Danfoss MCA 114 Operating guide

MAKING MODERN LIVING POSSIBLE
Operating Instructions
VLT® PROFIBUS Converter MCA 114
VLT® AutomationDrive FC 302 • VLT® 5000
www.danfoss.com/drives
Contents
Contents
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
1 Introduction
1.1 About this Manual
1.2 Technical Overview
1.3 Constraints
1.3.1 Software Versions 3
1.3.2 Relations 4
1.3.3 Hardware 4
1.3.4 Performance 5
1.4 Abbreviations
2 Safety
3 How to Install
3.1 Connecting the Bus Line
3.2 How to Install Option in Frequency Converter
3.2.1 Mechanical Installation 8
3.3 EMC Precautions
3 3 3 3
5
6
7 7 7
8
4 How to Configure the System
4.1 Configure the PROFIBUS Network
4.1.1 Setting the PROFIBUS Address using the Hardware Switches 9
4.1.2 Setting the PROFIBUS Address via 9-18 Node Address 9
4.1.3 Commissioning 10
4.2 LED Behaviour
4.3 Initialisation
5 Parameter Mapping Lists
5.1 VLT® 5000 Parameter Group 0
5.2 VLT® 5000 Parameter Group 1
5.3 VLT® 5000 Parameter Group 2
5.4 VLT® 5000 Parameter Group 3
5.5 VLT® 5000 Parameter Group 4
5.6 VLT® 5000 Parameter Group 5
5.7 VLT® 5000 Parameter Group 6
5.8 VLT® 5000 Parameter Group 7
9 9
10 11
12
12
14
18
21
29
34
36
38
5.9 VLT® 5000 Parameter Group 8
5.10 VLT® 5000 Parameter Group 9
6 Troubleshooting
6.1 Step-by-step Troubleshooting
39
40
43 43
MG34N202 - Rev. 2013-10-15 1
Contents
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
Index
44
2 MG34N202 - Rev. 2013-10-15
Introduction
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
1 Introduction
1.1 About this Manual
First-time users can find the most essential information for quick installation and set-up in these chapters:
1.2.1 Technical Overview
1.3 Constraints 3 How to Install
NOTICE
Some parameters in the VLT® 5000 are not supported in the FC 302 and some FC 302 parameters cannot be accessed via the PROFIBUS converter option MCA 114. Refer to 5 Parameter Mapping Lists for more information. If a write request is attempted to a parameter selection not supported, the frequency converter discards the value and issues a positive reply. Only parameters and functions described in this manual are supported.
1
1
For more detailed information including the full range of set-up options and diagnosis tools, refer to:
4 How to Configure the System 5 Parameter Mapping Lists
FC 300-related Literature
1.1.1
The following literature is available for the FC 300 series:
VLT® AutomationDrive FC 302 Operating
Instructions
VLT® AutomationDrive FC 302 Design Guide
VLT® AutomationDrive FC 302 Programming
Guide
www.danfoss.com/BusinessAreas/DrivesSolutions/Documen­tations/VLT+Technical+Documentation.htm
1.2
Technical Overview
The MCA 114 Profibus Converter is an option replacing a VLT® 5000 with a VLT® AutomationDrive FC 302 in a
PROFIBUS network.
NOTICE
The replacement frequency converter must match the power size, or be bigger than the replaced VLT® 5000. Make sure that the brake chopper matches the new frequency converter. Make sure that the new frequency converter meets the local regulations concerning the machinery directive, prefuses, and other appropriate regulations.
NOTICE
Observe local rules and regulations when replacing frequency converter in existing installations.
1.3 Constraints
1.3.1 Software Versions
VLT® AutomationDrive FC 302 with firmware
version 5.5X or higher. The MCA 114 Profibus Converter firmware is
based on a VLT® 5000 software version 3.9x and PROFIBUS software version 4.5x.
With this PROFIBUS converter option the FC 302 reacts as a VLT® 5000 on the PROFIBUS network. Changes to PLC
programming or configuration are normally not necessary.
The FC 302 identifies itself as a VLT® 5000 on the PROFIBUS network, and a write command to e.g. Ramp Up
Time in VLT® 5000 is automatically linked to the corresponding ramp up time parameter in VLT® Automa-
tionDrive FC 302.
MG34N202 - Rev. 2013-10-15 3
130BT310.11
Introduction
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
1
1.3.2 Relations
This manual relates to the following hardware:
VLT® PROFIBUS Converter option, type no.
