VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
1 Introduction
1.1 About this Manual
1.2 Technical Overview
1.3 Constraints
1.3.1 Software Versions3
1.3.2 Relations4
1.3.3 Hardware4
1.3.4 Performance5
1.4 Abbreviations
2 Safety
3 How to Install
3.1 Connecting the Bus Line
3.2 How to Install Option in Frequency Converter
3.2.1 Mechanical Installation8
3.3 EMC Precautions
3
3
3
3
5
6
7
7
7
8
4 How to Configure the System
4.1 Configure the PROFIBUS Network
4.1.1 Setting the PROFIBUS Address using the Hardware Switches9
4.1.2 Setting the PROFIBUS Address via 9-18 Node Address9
4.1.3 Commissioning10
4.2 LED Behaviour
4.3 Initialisation
5 Parameter Mapping Lists
5.1 VLT® 5000 Parameter Group 0
5.2 VLT® 5000 Parameter Group 1
5.3 VLT® 5000 Parameter Group 2
5.4 VLT® 5000 Parameter Group 3
5.5 VLT® 5000 Parameter Group 4
5.6 VLT® 5000 Parameter Group 5
5.7 VLT® 5000 Parameter Group 6
5.8 VLT® 5000 Parameter Group 7
9
9
10
11
12
12
14
18
21
29
34
36
38
5.9 VLT® 5000 Parameter Group 8
5.10 VLT® 5000 Parameter Group 9
6 Troubleshooting
6.1 Step-by-step Troubleshooting
39
40
43
43
MG34N202 - Rev. 2013-10-151
Contents
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
Index
44
2MG34N202 - Rev. 2013-10-15
Introduction
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
1 Introduction
1.1 About this Manual
First-time users can find the most essential information for
quick installation and set-up in these chapters:
1.2.1 Technical Overview
1.3 Constraints
3 How to Install
NOTICE
Some parameters in the VLT® 5000 are not supported in
the FC 302 and some FC 302 parameters cannot be
accessed via the PROFIBUS converter option MCA 114.
Refer to 5 Parameter Mapping Lists for more information.
If a write request is attempted to a parameter selection
not supported, the frequency converter discards the
value and issues a positive reply. Only parameters and
functions described in this manual are supported.
1
1
For more detailed information including the full range of
set-up options and diagnosis tools, refer to:
4 How to Configure the System
5 Parameter Mapping Lists
FC 300-related Literature
1.1.1
The following literature is available for the FC 300 series:
The MCA 114 Profibus Converter is an option replacing a
VLT® 5000 with a VLT® AutomationDrive FC 302 in a
PROFIBUS network.
NOTICE
The replacement frequency converter must match the
power size, or be bigger than the replaced VLT® 5000.
Make sure that the brake chopper matches the new
frequency converter.
Make sure that the new frequency converter meets the
local regulations concerning the machinery directive,
prefuses, and other appropriate regulations.
NOTICE
Observe local rules and regulations when replacing
frequency converter in existing installations.
1.3 Constraints
1.3.1 Software Versions
VLT® AutomationDrive FC 302 with firmware
•
version 5.5X or higher.
The MCA 114 Profibus Converter firmware is
•
based on a VLT® 5000 software version 3.9x and
PROFIBUS software version 4.5x.
With this PROFIBUS converter option the FC 302 reacts as
a VLT® 5000 on the PROFIBUS network. Changes to PLC
programming or configuration are normally not necessary.
The FC 302 identifies itself as a VLT® 5000 on the
PROFIBUS network, and a write command to e.g. Ramp Up
Time in VLT® 5000 is automatically linked to the
corresponding ramp up time parameter in VLT® Automa-
tionDrive FC 302.
MG34N202 - Rev. 2013-10-153
130BT310.11
Introduction
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
1
1.3.2 Relations
This manual relates to the following hardware:
VLT® PROFIBUS Converter option, type no.
•
130B1246
MCB 101 General I/O option, type no. 130B1125
•
(uncoated), 130B1212 (coated)
MCB 107 External 24 Volt DC Supply, type no.
•
130B1108 (uncoated), 130B1208 (coated)
PROFIBUS adaptor Sub-D9 connector, type no.
•
130B1112. for enclosure types A1, A2 & A3
PROFIBUS adaptor Sub-D9 connector, type no.
•
176F1742 for enclosure types D & E
Hardware
1.3.3
The VLT® PROFIBUS Converter MCA 114 supports
•
VLT® AutomationDrive FC 302 only.
There is no support for PROFIBUS FMS networks.
•
The FC 302 has fewer digital I/Os and analog
•
output signals than VLT® 5000. The General I/O
Option MCB 101 must be mounted in FC 302 to
map these signals and utilise all I/Os.
VLT® 5000
FC 302
TerminalFunctionTerminalFunction
01-03Relay01-03Relay
68RS-485-P68RS-485-P
69RS-485-N69RS-485-N
61GND RS-48561GND RS-485
1224 V out1224 V out
1324 V out1324 V out
5010 V out5010 V out
Illustration 1.1 Location of Switches S801, S201, and S202 (Left
to Right)
4MG34N202 - Rev. 2013-10-15
Introduction
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
1.3.4 Performance
The dynamic performance on the motor shaft in
•
the closed loop operation compared with VLT
5000 can be different in certain applications. If
necessary, adjust the PID controller manually.
The motor control algorithm of the VLT
•
AutomationDrive FC 302 results in a better motor
performance compared to VLT® 5000.
®
®
NOTICE
Factory values:
After initialisation most parameters are set to match the
factory settings of the VLT® 5000 parameters. For more
information about the initialisation, see the VLT Automa-
tionDrive FC 301/302 Programming Guide.
NOTICE
Linked Set-ups:
To synchronise set-up changes made with running
motor, ensure that FC 302 setups are linked. This is done
in 0-12 This Set-up Linked to.
1
1
1.4 Abbreviations
AOCApplication oriented control
CTWControl word
EMCElectromagnetic Compatibility
I/OInput/Output
LEDLight Emitting Diode
LSBLeast Significant Bit
MAVMain Actual Value (actual output)
MOCMotor oriented control
MSBMost Significant Bit
MRVMain Reference Value (Setpoint)
N/ANot applicable
PCDPeripherals Communication Data (process data)
PCVParameter Characteristics Value (Parameter
channel)
PLCProgrammable Logic Controller
PNUParameter Number
PPOParameter Process Data Object
PUPower Unit
REFReference (= MRV)
STWStatus Word
Table 1.2 Abbreviations
MG34N202 - Rev. 2013-10-155
Safety
2 Safety
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
22
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when
connected to AC mains input power. Failure to perform
installation, start-up, and maintenance by qualified
personnel could result in death or serious injury.
