGroup_0h_REC NMT_InterfaceGroup_0h_TYPE ro 1031 RECORD NMT_InterfaceGroup_1h_REC NMT_InterfaceGroup_0h_TYPE ro
1300 VAR SDO_SequLayerTimeout_U32 UNSIGNED32 rw 1400 RECORD PDO_RxCommParam_16h_REC UNSIGNED8 ro 1600 ARRAY PDO_RxMappParam_00h_AU64 UNSIGNED64 rw 1800 ARRAY PDO_TxCommParam_16h_REC UNSIGNED8 ro 1A00 ARRAY PDO_TxMappParam_00h_AU64 UNSIGNED64 rw
1C0A RECORD DLL_CNCollision_REC UNSIGNED32 rw 1C0B RECORD DLL_CNLossSoC_REC UNSIGNED32 rw 1C0F RECORD DLL_CNCRCError_REC UNSIGNED32 rw 1C14 VAR DLL_CNLossOfSocTolerance_U32 UNSIGNED32 rw 1E40 RECORD NWL_IPAddrTable_1_REC NWL_IpAddrTable_TYPE ro/rw 1E4A RECORD RECORD NWL_IpGroup_REC NWL_IpGroup_TYPE ro/rw 1F81 VAR NMT_NodeAssignment_AU32 1F82 VAR NMT_FeatureFlags_U32 UNSIGNED32 ro 1F83 VAR NMT_EPLVersion_U8 UNSIGNED8 ro 1F8C VAR NMT_CurrNMTState_U8 UNSIGNED8 ro 1F93 RECORD NMT_EPLNodeID_REC UNSIGNED8 ro 1F98 VAR NMT_CycleTiming_REC UNSIGNED32 ro 1F99 VAR NMT_CNBasicEthernetTimeout_U32 UNSIGNED32 rw 1F9A VAR NMT_HostName_VSTR VISIBLE_STRING32 rw 1F9B VAR NMT_MultiplCycleAssign_AU8 UNSIGNED8 rw 1F9E VAR NMT_ResetCmd_U8 UNSIGNED8 rw
6 6
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 25
Communication Prole Area MCA 123 POWERLINK
Index [hex] Object (symbolic name) Name Type Read/write
2000-5FFF Vendor specic area
603F VAR Error Code UNSIGNED16 ro 6040 VAR Control word UNSIGNED16 rw 6041 VAR Status word UNSIGNED16 ro 6042 VAR vl_target_velocity SIGNED16 rw 6043 VAR vl_velocity_demand SIGNED16 ro 6044 VAR vl_velocity_actual_value SIGNED16 ro 6046 ARRAY vl_velocity_min_max_amount UNSIGNED32 ro 6048 RECORD vl_velocity_acceleration See description ro 6049 RECORD vl_velocity_deceleration See description ro 6060 VAR Modes of operation SIGNED8 rw 6061 VAR Modes of operation display SIGNED8 ro 6502 VAR Supported drive mode UNSIGNED32 ro 6504 VAR Drive manufacture VISIBLE_STRING ro
See chapter 6.3 2000-5FFF Danfoss Specic Object
Area
66
Table 6.1 Communication Object Overview
1000h Device Type
6.2.1
This object describes the type of device and its functionality. It is composed of a 16-bit eld describing the device prole used, and a second 16-bit eld providing additional information about optional functionality of the device.
Additional information Device prole number Mode bits Type bits Bits
31.. 24 23.. 16 15.. 0 0 1 (frequency converters) 0=FC Prole
402=DS 402
Table 6.2 1000h Device Type
1001h Error Register
6.2.2
1006h Communication Cycle Period
6.2.3
This object denes the communication cycle time interval in μs. This object is reset to its default value by object 1011h. This object is set from the MN.
6.2.4 1008h Manufacturer Device Name
This object contains the device name as dened in parameter 15-40 FC Type.
Index Meaning
1008h for example, FC 302
Table 6.4 1008h Manufacturer Device Name
1009h Manufacturer Hardware
6.2.5 Version
This object is the error register of the device. Only bit 0 and bit 5 is supported. The two bits are active (high) if an alarm is active in alarm word 1 or alarm word 2.
This object contains the hardware version for the POWERLINK interface.
Bit Meaning
0 Generic error 1 Current 2 Voltage 3 Temperature 4 Communications error (overrun, error state) 5 Device prole specic 6 Reserved (always zero) 7 Manufacturer specic
Table 6.3 1001h Error Register
26 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
100Ah Manufacturer Software Version
6.2.6
This object contains the Danfoss software version as displayed in parameter 15-49 SW ID Control Card.
1010h Store Parameters
6.2.7
In the standard conguration, the contents of parameters written via eldbus are stored in volatile memory. The changed data will be lost after a power cycle. This index permits non-volatile storage of all frequency converter parameters which have been changed. Writing to one of the indexes will set parameter 12-28 Store Data Values.
Communication
Prole Area Operating Instructions
Index, sub-index Meaning
1010h 0 Number sub-index supported 1010h 1 Save option parameters 1010h 2 All 1010h 3 Not supported
Table 6.5 1010h Store Parameters
Writing the value “save” (0x65766173) to sub-index 1, stores all frequency converter parameters of all set-ups into non-volatile memory, all other values are rejected.
6.2.8 1011h Restore Default Parameters
To restore factory default settings:
1. Write the value “load” to sub-index 1.
2. Initiate the next power cycle manually.
The default value is restored.
Index, sub-index Meaning
1011h 0 Number of sub-index supported 1011h 1 Restore all default parameters and restart
Table 6.6 1011h Restore Default Parameters
Writing the value “load” (0x64616F6C) restores all frequency converter parameters of all set-ups to factory values, except the communications parameters. All other values are rejected, and abort code 0x08000020 is returned. The frequency converter has to be power cycled before the changes get active and the motor must be in the state coast or stopped.
1018h Identity Object
6.2.9
This object contains general information about the device.
The vendor ID (sub-index 1h) contains a unique value allocated to each manufacturer.
The manufacturer-specic product code (sub-index 2h) identies a specic device version.
The manufacturer-specic revision number (sub-index 3h) consists of a major revision number and a minor revision number.
Index, sub-index Meaning
1018h 0 Number of entries 1018h 1 Vendor ID 1018h 2 Product code 1018h 3 Revision number (major revision number and
minor revision number)
1018h 4 Serial number
Table 6.7 1018h Identity Object
6.2.10 1020h CFM_VerifyConguration_REC
This object contains the devices local conguration date and time. The object values are set by managing node or conguration tool.
Index, sub­index
1020h 0 Number of entries 1020h 1 ConfDate_U32, Days since January 1, 1984 1020h 2 ConfTime_U32, milliseconds after midnight 1020h 3 ConfId_U32, assigned by the conguration tool 1020h 4 VerifyConfInvalid_BOOL, Value False indicates
Table 6.8 1020h
6.2.11
This object is used to congure and retrieve parameters of the network interfaces (physical or virtual) via SDO.
Index, sub-index Meaning
1030h 0 Number of entries 1030h 1 InterfaceIndex_U16 1030h 2 InterfaceDescription_VSTR t 1030h 3 InterfaceType_U8 1030h 4 InterfaceMtu_U16 1030h 5 InterfacePhysAddress_OSTR 1030h 6 InterfaceName_VSTR 1030h 7 InterfaceOperStatus_U8 1030h 8 InterfaceAdminState_U8 1030h 9 Valid_BOOL
Table 6.9 1030h NMT_InterfaceGroup_0h_REC
6.2.12
Meaning
that conguration was not modied since last storage of ConfId_U32
CFM_VerifyConguration_REC
1030h NMT_InterfaceGroup_0h_REC
1031h NMT_InterfaceGroup_1h_REC
6 6
This object is used to congure and retrieve parameters of the network interfaces (physical or virtual) via SDO.
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 27
Communication
Prole Area MCA 123 POWERLINK
Index, sub-index Meaning
1031h 0 Number of entries 1031h 1 InterfaceIndex_U16 1031h 2 InterfaceDescription_VSTR t 1031h 3 InterfaceType_U8 1031h 4 InterfaceMtu_U16 1031h 5 InterfacePhysAddress_OSTR 1031h 6 InterfaceName_VSTR 1031h 7 InterfaceOperStatus_U8 1031h 8 InterfaceAdminState_U8 1031h 9 Valid_BOOL
Table 6.10 1031h NMT_InterfaceGroup_1h_REC
6.2.13
1300h SDO_SequLayerTimeout_U32
This object provides a timeout value in [ms] for the connection abort recognition of the SDO sequence Layer.
66
Default value is 30000. This object is linked to parameter 12-62 SDO Timeout.
6.2.14
1400h PDO_RxCommParam_16h_REC
Index, sub­index
1600h 0 Number of sub-index supported 1600h 1 parameter 12-21 Process Data Cong Write, [0]
1600h 2 parameter 12-21 Process Data Cong Write, [1]
1600h 3 parameter 12-21 Process Data Cong Write, [2]
1600h 4 parameter 12-21 Process Data Cong Write, [3]
1600h 5 parameter 12-21 Process Data Cong Write, [4]
1600h 6 parameter 12-21 Process Data Cong Write, [5]
1600h 7 parameter 12-21 Process Data Cong Write, [6]
1600h 8 parameter 12-21 Process Data Cong Write, [7]
1600h 9 parameter 12-21 Process Data Cong Write, [8]
1600h 10 parameter 12-21 Process Data Cong Write, [9]
Table 6.13 1600h PDO_RxCommParam_00h _AU64
Meaning
Index
Index
Index
Index
Index
Index
Index
Index
Index
Index
This object describes attributes of PDO Communication for RPDO. Object indices describe the Node ID and PDO
For every PDO channel up to ten objects can be mapped.
Mapping Version. Mapping Version must be set by congu-
ration tool depending on PDO mapping.
oset related to the start address of the PDO payload
The and the length of data is provided for every mapped
High Nibble Main version Sub version
Table 6.11 Mapping Version Structure
PDOs diering main version will be rejected. PDOs diering sub version is accepted. Mapping version 0
indicates that no mapping version is available.