130B1246 MCB 101 General I/O option, type no. 130B1125
(uncoated), 130B1212 (coated) MCB 107 External 24 Volt DC Supply, type no.
130B1108 (uncoated), 130B1208 (coated) PROFIBUS adaptor Sub-D9 connector, type no.
130B1112. for enclosure types A1, A2 & A3 PROFIBUS adaptor Sub-D9 connector, type no.
176F1742 for enclosure types D & E
Hardware
1.3.3
The VLT® PROFIBUS Converter MCA 114 supports
VLT® AutomationDrive FC 302 only. There is no support for PROFIBUS FMS networks.
The FC 302 has fewer digital I/Os and analog
output signals than VLT® 5000. The General I/O Option MCB 101 must be mounted in FC 302 to map these signals and utilise all I/Os.
VLT® 5000
FC 302
Terminal Function Terminal Function
01-03 Relay 01-03 Relay
68 RS-485-P 68 RS-485-P 69 RS-485-N 69 RS-485-N 61 GND RS-485 61 GND RS-485 12 24 V out 12 24 V out 13 24 V out 13 24 V out 50 10 V out 50 10 V out
Table 1.1 Terminal Mapping
* = General I/O option MCB 101
** = Switch “S201” must be OFF
*** = Switch “S202” must be ON
VLT
®
5000
FC 302
Terminal Function Terminal Function
16 Digital input X30/2* Digital input 17 Digital input X3/3* Digital input 18 Digital input 18 Digital input 19 Digital input 19 Digital input 27 Digital input 27 Digital input 29 Digital input 29 Digital input 32 Digital input 32 Digital input 33 Digital input 33 Digital input 20 GND Digital
input
53 Analog input
voltage
54 Analog input
voltage
60 Analog input
current
55 GND analog/
digital input
voltage
42
39 GND analog/
04-05 Relay 04-06 Relay
Analog/digital
output
digital output
20 GND Digital input
53 Analog input voltage**
X30/11*** Analog input voltage
54 Analog input
55 GND analog/digital
42 Analog output 0/4-20
X30/6* Digital output X30/7* Pulse output
39 GND analog /digital
current***
input voltage
mA
output
Illustration 1.1 Location of Switches S801, S201, and S202 (Left to Right)
4 MG34N202 - Rev. 2013-10-15
Introduction
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
1.3.4 Performance
The dynamic performance on the motor shaft in
the closed loop operation compared with VLT 5000 can be different in certain applications. If necessary, adjust the PID controller manually.
The motor control algorithm of the VLT
AutomationDrive FC 302 results in a better motor performance compared to VLT® 5000.
®
®
NOTICE
Factory values: After initialisation most parameters are set to match the factory settings of the VLT® 5000 parameters. For more information about the initialisation, see the VLT Automa-
tionDrive FC 301/302 Programming Guide.
NOTICE
Linked Set-ups: To synchronise set-up changes made with running motor, ensure that FC 302 setups are linked. This is done in 0-12 This Set-up Linked to.
1
1
1.4 Abbreviations
AOC Application oriented control CTW Control word EMC Electromagnetic Compatibility I/O Input/Output LED Light Emitting Diode LSB Least Significant Bit MAV Main Actual Value (actual output) MOC Motor oriented control MSB Most Significant Bit
MRV Main Reference Value (Setpoint) N/A Not applicable PCD Peripherals Communication Data (process data) PCV Parameter Characteristics Value (Parameter
channel) PLC Programmable Logic Controller PNU Parameter Number PPO Parameter Process Data Object PU Power Unit REF Reference (= MRV) STW Status Word
Table 1.2 Abbreviations
MG34N202 - Rev. 2013-10-15 5
Safety
2 Safety
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
22
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when connected to AC mains input power. Failure to perform installation, start-up, and maintenance by qualified personnel could result in death or serious injury.
Installation, start-up, and maintenance must be
performed by qualified personnel only.
Safety regulations
1. The frequency converter must be disconnected from mains, if repair work is to be carried out. Check that the mains supply has been discon­nected and that the necessary time has passed before removing motor and mains plugs, see
Discharge Time Table.
2. The [Off] key does not disconnect the equipment from mains and is thus not to be used as a safety switch.
3. Correct protective earthing of the equipment must be established, the user must be protected against supply voltage, and the motor must be protected against overload in accordance with applicable national and local regulations.
4. The earth leakage currents are higher than 3.5 mA.
5. Protection against motor overload is not included in the factory setting. If this function is desired, set 1-90 Motor Thermal Protection [4] ETR trip or [3] ETR warning.