Installation, start-up, and maintenance must be
•
performed by qualified personnel only.
Safety regulations
1.The frequency converter must be disconnected
from mains, if repair work is to be carried out.
Check that the mains supply has been disconnected and that the necessary time has passed
before removing motor and mains plugs, see
Discharge Time Table.
2.The [Off] key does not disconnect the equipment
from mains and is thus not to be used as a safety
switch.
3.Correct protective earthing of the equipment
must be established, the user must be protected
against supply voltage, and the motor must be
protected against overload in accordance with
applicable national and local regulations.
4.The earth leakage currents are higher than 3.5
mA.
5.Protection against motor overload is not included
in the factory setting. If this function is desired,
set 1-90 Motor Thermal Protection[4] ETR trip or
[3] ETR warning.
The function is initialised at 1.16 x rated motor current and
rated motor frequency. For the North American market; the
ETR functions provide class 20 motor overload protection
in accordance with NEC.
6.Do not remove the plugs for the motor and
mains supply while the frequency converter is
connected to mains. Check that the mains supply
has been disconnected and that the necessary
time has passed before removing motor and
mains plugs, see Discharge Time Table.
7.The frequency converter has more voltage inputs
than L1, L2 and L3, when load sharing (linking of
DC intermediate circuit) and external 24 V DC
have been installed. Check that all voltage inputs
have been disconnected and that the necessary
time has passed before commencing repair work,
see Discharge Time Table.
Warning against unintended start
1.The motor can be brought to a stop with digital
commands, bus commands, references or a local
stop, while the frequency converter is connected
to mains. These stop funcyions are not sufficient
to prevent unintended starts.
2.While parameters are being changed, the motor
may start. Consequently, [Off] must always be
activated.
3.A motor that has been stopped may start if faults
occur in the electronics of the frequency
converter, or if a temporary overload or a fault in
the supply mains or the motor connection ceases.
WARNING
Touching the electrical parts may be fatal - even after
the equipment has been disconnected from mains.
Minimum waiting time (minutes)
Voltage [V]
415
200-2400.25-3.7 kW5.5-37 kW
380-4800.25-7.5 kW11-75 kW
525-6000.75-7.5 kW11-75 kW
525-69011-75 kW
High voltage may be present even when the warning LED
indicator lights are off.
Table 2.1 Discharge Time
Also make sure that other voltage inputs have been
disconnected, such as external 24 V DC, load sharing
(linkage of DC intermediate circuit), as well as the motor
connection for kinetic back up.
6MG34N202 - Rev. 2013-10-15
130BT318.11
How to Install
3 How to Install
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
3.1 Connecting the Bus Line
Terminate the bus line at both ends of each segment. A
mismatch of impedance may result in reflections on the
line resulting in corrupt data transmission.
The Profibus Option Card contains a suitable termination.
To activate the termination, turn on Switch 1 on the
Profibus converter option. By default, the switch is turned
off.
NOTICE
Notice that pin numbers are colour
coded on the Profibus connector.
Unlike the VLT
colour-coded to avoid swapping the bus wires.
®
5000, the FC 302 Profibus connectors are
3.2
How to Install Option in Frequency
Converter
Illustration 3.2 Installing Fieldbus Option
33
Illustration 3.1 Connecting Bus Wires to VLT PROFIBUS
Converter MCA 114
Profibus B
Profibus A63 = RxD/TxDNegative, green cable
Table 3.1 Correct Colour-Coding
62 = RxD/TxDPositive, red cable
MG34N202 - Rev. 2013-10-157
Illustration 3.3 Cable Holders
1.Remove the LCP from the FC 302.
2.Remove the frame below the local control panel.
Fieldbus cable
Min.200mm
90° crossing
130BA080.11
How to Install
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
3.Push the option into place. Two positions are
possible, with cable terminal facing either up or
down. The cable up position is often most
suitable when several frequency converters are
installed side by side in a rack, as this position
permits shorter cable lengths.
33
3.2.1 Mechanical Installation
To ease the replacement of VLT 5000 with VLT® AutomationDrive FC 302, there is a number of adapter plates available. The
adapter plates have the same footprints as VLT 5000 and have threaded holes for VLT® AutomationDrive FC 302. The
adapter plate prevents damage that can occur from drilling new threaded holes in the backboard of the enclosure. The
adapter plate also decreases the time required to exchange a broken frequency converter.
The following mechanical adapter plates are available:
Ordering
number
130B0183Bookstyle, IP2039590
130B0184Bookstyle, IP20395130
130B0185Compact, IP20395220
StyleHeight [mm]Width [mm]Type
4.Push the fieldbus option adaptor frame for the FC
302 into place.
5.Remount the LCP.
6.Attach the cable.
7.Fasten the cable using cable holders.
5001-5003 200-240 V
5001-5005 380-500 V
5004-5006 200-240 V
5006-5011 380-500 V
5001-5003 200-240 V
5001-5005 380-500 V
5004-5006 200-240 V
5006-5011 380-500 V
5001-5011 550-600 V
Table 3.2 Mechanical Installation for VLT® 5000
3.3 EMC Precautions
To achieve interference-free operation of the PROFIBUS:
Maintain high distance (min. 200 mm [8"])
•
between the PROFIBUS communication cable and
the motor and brake resistor cables to avoid
coupling of high frequency noise from one cable
to the other.
When crossing is unavoidable, ensure that the
•
PROFIBUS cable crosses motor and brake resistor
cables at an angle of 90 degrees.
NOTICE
Observe relevant national and local regulations, for
example regarding protective earth connection.
Illustration 3.4 Correct EMC Installation
8MG34N202 - Rev. 2013-10-15
MCA 114
Probus
Converter
MS
NS
Option A
130B1246
NS
MS
ON
OFF
S600
ONON
1
ON
OFF
ON
S300
8 7 6 5 4 3 2
130BA084.11
How to Configure the System
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
4 How to Configure the System
4.1 Configure the PROFIBUS Network
All PROFIBUS stations connected to the same bus network
must have a unique station address.
Before a VLT® 5000 can be replaced with an FC 302 with
MCA 114, only the station address needs to be configured
in the FC 302.
The PROFIBUS address of the FC 302 can be selected via:
Hardware switches
•
9-18 Node Address
•
NOTICE
After installing PROFIBUS Converter MCA 114, check that
8-02 Control Word Source is set to [3] Option A.
Using the hardware switches, select an address range from
0 to 125 (factory setting 127) according to Illustration 4.1:
ON = 1, OFF = 0
44
4.1.1 Setting the PROFIBUS Address using
the Hardware Switches
Illustration 4.1 PROFIBUS Option A
CAUTION
Switch off the power supply before changing the
hardware switches.
