Danfoss MCA 117, FCD 300, FCM 300 Operating guide

Operating Guide
VLT® FCD 300 PROFIBUS Converter MCA 117 VLT® Decentral Drive FCD 300 and VLT® Decen­tral Drive FCM 300
ContentsOperating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117

Contents

1 Introduction 5
1.1 Purpose of this Operating Guide 5
1.2 Additional Resources 5
1.3 Document and Software Version 5
1.4 Product Overview 6
1.4.1 Intended Use 6
1.4.2 Hardware 6
1.4.3 Performance 7
2.1 Safety Symbols 8
2.2 Qualified Personnel 8
2.3 Safety Precautions 8
3.1 Introduction to Installation 11
3.2 Electrical Installation 11
3.2.1 Supply and Motor Terminals 11
3.2.2 Control Signal Connectors 13
3.2.3 EMC Precautions 16
4 Configuring the System 18
4.1 Preparing for Configuration 18
4.2 PROFIBUS Address Set via Hardware Switches 18
4.3 PROFIBUS Address Set via Parameter or SSA Command 20
4.4 Commissioning 20
4.5 LED Behavior 20
4.6 Factory Settings 22
5.1 FCD 300 Parameter Group 0 25
5.2 FCD 300 Parameter Group 1 31
5.3 FCD 300 Parameter Group 2 39
5.4 FCD 300 Parameter Group 3 48
5.5 FCD 300 Parameter Group 4 56
5.6 FCD 300 Parameter Group 5 65
5.7 FCD 300 Parameter Group 6 73
5.8 FCD 300 Parameter Group 8 78
5.9 FCD 300 Parameter Group 9 80
AQ289550754901en-000101 / | 3Danfoss A/S © 2019.11
ContentsOperating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
6 Troubleshooting 86
6.1 Troubleshooting Hints 86
7.1 Abbreviations 87
7.2 Conventions 87
AQ289550754901en-000101 /4 | Danfoss A/S © 2019.11
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117

Introduction

1 Introduction
1.1 Purpose of this Operating Guide
This operating guide provides information for the installation, commissioning, and parameter mapping of a VLT® FCD 300 PROFIBUS Converter MCA 117 when installed in a VLT® Decentral Drive FCD 302.
The operating guide is intended for use by qualified personnel. Users are assumed to be familiar with:
VLT® decentral drives.
PROFIBUS.
Read the instruction before installation and ensure that the instructions for safe installation are observed.
Essential information for quick installation and setup is found in:
1.4.1 Intended Use
1.4.2 Hardware
3.1 Introduction to Installation
3.2 Electrical Installation
Detailed information including the full range of setup options and diagnosis tools is found in:
5 Parameter Mapping Lists
VLT® is a registered trademark for Danfoss A/S.
1.2 Additional Resources
The following manuals may be helpful when installing the VLT® FCD 300 PROFIBUS Converter MCA 117:
VLT® Decentral Drive FCD 302 Operating Guide.
VLT® Decentral Drive FCD 302 Design Guide.
VLT® AutomationDrive FC 301/FC 302 Programming Guide.
More manuals are available at www.danfoss.com.
1.3 Document and Software Version
This manual is regularly reviewed and updated. All suggestions for improvement are welcome.
The original language of this manual is English.
NOTICE
The converter is based on the latest firmware release of the VLT® Decentral Drive FCD300 and VLT® Decentral Drive FCM300. The firmware versions are listed in table 1. If the FCD/FCM drive that has to be replaced has a older version (lower number) the converter works, but may not convert parameters correctly.
Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890| 5
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
Table 1: Document, Firmware, and Software Versions
Edition Remarks Drive firmware version PROFIBUS firmware version
AQ2895507549010101 First release VLT® Decentral Drive FCD 302, version 7.67 or higher FCD300 Converter, version 2.0x
VLT® Decentral Drive FCD 300, version 1.6x PROFIBUS, version 3.x/4.x
VLT® Decentral Drive FCM 300, version 3.2x PROFIBUS, version 2.x/4.x
Introduction
1.4 Product Overview
1.4.1 Intended Use
This manual relates to the VLT® FCD 300 PROFIBUS Converter MCA 117.