Index, sub-index Meaning
1400h 0 Number of sub-index supported 1400h 1 NodeID_U8 1400h 2 MappingVersion_U8
Table 6.12 1400h PDO_RxCommParam_16h_REC
6.2.15
1600h PDO_RxCommParam_00h _AU64
This objects indices describe mapping of object contained in RPDO payload to object dictionary entries.
Low Nibble
object.
Octet
oset
0-1 Index Index of the object to be mapped 2 Sub-index Sub-index of the object to be mapped 3 reserved 4-5 Oset Oset related to start of PDO payload (Bit
6-7 Length Length of the mapped object (Bit count)
Table 6.14 Description of Octet Oset
Bits 63 .. 48 47 .. 32 31 .. 24 23 .. 16 Name Length Oset Reserved Sub-index Encoding UNSIGNED16 UNSIGNED16 - UNSIGNED8
Bits 15 .. 0 Name Index Encoding UNSIGNED16
Name Description
count)
MSB
LSB
Table 6.15 Internal Mapping of PDO Mapping Entry
28 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
Communication
Prole Area Operating Instructions
6.2.16 1800h PDO_TxCommParam_16h_REC
This object describes attributes of PDO Communication for RPDO. Object indices describe the Node ID and PDO Mapping Version. Mapping Version must be set by congu- ration tool depending on PDO mapping. Access is read/ write. Mapping version 0 indicates that no mapping version is available.
Index, sub-index Meaning
1400h 0 Number of sub-index supported 1400h 1 NodeID_U8 1400h 2 MappingVersion_U8
Table 6.16 1800h PDO_TxCommParam_16h_REC
6.2.17
1A00h PDO_TxMappParam_00h_AU64
This objects indices describe mapping of object contained in RPDO payload to object dictionary entries.
Index, sub­index
1A00h0 Number of sub-index supported 1A00h1 parameter 12-22EN-22 Process Data Cong Read, [0]
1A00h2 parameter 12-22EN-22 Process Data Cong Read, [1]
1A00h3 parameter 12-22EN-22 Process Data Cong Read, [2]
1A00h4 parameter 12-22EN-22 Process Data Cong Read, [3]
1A00h5 parameter 12-22EN-22 Process Data Cong Read, [4]
1A00h6 parameter 12-22EN-22 Process Data Cong Read, [5]
1A00h7 parameter 12-22EN-22 Process Data Cong Read, [6]
1A00h8 parameter 12-22EN-22 Process Data Cong Read, [7]
1A00h9 parameter 12-22EN-22 Process Data Cong Read, [8]
1A00h10 parameter 12-22EN-22 Process Data Cong Read, [9]
Table 6.17 1A00h PDO_TxMappParam_00h_AU64
Map up to ten objects for every PDO channel.
The oset related to the start address of the PDO payload and the length of data is provided for every mapped object.
Meaning
Index
Index
Index
Index
Index
Index
Index
Index
Index
Index
Octet
oset
0-1 Index Index of the object to be mapped 2 Sub-index Sub-index of the object to be mapped 3 Reserved 4-5 Oset Oset related to start of PDO payload (Bit
6-7 Length Length of the mapped object (Bit count)
Table 6.18 Description of Octet Oset
Bits 63 .. 48 47 .. 32 31 .. 24 23 .. 16 Name Length Oset Reserved Sub-index Encoding UNSIGNED16 UNSIGNED16 - UNSIGNED8
15 .. 0 Index UNSIGNED16
Table 6.19 Internal Mapping of PDO Mapping Entry
6.2.18
Name Description
count)
MSB
LSB
1C0Ah DLL_CNCollision_REC
This object contains information regarding collisions on the network.
Index, sub-index Meaning
1C0Ah 0 Number of entries 1C0Ah 1 CumulativeCnt_U32 1C0Ah 2 1C0Ah 3
Table 6.20 1C0Ah DLL_CNCollision_REC
6.2.19
1C0Bh DLL_CNLossSoC_REC
parameter 12-68 Cumulative Counters parameter 12-68 Cumulative Counters
This object contains information regarding loss of SoC on the network.
Index, sub-index Meaning
1C0Bh 0 Number of entries 1C0Bh 1
1C0Bh 2
1C0Bh 3
Table 6.21 1C0Bh DLL_CNLossSoC_REC
6.2.20
1C0Fh DLL_CNCRCError_REC
CumulativeCnt_U32, [2]
parameter 12-68 Cumulative Counters
ThresholdCnt_U32, [2]
parameter 12-67 Threshold Counters
Threshold_U32, [2] parameter 12-66 Threshold
This object contains information regarding “CRC Errors” on the network. CumulativeCnt_U32 increases with one each time a CRC error occurs. CumulativeCnt_U32 decrements
6 6
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 29
Communication
Prole Area MCA 123 POWERLINK
with one for each cycle without an error. When Cumula­tiveCnt_U32 is equal or larger than ThresholdCnt_U32, the drive issues Warning 34 in the display.
Index, sub-index Meaning
1C0Fh 0 Number of entries 1C0Fh 1
1C0Fh 2
1C0Fh 3
CumulativeCnt_U32, [5]
parameter 12-68 Cumulative Counters
ThresholdCnt_U32, [5]
parameter 12-67 Threshold Counters Threshold_U32, [5] parameter 12-66 Threshold
Binary value NMT state
0001 1100 NMT_CS_NOT_ACTIVE (Default) 0001 1101 NMT_CS_PRE_OPERATIONAL_1 0101 1101 NMT_CS_PRE_OPERATIONAL_2 0110 1101 NMT_CS_READY_TO_OPERATE 1111 1101 NMT_CS_OPERATIONAL 0100 1101 NMT_CS_STOPPED 0001 1110 NMT_CS_BASIC_ETHERNET
Table 6.25 NMS State
6.2.24 1F93h NMT_EPLNodeID_REC
Table 6.22 1C0Fh DLL_CNCRCError_REC
This object contains the POWERLINK NodeID.
6.2.21
Feature ags indicate communication prole specic properties of the frequency converter.
66
Bit Name Remark
0 Isochronous 1 SDO by UDP/IP Not supported 2 SDO by ASnd 3 SDO by PDO Not supported 4 NMT Info Services Not supported 5 Extended NMT State Commands Not supported 6 Dynamic PDO Mapping 7 NMT Service by UDP/IP Not supported 8 Conguration Manager Not supported 9 Multiplexed Access 10 NodeID setup by SW Not supported 11 MN Basic Ethernet Mode Not supported 12 Routing Type 1 Support Not supported 13 Routing Type 2 Support Not supported 14 SDO Read/Write All by Index Not supported 15 SDO Read/Write Multiple Parameter by
16..31 Reserved
6.2.22
The object holds the POWERLINK communication prole version that is implemented.
1F82 NMT_FeatureFlags_U32
Index
Table 6.23 Bit Description
1F83h NMT_ EPLVersion_U8
Not supported
Index, sub-index Meaning
1F93h 0 Number of entries 1F93h 1
1F93h 2 NodeIDByHW_BOOL, DIP switch reading
Table 6.26 1F93h NMT_EPLNodeID_REC
6.2.25
1F98h NMT_CycleTiming_REC
NodeID_U8, [5] parameter 12-68 Cumulative
Counters
This object contains node-specic timing parameters which inuence the POWERLINK cycle timing.
Index, sub­index
1F98h 0 Number of entries 1F98h 1 IsochrTxMax-
1F98h 2 IsochrRxMax-
1F98h 3 PResMaxLatency_U32 Latency, xed to 10 (nS) 1F98h 4 PReqActPayloa-
1F98h 5 PResActPayloa-
1F98h 6 ASndMaxLatency_U32 Latency, xed to 10 (nS) 1F98h 7 MultiplCycleCnt_U8 Set by MN during congu-
1F98h 8 AsyncMTU_U16 Congurable in the range
Meaning Remark
Number of transmit bits,
Payload_U16
Payload_U16
dLimit_U16
dLimit_U16
320=10 signals, 32 bit each Number of receive bits, 320=10 signals, 32 bit each
Set by MN during congu-
ration Set by MN during congu­ration
ration
of 300 to 1500
High nibble Low nibble
POWERLINK Main Version POWERLINK Sub Version
Table 6.24 Implemented Communication Prole
6.2.23
1F8C NMT_CurrNMTState_U8
Table 6.27 Node-specic Timing Parameters
6.2.26
1F99h NMT_CNBasicEthernetTimeout_U32
This object species the time in µs for which the option must wait for SoC before switching to basic Ethernet
This object holds the node‘s current NMT state.
30 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
mode.
Communication Prole Area Operating Instructions
Index, sub­index
1F99 NMT_CNBasicEthernet-
Meaning Remark
Timeout_U32
Table 6.28 Basic Ethernet Timeout
Time in microseconds before switching to basic Ethernet mode. Default 5000000 (5 s) Mapped to
parameter 12-63 Basic Ethernet Timeout
6.2.27 1F9Ah NMT_HostName_VSTR _U32
Index, sub­index
1F9A NMT_HostName_VSTR Mapped to
Table 6.29 DNS Host Name
6.2.28
This object is used to reset the frequency converter, communication or conguration.
Hex value NMT service
FFh NMTInvalidService 2Bh NMTSwReset 28h NMTResetNode 2Ah NMTResetConguration 29h NMTResetCommunication
Table 6.30 Reset Command
6.3
Meaning Meaning
parameter 12-08 Host Name
1F9E NMT_ResetCmd_U8
2000-5FFF Danfoss Specic Object Area
6.3.1 2000h–5FFFh Vendor Specic Object
Area
The area 2000h to 5FFFh holds the indexes for accessing the Danfoss frequency converter parameters. All parameters in the frequency converter are linked to indexes in this area. The rst index available is index
2001h. This index is linked to the frequency converters parameter 0-01 Language. The rest of the POWERLINK index follows the same rule, where the frequency converters parameter number plus 2000h gives the POWERLINK index. For example, reading the running hours in parameter 15-01 Running Hours, is calculated by 2000h + parameter number in hex number=2000h+5DD=index 25DDh. The XDD le only contains a subset of the frequency converters parameters. This subset has the indexes that are required for setting up the PDO communi­cation. All parameters can be read or written via SDO communication from the PLC. Table 6.31 shows a few indexes and their mapping.