CAUTION
The address change comes into effect at the next powerup, and can be read in 9-18 Node Address
4.1.2 Setting the PROFIBUS Address via
9-18 Node Address
FC 302
Setting the address via 9-18 Node Address or the PROFIBUS
SSA-command is possible, if the hardware switches are set
to 126 or 127 (factory switch setting). The new address
becomes active at the next power-up.
MG34N202 - Rev. 2013-10-159
How to Configure the System
4.1.3 Commissioning
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
After setting the station address from VLT® 5000 to VLT
AutomationDrive FC 302, cycle power on the frequency
®
4.2 LED Behaviour
The option has 2 bi-coloured LEDs:
converter to activate the new address. The master/PLC
now recognizes the frequency converter as VLT® 5000. A
solid green NS LED on the MCA 114 option indicates that
communication between the master and the frequency
LED labelDescription
NSNetwork Status
MSModul Status ( DP-V1 communication)
converter is established. If the NS LED flashes, the
44
master/PLC has not recognised the frequency converter.
Table 4.2 Bi Coloured LEDs
For more information, refer to 6.1 Step-by-step Troubleshooting
StateLEDDescription
The option is defect. Contact
Danfoss
The option is OK.
Searching for the baud rate.
Check the connection to the
master if the option stays in this
state.
Baud rate found - waiting for
parameters from the master.
Wrong parameters from the
master.
Parameters from master OK –
waiting for configuration data.
Wrong Configuration data from
the master.
Data Exchange between the
master and the FC 300 is active.
Clear State. Warning 34 is active
and a bus reaction in par. 8-04 is
executed.
Power On
Baud rate search
Wait Parameterising
Wait Configuration
Data Exchange
Red:
Green:
Green:
Green:
Red:
Green:
Red:
Green:
Red:
Solid red
Flashing green
Flashing green
Long green
flash
Long red flash
Short green
flash
Short red flash
Solid green
Flashing red
Table 4.3 Net Status
LEDDescription
No lightOffNo PROFIBUS DPV1 communication is active.
Green:
Green:
Green:
Red:
Table 4.4 Module Status ( DP-V1 Communication)
Short green flashDP V1 communication from a Master Class 1
(PLC) is active.
Long green flashDP V1 communication from a Master Class 2
(MCT 10, FDT) is active.
Solid greenDP V1 communication from a Master Class 1
and 2 is active.
Flashing redInternal error.
NOTICE
The LEDs flash patterns of the MCA114 are not
compatible with the patterns of the VLT®5000 PROFIBUS
LEDs.
10MG34N202 - Rev. 2013-10-15
How to Configure the System
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
4.3 Initialisation
Factory copy via VLT® 5000 parameter 006 is supported
and initialises the FC 302 and also set it to the VLT® 5000
To achieve the best performance, initialise the frequency
default settings.
converter after the option is mounted. If the frequency
converter is delivered from factory with the option
installed, skip this step. The initialisation is done via
The following parameters are set during the initialisation:
14-22 Operation Mode or a 3 finger reset. The parameters
of the FC 302 are set to factory values, and a number of
FC 302 parameters are set to values that match the VLT
®
5000 initial values.
ParameterInitialisation setting
0-02 Motor Speed Unit[Hz]
1-52 Min Speed Normal Magnetising [Hz]1.0 Hz
3-16 Reference Resource 2[0] No function
4-12 Motor Speed Low Limit [Hz]132.0 Hz
3-00 Reference Rangemin – max
3-01 Reference/Feedback Unit[1] %
3-11 Jog Speed [Hz]10.0 Hz
4-30 Motor Feedback Loss Function[0] Disabled
4-56 Warning Feedback Low-4000000
4-57 Warning Feedback High4000000
6-10 Terminal 53 Low Voltage0.00 Volt
6-20 Terminal 54 Low Voltage0.00 Volt
6-22 Terminal 54 Low Current0.00 Volt
5-51 Term. 29 High Frequency5000 Hz
5-56 Term. 33 High Frequency25000 Hz
4-32 Motor Feedback Loss Timeout1.00 s
44
14-21 Automatic Restart Time5 s
14-03 Overmodulation[0] Off
7-33 Process PID Proportional Gain0.01
8-54 Reversing Select[0] Digital input
8-90 Bus Jog 1 Speed300 RPM
8-91 Bus Jog 2 Speed300 RPM
7-04 Speed PID Differentiation TimeOFF
2-10 Brake Function[0] Off
2-17 Over-voltage Control[0] Off
5-40 Function Relay[22] Ready, no thermal Warning
5-41 On Delay, Relay[23] Remote, ready, no TW
7-09 Speed PID Error Correction w/ Ramp100000 (max)
14-11 Mains Voltage at Mains Faultcalculated value: VLT5000 level = FC 302 level
* 1,35 / sqrt(2)
MCB 101 option specific parameters
5-16 Terminal X30/2 Digital Input[1] Reset
5-17 Terminal X30/3 Digital Input[19] Freeze reference
PROFIBUS specific parameters
9-71 Profibus Save Data Values[1] Store all setups
Table 4.5 Parameter Setup at Initialisation
MG34N202 - Rev. 2013-10-1511
Parameter Mapping Lists
5 Parameter Mapping Lists
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
5.1
VLT® 5000 Parameter Group 0
Parameter001 Language select0-01 Language
Options[0] English[0] English
[Unit]
[4] Frequency [Hz][1613] Frequency [Hz]
[5] Frequency x scale[1609] Custom
readout
[6] Motor current [A][1614] Motor current
[A]
[7] Torque [%][1622] Torque [%]
[8] Power [kW][1610] Power [kW]
[9] Power [HP][1611] Power [HP]
[10] Output energy
[kWh]
[11] Motor voltage [V][1612] Motor voltage
[1502] kWh counter
[kWh]
[V]
12MG34N202 - Rev. 2013-10-15
Parameter Mapping Lists