The VLT® FCD 300 PROFIBUS Converter MCA 117 is intended for replacing a VLT® Decentral Drive FCD 300 or a VLT® Decentral Drive FCM 300 with a VLT® Decentral Drive FCD 302 in a PROFIBUS network.
With this PROFIBUS converter option, the FCD 302 reacts as an FCD 300 or an FCM 300 on the PROFIBUS network. Changes to PLC programming or configuration are normally not necessary.
The FCD 302 identifies itself either as an FCD 300 or an FCM 300 on the PROFIBUS network. A write command to, for example, ramp-up time in FCD 300 is automatically linked to the corresponding ramp-up time parameter in the VLT® Decentral Drive FCD 302.
NOTICE
Some parameters in the FCD 300 and FCM 300 are not supported in the FCD 302, and some parameters cannot be accessed via the VLT® FCD 300 PROFIBUS Converter MCA 117. Refer to 5 Parameter Mapping Lists for more information. If a write request is attempted to a parameter selection which is not supported, the drive discards the value and issues a positive reply. Only parameters and functions described in this manual are supported.
NOTICE
The replacement drive must match the power size or be bigger than the replaced FCD 300 or FCM 300. Make sure that the brake chopper matches the new drive. Make sure that the new drive meets the local regulations concerning the Machinery Directive, pre-fuses, and other appropriate regulations.
NOTICE
Observe local rules and regulations when replacing a drive in an existing installation.
1.4.2 Hardware
The VLT® FCD 300 PROFIBUS Converter MCA 117 supports VLT® Decentral Drive FCD 302 only.
There is no support for PROFIBUS FMS networks.
6 | Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
Introduction
1.4.3 Performance
The VLT® Decentral Drive FCD 302 reacts faster on most commands as the VLT® Decentral Drive FCD 300/FCM 300, which can influence the applications. When replacing a VLT® Decentral Drive FCD 300/FCM 300 with the VLT® FCD 300 PROFIBUS Converter MCA 117, the installer must ensure that the functionality is maintained. Due to the different timing, it may be necessary to reprogram the controller, where signals from the drives react faster.
The motor control algorithm of the VLT® Decentral Drive FCD 302 results in a better motor performance compared to FCD 300/FCM
300.
NOTICE
FACTORY SETTING OF PARAMETERS
After initialization of the FCD 302, most parameters are set to match the factory settings of the FCD 300/FCM 300 parameters.
NOTICE
LINKED SETUPS
To synchronize changes made with a running motor, ensure that setups are linked. Link the setups in parameter 0-12 This Setup Linked to.
Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890| 7
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
2 Safety
2.1 Safety Symbols
The following symbols are used in this manual:
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

Safety

NOTICE
Indicates information considered important, but not hazard-related (for example, messages relating to property damage).
2.2 Qualified Personnel
Correct and reliable transport, storage, installation, operation, and maintenance are required for the trouble-free and safe operation of the drive. Only qualified personnel are allowed to install and operate this equipment.
Qualified personnel are defined as trained staff, who are authorized to install, commission, and maintain equipment, systems, and circuits in accordance with pertinent laws and regulations. Also, the qualified personnel must be familiar with the instructions and safety measures described in this manual.
2.3 Safety Precautions
WARNING
HIGH VOLTAGE
AC drives contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation, start-up, and maintenance by qualified personnel can result in death or serious injury.
Only qualified personnel must perform installation, start-up, and maintenance.
-
8 | Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
WARNING
UNINTENDED START
When the drive is connected to the AC mains, the motor may start at any time, causing risk of death, serious injury, and equipment or property damage. The motor may start by activation of an external switch, a fieldbus command, an input reference signal from the LCP or LOP, via remote operation using MCT 10 Set-up software, or after a cleared fault condition.
Press [Off] on the LCP before programming parameters.
-
Disconnect the drive from the mains whenever personal safety considerations make it necessary to avoid unintended
-
motor start. Check that the drive, motor, and any driven equipment are in operational readiness.
-
WARNING
DISCHARGE TIME
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be present even when the warning indicator lights are off.
Failure to wait the specified time after power has been removed before performing service or repair work could result in death or serious injury.
Stop the motor.
-
Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and
-
DC-link connections to other drives. Wait for the capacitors to discharge fully. The time for full discharge of the capacitors is minimum 4 minutes for VLT®
-
Decentral Drive FCD 302, 400 V AC, 0.37–3.0 kW (0.5–4.0 hp). Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors
-
are fully discharged.