Index Parameter
2001h parameter 0-01 Language 2002h parameter 0-02 Motor Speed Unit 2003h parameter 0-03 Regional Settings .. 2078h parameter 1-20 Motor Power [kW] 2079h parameter 1-22 Motor Voltage .. 24B1h parameter 12-01 IP Address 24B2h parameter 12-02 Subnet Mask
Table 6.31 2000h-5FFFh Vendor Specic Object Area
6.4
6000-Device prole Object Area
6.4.1 6000h–9FFFh Standardised Device Prole Area
The area 6000h to 9FFFh holds the indexes specied by the IEC for various device proles. The Danfoss POWERLINK does support three proles, FC Prole, MCO, and the DS 402 prole, velocity mode. The prole is selected via
parameter 8-10 Control Word
via Index 6060h Modes of operation. The prole area has up to 13 indexes depending on the selection made in
parameter 8-10 Control Word Prole.
Table 6.32 shows the support of indexes, depending on
setting of parameter 8-10 Control Word Prole (Index 6060h)
Prole, Control Word Prole, or
6 6
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 31
Communication Prole Area MCA 123 POWERLINK
Index Name parameter 8-10 Control
Word Prole =FC Prole
603Fh Error code - - √ 6040h Control word - - √ 6041h Status word - - √ 6042h Vl_target_velocity - - √ 6043h Vl_velocity_demand - - √ 6044h Vl_velocity_actual_value - - √ 6046h Vl_velocity_min_max_amount - - √ 6048h Vl_velocity_acceleration - - √ 6049h Vl_velocity_deceleration - - √ 6060h Modes of operation √ 6061h Modes of operation display √ 6502h Supported frequency converter mode √ 6504h Frequency converter manufacture
Table 6.32 6000h-9FFFh Standardised Device Prole Area
parameter 8-10 Control Word Prole= MCO
parameter 8-10 Control Word Prole= DS 402
66
603Fh Error Code
6.4.2
Error signaling mechanism is used to signal alarms and events generated on the frequency converter to the MN. The error code consist of 8 byte of data, where: Byte 0 (zero) is a copy of object 1001h. Byte 1 & 2, not used. Byte 3 contains: Bit 0=1, Alarmword 1 has an active Alarm (parameter 16-90 Alarm Word). Bit 1=1, Alarmword 2 has an active Alarm (Future ext. parameter 16-91 Alarm Word 2). Bit 2=0, Reserved. Bit 3=1, Warningword 1 has an active Warning (parameter 16-92 Warning Word). Bit 4=1, Warningword 2 has an active Warning (Future ext. parameter 16-93 Warning Word 2). Bit 5-7=0, Reserved. Byte 4 and 5, Prole specic. Byte 6 and 7, reserved.
6040h Control Word
6.4.3
This object contains the control word in accordance with DS 402. The control word consists of 16 bit, these 16 bit are used for controlling the frequency converter (for example, start, stop, reset). The control word is described in chapter 5.4 DS 402 Control Prole.
6041h Status Word
6.4.4
6043h vl_velocity_demand
6.4.6
The vl_velocity_demand is the velocity of the system after the ramp controller. The velocity is in RPM.
6.4.7 6044h vl_actual_velocity_value
The vl_actual_velocity_value is the velocity at the motor shaft. The velocity is in RPM, and is obtained from parameter 16-17 Speed [RPM]. The velocity is in RPM.
6.4.8 6046h vl_velocity_min_max_amount
The vl_ velocity_min_max_amount is the minimum and maximum RPM at the motor shaft. The two values are obtained from parameter 3-02 Minimum Reference and
parameter 3-03 Maximum Reference. The readout values in parameter 3-02 Minimum Reference and parameter 3-03 Maximum Reference will be truncated.
Index, sub-index Meaning
1046h 0 Number of sub-index supported 1046h 1 vl_velocity_min_max_amount 1046h 2 vl_velocity_min_amount
This object contains the Status word in accordance to DS
402. The status word consists of 16 bit. The 16 bits show the state and status of the frequency converter (for example, running, ramping, on speed). The Status word is described in chapter 5.4 DS 402 Control
6042h vl_target_velocity
6.4.5
The vl_target_velocity is the required velocity of the system. The velocity is in RPM.
32 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
Prole.
Table 6.33 Minimum/Maximum RPM at Motor Shaft
6048h vl_velocity_acceleration
6.4.9
The vl_ velocity_acceleration index species the slope of the acceleration ramp. It is generated as the quotient of the delta_speed and delta_time. The Delta time is stored in parameter 3-41 Ramp 1 Ramp Up Time, and the Delta speed is store locally in the options non volatile memory. After a power down the delta speed will be generated from the frequency converter parameter 1-25 Motor Nominal Speed.
Communication Prole Area Operating Instructions
This can give a dierent readout from the frequency converter, but the slope value is maintained.
Index, sub-index Meaning
1048h 0 Number of sub-index supported 1048h 1 Delta speed 1048h 2 Delta time
Table 6.34 6048h vl_velocity_acceleration
6.4.10 6049h vl_velocity_deceleration
The vl_ velocity_deceleration index species the slope of the deceleration ramp. It is generated as the quotient of the delta_speed and delta_time. The Delta time is stored in parameter 3-42 Ramp 1 Ramp Down Time, and the Delta speed is stored locally in the options non volatile memory. After a power down, the delta speed is generated from the frequency converter parameter 1-25 Motor Nominal Speed. This can give a converter, but the slope value is maintained.
Index, sub-index Meaning
1049h 0 Number of sub-index supported 1049h 1 Delta speed 1049h 2 Delta time
Table 6.35 6049h vl_velocity_deceleration
dierent readout from the frequency
Index, 6061h value
-2 MCO prole (only possible if MCO305 is
-1 FC Prole 2 DS 402 prole
Table 6.37 6061h Modes of Operation Display
Meaning
mounted)
6.4.13 6502h Supported Frequency
Converter Mode
This index informs the user of which operating mode the frequency converter is capable of. Bit 1 is set, indicating that the frequency converter can run DS 402 velocity mode, bit 16 FC prole and 17 indicates MCO prole.
6.4.14
6504h Frequency Converter Manufacturer
This index does readout the name of the frequency converter manufacturer. Data is coded as a string.
Index, sub-index Meaning
6504Ch 0 Manufacturer “DANFOSS DRIVES”
Table 6.38 6504h Drive Manufacturer (read only)
6 6
6.4.11
This index is used for selection the Danfoss FC prole, MCO prole, or the DS 402 prole. The index links directly to parameter 8-10 Control Word Prole. If this value is changed while in operation, the option enters the “Error PREOP” state.
Index, 6060h value
-2 MCO prole (only possible if MCO305 is
-1 FC Prole 2 DS 402 prole
6.4.12
This index is used to display which mode the frequency converter is in. The mode can be changed via index 6060. The values are the same as used for index 6060.
6060h Modes of Operation
Meaning
mounted)
Table 6.36 6060h Modes of Operation
6061h Modes of Operation Display
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 33
Parameters MCA 123 POWERLINK
7 Parameters
7.1 Parameter Group 8-** Communication and Option
8-01 Control Site
Option: Function:
The setting in this parameter overrides the settings in parameter 8-50 Coasting Select to parameter 8-56 Preset Reference Select.
[0] Digital and
ctrl.word
[1] Digital only Control by using digital inputs only.
[2] Controlword
only
8-02 Control Word Source
Option: Function:
77
None
[0] [1] FC RS485 [2] FC USB [3] Option A [4] Option B [5] Option C0 [6] Option C1 [30] External Can
Control by using both digital input and control word.
Control by using control word only.
NOTICE
This parameter cannot be adjusted while the motor runs.
Select the source of the control word: 1 of 2 serial interfaces or 4 installed options. During initial power-up, the frequency converter automatically sets this parameter to [3] Option A, if it detects a valid in slot A. When the option is removed, the frequency converter detects a conguration change, sets parameter 8-02 Control Word Source to default setting RS485, and trips. If an option is installed after initial power-up, the setting of parameter 8-02 Control Word Source does not change, but the frequency converter trips and shows: Alarm 67, Option Changed.
retrotting a bus option into a
When frequency converter that did not have a bus option installed earlier, change the control to bus-based. This change is required for safety reasons to avoid an unintended change.
eldbus option installed
8-03 Control Word Timeout Time
Range: Function:
1 s* [ 0.1 -
18000 s]
Enter the maximum time expected to pass between the reception of 2 consecutive telegrams. If this time is exceeded, it indicates that the telegram communication has stopped. The function selected in parameter 8-04 Control Word Timeout Function is then carried out. A valid control word triggers the timeout counter.
8-04 Control Word Timeout Function
Select the timeout function. The timeout function activates when the control word fails to be updated within the time period specied in parameter 8-03 Control Word Timeout Time.
Option: Function:
[0] O Resumes control via eldbus (eldbus or
standard) using the most recent control word.
[1] Freeze output Freezes output frequency until communi-
cation resumes.
[2] Stop Stops with auto restart when communi-
cation resumes.
[3] Jogging Runs the motor at jog frequency until
communication resumes.
[4] Max. speed Runs the motor at maximum frequency until
communication resumes.
[5] Stop and trip Stops the motor, then resets the frequency
converter to restart:
Via the eldbus.
Via [Reset].
Via a digital input.
[7] Select setup1Changes the set-up after reestablishment of
communication following a control word timeout. If communication resumes after a timeout, parameter 8-05 End-of-Timeout Function denes whether to resume the set- up used before the timeout, or to retain the set-up endorsed by the timeout function.
NOTICE
To change the set-up after a timeout, congure as follows: Set parameter 0-10 Active Set-up to [9] Multi set-up and select the relevant link in parameter 0-12 This Set-up Linked to.
[8] Select setup
2
34 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
See [7] Select set-up 1.
Parameters Operating Instructions
8-04 Control Word Timeout Function
Select the timeout function. The timeout function activates when the control word fails to be updated within the time period specied in parameter 8-03 Control Word Timeout Time.
Option: Function:
[9] Select setup
3
[10] Select setup
4
[26] Trip
See [7] Select set-up 1.
See [7] Select set-up 1.