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
Parameter
number
Parameter
number
Parameter
number
Parameter
number
Options[12] DC link voltage
VLT 5000 seriesFC 302 series
0090-09 Performance Monitor
0100-10 Active Set-up
0110-11 Edit Set-up
0120-12 This Set-up Linked to
[V]
[13] Thermal load,
motor [%]
[14] Thermal load,
VLT® [%]
[15] Running hours
[hours]
[16] Digital input[1660] Digital input
Par. 1-00 = [4] Torque open loop
Par.1-01 = [1] VVC
Par. 1-00 = [2] Torque close loop
Par. 1-01 = [3] Flux with motor fb
Par. 5-71 = [1] Counter clockwise
1-03 Torque Characteristics
1-04 Overload Mode
14-40 VT Level
Par. 1-03 = [0] Constant torque
Par. 1-04 Over load = [0] High
Par. 1-03 = [1] Variable torque
Par. 14-40 VT level = 45%
Par. 1-04 Over load = [0] High
Par. 1-03 = [1] Variable torque
Par. 14-40 VT level = 66%
Par. 1-04 Over load = [0] High
Par. 1-03 = [1] Variable torque
Par. 14-40 VT level = 85%
Par. 1-04 Over load = [0] High
Par. 1-01 = [0] U/f
Par. 1-04 Over load = [0] High
Par. 1-03 = [1] Variable torque
Par. 14-40 VT level = 45%
Par. 1-04 Over load = [0] High
plus
plus
plus
Table 5.20 Conversion of Parameter 101
14MG34N202 - Rev. 2013-10-15
Parameter Mapping Lists
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
Parameter 101 Torque charac-
Options[7] High variable
VLT 5000 seriesFC 302 series
teristic
torque with
medium starting
torque
[8] High variable
torque with high
starting torque
[11] Normal
constant torque
[12] Normal
variable torque low
[13] Normal
variable torque
medium
[14] Normal
variable torque
high
[15] Normal special
motor characteristic
[16] Normal
variable torque
with low constant
starting torque
[17] Normal
variable torque
with medium
constant starting
torque
[18] Normal
variable torque
with high constant
starting torque
Parameter 121 Start function1-72 Start Function
Options[0] DC hold in start delay
Table 5.40 Conversion of Parameter 121
Parameter122 Function at stop1-80 Function at Stop
Options[0] Coasting[0] Coast
Table 5.41 Conversion of Parameter 122
Parameter 123 Min frequency for
Range0.0 – 10.0 Hz0.0 – 20.0 Hz
VLT 5000 seriesFC 302 series
[0] DC hold/delay time
time
[1] DC brake in start delay
time
[2] Coasting in start delay
time
[3] Start frequency/voltage
clockwise
[4] Start frequency/voltage
in reference direction
plus
[5] VVC
VLT 5000 seriesFC 302 series
function at stop
clockwise[5] VVC
VLT 5000 seriesFC 302 series
[1] DC hold[1] DC hold
[2] Motor check[2] Motor check
[3] Pre-magnetizing[3] Pre-magnetizing
[1] DC Brake/delay
time
[2] Coast/delay time
[3] Start speed cw
[4] Horizontal
operation
plus
/Flux
clockwise
1-82 Min Speed for
Function at Stop [Hz]
Table 5.37 Conversion of Parameter 118
Parameter119 High starting torqueNot converted
Table 5.38 Conversion of Parameters 119
Parameter120 Start delay
Option0.0 – 10.0 s0.0 – 10.0 s
Table 5.39 Conversion of Parameter 120
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
1-71 Start Delay
Table 5.42 Conversion of Parameter 123
Parameter 124 DC holding current 2-00 DC Hold Current
Range0 - 100%0 - 160% (motor depending)
Table 5.43 Conversion of Parameter 124
Parameter 125 DC braking current2-01 DC Brake Current
Range0 - 100%0 – 160% P.U depending
Table 5.44 Conversion of Parameter 125
Parameter126 DC braking time2-02 DC Braking Time
Range0.0 – 60.0 s0.0 – 60.0 s
Table 5.45 Conversion of Parameter 126
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
16MG34N202 - Rev. 2013-10-15
Parameter Mapping Lists
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
Parameter 200 Output Frequency Range/
Options[0] Only clockwise, 0 – 132 Hz[0] Clockwise
[1] Both directions, 0 – 132 Hz[2] Both directions
[2] Only clockwise, 0 – 1000 Hz [0] Clockwise
[3] Both directions, 0 – 1000 Hz [2] Both directions
[4] Only counter clockwise, 0 –
55
[5] Only counter clockwise, 0 –
Table 5.52 Conversion of Parameter 200
Parameter 201 Output frequency
Range0.0 – par. 202 F
Table 5.53 Conversion of Parameter 201
Parameter 202 Output frequency
Range0.0 – 132/1000 Hz0 – 1000 Hz
Table 5.54 Conversion of Parameter 202
Parameter 203 Reference/feedback area 3-00 Reference Range
Options[0] Min – Max[0] Min – Max
Table 5.55 Conversion of Parameter 203
Parameter204 Minimum
Range-100,000.000 – par.
Table 5.56 Conversion of Parameter 204
VLT 5000 seriesFC 302 series
4-10 Motor Speed
Direction
132 Hz
1000 Hz
VLT 5000 seriesFC 302 series
low limit
max
VLT 5000 seriesFC 302 series
high limit
VLT 5000 seriesFC 302 series
[1] - Max - +Max[1] - Max - +Max
VLT 5000 seriesFC 302 series
reference
205 Ref
max
Direction
[1] Counter
clockwise
[1] Counter
clockwise
4-12 Motor Speed Low
Limit [Hz]
0 – par. 414 F
4-14 Motor Speed High
Limit [Hz]
4-19 Max Output Frequency
3-02 Minimum
Reference
-100,000.000 – par.
3-03 Ref
max
max
[Hz]
Parameter 205 Maximum
RangePar. 204 Ref
Table 5.57 Conversion of Parameter 205
Parameter 206 Ramp Type3-40 Ramp 1 Type
Options[0] LinearPar. 3-40 = [0] Linear
VLT 5000 seriesFC 302 series
3-03 Maximum Reference
reference
100,000.000
VLT 5000 seriesFC 302 series
[1] Sine shape (S1) Par. 3-40 = [2] S-ramp Const Time
[2] Sin2 Shape
(S2)
6-15 Terminal 53 High Ref./Feedb.
Value
6-25 Terminal 54 High Ref./Feedb.
Value
5-53 Term. 29 High Ref./Feedb.
Value
5-58 Term. 33 High Ref./Feedb.