Safety
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the drive properly can result in death or serious injury.
Ensure the correct grounding of the equipment by a certified electrical installer.
-
WARNING
ROTATING SHAFTS
Contact with rotating shafts and electrical equipment can result in death or serious injury.
Ensure that only trained and qualified personnel perform installation, start-up, and maintenance.
-
Ensure that electrical work conforms to national and local electrical codes.
-
Follow the procedures in this guide.
-
Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890| 9
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
WARNING
UNINTENDED MOTOR ROTATION WINDMILLING
Unintended rotation of permanent magnet motors creates voltage and can charge the unit, resulting in death, serious injury, or equipment damage.
Ensure that permanent magnet motors are blocked to prevent unintended rotation.
-
CAUTION
INTERNAL FAILURE HAZARD
An internal failure in the drive can result in serious injury when the drive is not properly closed.
Ensure that all safety covers are in place and securely fastened before applying power.
-
Safety
10 | Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117

Installation

3 Installation
3.1 Introduction to Installation
The VLT® FCD 300 PROFIBUS Converter MCA 117 changes the functionality of a VLT® Decentral Drive FCD 302 so that it can be used as a spare part for a VLT® Decentral Drive FCD 300 or a VLT® DriveMotor FCM 300.
A VLT® Decentral Drive FCD 302 (0.37–2.2 kW (0.5–3.0 hp)) with flat bracket and adapter brackets (order number 134B6775) can be mounted using the same drilling holes as for the FCD 300.
For a 3.0 kW (4.0 hp) FCD 302, mounting with adapter brackets is not possible. Thus, new holes must be drilled to mount the drive.
The FCD 302 cannot be used as a direct replacement of the VLT® Decentral Drive FCM 300 electronic part. For reuse of the existing electric motor, a terminal box has to be fitted to the motor, and a motor cable has to be used as connection between the motor and the FCD 302. Observe local regulations when changing the installation.
Initial power-up
The VLT® FCD 300 PROFIBUS Converter MCA 117sets the parameters of the VLT® Decentral Drive FCD 302 to FCD 300 defaults in 3 cases:
At first time power up.
When the drive has been set to initialize via parameter 14-22 Operation Mode.
When a 3-finger reset is performed from the LCP at power-up.
This gives a short commissioning time and improves the backwards compatibility.
The MCA 117 also changes the default settings of the I/Os of the FCD 302 to match those of the FCD 300.
3.2 Electrical Installation
For electrical installation, local regulations might require further updates. This could be the case where the installation must be updated to fulfill newer standards when machines are updated, or if local regulations have changed since the original decentral drives were installed.
The following sections contain illustrations showing the old terminal number and their equivalents in the new drive. If a box in a drawing is empty, there is no equivalent in the VLT® Decentral Drive FCD 302. In most cases, it is possible to program the FCD 302 to deliver the same function on 1 of the terminals. If there are no boxes at all in an illustration, the drive has no terminal. For example, the VLT® DriveMotor FCM 300 has a limited number of I/Os compared to the FCD 300.
3.2.1 Supply and Motor Terminals
Power cable terminals are 1:1 compatible between VLT® Decentral Drive FCD 300/VLT® DriveMotor FCM 300 and the VLT® Decentral Drive FCD 302. If shielded cables are used, ensure that the shield is mounted as stated in the VLT® Decentral Drive FCD 302 Operating Guide.
Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890| 11
FCD 300
FCD 302
PE
L1
(91)
L2
(92)
L3
(93)
PE
(95)
L1
(91)
L2
(92)
L3
(93)
POWER
input
FCM 300
PE
L1
L2
L3
e30bh597.10
PE
PE
(99)
U
(96)
V
(97)
W
(98)
U
(96)
V
(97)
W
(98)
Motor
connector
FCD 300
FCD 302
FCM 300
e30bh604.10
122
123
122
123
Mechanical brake
FCD 300
FCD 302
FCM 300
e30bh603.10
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
Installation
Illustration 1: Power Cable Connections
Motor terminals are 1:1 compatible between FCD 300 and FCD 302. If shielded cables are used, ensure that the shield is mounted as stated in the VLT® Decentral Drive FCD 302 Operating Guide.