The function is initialised at 1.16 x rated motor current and rated motor frequency. For the North American market; the ETR functions provide class 20 motor overload protection in accordance with NEC.
6. Do not remove the plugs for the motor and mains supply while the frequency converter is connected to mains. Check that the mains supply has been disconnected and that the necessary time has passed before removing motor and mains plugs, see Discharge Time Table.
7. The frequency converter has more voltage inputs than L1, L2 and L3, when load sharing (linking of DC intermediate circuit) and external 24 V DC have been installed. Check that all voltage inputs have been disconnected and that the necessary time has passed before commencing repair work, see Discharge Time Table.
Warning against unintended start
1. The motor can be brought to a stop with digital commands, bus commands, references or a local stop, while the frequency converter is connected to mains. These stop funcyions are not sufficient to prevent unintended starts.
2. While parameters are being changed, the motor may start. Consequently, [Off] must always be activated.
3. A motor that has been stopped may start if faults occur in the electronics of the frequency converter, or if a temporary overload or a fault in the supply mains or the motor connection ceases.
WARNING
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains.
Minimum waiting time (minutes)
Voltage [V]
4 15
200-240 0.25-3.7 kW 5.5-37 kW 380-480 0.25-7.5 kW 11-75 kW 525-600 0.75-7.5 kW 11-75 kW 525-690 11-75 kW High voltage may be present even when the warning LED indicator lights are off.
Table 2.1 Discharge Time
Also make sure that other voltage inputs have been disconnected, such as external 24 V DC, load sharing (linkage of DC intermediate circuit), as well as the motor connection for kinetic back up.
6 MG34N202 - Rev. 2013-10-15
130BT318.11
How to Install
3 How to Install
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
3.1 Connecting the Bus Line
Terminate the bus line at both ends of each segment. A mismatch of impedance may result in reflections on the line resulting in corrupt data transmission.
The Profibus Option Card contains a suitable termination. To activate the termination, turn on Switch 1 on the Profibus converter option. By default, the switch is turned off.
NOTICE
Notice that pin numbers are colour coded on the Profibus connector.
Unlike the VLT colour-coded to avoid swapping the bus wires.
®
5000, the FC 302 Profibus connectors are
3.2
How to Install Option in Frequency Converter
Illustration 3.2 Installing Fieldbus Option
3 3
Illustration 3.1 Connecting Bus Wires to VLT PROFIBUS Converter MCA 114
Profibus B Profibus A 63 = RxD/TxD Negative, green cable
Table 3.1 Correct Colour-Coding
62 = RxD/TxD Positive, red cable
MG34N202 - Rev. 2013-10-15 7
Illustration 3.3 Cable Holders
1. Remove the LCP from the FC 302.
2. Remove the frame below the local control panel.
Fieldbus cable
Min.200mm
90° crossing
130BA080.11
How to Install
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
3. Push the option into place. Two positions are possible, with cable terminal facing either up or down. The cable up position is often most suitable when several frequency converters are installed side by side in a rack, as this position permits shorter cable lengths.
33
3.2.1 Mechanical Installation
To ease the replacement of VLT 5000 with VLT® AutomationDrive FC 302, there is a number of adapter plates available. The adapter plates have the same footprints as VLT 5000 and have threaded holes for VLT® AutomationDrive FC 302. The
adapter plate prevents damage that can occur from drilling new threaded holes in the backboard of the enclosure. The adapter plate also decreases the time required to exchange a broken frequency converter. The following mechanical adapter plates are available:
Ordering
number
130B0183 Bookstyle, IP20 395 90
130B0184 Bookstyle, IP20 395 130
130B0185 Compact, IP20 395 220
Style Height [mm] Width [mm] Type
4. Push the fieldbus option adaptor frame for the FC 302 into place.
5. Remount the LCP.
6. Attach the cable.
7. Fasten the cable using cable holders.
5001-5003 200-240 V 5001-5005 380-500 V 5004-5006 200-240 V 5006-5011 380-500 V 5001-5003 200-240 V 5001-5005 380-500 V 5004-5006 200-240 V 5006-5011 380-500 V 5001-5011 550-600 V
Table 3.2 Mechanical Installation for VLT® 5000
3.3 EMC Precautions
To achieve interference-free operation of the PROFIBUS:
Maintain high distance (min. 200 mm [8"])
between the PROFIBUS communication cable and the motor and brake resistor cables to avoid coupling of high frequency noise from one cable to the other.