Value
Parameter 307 Terminal 33, input5-15 Terminal 33 Digital
Options[0] No function[0] No operation
Table 5.94 Conversion of Parameter 307
VLT 5000 seriesFC 302 series
Input
7-00 Speed PID Feedback
Source
[1] Reset[1] Reset
[2] Stop inverse[6] Stop inverse
[3] Only start
anticlockwise, on
[4] Jog[14] Jog
[5] Preset reference, on[15] Preset reference, on
[6] Preset reference, msb [17] Preset reference bit 1
[7] Freeze reference[19] Freeze reference
[8] Freeze output[20] Freeze output
[9] Speed down[22] Speed down
[10] Choice of Setup,
msb
[11] Choice of Setup,
msb / Speed down
[12] Slow down[29] Slow down
[13] Ramp 2[34] Ramp bit 0
[14] Mains failure
inverted
[24] Pulse feedback[32] Pulse input,
[25] Encoder input 2B[0] No operation
[29] Data change lockNot supported
[13] Enable start reverse
[24] Setup select bit 1
Not supported
Not supported
Parameter 700 = [9]
Frequency input 33
Parameter 700 = [1] 24 V
encoder
[4] Jog[14] Jog
[5] Preset reference, on[15] Preset reference, on
[6] Preset reference, lsb[16] Preset reference bit 0
[7] Freeze reference[19] Freeze reference
[8] Freeze output[20] Freeze output
[9] Speed up[21] Speed up
[10] Choice of Setup, lsb [23] Setup select bit 0
[11] Choice of Setup,
msb / Speed up
[12] Catch up[28] Catch up
[13] Ramp 2[34] Ramp bit 0
[14] Mains failure
inverted
[24] Encoder input 2A[0] No operation
[29] Data change lockNot supported
Table 5.93 Conversion of Parameter 306
22MG34N202 - Rev. 2013-10-15
Not supported
Not supported
Parameter Mapping Lists
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
Parameter 308 Terminal
Options[0] No
Table 5.95 Conversion of Parameter 308
Parameter 309 Terminal 53, min.
Range0 – 10.0 Volt-10.00 – Par. 6-11
Table 5.96 Conversion of Parameter 309
Parameter 310 Terminal 53, max.
Range0 – 10.0 VoltPar. 6-10 - 10.00 Volt
Table 5.97 Conversion of Parameter 310
VLT 5000
series
53, Analogue
Input Voltage
Operation
[1] ReferencePar. 3-15 Reference resource 1 set to
[2] Feedback
signal
[3] Torque
limit
[4] Thermistor Par. 3-15 Reference resource 1 set to
VLT 5000 seriesFC 302 series
scaling
VLT 5000 seriesFC 302 series
scaling
FC 302 series
3-15 Reference Resource 1
7-00 Speed PID Feedback Source
1-93 Thermistor Resource
4-20 Torque Limit Factor Source
Par. 3-15 Reference resource 1 set to
[0] No function
[1] Analog input 53
Par. 3-15 Reference resource 1 set to
[1] Analog input 53
Par. 7-00 Speed PID Feedback
Source set to [6] Analog input 53
Par. 3-15 Reference resource 1 set to
[1] Analog input 53
Par. 4-20 Torque Limit Factor Source
set to [2] Analog in 53
[0] No function
Par. 1-93 Thermistor Ressource set to
[1] Analog input 53
6-10 Terminal 53 Low
Voltage
6-11 Terminal 53 High
Voltage
Parameter311 Terminal 54,
Options[0] No OperationPar. 3-16 Reference
Table 5.98 Conversion of Parameter 311
Parameter 312 Terminal 54, min.
Range0 – 10.0 Volt-10.00 – Par. 6-21
Table 5.99 Conversion of Parameter 312
VLT 5000 seriesFC 302 series
scaling
VLT 5000 seriesFC 302 series
3-16 Reference
Analogue Input
Voltage
[1] ReferencePar. 3-16 Reference
[2] Torque limitPar. 4-20 Torque
[3] ThermistorPar. 1-93 Thermistor
[4] Relative
reference
[5] Max. torque
frequency
Resource 2
7-00 Speed PID
Feedback Source
4-20 Torque Limit
Factor Source
1-93 Thermistor
Resource
4-21 Speed Limit
Factor Source
resource 2 set to [0]
No function
resource 1 set to [2]
Analog input 53
Limit Factor Source
set to [6] Analog in
54
Ressource set to [2]
Analog input 54
Not supported
Par. 4-21 Speed
Limit Factor Source
set to [6] Analog in
54
6-20 Terminal 54 Low
Voltage
55
Parameter 313 Terminal 54, max.
Range0 – 10.0 VoltPar. 6-20 - 10.00 Volt
Table 5.100 Conversion of Parameter 313
MG34N202 - Rev. 2013-10-1523
VLT 5000 seriesFC 302 series
6-21 Terminal 54 High
scaling
Voltage
Parameter Mapping Lists
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
Parameter 314 Terminal 60,
Options[0] No Operation Par. 3-17 Reference resource 3 set
55
Comments The HW switch S202 for analogue input 54 must be
Table 5.101 Conversion of Parameter 314
Parameter 315 Terminal 60, min.
Range0.0 – 20.0 mA0.00 – Par. 6-23
Table 5.102 Conversion of Parameter 315
Parameter 316 Terminal 60, max.
Range0.0 – 20.0 mAPar. 6-22 - 20.00 mA
Table 5.103 Conversion of Parameter 316
Parameter 317 Time Out6-00 Live Zero Timeout Time
Range0 – 99 sec0 – 99 sec
Table 5.104 Conversion of Parameter 317
VLT 5000 seriesFC 302 series
3-17 Reference Resource 3
Analogue Input
current
[1] ReferencePar. 3-17 Reference resource 3 set
[2] Feedback
signal
[3] Torque limitPar. 3-17 Reference resource 3 set
[4] Relative
reference
set to current (ON).