Illustration 2: Motor Cable Connections
Mechanical brake cable terminals are 1:1 compatible between the FCD 300 EB versions and the FCD 302 with brake chopper and mechanical brake supply. If shielded cables are used, ensure that the shield is mounted as stated in the VLT® Decentral Drive FCD 302 Operating Guide. To enable this functionality, the VLT® FCD 300 PROFIBUS Converter MCA 117 sets parameter 5-40 [1] Function Relay to [32] Mech Brake Ctrl. In the FCD 302, it is not possible to enable mechanical brake control and use relay 2 for another purpose.
Illustration 3: Mechanical Brake Connection
12 | Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890
81 -
82 +
81 -
82 +
Brake
Resistor
FCD 300
FCD 302
FCM 300
e30bh599.10
e30bh605.10
31A
31B
50
54
FCD300
FCD302FCM300
1 2
ON
S202
A54 OFF
36
(+)
36 (+)
35
(-)
35 (-)
36 (+)
36 (+)
35 (-)
35 (-)
External 24 V DC back-up
FCD 300
FCD 302FCM 300
e30bh602.10
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
Installation
Brake resistor cable terminals are 1:1 compatible between the FCD 300 EB versions and the FCD 302. If shielded cables are used, ensure that the shield is mounted as stated in the VLT® Decentral Drive FCD 302 Operating Guide.
Illustration 4: Brake Resistor Cable Connections
The FCD 300 has dedicated connectors 31A and 31B for connection of the motor thermistors. The FCD 302 with MCA 117 installed uses AI54 as motor thermistor connector. The FCD 302 can also use 1 of the digital inputs as thermistor source, but if multiple sensors are connected in series, it might cause false alarms/warnings. The motor thermistor configuration is done via parameter 1-90 Motor Thermal Protection and parameter 1-93 Thermistor Resource.
Illustration 5: Motor Thermistor Cable Connection
The 24 V external supply cable terminals are 1:1 compatible between FCD 300 EB versions and the FCD 302. The FCD 302 may draw a higher current from the 24 V supply. The FCD 300 has a power consumption of 12 W, where the FCD 302 consumes up to 50 W. The consumption depends on the configuration of the I/O modules and the sensors connected to the drive.
Illustration 6: External 24 V Cable Connection
3.2.2 Control Signal Connectors
Digital input cable connection
Digital input terminals are 1:1 compatible between the VLT® Decentral Drive FCD 300 and the VLT® Decentral Drive FCD 302. If shielded cable is used, ensure that the shield is mounted as stated in the VLT® Decentral Drive FCD 302 Operating Guide.
The FCD 300 reads the digital inputs every 12 ms whereas the FCD 302 reads the digital inputs every 1 ms.
Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890| 13
20
27
12
18
19
29
33
20
27
12-
13
18
19
29
33
FCD 300
FCD 302
Digital in
FCM 300
6
4
5
8
3
e30bh600.11
46
Digital out
FCD 300
FCD 302
FCM 300
9
e30bh601.10
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
Installation
The digital inputs of the FCD 300 are converted fully to the I/Os of the FCD 302. Terminal 3 of the VLT® DriveMotor FCM 300 is not converted to a corresponding terminal in FCD 302. To support terminal 3 in FCM 300, configure the FCD 302 manually.
Illustration 7: Digital Input Cable Connections
Digital output cable connections
The FCD 300 has 1 dedicated digital output, which is terminal 46. This terminal is not converted to an existing FCD 302 output.
In FCM 300, terminal 9 could be used as either analog or digital output. To obtain the same functionality in FCD 302, configure an analog or digital output manually.
Illustration 8: Digital Output Cable Connections
Analog I/O cable connections
The analog I/Os of the FCD 302 can be configured to cover most use cases. The default conversion from FCD 300 has a limitation as there is no input 60 in the FCD 302. If analog input 54 in the FCD 302 is not used for motor thermistor, this input can be configured to provide the functionality of output 60 in the FCD 300.