When crossing is unavoidable, ensure that the
PROFIBUS cable crosses motor and brake resistor cables at an angle of 90 degrees.
NOTICE
Observe relevant national and local regulations, for example regarding protective earth connection.
Illustration 3.4 Correct EMC Installation
8 MG34N202 - Rev. 2013-10-15
MCA 114
Probus
Converter
MS
NS
Option A
130B1246
NS
MS
ON
OFF
S600
ON ON
1
ON
OFF
ON
S300
8 7 6 5 4 3 2
130BA084.11
How to Configure the System
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
4 How to Configure the System
4.1 Configure the PROFIBUS Network
All PROFIBUS stations connected to the same bus network must have a unique station address.
Before a VLT® 5000 can be replaced with an FC 302 with MCA 114, only the station address needs to be configured in the FC 302.
The PROFIBUS address of the FC 302 can be selected via:
Hardware switches
9-18 Node Address
NOTICE
After installing PROFIBUS Converter MCA 114, check that 8-02 Control Word Source is set to [3] Option A.
Using the hardware switches, select an address range from 0 to 125 (factory setting 127) according to Illustration 4.1: ON = 1, OFF = 0
4 4
4.1.1 Setting the PROFIBUS Address using the Hardware Switches
Illustration 4.1 PROFIBUS Option A
CAUTION
Switch off the power supply before changing the hardware switches.
CAUTION
The address change comes into effect at the next power­up, and can be read in 9-18 Node Address
Switch 1 2 3 4 5 6 7 8 8 7 6 5 4 3 2 1 Address +1 +2 +4 +8 +16 +32 +64 - - +64 +32 +16 +8 +4 +2 +1 Example: 1 1 0 0 0 0 0 0 - - 0 0 0 0 0 0 1 35 1 1 0 0 0 1 0 - - 0 1 0 0 0 1 1 82 0 1 0 0 1 0 1 - - 1 0 1 0 0 1 0
Table 4.1 Hardware Switches
VLT® 5000
4.1.2 Setting the PROFIBUS Address via 9-18 Node Address
FC 302
Setting the address via 9-18 Node Address or the PROFIBUS SSA-command is possible, if the hardware switches are set to 126 or 127 (factory switch setting). The new address becomes active at the next power-up.
MG34N202 - Rev. 2013-10-15 9
How to Configure the System
4.1.3 Commissioning
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
After setting the station address from VLT® 5000 to VLT AutomationDrive FC 302, cycle power on the frequency
®
4.2 LED Behaviour
The option has 2 bi-coloured LEDs:
converter to activate the new address. The master/PLC now recognizes the frequency converter as VLT® 5000. A
solid green NS LED on the MCA 114 option indicates that communication between the master and the frequency
LED label Description
NS Network Status MS Modul Status ( DP-V1 communication)
converter is established. If the NS LED flashes, the
44
master/PLC has not recognised the frequency converter.
Table 4.2 Bi Coloured LEDs
For more information, refer to 6.1 Step-by-step Trouble­shooting
State LED Description
The option is defect. Contact Danfoss The option is OK.
Searching for the baud rate. Check the connection to the master if the option stays in this state. Baud rate found - waiting for parameters from the master. Wrong parameters from the master. Parameters from master OK – waiting for configuration data. Wrong Configuration data from the master. Data Exchange between the master and the FC 300 is active. Clear State. Warning 34 is active and a bus reaction in par. 8-04 is executed.
Power On
Baud rate search
Wait Parameterising
Wait Configuration
Data Exchange
Red:
Green:
Green:
Green:
Red:
Green:
Red:
Green:
Red:
Solid red
Flashing green
Flashing green
Long green flash
Long red flash
Short green flash
Short red flash
Solid green
Flashing red
Table 4.3 Net Status
LED Description
No light Off No PROFIBUS DPV1 communication is active.
Green:
Green:
Green:
Red:
Table 4.4 Module Status ( DP-V1 Communication)
Short green flash DP V1 communication from a Master Class 1
(PLC) is active.
Long green flash DP V1 communication from a Master Class 2
(MCT 10, FDT) is active.
Solid green DP V1 communication from a Master Class 1
and 2 is active.
Flashing red Internal error.
NOTICE
The LEDs flash patterns of the MCA114 are not compatible with the patterns of the VLT®5000 PROFIBUS LEDs.