VLT 5000 seriesFC 302 series
scaling
VLT 5000 seriesFC 302 series
scaling
VLT 5000 seriesFC 302 series
7-00 Speed PID Feedback Source
1-93 Thermistor Resource
4-20 Torque Limit Factor Source
to [0] No function
to [2] Analog input 54 Par. 7-00
Speed PID
Feedback Source set to [7]
Analog input 54
Par. 7-00 Speed PID Feedback
Source set to [7] Analog input 54
to [2] Analog input 54 Par. 4-20
Torque Limit
Factor Source set to [6] Analog in
54
Not supported
6-22 Terminal 54 Low
Current
6-23 Teminal 54 High
Current
Parameter 318 Function after time
Options[0] Off[0] Off
Table 5.105 Conversion of Parameter 318
Parameter 319 Terminal 42,
Parameter 321 Terminal 45,
Options[0] No functionPar. 5-32 = [0] No operation
VLT 5000 seriesFC 302 series
6-01 Live Zero Timeout
out
[1] Freeze output
frequency
[2] Stop[2] Stop
[3] Jogging[3] Jog
[4] Max Speed, p202[4] Max Speed
[5] Stop and trip[5] Stop and trip
VLT 5000 seriesFC 302 series
Output
Output
[1] Control ReadyPar. 5-32 = [1] Control Ready
[2] Ready signalPar. 5-32 = [2] Drive ready
[3] Ready - Remote
Control
[4] Enabled, no
warning
[5] Running
[6] Running, no
Warning
[7] Running within
range, no Warning
[8] Run at
reference, no
Warning
[9] AlarmPar. 5-32 = [9] Alarm
[10] Alarm or
Warning
[11] Torque limitPar. 5-32 = [11] At torque limit
[12] Out of current
range
[13] Above I lowPar. 5-32 = [13] Below current,
[14] Under I highPar. 5-32 = [14] Above current,
Function
[1] Freeze output
frequency
Digital = Par. 5-32 DO X30/7
(MCB 101)
Analogue values = Par. 6-50 AO
42
Pulse = Par. 5-66 DO X30/6
Digital = Par. 5-33 DO X30/7
(MCB 101)
Analogue values= Par. 6-60 AO
X30/8
Pulse = Par. 5-66 DO X30/6
Par. 5-32 = [5] VLT® running
Par. 5-32 = [6] Running /no
warning
Par. 5-32 = [7] Run in range/no
warning
Par. 5-32 = [8] Run on ref/no
warning
Par. 5-32 = [10] Alarm or
Warning
Par. 5-32 = [12] Out of current
range
1)
low
1)
high
Table 5.106 Conversion of Parameters 319 to 321
24MG34N202 - Rev. 2013-10-15
Parameter Mapping Lists
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
Parameter 319 Terminal 42,
Parameter 321 Terminal 45,
Options[15] Out of
Table 5.107 Conversion of Parameters 319 to 321
VLT 5000 seriesFC 302 series
Digital = Par. 5-32 DO X30/7
Output
Output
frequency range
[16] Over f lowPar. 5-32 = [16] Below speed
[17] Under f highPar. 5-32 = [17] Above speed
[18] Out of feedback
range
[19] Over feedback
low
[20] Under feedback
high
[21] Thermal
warning
[22] Ready, no
thermal warning
[23] Ready - remote
control - no thermal
warning
[24] Ready – mains
voltage within range
[25] ReversingPar. 5-32 = [25] Reverse
[26] Bus OKPar. 5-32 = [26] Bus OK
[27] Torque limit and
stop
(MCB 101)
Analogue values= Par. 6-50 AO
42
Pulse = Par. 5-66 DO X30/6
Digital = Par. 5-33 DO X30/7
(MCB 101)
Analogue values= Par. 6-60 AO
X30/8
Pulse = Par. 5-66 DO X30/6
Par. 5-32 = [15] Out of speed
range
1)
low
1)
high
Par. 5-32 = [18] Out of feedb.
Range
Par. 5-32 = [19] Below
feedback low
Par. 5-32 = [20] Above
feedback high
Par. 5-32 = [21] Thermal
warning
Par. 5-32 = [12] Ready,no
thermal W
Par. 5-32 = [23] Remote, ready,
no TW
Par. 5-32 = [24] Ready, Voltage
OK
Par. 5-32 = [27] Torque limit &
stop
Parameter 319 Terminal 42, Output Digital = Par. 5-32 DO
Parameter 321 Terminal 45, Output Digital = Par. 5-33 DO
Options[28] Brake, no brake
1)
1)
VLT 5000 seriesFC 302 series
X30/7 (MCB 101)
Analogue values= Par. 6-50
AO 42
Pulse = Par. 5-66 DO X30/6
X30/7 (MCB 101)
Analogue values= Par. 6-60
AO X30/8
Pulse = Par. 5-66 DO X30/6
Par. 5-32 = [28] Brake, no
warning
[29] Brake ready, no
fault
[30] Brake faultPar. 5-32 = [30] Brake fault
[31] Relay 123Par. 5-32 = [31] Relay 123
[32] Mechanical brake
control
[34] Extended
mechanical brake
control
[35] Safety InterlockNot supported
[36] 0 – 100 Hz ⇒ 0 – 20
mA
[37] 0 – 100 Hz ⇒ 4 – 20
mA
[38] 0 – 100 Hz ⇒ 0 –
32000 p
[39] 0 – f max ⇒ 0 – 20
mA
[40] 0 – f max ⇒ 4 – 20
mA
[41] 0 – f max ⇒ 0 –
32000 p
[42] Ref min – Ref max
⇒ 0 – 20 mA
brake warning
Par. 5-32 = [29] Brake
ready, no fault
(IGBT)
Par. 5-32 = [32] Mech
brake ctrl
Par. 5-32 = [32] Mech
brake ctrl
Not supported
Not supported
Not supported
Par. 6-50 = [109] Max Out
freq. 0 – 20 mA
Par. 6-50 = [130] Max Out
freq. 4 – 20 mA
Par. 5-66 = [109] Max Out
freq. 0 – 32000p Par. 568 =
32000
Par. 6-50 = [101] Reference
0 -20 mA
55
Table 5.108 Conversion of Parameters 319 to 321
MG34N202 - Rev. 2013-10-1525
Parameter Mapping Lists
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
Parameter 319 Terminal 42,
Parameter 321 Terminal 45,
Options[43] Ref min – Ref max
55
VLT 5000 seriesFC 302 series
Digital = Par. 5-32 DO X30/7
Output
Output
⇒ 4 – 20 mA
[44] Ref min – Ref max
⇒ 0 - 32000 p
[45] FB min – FB max
⇒ 0 – 20 mA
[46] FB min – FB max
⇒ 4 – 20 mA
[47] FB min – FB max
⇒ 0 - 32000 p
[48] 0 – I max ⇒ 0 – 20
mA
[49] 0 – I max ⇒ 4 – 20
mA
[50] 0 – I max ⇒ 0 –
32000 p
[51] 0 – T lim ⇒ 0 – 20
mA
[52] 0 – T lim ⇒ 4 – 20
mA
[53] 0 – T lim ⇒ 0 –
32000 p
[54] 0 – T nom ⇒ 0 –
20 mA
[55] 0 – T nom ⇒ 4 –
20 mA
[56] 0 – T nom ⇒ 0 –
32000 p
[57] 0 – P nom ⇒ 0 –
20 mA
[58] 0 – P nom ⇒ 4 –
20 mA
[59] 0 – P nom ⇒ 0 –
32000 p
(MCB 101)
Analogue values= Par. 6-50
AO 42
Pulse = Par. 5-66 DO X30/6
Digital = Par. 5-33 DO X30/7
(MCB 101)
Analogue values= Par. 6-60
AO X30/8
Pulse = Par. 5-66 DO X30/6
Par. 6-50 = [131] Reference
4 -20 mA
no TW
warning
[24] Ready – mains
voltage within range
Par. 5-40 = [24] Ready, Voltage
OK
[25] ReversingPar. 5-40 = [25] Reverse
[26] Bus OKPar. 5-40 = [26] Bus OK
[27] Torque limit and
stop
[28] Brake, no brake
warning
[29] Brake ready, no
fault
Par. 5-40 = [27] Torque limit &
stop
Par. 5-40 = [28] Brake, no
brake warning
Par. 5-40 = [29] Brake ready,
no fault
[30] Brake faultPar. 5-40 = [30] Brake fault
Parameter361 Encoder loss thresholdNot converted
Range0 – 600%
Table 5.127 Conversion of Parameter 361
VLT 5000 seriesFC 302 series
6-62 Terminal X30/8 Max.