14 | Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890
e30bh598.10
53
50
10 V
42
42
53
60
50
10 V
55
Gnd
55
Gnd
FCD300
FCD302
Analog
I/O
2
9
7
8
1
FCM300
1 2
ON
S202
A53 switch OFF = 0‐10V
01
C
02
NO
03
NC
01
C
02
NO
03
NC
FCD 300
FCD 302
Relay
1
x102
2
x102
3
x102
FCM 300
e30bh607.10
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
Installation
Illustration 9: Analog I/O Cable Connections
The 0–10 V analog input 53 of the FCD 300 is converted into the FCD 302 analog input 53. The analog input 53 of the FCD 302 can be set to 0–10 V or 0–20 mA via switch S201. From factory, the switch is set in OFF position, which sets the analog input to 0–10 V.
Relay cable connections
The relays of the FCD 302 are compatible to the relays in FCD 300.
NOTICE
The relay in FCM 300 is rated to a resistive load of 5 A, 250 V AC, whereas the relay in FCD 302 is rated to a load of 2 A, 240 V AC.
Illustration 10: Relay Cable Connections
PROFIBUS cable connections
The PROFIBUS terminals of the FCD 300/FCM 300 are all converted to the PROFIBUS terminals of the FCD 302. The compensation coils activated by the switches S101 to S104 of the FCD 300 are not needed in the FCD 302 PROFIBUS interface. The Termination of the PROFIBUS line is done via the PROFIBUS termination switch.
Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890| 15
e30bh606.10
67
68
68
69 69
70
67
68
68
69 69
66
FCD300
FCD302
PROFIBUS
3
x100
1
x100
2
x100
4
x100
FCM300
1 2 3
ON
PROFIBUS
TERM.
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
Installation
Illustration 11: PROFIBUS Cable Connections
3.2.3 EMC Precautions
To achieve interference-free operation of the PROFIBUS, install the VLT® Decentral Drive FCD 302 and the cables as described in the VLT® Decentral Drive FCD 302 Design Guide: When routing the PROFIBUS cable:
maintain high distance (minimum 200 mm (8 in)) between the PROFIBUS communication cable and the motor and brake resistor cables to avoid coupling of high-frequency noise from one cable to another.
ensure that, when crossing is unavoidable, the PROFIBUS cable crosses the motor and brake resistor cables at an angle of 90° .
For installation on machines where the FCD 302 has poor electrical contact to the machine due to paint or high ohmic surface, a special stainless steel plug and bracket exist. The order number is 175N2598.
This plug can be mounted in 1 of the unused cable entry holes and the supplied bracket has to be mounted to the plug and to the metal construction of the machine. This ensures a low ohmic path for high-frequency noise that otherwise would have been added to the shield of the PROFIBUS cable, causing disturbance of the communication.
NOTICE
Observe relevant national and local regulations, for example, regarding protective-earth connection.
16 | Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890
2
1
3
90°
e30bh659.10
1
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
Installation
1 PROFIBUS cable
3 ≥200 mm (≥7.9 in)
Illustration 12: EMC-correct Installation
2 90° intersection
Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890| 17
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117

Configuring the System

4 Configuring the System
4.1 Preparing for Configuration
Context:
All PROFIBUS stations connected to the same bus network must have a unique station address.
Prerequisites:
Before replacing an FCD 300 or FCM 300 by a VLT® Decentral Drive FCD 302 with VLT® FCD 300 PROFIBUS Converter MCA 117, configure the station address in the FCD 302. Also, check that the FCD 302 detects which type of drive it has to replace.
Procedure
1. Set the PROFIBUS address of the VLT® Decentral Drive FCD 302 to the same address as the drive that has to be replaced.
2. Set parameter 8-02 Control Word Source to [3] Option A.
3. Cycle power (400 V AC and 24 V DC back-up if applied) to the FCD 302.
The MCA 117 probes for the different FCD300/FCM300 Ident numbers. While probing, the drive flashes the ST/MS LED (see
4.5 LED Behavior). When the matching Ident number used by the master is detected, the VLT® Decentral Drive FCD 302
locks the ident number to the option, and sets the parameters of the FCD 302 to match the functionality of the old drive.
The master/PLC now recognizes the FCD 302 as an FCD 300 or FCM 300.
4.2 PROFIBUS Address Set via Hardware Switches
WARNING
SHOCK HAZARD
Working with the hardware switches while the power supply is still on may cause personal injuries.
Switch off the power supply before changing the hardware switches.
-
NOTICE
The address change comes into effect at the next power-up and can be read in parameter 9-18 Node Address.