10 MG34N202 - Rev. 2013-10-15
How to Configure the System
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
4.3 Initialisation
Factory copy via VLT® 5000 parameter 006 is supported and initialises the FC 302 and also set it to the VLT® 5000
To achieve the best performance, initialise the frequency
default settings.
converter after the option is mounted. If the frequency converter is delivered from factory with the option installed, skip this step. The initialisation is done via
The following parameters are set during the initialisation:
14-22 Operation Mode or a 3 finger reset. The parameters of the FC 302 are set to factory values, and a number of
FC 302 parameters are set to values that match the VLT
®
5000 initial values.
Parameter Initialisation setting
0-02 Motor Speed Unit [Hz] 1-52 Min Speed Normal Magnetising [Hz] 1.0 Hz 3-16 Reference Resource 2 [0] No function 4-12 Motor Speed Low Limit [Hz] 132.0 Hz 3-00 Reference Range min – max 3-01 Reference/Feedback Unit [1] % 3-11 Jog Speed [Hz] 10.0 Hz
4-30 Motor Feedback Loss Function [0] Disabled 4-56 Warning Feedback Low -4000000 4-57 Warning Feedback High 4000000 6-10 Terminal 53 Low Voltage 0.00 Volt 6-20 Terminal 54 Low Voltage 0.00 Volt 6-22 Terminal 54 Low Current 0.00 Volt 5-51 Term. 29 High Frequency 5000 Hz 5-56 Term. 33 High Frequency 25000 Hz 4-32 Motor Feedback Loss Timeout 1.00 s
4 4
14-21 Automatic Restart Time 5 s 14-03 Overmodulation [0] Off 7-33 Process PID Proportional Gain 0.01 8-54 Reversing Select [0] Digital input 8-90 Bus Jog 1 Speed 300 RPM 8-91 Bus Jog 2 Speed 300 RPM 7-04 Speed PID Differentiation Time OFF 2-10 Brake Function [0] Off 2-17 Over-voltage Control [0] Off 5-40 Function Relay [22] Ready, no thermal Warning 5-41 On Delay, Relay [23] Remote, ready, no TW 7-09 Speed PID Error Correction w/ Ramp 100000 (max) 14-11 Mains Voltage at Mains Fault calculated value: VLT5000 level = FC 302 level
* 1,35 / sqrt(2)
MCB 101 option specific parameters
5-16 Terminal X30/2 Digital Input [1] Reset 5-17 Terminal X30/3 Digital Input [19] Freeze reference
PROFIBUS specific parameters
9-71 Profibus Save Data Values [1] Store all setups
Table 4.5 Parameter Setup at Initialisation
MG34N202 - Rev. 2013-10-15 11
Parameter Mapping Lists
5 Parameter Mapping Lists
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
5.1
VLT® 5000 Parameter Group 0
Parameter 001 Language select 0-01 Language Options [0] English [0] English
55
Table 5.1 Conversion of Parameter 001
Parameter 002 Local/remote control Not converted Options [0] Remote
Table 5.2 Conversion of Parameter 002
Parameter 003 Local reference Not converted
Table 5.3 Conversion of Parameter 003
Parameter 004 Active Set-up 0-10 Active Set-up Options [0] Factory Setup [0] Factory Setup
Table 5.4 Conversion of Parameter 004
Parameter 005 Setup Copy 0-51 Set-up Copy Options [0] Factory Set-up [0] Factory Set-up
Table 5.5 Conversion of Parameter 005
VLT 5000 series FC 302 series
[1] Deutsch [1] Deutsch [2] French [2] French [3] Dansk [3] Dansk [4] Spanish [4] Spanish [5] Italian [5] Italian
VLT 5000 series FC 302 series
[1] Local with External Stop [2] Local
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
[1] Setup 1 [1] Setup 1 [2] Setup 2 [2] Setup 2 [3] Setup 3 [3] Setup 3 [4] Setup 4 [4] Setup 4 [5] Multi Setup [9] Multi Setup
VLT 5000 series FC 302 series
[1] Setup 1 [1] Setup 1 [2] Setup 2 [2] Setup 2 [3] Setup 3 [3] Setup 3 [4] Setup 4 [4] Setup 4 [5] Active Setup [9] Active Setup
Parameter 006 Setup Copy 0-51 Set-up Copy Options [0] No Copy [0] No Copy
Table 5.6 Conversion of Parameter 006
Parameter 007 LCP Copy Not converted
Table 5.7 Conversion of Parameter 007
Parameter 008 Display scaling of motor