max. scale
VLT 5000 seriesFC 302 series
Scale
Parameter 346 Encoder loss
Range[0] Off[0] Disable
Table 5.122 Conversion of Parameter 346
Parameter 357 Term. 42, Output
Range0 – 100%0 – 200%
Table 5.123 Conversion of Parameter 357
Parameter 358 Term. 42, Output
Range0 – 500%0 – 200%
VLT 5000 seriesFC 302 series
4-30 Motor Feedback Loss
function
[1] Freeze output
frequency
[3] Jog[3] Jog
[4] Max speed[5] Max speed
[5] Stop and trip[11] Stop and trip
[7] Select setup 4[10] Select setup 4
VLT 5000 seriesFC 302 series
min. scale
VLT 5000 seriesFC 302 series
max. scale
Function
[4] Freeze output
frequency
6-51 Terminal 42 Output
Min Scale
6-52 Terminal 42 Output
Max Scale
Table 5.124 Conversion of Parameter 358
Parameter 359 Term. 45, Output
Range0 – 100%0 – 200%
Table 5.125 Conversion of Parameter 359
28MG34N202 - Rev. 2013-10-15
VLT 5000 seriesFC 302 series
6-61 Terminal X30/8 Min.
min. scale
Scale
Parameter Mapping Lists
5.5
VLT® 5000 Parameter Group 4
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
Parameter 400 Brake function/
Options[0] Off[0] Off
Table 5.128 Conversion of Parameter 400
Parameter
OptionsPower unit dependable Power unit dependable
Table 5.129 Conversion of Parameter 401
Parameter 402 Brake power limit,
RangeDepends on unitDepends on unit
VLT 5000 seriesFC 302 series
2-10 Brake Function
over voltage cont.
[1] Resistor brakePar. 2-10 = *1* Resistor brake
[2] Over voltage
control
[3] Over voltage
control and stop
VLT 5000 seriesFC 302 series
401 Brake resistor, [Ω]
VLT 5000 seriesFC 302 series
[kW]
2-17 Over-voltage Control
Par. 2-17 = [0] Off
Par. 2-10 = [0] Off
Par. 2-17 = [2] Enabled
Par- 2-10 = [0] Off
Par. 2-17 = [1] Enabled (not at
stop)
30-81 Brake Resistor (ohm)
2-12 Brake Power Limit
(kW)
Parameter405 Reset14-20 Reset Mode
Options[0] Manual reset[0] Off
VLT 5000 seriesFC 302 series
[1] Automatic reset
x 1
[2] Automatic reset
x 2
[3] Automatic reset
x 3
[4] Automatic reset
x 4
[5] Automatic reset
x 5
[6] Automatic reset
x 6
[7] Automatic reset
x 7
[8] Automatic reset
x 8
[9] Automatic reset
x 9
[10] Automatic reset
x 10
[1] Automatic reset x
1
[2] Automatic reset x
2
[3] Automatic reset x
3
[4] Automatic reset x
4
[5] Automatic reset x
5
[6] Automatic reset x
6
[7] Automatic reset x
7
[8] Automatic reset x
8
[9] Automatic reset x
9
[10] Automatic reset x
10
55
Table 5.130 Conversion of Parameter 402
Parameter 403 Power monitoring 2-13 Brake Power Monitoring
Options[0] Off[0] Off
Table 5.131 Conversion of Parameter 403
Parameter404 Brake check2-15 Brake Check
Options[0] Off[0] Off
Table 5.132 Conversion of Parameter 404
VLT 5000 seriesFC 302 series
[1] Warning[1] Warning
[2] Trip[2] Trip
VLT 5000 seriesFC 302 series
[1] Warning[1] Warning
[2] Trip[2] Trip
Table 5.133 Conversion of Parameter 405
Parameter 406 Automatic restart
Range0 – 10 s0 – 600 s
Table 5.134 Conversion of Parameter 406
Parameter 407 Mains failure14-10 Mains Failure
Data range [0] No function[0] No function
Table 5.135 Conversion of Parameter 407
Parameter408 Quick dischargeNot converted
VLT 5000 seriesFC 302 series
14-21 Automatic Restart
time
5000 seriesFC 302 series
[1] Controlled ramp
down
[2] Controlled ramp
down and trip
[3] Coast[3] Coast
[4] Kinetic back-up[4] Kinetic back-up
[5] Controlled alarm
suppression
VLT 5000 seriesFC 302 series
Time
[1] Controlled ramp down
[2] Controlled ramp down
and trip
[5] Kinetic back-up, trip
Table 5.136 Conversion of Parameter 408
MG34N202 - Rev. 2013-10-1529
Parameter Mapping Lists
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
Parameter 409 Trip delay torque 14-25 Trip Delay at Torque
Range0 – 60 s (60=OFF)0 – 60 s (60=OFF)
Table 5.137 Conversion of Parameter 409
Parameter 410 Trip delay inverter 14-26 Trip Delay at Inverter
Range0 – 35 s0 – 35 s
55
Table 5.138 Conversion of Parameter 410
Parameter 411 Switching frequency 14-01 Switching Frequency
RangeUnsigned 16 (6)Unsigned 8 (5)
Table 5.139 Conversion of Parameter 411
Parameter 412 Output frequency dependent
VLT 5000 seriesFC 302 series
Limit
VLT 5000 seriesFC 302 series
Fault
VLT 5000 seriesFC 302 series
1.5 – 14 kHz
VLT 5000 seriesFC 302 series
switching frequency
< 2.3 ⇒ 2.0 kHz [2]
2.3 > 2.7 ⇒ 2.5 kHz [3]
2.8 > 3.2 ⇒ 3.0 kHz [4]
3.3 > 3.7 ⇒ 3.5 kHz [5]
3.8 > 4.5 ⇒ 4.0 kHz [6]
4.6 > 5.5 ⇒ 5.0 kHz [7]
5.6 > 6.5 ⇒ 6.0 kHz [8]
6.6 > 7.5 ⇒ 7.0 kHz [9]
7.6 > 9.0 ⇒ 8.0 kHz [10]
9.1 > ⇒ 10.0 kHz [11]
Not converted
Parameter416 Feedback Unit3-01 Reference/
Options
VLT 5000 seriesFC 302 series
feedback Unit
[0] None[0] None
[1] %[1] %
[2] PPM[5] PPM
[3] rpm[2] RPM
[4] bar[71] bar
[5] Cycle/minNot supported
[6] Pulse/s[12] Pulse/s
[7] Unit s/sNot supported
[8] Unit s/minNot supported
[9] Unit s/hNot supported
[10] °C[60] °C
[11] Pa[72] Pa
[12] l/s[20] l/s
[13] m3/s[23] m3/s
[14] l/min[21] l/min
[15] m3/min[24] m3/min
[16] l/h[22] l/h