18 | Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890
e30bh608.10
1
2 3 4 5 6 7 8
8 7 6 5 4 3 2 1
ON
OFF
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
Configuring the System
Illustration 13: Setting the PROFIBUS Address via Hardware Switches
Table 2: Hardware Switch Settings
VLT® Decentral Drive FCD 300 VLT® Decentral Drive FCD 302
Switch 1 2 3 4 5 6 7 8 8 7 6 5 4 3 2 1
Address +1 +2 +4 +8 +16 +32 +64 +64 +32 +16 +8 +4 +2 +1
Example:
1 1 0 0 0 0 0 0 0 0 0 0 0 0 1
35 1 1 0 0 0 1 0 0 1 0 0 0 1 1
82 0 1 0 0 1 0 1 1 0 1 0 0 1 0
Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890| 19
BUS
ON
ALARM
ST/MS LA2/NS2
WARNING
LA1/NS1
e30bh741.10
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
Configuring the System
4.3 PROFIBUS Address Set via Parameter or SSA Command
If all hardware switches are set to ON or OFF (factory switch setting), the PROFIBUS address can be set via parameter 9-18 Node Address or the PROFIBUS SSA command. The address becomes valid after the next power cycle.
4.4 Commissioning
Prerequisites:
The station address of the VLT® Decentral Drive FCD 302 must be the same as for VLT® Decentral Drive FCD 300.
Procedure
1. Cycle power to the FCD 302.
The master/PLC now recognizes FCD 302 as an FCD 300.
Example:
A solid green NS LED on the VLT® FCD 300 PROFIBUS Converter MCA 117 indicates that communication between master and slave is established.
If the NS LED flashes, the master/PLC has not recognized the FCD 302.
For more information, refer to 6.1 Troubleshooting Hints.
4.5 LED Behavior
Illustration 14: Overview of LEDs
Table 3: Bicolored LEDs
LED label Description
LA1/NS1 Network status
20 | Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
Configuring the System
LED label Description
ST/MS Module status (DP-V1 communication and Ident number detection)
LA2/NS2 Not used
Table 4: Net Status, ST/MS
State LED Description
Power on Red: Solid red The option is defect. Contact Danfoss.
Green: Flashing
The option is OK.
green
Baud rate search Green: Flashing
green
Wait parameterizing Green: Long green
flash
Searching for the baud rate. Check the connection to the master if the option stays in this state.
Baud rate found - waiting for parameters from the master.
Red: Long red flash Wrong parameters from the master.
Wait configuration Green: Short green
flash
Parameters from master OK - waiting for configura­tion data.
Red: Short red flash Wrong configuration data from the master.
Data exchange Green: Solid green Data exchange between the master and the FCD 302
is active.
Red: Flashing red Clear state. Warning 34, Fieldbus Fault is active and a
bus reaction in parameter 8-04 Control Word Timeout Function is executed.
Table 5: Module Status (ST/MS LED while Detecting Ident Number)
LED description Description
Green One short flash Testing for FCD 300, 12 MB version
Green Two short flashes Testing for FCD 300, 3 MB version
Green Three short flashes Testing for FCD 302
Green One long, one short flash Testing for FCM 300, 3 MB version
Green One long, 2 short flashes Testing for FCM 300, 12 MB version
Table 6: Module Status (DP-V1 Communication)
Description
No light Off No PROFIBUS DP-V1 communication is active.
Green: Short green flash DP-V1 communication from a Master Class 1 (PLC) is active.
Green: Long green flash DP-V1 communication from a Master Class 2 (MCT 10, FDT) is active.
Green: Solid green DP-V1 communication from a Master Class 1 and 2 is active.
Red: Flashing red Internal error.
Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890| 21
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
Configuring the System
NOTICE
The LED flash patterns of the VLT® FCD 300 PROFIBUS Converter MCA 117 are not compatible with the patterns of the FCD 300/FCM 300 PROFIBUS LEDs.
4.6 Factory Settings
The VLT® FCD 300 PROFIBUS Converter MCA 117 is delivered from factory with the optimal settings to replace a VLT® Decentral Drive FCD 300. If the VLT® FCD 300 PROFIBUS Converter MCA 117 is moved from one application to another, it is recommend to initialize the drive. This initialization activates the factory settings and re-invoke of the Ident number detection. If the drive has been delivered from factory with the option installed, initialization can be skipped.