8-05 End-of-Timeout Function
Option: Function:
Select the action after receiving a valid control word following a timeout. This parameter is active only when parameter 8-04 Control Timeout
Function is set to:
[7] Set-up 1.
[8] Set-up 2.
[9] Set-up 3.
[10] Set-up 4.
[0] Hold set-upRetains the set-up selected in
parameter 8-04 Control Timeout Function and displays a warning until parameter 8-06 Reset Control Timeout toggles. Then the frequency converter resumes its original set-up.
[1] Resume
set-up
Resumes the set-up active before the timeout.
8-06 Reset Control Word Timeout
This parameter is active only when [0] Hold set-up has been selected in parameter 8-05 End-of-Timeout Function.
Option: Function:
[0] Do not reset
[1] Do reset Returns the frequency converter to the original
Retains the set-up specied in parameter 8-04 Control Word Timeout Function, following a control word timeout.
set-up following a control word timeout. The frequency converter performs the reset and then immediately reverts to the [0] Do not reset setting.
8-07 Diagnosis Trigger
This parameter enables and controls the frequency converter diagnosis/Emergency function. In Probus, it expands the diagnosis data to 24 byte. In EtherCAT, it activates the transmission of the Emergency object. In POWERLINK, it enables the Error signaling. The Emergency/Error signaling object consists of 8 byte of data, where byte 3 indicates an active alarm or warning. Bit 0=1 Alarmword 1 has an active Alarm. Bit 1=1 Alarmword 2 has an active Alarm. Bit 2, reserved, Bit 3=1 Warningword 1 has an active warning. Bit 4=1 Warningword 2 has an active warning. Bits 5-7, reserved.
Option: Function:
[0] Disable [1] Trigger on alarms [2] Trigger alarm/warn.
NOTICE
The following is only valid for Probus and EtherCAT.
[0] Disable: Do not send extended diagnosis/
-
emergency data even if they appear in the frequency converter.
[1] Trigger on alarms: Send extended diagnosis/
-
emergency data when one or more alarms appear in alarm parameter 16-90 Alarm Word or
parameter 9-53 [2] Trigger alarms/warn.: Send extended diagnosis/
-
emergency data if one or more alarms or warnings appear in alarm parameter 16-90 Alarm Word, parameter 9-53 warning parameter 16-92 Warning Word.
Enabling diagnosis can cause increased bus eldbus types support Diagnosis functions.
8-08 Readout Filtering
If the speed feedback value readouts on eldbus are uctuating, this function is used. Select ltered, if the function is required. A power cycle is required for changes to take eect.
Option: Function:
[0] Motor Data
Std-Filt.
[1] Motor Data LP-
Filter
Probus Warning Word.
Probus Warning Word, or
trac. Not all
Normal eldbus readouts.
Filtered eldbus readouts of the following parameters:
Parameter 16-10 Power [kW ]. Parameter 16-11 Power [hp]. Parameter 16-12 Motor Voltage. Parameter 16-14 Motor current. Parameter 16-16 Torque [Nm]. Parameter 16-17 Speed [RPM]. Parameter 16-22 Torque [%]. Parameter 16-25 Torque [Nm] High.
7 7
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 35
Parameters MCA 123 POWERLINK
8-10 Control Word Prole
Select the interpretation of the control and status words corresponding to the installed eldbus. Only the selections valid for the eldbus installed in slot A are visible in the LCP display. If the parameter is changed while the frequency converter is in operation mode, the frequency converter goes to error state, and the control of the frequency converter is lost. This parameter should not be changed while the motor is running, since it can lead to a unknown state of the prole.
Option: Function:
[0] * FC Prole [7] CANopen DSP 402
8-13 Congurable Status Word STW
Option: Function:
This parameter enables conguration of bits
12–15 in the status word. [0] No function [1] * Prole Default Function corresponds to the prole default
selected in parameter 8-10 Control Prole.
77
[2] Alarm 68
Only
[3] Trip excl.
Alarm 68
[10] T18 DI status. The bit indicates the status of terminal 18.
[11] T19 DI status. The bit indicates the status of terminal 19.
[12] T27 DI status. The bit indicates the status of terminal 27.
[13] T29 DI status. The bit indicates the status of terminal 29.
[14] T32 DI status. The bit indicates the status of terminal 32.
[15] T33 DI status. The bit indicates the status of terminal 33.
[16] T37 DI status The bit indicates the status of terminal 37.
[21] Thermal
warning
[30] Brake fault
(IGBT)
Only set in case of an Alarm 68.
Set in case of a trip, except if Alarm 68
executes the trip.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
0 indicates terminal 37 is low (Safe Torque
stop).
1 indicates terminal 37 is high (normal).
The thermal warning turns on when the
temperature exceeds the limit in the motor,
the frequency converter, the brake resistor,
or the thermistor.
Output is logic 1 when the brake IGBT is
short-circuited. Use this function to protect
the frequency converter if there is a fault
on the brake modules. Use the output/relay
to cut out the main voltage from the
frequency converter.
8-13 Congurable Status Word STW
Option: Function:
[40] Out of ref.
range
[60] Comparator 0
[61] Comparator 1
[62] Comparator 2
[63] Comparator 3
[64] Comparator 4
[65] Comparator 5
[70] Logic Rule 0
[71] Logic Rule 1
[72] Logic Rule 2
[73] Logic Rule 3
[74] Logic Rule 4
[75] Logic Rule 5
[80] SL Digital
Output A
[81] SL Digital
Output B
[82] SL Digital
Output C
See parameter group 13-1* Comparators. If comparator 0 is evaluated as TRUE, the output goes high. Otherwise, it is low. See parameter group 13-1* Comparators. If comparator 1 is evaluated as TRUE, the output goes high. Otherwise, it is low. See parameter group 13-1* Comparators. If comparator 2 is evaluated as TRUE, the output goes high. Otherwise, it is low. See parameter group 13-1* Comparators. If comparator 3 is evaluated as TRUE, the output goes high. Otherwise, it is low. See parameter group 13-1* Comparators. If comparator 4 is evaluated as TRUE, the output goes high. Otherwise, it is low. See parameter group 13-1* Comparators. If comparator 5 is evaluated as TRUE, the output goes high. Otherwise, it is low. See parameter group 13-4* Logic Rules. If logic rule 0 is evaluated as TRUE, the output goes high. Otherwise, it is low. See parameter group 13-4* Logic Rules. If logic rule 1 is evaluated as TRUE, the output goes high. Otherwise, it is low. See parameter group 13-4* Logic Rules. If logic rule 2 is evaluated as TRUE, the output goes high. Otherwise, it is low. See parameter group 13-4* Logic Rules. If logic rule 3 is evaluated as TRUE, the output goes high. Otherwise, it is low. See parameter group 13-4* Logic Rules. If logic rule 4 is evaluated as TRUE, the output goes high. Otherwise, it is low. See parameter group 13-4* Logic Rules. If logic rule 5 is evaluated as TRUE, the output goes high. Otherwise, it is low. See parameter 13-52 SL Controller Action. The output goes high whenever the smart logic action [38] Set digital out A high is executed. The output goes low whenever the smart logic action [32] Set digital out A low is executed. See parameter 13-52 SL Controller Action. The input goes high whenever the smart logic action [39] Set digital out B high is executed. The input goes low whenever the smart logic action [33] Set digital out B low is executed. See parameter 13-52 SL Controller Action. The input goes high whenever the smart logic action [40] Set digital out C high is executed. The input goes low whenever the smart
36 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
Parameters Operating Instructions
8-13 Congurable Status Word STW
Option: Function:
logic action [34] Set digital out C low is
executed. [83] SL Digital
Output D
[84] SL Digital
Output E
[85] SL Digital
Output F
See parameter 13-52 SL Controller Action. The
input goes high whenever the smart logic
action [41] Set digital out D high is executed.
The input goes low whenever the smart
logic action [35] Set digital out D low is
executed.
See parameter 13-52 SL Controller Action. The
input goes high whenever the smart logic
action [42] Set digital out E high is executed.
The input goes low whenever the smart
logic action [36] Set digital out E low is
executed.
See parameter 13-52 SL Controller Action. The
input goes high whenever the smart logic
action [43] Set digital out F high is executed.
The input goes low whenever the smart
logic action [37] Set digital out F low is
executed.
8-14 Congurable Control Word CTW
Option: Function:
This parameter is not valid in software versions below 4.93.
[0] None The information in this bit is ignored by the
frequency converter.
[1] Prole
default
[2] CTW
Valid, active low
[3] Safe
Option Reset
[4] PID error
inverse
[5] PID reset
I part
[6] PID
enable
The functionality of the bit is depending on the selection in parameter 8-10 Control Word Prole.
If set to 1, the frequency converter ignores the remaining bits of the Control Word.
This function is only available in bits 12-15 of the control word, if a a safe option is mounted in the frequency converter. The reset is executed on a 0­>1 transition, and reset the safe option as set in parameter 42-24.
When enabled, it inverts the resulting error from the process PID controller. Available only if
parameter 1-00 Conguration Mode is set to [6] Surface Winder, [7] Extended PID Speed OL or [8] Extended PID Speed CL.
When enabled, resets the I-part of the process PID controller. Equivalent to parameter 7-40 Process PID
I-part Reset. Available only if parameter 1-00 Conguration Mode is set to [6] Surface Winder, [7] Extended PID Speed OL or [8] Extended PID Speed CL.
When enabled, enables the extended process PID controller. Equivalent to parameter 7-50 Process PID Extended PID. Available only if
8-14 Congurable Control Word CTW
Option: Function:
parameter 1-00 Conguration Mode is set to [6] Surface Winder, [7] Extended PID Speed OL or [8] Extended PID Speed CL.
8-50 Coasting Select
Option: Function:
Select control of the coasting function via the terminals (digital input) and/or via the bus.
[0] Digital
input
[1] Bus Activates start command via the serial communi-
[2] Logic AND Activates start command via the eldbus/serial
[3] Logic OR Activates start command via the eldbus/serial
Activates start command via a digital input.
cation port or eldbus option.
communication port, and 1 extra digital input.
communication port, or via 1 of the digital inputs.
8-51 Quick Stop Select
Select control of the quick stop function via the terminals (digital input) and/or via the bus.