Table 5.8 Conversion of Parameter 008
Parameter number Parameter number Parameter number Parameter number Options [0] None [0] None
Table 5.9 Conversion of Parameters 009 to 012
VLT 5000 series FC 302 series
[1] [1] [2] [2] [3] [3] [4] [4]
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
Not converted
frequency
VLT 5000 series FC 302 series
009 Display line 0-23
010 Display line 0-20
011 Display line 0-21
012 Display line 0-22
[1] Reference % [1602] Reference % [2] Reference [Unit] [1601] Reference
[Unit]
[3] Feedback [Unit] [1652] Feedback
[Unit] [4] Frequency [Hz] [1613] Frequency [Hz] [5] Frequency x scale [1609] Custom
readout [6] Motor current [A] [1614] Motor current
[A] [7] Torque [%] [1622] Torque [%] [8] Power [kW] [1610] Power [kW] [9] Power [HP] [1611] Power [HP] [10] Output energy [kWh] [11] Motor voltage [V] [1612] Motor voltage
[1502] kWh counter
[kWh]
[V]
12 MG34N202 - Rev. 2013-10-15
Parameter Mapping Lists
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
Parameter number Parameter number Parameter number Parameter number Options [12] DC link voltage
VLT 5000 series FC 302 series
009 0-09 Performance Monitor
010 0-10 Active Set-up
011 0-11 Edit Set-up
012 0-12 This Set-up Linked to
[V] [13] Thermal load, motor [%] [14] Thermal load, VLT® [%] [15] Running hours [hours] [16] Digital input [1660] Digital input
[17] Analogue input 53 [V] [18] Analogue input 54 [V] [19] Analogue input 60 [mA] [20] Pulse reference [Hz] [21] Ext. reference [%] [22] Status word [hex] [23] Brake effect/2 min [kW] [24] Brake effect/sec [kW] [25] Heat sink temp. [1634] Heat sink temp.
[26] Alarm word [hex] [27] Control word [hex] [28] Warning word 1 [hex] [29] Warning word 2 [hex] [30] Com. Option warning [hex] [31] RPM [min] [1617] Speed RPM [min]
[32] RPM x scaling [min] [33] LCP display text Not possible
[1630] DC link voltage [V]
[1618] Thermal load, motor [%] [1635] Inverter thermal [%]
[1501] Running hours [hours]
[1662] Analogue input 53 [V] [1664] Analogue input 54 [V] [1662] Analogue input 53 [mA] [1651] Pulse reference [Hz]
[1650] Ext. reference [%]
[1603] Status word [hex]
[1633] Brake effect/2 min [kW] [1632] Brake effect/sec [kW]
[1600] Control word [hex]
[953] Com. Option warning [hex]
[1609] Custom readout
Parameter 013 Local Ctrl./config Not converted
Table 5.11 Conversion of Parameter 013
Parameter 014 Local Stop key 0-41 [Off] Key on LCP Options [0] Disable [0] Disable
Table 5.12 Conversion of Parameter 014
Parameter 015 Local Jogging Not converted Options [0] Disable
Table 5.13 Conversion of Parameter 015
Parameter 016 Local Reversing Not converted Options [0] Disable
Table 5.14 Conversion of Parameter 016
Parameter 017 Local Stop key 0-43 [Reset] Key on LCP Options [0] Disable [0] Disable
Table 5.15 Conversion of Parameter 017
Parameter 018 Lock for data
Options [0] Not locked [0] Full access
Table 5.16 Conversion of Parameter 018
Parameter 019 Power-Up Mode 0-04 Operating State at
Options [0] Auto Restart, use
Table 5.17 Conversion of Parameter 019
VLT 5000 series FC 302 series
VLT 5000 series FC 302 series
[1] Enable [1] Enable [2] Password
VLT 5000 series FC 302 series
[1] Enable
VLT 5000 series FC 302 series
[1] Enable
VLT 5000 series FC 302 series
[1] Enable [1] Enable [2] Password
VLT 5000 series FC 302 series
0-61 Access to Main Menu
change
[1] Lock [1] LCP: Read only
VLT 5000 series FC 302 series
saved ref. [1] Forced stop, use saved ref. [2] Forced stop, set ref = 0.
w/o Password
Power-up (Hand) [0] Resume
[1] Forced stop, use saved ref. [2] Forced stop, set ref = 0
5 5
Table 5.10 Conversion of Parameters 009 to 012
MG34N202 - Rev. 2013-10-15 13
Loading...
+ 33 hidden pages