Do the initialization via:
Parameter 14-22 Operation Mode, or
Three-finger reset by removing power to the drive, pressing [Status], [Main Menu], and [OK], and applying 400 V AC or 24 V DC back-up power to the drive.
The MCA 117 sets the parameters of the FCD 302 so that the FCD 302/MCA 117 emulate the FCD 300 in the best way.
The parameters of the VLT® Decentral Drive FCD 302 are set to factory values and some FCD 302 parameters are set to values that match the initial values of VLT® Decentral Drive FCD 300.
Factory copy via the FCD 300 parameter 006 Setup Copy is supported and initializes the FCD 302 and sets it to the FCD 300 default settings.
Table 7: Parameters Set During Initialization
Parameter Initialization setting
Parameter 0-02 Motor Speed Unit [Hz]
Parameter 1-51 Min Speed Normal Magnetizing [RPM] 30 RPM
Parameter 1-52 Min Speed Normal magnetising [Hz] 1.0 Hz
Parameter 1-64 Resonance Damping 0
Paramter 1-81 Min Speed for Function at Stop [RPM] 3 RPM
Parameter 1-82 Min Speed for Function at Stop [Hz] 0.1 Hz
Parameter 1-93 Thermistor Resource Analog input 54
Parameter 2-10 Brake Function [0] Off
Parameter 2-17 Overvoltage Control [0] Off
Parameter 3-00 Reference Range min – max
Parameter 3-01 Reference/Feedback Unit [1]%
Parameter 3-03 Maximum Reference 50.000
Parameter 3-11 Jog Speed [Hz] 10.0 Hz
Parameter 3-16 Reference Resource 2 [0] No function
Parameter 3-19 Jog Speed [RPM] 300 RPM
Parameter 4-13 Motor Speed High Limit [RPM] 3960 RPM
22 | Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
Parameter Initialization setting
Parameter 4-14 Motor Speed Low Limit [Hz] 132.0 Hz
Parameter 4-16 Torque Limit Motor Mode 355.6
Parameter 4-17 Torque Limit Generator Mode 355.6
Parameter 4-30 Motor Feedback Loss Function [0] Disabled
Parameter 4-32 Motor Feedback Loss Timeout 1.00 s
Parameter 4-53 Warning Speed High 3960
Parameter 4-56 Warning Feedback Low -4000000
Parameter 4-57 Warning Feedback High 4000000
Parameter 5-02 Terminal 29 Mode [1] Output
Parameter 5-10 Terminal 18 Digital Input [8] Start
Parameter 5-11 Terminal 19 Digital Input [10] Reversing
Parameter 5-12 Terminal 27 Digital Input [3] Coast and reset inv
Parameter 5-14 Terminal 32 Digital Input [14] Jog
Configuring the System
Parameter 5-40.0 Function Relay [22] Ready, No Thermal Warning
Parameter 5-40.1 Function Relay [32] Mech Brake Ctrl
Parameter 5-41 On Delay, Relay [23] Remote, Ready, No TW
Parameter 5-51 Term. 29 High Frequency 5000 Hz
Parameter 5-53 Term. 29 High Ref./Feedb. Value 50.000
Parameter 5-56 Term. 33 High Frequency 25000 Hz
Parameter 5-58 Term. 33 High Ref./Feedb. Value 50.000
Parameter 6-10 Terminal 53 Low Voltage 0.00 V
Parameter 6-15 Term. 53 High Ref./Feedb. Value 50.000
Parameter 6-20 Terminal 54 Low Voltage 0.00 V
Parameter 6-22 Terminal 54 Low Current 0.00 V
Parameter 6-25 Terminal 54 High Ref./Feedb. Value 50.000
Parameter 6-50 Terminal 42 Output [103] Motor current
Parameter 7-04 Speed PID Differention Time 0.0
Parameter 7-08 Speed PID Feed Forward Factor 100
Parameter 7-09 Speed PID Error Correction w/Ramp 100000 (max)
Parameter 7-33 Process PID Proportional Gain 0.01
Parameter 8-54 Reversing Select [0] Digital input
Parameter 8-90 Bus Jog 1 Speed 300 RPM
Parameter 8-91 Bus Jog 2 Speed 300 RPM
Parameter 14-03 Overmodulation [0] Off
Parameter 14-11 Mains Voltage at Mains Fault 327
Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890| 23
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
Parameter Initialization setting
Parameter 14-15 Kin. Back-up Trip Recovery Level 1,000.000
Parameter 14-21 Automatic Restart Time 5 s
Parameter 14-32 Current Lim Ctrl, Filter Time 27
Parameter 30-84 Process PID Proportional Gain 0.010
PROFIBUS-specific parameters
Parameter 9-71 PROFIBUS Save Data Values [1] Store All Setups
Configuring the System
24 | Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
5 Parameter Mapping Lists
5.1 FCD 300 Parameter Group 0
5.1.1 Conversion of Parameter 001 Language Select
Table 8: Parameter 001
FCD 300 series FCD 302 series
Parameter 001 Language Select 0-01 Language
Options [0] English [0] English
[1] Deutsch [1] Deutsch
[2] French [2] French
[3] Dansk [3] Dansk
[4] Spanish [4] Spanish
[5] Italian [5] Italian

Parameter Mapping Lists

5.1.2 Conversion of Parameter 002 Operation Site
Table 9: Parameter 002
FCD 300 series FCD 302 series
Parameter 002 Operation Site Not converted
Options [0] Remote
[1] Local with External Stop
[2] Local
5.1.3 Conversion of Parameter 003 Local Reference
Table 10: Parameter 003
FCD 300 series FCD 302 series
Parameter 003 Local Reference Not converted
5.1.4 Conversion of Parameter 004 Active Set-up
Table 11: Parameter 004
FCD 300 series FCD 302 series
Parameter 004 Active Set-up 0-10 Active Set-up
Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890| 25
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
FCD 300 series FCD 302 series
Options [0] Factory Setup [0] Factory Setup
[1] Setup 1 [1] Setup 1
[2] Setup 2 [2] Setup 2
[3] Setup 3 [3] Setup 3
[4] Setup 4 [4] Setup 4
[5] Multi Setup [9] Multi Setup
5.1.5 Conversion of Parameter 005 Edit Setup
Table 12: Parameter 005
FCD 300 series FCD 302 series
Parameter 005 Edit Setup 9-70 Set-up Copy
Options [0] Factory Set-up [0] Factory Set-up
Parameter Mapping Lists
[1] Setup 1 [1] Setup 1
[2] Setup 2 [2] Setup 2
[3] Setup 3 [3] Setup 3
[4] Setup 4 [4] Setup 4
[5] Active Setup [9] Active Setup
5.1.6 Conversion of Parameter 006 Setup Copy
Table 13: Parameter 006
FCD 300 series FCD 302 series
Parameter 006 Setup Copy 0-51 Set-up Copy
Options [0] No Copy [0] No Copy
[1] Copy to 1 from # [9] Copy to ALL from #
[2] Copy to 2 from # [9] Copy to ALL from #
[3] Copy to 3 from # [9] Copy to ALL from #
[4] Copy to 4 from # [9] Copy to ALL from #
[5] Copy to ALL from # [9] Copy to ALL from #
26 | Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890
Operating Guide | VLT® FCD 300 PROFIBUS Converter MCA 117
5.1.7 Conversion of Parameter 007 LCP Copy
Table 14: Parameter 007
FCD 300 series FCD 302 series
Parameter 007 LCP Copy 0-50 LCP Copy
Options [0] No copy Not converted
[1] Upload all Param Not converted
[2] Download All Not converted
[3] Download Size Inde Not converted
5.1.8 Conversion of Parameter 008 Frequency Scale
Table 15: Parameter 008
FCD 300 series FCD 302 series
Parameter 008 Frequency Scale Not converted
Parameter Mapping Lists
5.1.9 Conversions of Parameters 009 to 012 Display Line
Table 16: Parameters 009 to 012
FCD 300 series FCD 302 series
Parameter 009 Display Line 0-23 Display Line 2
010 Display Line 0-20 Display Line 1.1
011 Display Line 0-21 Display Line 1.2
012 Display Line 0-22 Display Line 1.3
Danfoss A/S © 2019.11
AQ289550754901en-000101 / 130R0890| 27
Loading...
+ 63 hidden pages