Option: Function:
[0] Digital input [1] Bus [2] Logic AND [3] Logic OR
8-52 DC Brake Select
Option: Function:
Select control of the DC brake via the terminals (digital input) and/or via the eldbus.
NOTICE
When parameter 1-10 Motor Construction is set to [1] PM non-salient SPM, only selection [0] Digital input is available.
[0] Digital
input
8-53 Start Select
Option: Function:
[0] Digital
input
[1] Bus Activates a start command via the serial
Activates start command via a digital input.
Select control of the frequency converter start function via the terminals (digital input) and/or via the eldbus.
Activates a start command via a digital input.
communication port or eldbus option.
7 7
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 37
Parameters MCA 123 POWERLINK
8-53 Start Select
Option: Function:
[2] Logic
AND
[3] Logic OR Activates a start command via the eldbus/serial
Activates a start command via the eldbus/serial communication port, and additionally via 1 of the digital inputs.
communication port, or via 1 of the digital inputs.
8-54 Reversing Select
Option: Function:
[0] Digital
input
[1] Bus Activates the reverse command via the serial
[2] Logic AND Activates the reverse command via the eldbus/
[3] Logic OR Activates the reverse command via the eldbus/
77
Select control of the frequency converter reverse function via the terminals (digital input) and/or via the eldbus.
communication port, or eldbus option.
serial communication port, and additionally via 1 of the digital inputs.
serial communication port, or via 1 of the digital inputs.
8-55 Set-up Select
7.2 Parameter Group 12-** Ethernet
7.2.1 12-0* IP Settings
12-00 IP Address Assignment
Option: Function:
Selects the IP Address assignment method.
[0] MANUAL
[1] DHCP IP-address is assigned via DHCP server.
[2] BOOTP IP-address is assigned via BOOTP server.
[10] DCP DCP Assigned via the DCP protocol.
[20] From node
ID
12-01 IP Address
Range: Function:
0 * [0 -
2147483647 ]
IP-address can be set in parameter 12-01 IP Address IP Address.
Address is set from parameter 12-60 Node ID only.
Congure the IP address of the option. Read-only if parameter 12-00 IP Address Assignment set to DHCP or BOOTP. In POWERLINK, the IP address follows the parameter 12-60 Node ID last byte and the rst part is xed to 192.168.100 (node ID).
Option: Function:
Select control of the frequency converter set-up selection via the terminals (digital input) and/or via the eldbus.
[0] Digital
input
[1] Bus Activates the set-up selection via the serial
[2] Logic
AND
[3] Logic OR Activates the set-up selection via the eldbus/
Activates the set-up selection via a digital input.
communication port, or eldbus option.
Activates the set-up selection via the eldbus/ serial communication port, and via 1 of the digital inputs.
serial communication port, or via 1 of the digital inputs.
8-90 Bus Jog 1 Speed
Range: Function:
100 RPM* [ 0 - par. 4-13
RPM]
Enter the jog speed. Activate this xed jog speed via the serial port or eldbus option.
12-02 Subnet Mask
Range: Function:
0 * [0 -
4244635647 ]
Congure the IP subnet mask of the option. Read-only if parameter 12-00 IP Address Assignment set to DHCP or BOOTP. In POWERLINK it is xed to
255.255.255.0.
12-03 Default Gateway
Range: Function:
0 * [0 -
2147483647 ]
Congure the IP default gateway of the option. Read-only if parameter 12-00 IP Address Assignment set to DHCP or BOOTP. In a non-routed network this address is set to the IP address of the IO Device
12-08 Host Name
Range: Function:
0 * [0 - 2147483647 ] Logical (given) name of option.
8-91 Bus Jog 2 Speed
Range: Function:
200 RPM* [ 0 - par. 4-13
RPM]
38 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
Enter the jog speed. Activate this xed jog speed via the serial port or eldbus option.
NOTICE
The display of the frequency converter only shows the rst 19 characters, but the remaining characters are stored in the frequency converter. If hardware switches are dierent from all ON or all OFF, the switches have priority.
Parameters Operating Instructions
12-09 Physical Address
Range: Function:
0 * [0 - 0 ] Read-only. Displays the physical (MAC) address of
the option.
7.2.2 12-1* Ethernet Link Parameters
7.2.3 12-1* Ethernet Link Parameters
Applies for the whole parameter group.
Index [0] is used for port 1, and Index [1] is used for port
2. For EtherCAT, index [0] is for the in-port and index [1] is for the out-port.
12-10 Link Status
Option: Function:
Read-only. Displays the link status of the Ethernet ports.
[0] No Link [1] Link
12-11 Link Duration
Range: Function:
Size related* [ 0 - 0 ] Read-only. Displays the duration of the
present link on each port in dd:hh:mm:ss.
12-12 Auto Negotiation
Option: Function:
Congures auto negotiation of Ethernet link parameters, for each port: ON or OFF.
[0] O
[1] On
Link Speed and Link Duplex can be congured in parameter 12-13 Link Speed and parameter 12-14 Link Duplex.
NOTICE
In POWERLINK, this parameter is xed to OFF setting.
12-13 Link Speed
Option: Function:
Forces the link speed for each port in 10 Mbps or 100 Mbps. If parameter 12-12 Auto Negotiation is set to: ON, this parameter is read-only and displays the actual link speed. If no link is present, None is displayed.
[0] None [1] 10 Mbps [2] 100
Mbps
NOTICE
In POWERLINK, this parameter is locked to 100 Mbs.
12-14 Link Duplex
Option: Function:
Forces the duplex for each port to full or half duplex. If parameter 12-12 Auto Negotiation is set to: [ON], this parameter is read-only.
[0] Half Duplex [1] Full Duplex
NOTICE
In POWERLINK this parameter is locked to half duplex.
7.2.4 12-2* Process Data
12-20 Control Instance
Range: Function:
[None, 20, 21, 23, 100, 101, 103]
12-21 Process Data Cong Write
Range: Function:
[[0 - 9] PCD read 0 - 9] Conguration of readable process
In POWERLINK, this parameter is read-only. The same applies for:
12-22 Process Data
Range: Function:
[[0 - 9] PCD read 0 - 9] Conguration of readable process
12-23 Process Data Cong Write Size
Range: Function:
16 * [8 - 32 ] Sets the number of bits being sent from the
12-24 Process Data Cong Read Size
Range: Function:
16 * [8 - 32 ] Sets the number of bits being sent to the
Read-only. Displays the connection to the master. In Ethernet/IP: If no CIP connection is present, None is displayed. In EtherCAT: If no connection is active None is displayed, else it displays the active PDO. In POWERLINK: If no connection is active None is displayed, else it displays the active PDO (23).
data.
parameter 12-22EN-22 Process Data Cong Read parameter 12-23 Process Data Cong Write Size parameter 12-24 Process Data Cong Read Size
Cong Read
data.
frequency converter as process data. The setting counts from right (LSB). The value 1 means that only the least signicant bit of the signal is transferred from the frequency converter.
frequency converter as process data. The setting counts from right (LSB). The value 1 means that only the least signicant bit of the signal is
7 7
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 39
Parameters MCA 123 POWERLINK
12-24 Process Data Cong Read Size
Range: Function:
transferred to the frequency converter. The preceding bits are set to zero.
12-28 Store Data Values
Option: Function:
[0] O [1] Store all setups [2] Store all setups
12-29 Store Always
Option: Function:
Activates function that always stores received
parameter data in non-volatile memory (EEPROM). [0] * O [1] On
7.2.5 12-6* Ethernet PowerLink
77
12-60 Node ID
Range: Function:
1 * [1 -
239 ]
Enter the Node ID in this parameter or alternatively in the hardware switch. In order to adjust the Node ID in parameter 12-60 Node ID, the hardware switch must be set to 0 or 255 (i.e. all switches set to [ON] or to [OFF]). Otherwise this parameter displays the actual setting of the switch. Setting this parameter will
rst be active at the next power up cycle.
12-66 Threshold
Range: Function:
15* [0 -
2000000000 ]
Parameter 12-66 Threshold holds six threshold values. If one of these thresholds are exceeded, the POWERLINK Interface exits operational mode. The parameters are set to optimal settings and should not be changed. The actual value of the counters can be read out via parameter 12-67 Threshold Counters.
12-67 Threshold Counters
Range: Function:
0* [0 -
4294967295 ]
Parameter 12-67 Threshold Counters hold 6 counters. The counter reects the actual value in the POWERLINK interface. Counters increases with a count of eight at detection of an error and decreases with a count of one when no errors are detected. The values are read only.
12-68 Cumulative Counters
Range: Function:
0 * [0 - 2147483647 ] Loss o SoC Cumulative. This parameter
reects the value in object 1C0Bh,
subindex 1.
12-69 Ethernet PowerLink Status
Range: Function:
0 * [0 - 4294967295 ]
12-62 SDO Timeout
Range: Function:
30000 ms*
[0 ­2000000000 ms]
parameter 12-62 SDO Timeout is the SDO Timeout in milliseconds. Value of this parameter is read during communication initialization into Object 1300h
12-63 Basic Ethernet Timeout
Range: Function:
5000.000 ms*
[0 -
2000000.000 ms]
Parameter 12-63 Basic Ethernet Timeout in microseconds. This
parameter is mapped to Object 1F99h. If the POWERLINK interface does not receive a SoC frame within the specied period of time, the interface shifts to standard Ethernet mode. This feature is from version 2.00 of the POWERLINK Interface.
rst available
7.2.6 12-8* Other Ethernet Services
12-80 FTP Server
Option: Function:
[0] Disabled Disables the built-in FTP server.
12-81 HTTP Server
Option: Function:
[0] Disabled
12-82 SMTP Service
Option: Function:
[0] Disabled
12-89 Transparent Socket Channel Port
Range: Function:
Size related*
[ 0 ­0 ]
Congures the TCP port number for the transparent socket channel. This congu- ration enables FC telegrams to be sent transparently on Ethernet via TCP. Default value is 4000, 0 means disabled. The MCT 10 Set-up Software uses this port.
40 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
Parameters Operating Instructions
7.2.7 12-9* Advanced Ethernet Settings
12-90 Cable Diagnostic
Option: Function:
Enables/disables advanced cable diagnosis function. If enabled, the distance to cable errors can be read out in parameter 12-93 Cable Error Length. The parameter resumes to the default setting of disable after the diagnostics have
nished.
[0] Disabled [1] Enabled
NOTICE
The cable diagnostics function is only issued on ports where there is no link (see parameter 12-10 Link Status, Link Status)
12-91 Auto Cross Over
Option: Function:
[0] Disabled Disables the auto cross-over function.
[1] Enabled Enables the auto cross-over function.
12-96 Port Cong
Enables/disables port-mirroring function. For troubleshooting with a network analyser tool.
Option: Function:
[0] Normal No port-mirroring
[1] Mirror Port 1 to 2 All network trac on port 1
is mirrored to port 2.
[2] Mirror Port 2 to 1 All network trac on port 2
is mirrored to port 1.
[10] Port 1 disabled [11] Port 2 disabled [254] Mirror Int. Port to 1 [255] Mirror Int. Port to 2
7 7
12-93 Cable Error Length
Range: Function:
0 * [0 -
65535 ]
If cable diagnostics is enabled in parameter 12-90 Cable Diagnostic, the built-in switch is possible via time domain reectometry (TDR). This measurement technique detects common cabling problems such as open circuits, short circuits, and impedance mismatches or breaks in transmission cables. The distance from the option to the error is displayed in meters with an accuracy of ±2 m. The value 0 means that no errors detected.
7.3 POWERLINK - Specic Parameter List
Parameter Default value Range Conversion index Data type
Parameter 8-01 Control Site [0] Dig. & ctrl. word [0-2] - Uint8 Parameter 8-02 Control Word Source [0] FC RS485 [0-4] - Uint8 Parameter 8-03 Control Word Timeout Time 1 0.1-18000 -1 Uint32 Parameter 8-04 Control Word Timeout Function [0] O [0-10] - Uint8 Parameter 8-05 End-of-Timeout Function [0] Hold set-up [0-1] - Uint8 Parameter 8-06 Reset Control Word Timeout [0] Do not reset [0-1] - Uint8 Parameter 8-07 Diagnosis Trigger [0] Disable [0-3] - Uint8 Parameter 8-10 Control Word Prole [0] FC prole [0-x] - Uint8 Parameter 8-13 Congurable Status Word STW Parameter 8-50 Coasting Select [3] *Logic OR [0-3] - Uint8 Parameter 8-51 Quick Stop Select [3] *Logic OR [0-3] - Uint8
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 41
Parameters
Parameter Default value Range Conversion index Data type
Parameter 8-52 DC Brake Select [3] *Logic OR [0-3] - Uint8 Parameter 8-53 Start Select [3] *Logic OR [0-3] - Uint8 Parameter 8-54 Reversing Select [3] *Logic OR [0-3] - Uint8 Parameter 8-55 Set-up Select [3] *Logic OR [0-3] - Uint8 Parameter 8-56 Preset Reference Select [3] *Logic OR [0-3] - Uint8
Parameter 8-90 Bus Jog 1 Speed 100 rpm
Parameter 8-91 Bus Jog 2 Speed 200 rpm parameter 12-00 IP Address Assignment [20] *From node ID - - Unsigned 8 parameter 12-01 IP Address 192.168.100.xxx - - Unsigned 32 parameter 12-02 Subnet Mask 255.255.255.0 - - Unsigned 32 parameter 12-03 Default Gateway 0.0.0.0 - - Unsigned 32 parameter 12-08 Host Name - - String Parameter 12-09 Physical Address 00:1B:08:00:00:00 - - Visible string 17 Parameter 12-10 Link Status [0] No Link [0-1] - Unsigned 8 Parameter 12-11 Link Duration 00:00:00:00 - - Time di. w/date Parameter 12-12 Auto Negotiation [1] On [0-1] - Unsigned 8 Parameter 12-13 Link Speed [2] 100 Mbps [0-2] - Unsigned 8
77
Parameter 12-14 Link Duplex [0] Hal Duplex [0-1] - Unsigned 8[ parameter 12-20 Control Instance Application Dependent 0-255 parameter 12-21 Process Data Cong Write Application Dependent parameter 12-22EN-22 Process Data Cong Read 16 1-32 parameter 12-23 Process Data Cong Write Size 16 1-32 parameter 12-24 Process Data Cong Read Size 0 0-4294967295 parameter 12-28 Store Data Values parameter 12-29 Store Always [0] O parameter 12-60 Node ID [1] [0-240] Unsigned 8
parameter 12-62 SDO Timeout parameter 12-63 Basic Ethernet Timeout parameter 12-66 Threshold parameter 12-67 Threshold Counters parameter 12-68 Cumulative Counters
Parameter 12-80 FTP Server [0] Disable [0–1] - Unsigned 8 Parameter 12-81 HTTP Server [0] Disable [0–1] - Unsigned 8 Parameter 12-82 SMTP Service [0] Disable [0–1] - Unsigned 8 Parameter 12-89 Transparent Socket Channel Port [0] Disable [0–1] - Unsigned 8 Parameter 12-90 Cable Diagnostic [0] Disable [0-1] - Unsigned 8 Parameter 12-91 Auto Cross Over [0] Enable [0-1] - Unsigned 8 Parameter 12-93 Cable Error Length 0 0-200 0 Unsigned 16 Parameter 12-98 Interface Counters 0 0-65535 - Unsigned 16 Parameter 12-99 Media Counters 0 0-65535 - Unsigned 16 Parameter 16-84 Comm. Option STW 0 0-FFFF 0 V2 Parameter 16-90 Alarm Word 0 0-FFFF 0 Uint32 Parameter 16-92 Warning Word 0 0-FFFF 0 Uint32
MCA 123 POWERLINK
0-parameter 4-13 Motor Speed High Limit [RPM] 0-parameter 4-13 Motor Speed High Limit [RPM]
30000 [0-65535] Unsigned 16 [5000000] [0-4294967296] Unsigned 32 [15] [0-4294967296] Unsigned 32 [0] [0-4294967296] Unsigned 32 [0] [0-4294967296] Unsigned 32
67 Uint16
67 Uint16
Table 7.1 Specic Parameters
Refer to the relevant Operating Instructions for a comprehensive parameter list.
42 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
Parameters Operating Instructions
7 7
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 43
Recieve PDO’s (PLC Drive)
Transmit PDO’s (Drive
PLC )
PCD 0
CTW
PCD 1
REF
PCD 3
Digital Inputs
PCD 0
STW
PCD 1
MAV
PCD 2
Torque [Nm]
Sensor
Reversing
18
Ext. Device
Relay 04-05
230 VAC
12
20
19
+
-
13
20
­+
130BD148.10
Application Examples MCA 123 POWERLINK
8 Application Examples
8.1 Example: Process Data with PDO 23
This example shows how to work with PDO 23, which consists of Control Word/Status Word and Reference/Main Actual Value. In the example the frequency converter is set to [0] FC prole in Parameter 8-10 Control Word Prole. The PDO contains up to ten objects, which can be programmed to monitor process signals.
From controller
From frequency
converter
0 1 2 3
CTW MRV PCD[2] PCD
04 7C 20 00 00 00 00 00
STW MAV PCD[2] PCD[3]
07
0F
20
00
PCD
3F A6 00 08
Byte # 1 2 3 4 5 6 7 8
Table 8.1 Example of FC Prole
The application requires monitoring of the motor torque and digital input, so PCD 2 is set up to read the current motor torque. PCD 3 is set up to monitor the state of an
88
external sensor via the process signal digital input. The sensor is connected to digital input 18.
An external device is also controlled via control word bit 11 and the built-in relay of the frequency converter. Reversing is permitted only when the reversing bit 15 in the control word and the digital input 19 are set to high.
For safety reasons, the frequency converter stops the motor if the POWERLINK cable is broken, the master has a system failure, or the PLC is in stop mode.
Illustration 8.1 Application Example
44 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
Application Examples Operating Instructions
Program the frequency converter as shown in Table 8.2.
Parameter Setting
Parameter 4-10 Motor Speed Direction [2] Both directions Parameter 5-10 Terminal 18 Digital Input [0] No operation Parameter 5-11 Terminal 19 Digital Input [10] Reversing Parameter 5-40 Function Relay [36/37] Control word bit 11/12 Parameter 8-03 Control Word Timeout Time 1 s Parameter 8-04 Control Word Timeout Function [2] Stop Parameter 8-10 Control Word Prole [0] FC Prole Parameter 8-50 Coasting Select [1] Bus Parameter 8-51 Quick Stop Select [1] Bus Parameter 8-52 DC Brake Select [1] Bus Parameter 8-53 Start Select [1] Bus Parameter 8-54 Reversing Select [2] Logic AND Parameter 8-55 Set-up Select [1] Bus Parameter 8-56 Preset Reference Select [1] Bus
Table 8.2 Programming of Frequency Converter
8 8
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 45
Application Examples
MCA 123 POWERLINK
8.2 Example: Simple Control Word, Reference, Status Word and Main Actual Value
This example shows how the control word telegram relates to the controller and the frequency converter, using FC Control
Prole.
The control word telegram is sent from the PLC to the frequency converter. Standard Telegram 1 is used in the example to demonstrate the full range of modules. All the values shown are arbitrary, and are provided for demonstration purposes only.
PQW:
Bit no.:
0 4 7 C 2 0 0 0
0 1 2 3
CTW MRV PCD PCD
04 7C 20 00
256 258
CTW MRV
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 0 0 0 0 1 0 0 0 1 1 1 1 1 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0
PCD
260 262
Table 8.3 Standard Telegram 1 Example
Table 8.3 indicates the bits contained within the control word, and how they are presented as process data in Standard Telegram 1 for this example.
Table 8.4 indicates which bit functions, and which corresponding bit values are active for this example.
88
Function active
Bit Bit value=0 Bit value=1 Bit value
00 Reference value External selection lsb 0 01 Reference value External selection msb 0 02 DC brake Ramp 1 03 Coasting Enable 1 04 Quick stop Ramp 1 05 Freeze output Ramp enable 1 06 Ramp stop Start 1 07 No function Reset 0 08 No function Jog 0 09 Ramp 1 Ramp 2 0 10 Data not valid Valid 1 11 No function Relay 01 active 0 12 No function Relay 02 active 0 13 Parameter set-up Selection lsb 0 14 Parameter set-up Selection msb 0 15 No function Reversing 0
C
7
4
0
Function inactive
Table 8.4 Bit Functions
46 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
Application Examples Operating Instructions
8 8
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 47
MCA123 POWERLINK
SW. ver. TM. ver.
S/E LED
L/C LED P1
L/C LED P2
Port 1 Port 2
Option A 130B1489
MAC 00-1B-08-00-00-00
Address
8 7 6 5 4 3 2 1
ON OFF
130BD146.11
1
2
3 4 5
6
A
B
A
B
Troubleshooting MCA 123 POWERLINK
9 Troubleshooting
9.1 LED Status
Illustration 9.1 LED Status
Illustration 9.7 S/E LED Status - Single Green Flash
Illustration 9.8 S/E LED Status - Red (B)/Green (A) Flash
Illustration 9.9 S/E LED Status - Double Green Flash
Item # Description
Illustration 9.10 S/E LED Status - Tripple Green Flash
1 POWERLINK port 1 2 POWERLINK port 2 3 Status/error 4 Link/collision port 1
99
5 Link/collision port 2
Illustration 9.11 S/E LED Status - Yellow Flash
6 Node ID dip switches
Table 9.1 Legend to Illustration 9.1
LED ash
Powerlink option state Description
pattern
Illustration 9.2 S/E LED Status - Power OFF or State
Power OFF or init State
Flickering Green
NMT_GS, NMT_GS_INITIALISATION NMT_CS_NOT_ACTIVE,
No power supplied to drive or Initialising
Basic Ethernet mode POWERLINK
interface is in basic Ethernet mode
Illustration 9.3 S/E LED Status - Green (A)/Red (B) Flash
Solid green POWERLINK
interface is on operational state
Illustration 9.4 S/E LED Status - Flickering Green
Blinking greed Single green
ash
NMT_CS_Stopped PLC has stopped
the Network
NMT_CS_PRE_OPERATIONAL_1 POWERLINK
interface is in Pre­operation mode state 1
Illustration 9.5 S/E LED Status - Solid Green
Red/green
ash
Double green ash
NMT_CS_PRE_OPERATIONAL_1 Communication to
PLC lost
NMT_CS_PRE_OPERATIONAL_2 POWERLINK
interface is in Pre­operation mode state 2
Illustration 9.6 S/E LED Status - Blinking Red
Tripple green ash
NMT_CS_READY_TO_OPERATE POWERLINK
interface is
48 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
A
B
A
B
Troubleshooting Operating Instructions
LED ash
pattern
Yellow ash Wink command Node Identication
Table 9.2 S/E LED Pattern
Illustration 9.12 L/C LED Status - Power OFF or No Link
Illustration 9.13 L/C LED Status - Link
Illustration 9.14 L/C LED Status - Power-up Green (A)/Red (B)
Illustration 9.15 L/C LED Status - Collision Red (B)/Green (A)
Illustration 9.16 L/C LED Status - Yellow Flash
LED ash
pattern
Power OFF or no link
Link NMT_GS_INITIALISATION Only shown once at
Power up Various states Link established Collision Yellow ash Wink command Node Identication
Table 9.3 L/C LED Pattern
9.2
Communication Problems
Powerlink option state Description
activated from MCT10
Powerlink option state Description
NMT_GS, NMT_GS_INITIALISATION NMT_CS_NOT_ACTIVE
No power supplied to drive or Initialising
power up
activated from MCT 10 Set-up Software
9.2.1 No Communication with the Frequency Converter
If there is no communication with the frequency converter, proceed with the following checks:
Check 1: Is the cabling correct? Check that the cable is mounted correctly. Check if the corresponding L/C LED shows link activity.
Check 2: Does the hardware conguration match? Check that parameter 12-60 Node ID is congured to the same value in the PLC. For correct function, the Node ID must be set correctly. This parameter can also be set from the DIP switches. If the DIP switches are set, they have priority over the parameter.
Check 3: Is the correct XDD le installed? Download the correct XDD le from www.danfoss.com/BusinessAreas/DrivesSolutions/. Check that the process data matches the active prole in the drive.
Check 4: What is the value of parameter 12-69 Ethernet
PowerLink Status? Parameter 12-69 Ethernet PowerLink Status contains 32 bits,
which each is linked to internal information. The dierent bits give an overview over possible errors.
Bit
Description Value=[0] Value=[1] Comment
no.
0 Initialisation
State
1 Not Active
State
2 Basic
Ethernet State
3 Pre-
Operational 1 State
4 Pre-
Operational 2 State
5 Ready to
Operate State
6 Operational
State
7 Stopped
State
8 Reserved Value shall be
9 Reserved Value shall be
10 Reserved Value shall be
11 Reserved Value shall be
12 Reserved Value shall be
13 Reserved Value shall be
NMT_GS_INITIL
ASATION
NMT_CS_NOT_
ACTIVE
NMT_CS_BASIC
_ETHERNET
NMT_CS_PRE_
OPERATIONAL_ 1
NMT_CS_PRE_
OPERATIONAL_ 2
NMT_CS_OPER
ATIONAL
NMT_CS_STOP
PED
Value shall be
Mapped to Object 1F8Ch Mapped to Object 1F8Ch Mapped to Object 1F8Ch
Mapped to Object 1F8Ch
Mapped to Object 1F8Ch
Mapped to Object 1F8Ch Mapped to Object 1F8Ch
read as 0
read as 0
read as 0
read as 0
read as 0
read as 0
read as 0
9 9
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 49
Troubleshooting
Bit
Description Value=[0] Value=[1] Comment
no.
14 Reserved Value shall be
15 Reserved Value shall be
16 Reserved Value shall be
17 Reserved Value shall be
18 Reserved Value shall be
19 Reserved Value shall be
20 Physical link
on Port 1
21 Physical link
on Port 2
22 Reserved Value shall be
23 Reserved Value shall be
24 W34 source
No Op State
25 W34 source
99
Alarm
26 W34 source
IP Address
Conict
27 W34 source
Invalid Node ID
28 W34 source
Incorrect PDO mapping
29 Reserved Value shall be
30 Reserved Value shall be
31 Reserved Value shall be
Table 9.4 POWERLINK Bits
No link present on Port 1 No link present on Port 2
Mapped to
Mapped to
IP address
Value read
Set on
Link present on Port 1
Link present on Port 2
MCA 123 POWERLINK
read as 0
read as 0
read as 0
read as 0
read as 0
read as 0 Mapped to object 1030h subindex 7 Mapped to object 1030h subindex 7
read as 0
read as 0
object 178Ch
Alarm Word and Alarm Word 1
conict
detection in Basic Ethernet mode
from DIP switch
incorrect Tx or Rx PDO mapping
read as 0
read as 0
read as 0
Check 1: Is the control word valid?
If bit 10=0 in the control word, the frequency converter does not accept the control word.
Check 2: Is the relationship between bits in the control word and the terminal I/Os correct?
Check the logical relationship in the frequency converter. Dene the desired logical relationship in
parameter 8-50 Coasting Select to parameter 8-56 Preset Reference Select according to the following range of
options. Select the FC control mode, digital input and/or serial communication, using parameter 8-50 Coasting Select to parameter 8-56 Preset Reference Select.
If parameter 8-01 Control Site is set to digital only, the frequency converter does not react on commands sent via the control word.
Table 9.5 to Table 9.12 show a coast command's eect upon the frequency converter for the full range of parameter 8-50 Coasting Select settings.
The
eect of control mode upon the function of
parameter 8-50 Coasting Select, parameter 8-51 Quick Stop Select, and parameter 8-52 DC Brake Select is as follows:
If [0] Digital input is selected, the terminals control the coast and DC brake functions.
NOTICE
Coasting, quick stop, and DC brake functions are active for logic 0.
Terminal Bits 02/03/04 Function
0 0 Coast/DC brake/Q-Stop 0 1 Coast/DC brake/Q-Stop 1 0 No Coast/DC brake/Q-Stop 1 1 No Coast/DC brake/Q-Stop
Table 9.5 [0] Digital Input
If [1] Serial communication is selected, commands are activated only when given via serial communication.
Terminal Bits 02/03/04 Function
0 0 Coast/DC brake/Q-Stop 0 1 No Coast/DC brake/Q-Stop 1 0 Coast/DC brake/Q-Stop 1 1 No Coast/DC brake/Q-Stop
Table 9.6 [1] Serial Communication
If [2] Logic AND is selected, both signals must be activated to perform the function.
If the master is in stop mode, Warning 34 appears. Check that the master is in run mode. If the frequency converter is not in operational state, Warning 34 will appear (60 s after power up or immediately if the frequency converter has been in operational state).
50 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
Troubleshooting Operating Instructions
Terminal Bits 02/03/04 Function
0 0 Coast/DC brake/Q-Stop 0 1 No Coast/DC brake/Q-Stop 1 0 No Coast/DC brake/Q-Stop 1 1 No Coast/DC brake/Q-Stop
Table 9.7 [2] Logic AND
If [3] Logic OR is selected, activation of one signal activates the function.
Terminal Bits 02/03/04 Function
0 0 Coast/DC brake/Q-Stop 0 1 Coast/DC brake/Q-Stop 1 0 Coast/DC brake/Q-Stop 1 1 No Coast/DC brake/Q-Stop
Table 9.8 [3] Logic OR
The eect of control mode upon the function of
parameter 8-53 Start Select and parameter 8-54 Reversing Select:
If [0] Digital input is selected, the terminals control the start and reversing functions
Terminal Bits 06/15 Function
0 0 Stop/Counterclockwise 0 1 Stop/Counterclockwise 1 0 Start/Clockwise 1 1 Start/Clockwise
Table 9.9 [0] Digital input
If [1] Serial communication is selected, commands are activated only when given via serial communication.
Terminal Bits 02/03/04 Function
0 0 Stop/Counterclockwise 0 1 Start/Clockwise 1 0 Stop/Counterclockwise 1 1 Start/Clockwise
Table 9.10 [1] Serial Communication
[3] Logic OR is selected, activation of one signal activates
If the function.
Terminal Bits 02/03/04 Function
0 0 Stop/Counterclockwise 0 1 Start/Clockwise 1 0 Start/Clockwise 1 1 Start/Clockwise
Table 9.12 [3] Logic OR
The eect of control mode upon the function of
parameter 8-55 Set-up Select and parameter 8-56 Preset Reference Select:
If [0] Digital input is selected, the terminals control the set­up and preset reference functions.
Terminal Bits 00/01,
13/14
Msb Lsb Msb Lsb Preset ref. set-up number
0 0 0 0 1 0 0 0 1 1 0 0 1 0 1 0 0 1 1 1 0 1 0 0 2 0 1 0 1 2 0 1 1 0 2 0 1 1 1 2 1 0 0 0 3 1 0 0 1 3 1 0 1 0 3 1 0 1 1 3 1 1 0 0 4 1 1 0 1 4 1 1 1 0 4 1 1 1 1 4
Table 9.13 [0] Digital Input
Function
If [1] Serial communication is selected, commands are activated only when given via serial communication.
9 9
If [2] Logic AND is selected, both signals must be activated to perform the function.
Terminal Bits 02/03/04 Function
0 0 Stop/Counterclockwise 0 1 Stop/Counterclockwise 1 0 Stop/Counterclockwise 1 1 Start/Clockwise
Table 9.11 [2] Logic AND
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 51
Troubleshooting
MCA 123 POWERLINK
Terminal Bits 00/01,
13/14
Msb Lsb Msb Lsb Preset ref. set-up number
0 0 0 0 1 0 0 0 1 2 0 0 1 0 3 0 0 1 1 4 0 1 0 0 1 0 1 0 1 2 0 1 1 0 3 0 1 1 1 4 1 0 0 0 1 1 0 0 1 2 1 0 1 0 3 1 0 1 1 4 1 1 0 0 1 1 1 0 1 2 1 1 1 0 3 1 1 1 1 4
Table 9.14 [1] Serial Communication
Function
Terminal Bits 00/01,
13/14
Msb Lsb Msb Lsb Preset ref. set-up number
0 0 0 0 1 0 0 0 1 2 0 0 1 0 3 0 0 1 1 4 0 1 0 0 2 0 1 0 1 2 0 1 1 0 4 0 1 1 1 4 1 0 0 0 3 1 0 0 1 4 1 0 1 0 3 1 0 1 1 4 1 1 0 0 4 1 1 0 1 4 1 1 1 0 4
Table 9.16 [3] Logic OR
Endless Power-down - Power-up Cycle
9.2.2
Function
If [2] Logic AND is selected, both signals must be activated to perform the function.
Check 1: Is the frequency converter set to Controlled Node = ON in the Automation Studio?
Terminal Bits 00/01,
99
Msb Lsb Msb Lsb Preset ref. set-up number
0 0 0 0 1 0 0 0 1 1 0 0 1 0 1 0 0 1 1 1 0 1 0 0 1 0 1 0 1 2 0 1 1 0 1 0 1 1 1 2 1 0 0 0 1 1 0 0 1 1 1 0 1 0 3 1 0 1 1 3 1 1 0 0 1 1 1 0 1 2 1 1 1 0 3 1 1 1 1 4
13/14
Function
The PLC can force the frequency converter into an endless power-down - power-up cycle. Set the value to OFF.
Is the XDD le correct? Check that the correct XDD le and rmware of the option are used. See chapter 4.1 Importing the XDD File for more information.
9.3
Warnings and Alarms
9.3.1 Alarm and Warning Words
Alarm word, Warning word, and POWERLINK Status word are shown in the display in Hex format. If there is more than one warning or alarm, a sum of all warnings or alarms is shown. Alarm word, warning word, and POWERLINK Status word can also be displayed using the serial bus in parameter 16-90 Alarm Word,
parameter 16-92 Warning Word, and parameter 12-69 Ethernet PowerLink Status.
Table 9.15 [2] Logic AND
If [3] Logic OR is selected, activation of 1 signal activates the function.
52 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
Troubleshooting Operating Instructions
Bit (Hex) Unit
diagnose bit
00000001 48 Brake check 28 00000002 49 Power card over
00000004 50 Earth fault 14 00000008 51 Control card over
00000010 52 Control word timeout 18 00000020 53 Over current 13 00000040 54 Torque limit 12 00000080 55 Motor thermistor over
00000100 40 Motor ETR over
00000200 41 Inverter overloaded 9 00000400 42 DC link under voltage 8 00000800 43 DC link over voltage 7 00001000 44 Short circuit 16 00002000 45 Inrush fault 33 00004000 46 Mains phase loss 4 00008000 47 AMA not OK 50 00010000 32 Live zero error 2 00020000 33 Internal fault 38 00040000 34 Brake overload 26 00080000 35 Motor phase U is missing 30 00100000 36 Motor phase V is missing 31 00200000 37 Motor phase W is missing 32 00400000 38 Fieldbus comm. fault 34 00800000 39 24 V supply fault 47 01000000 24 Mains failure 36 02000000 25 1.8 V supply fault 48 04000000 26 Brake resistor short circuit 25 08000000 27 Brake chopper fault 27 10000000 28 Option change 67 20000000 29 Drive initialisation 80 40000000 30 Safe stop 68 80000000 31 Mechanical brake low 63
Alarm word (parameter 16-90 Alarm Word)
temperature
temperature
temp.
temperature
Alarm no.
29
65
11
10
Bit (Hex) Unit
diagnose bit
00000001 112 Brake check 28 00000002 113 Power card over
00000004 114 Earth fault 14 00000008 115 Control card 65 00000010 116 Control word timeout 18 00000020 117 Over current 13 00000040 118 Torque limit 12 00000080 119 Motor thermistor over
00000100 104 Motor ETR over
00000200 105 Inverter overloaded 9 00000400 106 DC link under voltage 8 00000800 107 DC link over voltage 7 00001000 108 DC link voltage low 6 00002000 109 DC link voltage high 5 00004000 110 Mains phase loss 4 00008000 111 No motor 3 00010000 96 Live zero error 2 00020000 97 10 V low 1 00040000 98 Brake overload 26 00080000 99 Brake resistor short circuit 25 00100000 100 Brake chopper fault 27 00200000 101 Speed limit 49 00400000 102 Fieldbus comm. fault 34 00800000 103 24 V supply fault 47 01000000 88 Mains failure 36 02000000 89 Current limit 59 04000000 90 Low temperature 66 08000000 91 Voltage limit 64 10000000 92 Encoder loss 61 20000000 93 Output frequency limit 62 40000000 94 Unused ­80000000 95 Warning word 2 (ext. stat.
Warning word (parameter 16-92 Warning Word)
temperature
temp.
temperature
word)
Alarm no.
29
11
10
9 9
-
Table 9.17 Alarm Word Bits
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 53
Table 9.18 Warning Word Bits
Troubleshooting
Bit (Hex) Comm. option STW (parameter 16-84 Comm.
Option STW)
00000001 parameterization ok 00000002 conguration ok 00000004 clearmode active 00000008 baudrate search 00000010 waiting for parameterization 00000020 waiting for conguration 00000040 in data exchange 00000080 not used 00000100 not used 00000200 not used 00000400 not used 00000800 MCL2/1 connected 00001000 MCL2/2 connected 00002000 MCL2/3 connected 00004000 data transport active 00008000 not used
Table 9.19 Status Word Bits
MCA 123 POWERLINK
NOTICE
Parameter 16-84 Comm. Option STW is not part of
extended diagnosis.
There is a clear distinction between alarms and warnings.
99
An alarm make the frequency converter enter a fault condition. After the cause for the alarm has been cleared, the master will have to acknowledge the alarm message before the frequency converter can start operating again. A warning condition triggers a warning which disappears when condition returns to normal, without interfering with the process.
Warnings
A single bit within a warning word represents warnings within the frequency converter. Bit status [0] False means no warning, while bit status [1] True means warning. Any bit change in the warning word is notied by a change of bit 7 in the status word.
Alarms
Following an alarm message, the frequency converter enters fault condition. When the fault has been removed and the controller has acknowledged the alarm message by setting bit 7 in the control word, the frequency converter resumes operation. A single bit within an alarm word represents alarms within the frequency converter. Bit status [0] False means no fault, while bit status [1] True means fault.
54 Danfoss A/S © Rev. 2013-02-11 All rights reserved. MG92C202
Index Operating Instructions
Index
A
Abbreviations........................................................................................... 4
Alarm word............................................................................................. 52
Assumptions............................................................................................. 3
B
Background Knowledge....................................................................... 3
P
Parameter.................................................................................................. iv
Parameters.............................................................................................. 10
PDO Communication.......................................................................... 15
Process Control Data........................................................................... 15
Process control operation.................................................................. 16
Process Status Data.............................................................................. 15
Probus....................................................................................................... 3
C
Cabling..................................................................................................... 41
Conguration...................................................................... 4, 34, 36, 39
Control Prole........................................................................................ 17
D
DC Back-up................................................................................................ 3
DeviecNet.................................................................................................. 3
E
EMC Precautions...................................................................................... 8
EtherCAT..................................................................................................... 3
Ethernet........................................................................................ 8, 39, 40
H
Hardware.............................................................................................. iii, 3
I
I/O................................................................................................................. 4
Installation....................................................................................... iii, 3, 5
IP Settings................................................................................................ 10
IP21/Type 1................................................................................................ 3
R
Reference................................................................................................... 4
S
Safety.......................................................................................................... iii
T
Topology.................................................................................................... 7
V
VLT Parameters...................................................................................... 10
W
Warning word........................................................................................ 52
L
LED............................................................................................................... 4
LED Status............................................................................................... 48
Literature.................................................................................................... 3
N
Network............................................................................................. 3, 5, 8
No communication.............................................................................. 49
No response to control signals........................................................ 50
O
Overview.................................................................................................... 6
MG92C202 Danfoss A/S © Rev. 2013-02-11 All rights reserved. 55
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss A/S Ulsnaes 1 DK-6300 Graasten vlt-drives.danfoss.com
130R0387 MG92C202 Rev. 2013-02-11
*MG92C202*
Loading...