Table 5.140 Conversion of Parameter 412
Parameter 413 Overmodulation
Options[0] Off[0] Off
Table 5.141 Conversion of Parameter 413
Parameter414 Minimum feedbackNot converted
Table 5.142 Conversion of Parameter 414
Parameter415 Maximum feedbackNot converted
Table 5.143 Conversion of Parameter 415
VLT 5000 seriesFC 302 series
14-03 Overmodulation
function
[1] On[1] On
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
function
[17] m3/h[25] m3/h
[18] kg/s[30] kg/s
[19] kg/min[31] kg/min
[20] kg/h[32] kg/h
[21] t/min[33] t/min
[22] t/h[34] t/h
[23] m[45] m
[24] Nm[4] Nm
[25] m/s[40] m/s
Table 5.144 Conversion of Parameter 416 part 1
30MG34N202 - Rev. 2013-10-15
Parameter Mapping Lists
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
Parameter416 Feedback Unit3-01 Reference/
VLT 5000 seriesFC 302 series
feedback Unit
[26] m/min[41] m/min
[27] °F[160] °F
[28] in wg[172] in wg
[29] gal/s[121] gal/s
[30] ft3/s[125] ft3/s
[31] gal/min[122] gal/min
[32] ft3/min[126] ft3/min
[33] gal/h[123] gal/h
[34] ft3/h[127] ft3/h
[35] lb/s[130] lb/s
[36] lb/min[131] lb/min
[37] lb/h[132] lb/h
Parameter 420 Speed PID D-gain
Data range 5.0 – 50.01.0 – 20.0
Table 5.149 Conversion of Parameter 420
Parameter 421 Speed PID low-pass
Data range 5.0 – 200.0 ms1.0 – 100.0
Table 5.150 Conversion of Parameter 421
Parameter422 U0 voltage at 0 Hz1-55 U0 voltage
Data range0.0 – par. 1030.0 – 1000.0 V
Table 5.151 Conversion of Parameter 422
Parameter423 U1 voltage1-55 U1 voltage
Data range0.0 – par. 1030.0 – 1000.0 V
Table 5.152 Conversion of Parameter 423
VLT 5000 seriesFC 302 series
7-05 Speed PID Diff. Gain
limit
VLT 5000 seriesFC 302 series
filter
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
Limit
7-06 Speed PID Lowpass
Filter Time
55
[38] lb ft[150] lb ft
[39] ft/s[140] ft/s
[40] ft/min[141] ft/min
Table 5.145 Conversion of Parameter 416 part2
Parameter 417 Speed PID propor-
Data range 0.000 – 0.1500.000 – 1.000
Table 5.146 Conversion of Parameter 417
Parameter 418 Speed PID Integral
Data range 2.0 – 999.92.0 – 20000.0
Table 5.147 Conversion of Parameter 418
Parameter 419 Speed PID Differen-
Data range 0.0 – 200.00.0 – 200.0
Table 5.148 Conversion of Parameter 419
VLT 5000 seriesFC 302 series
7-02 Speed PID propor-
tional gain
VLT 5000 seriesFC 302 series
Time
VLT 5000 seriesFC 302 series
tiation Time
tional gain
7-03 Speed PID proportional gain
7-04 Speed PID Differentiation Time
Parameter424 F1 frequency1-56 F1 frequency
Data range0.0 – par. 1040.0 – 1000.0 Hz
Table 5.153 Conversion of Parameter 424
Parameter425 U2 voltage1-55 U2 voltage
Data range0.0 – par. 1030.0 – 1000.0 V
Table 5.154 Conversion of Parameter 425
Parameter426 F2 frequency1-56 F2 frequency
Data range0.0 – par. 1040.0 – 1000.0 Hz
Table 5.155 Conversion of Parameter 426
Parameter427 U3 voltage1-55 U3 voltage
Data range0.0 – par. 1030.0 – 1000.0 V
Table 5.156 Conversion of Parameter 427
Parameter428 F3 frequency1-56 F3 frequency
Data range0.0 – par. 1040.0 – 1000.0 Hz
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
Table 5.157 Conversion of Parameter 428
MG34N202 - Rev. 2013-10-1531
Parameter Mapping Lists
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
Parameter429 U4 voltage1-55 U4 voltage
Data range0.0 – par. 1030.0 – 1000.0 V
Table 5.158 Conversion of Parameter 429
Parameter430 F4 frequency1-56 F4 frequency
Data range0.0 – par. 1040.0 – 1000.0 Hz
Table 5.159 Conversion of Parameter 430
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
55
Parameter431 U5 voltage1-55 U5 voltage
Data range0.0 – par. 1030.0 – 1000.0 V
Table 5.160 Conversion of Parameter 431
Parameter432 F5 frequency1-56 F5 frequency
Data range0.0 – par. 1040.0 – 1000.0 Hz
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
Parameter438 Process PID Anti
Options[0] Off[0] Off
Table 5.165 Conversion of Parameter 438
Parameter439 Process PID
Data rangeFmin – fmax0 – 6000 rpm
Table 5.166 Conversion of Parameter 439
Parameter440 Process PID
Data range0.00 – 10.000.00 – 10.00
Table 5.167 Conversion of Parameter 440
VLT 5000 seriesFC 302 series
7-31 Process PID
windup
[1] On[1] On
VLT 5000 seriesFC 302 series
start frequency
VLT 5000 seriesFC 302 series
proportional gain
Anti Windup
7-32 Process PID
Start Speed
7-33 Process PID
proportional gain
Table 5.161 Conversion of Parameter 432
Parameter433 Torque control,
Data range0 (Off) – 500%0 (Off) – 500%
Table 5.162 Conversion of Parameter 433
Parameter434 Torque control,
Data range0.002 – 2.000 sec0.002 – 2.000 sec
Table 5.163 Conversion of Parameter 434
Parameter437 Process PID
Options[0] Normal[0] Normal
VLT 5000 seriesFC 302 series
7-12 Torque PI
open loop proportional gain
VLT 5000 seriesFC 302 series
open loop integral
time
VLT 5000 seriesFC 302 series
Normal/Inverse
contr
[1] Inverse[1] Inverse
Integration Time
7-13 Torque PI
Integration Time
7-30 Process PID
Normal/ Inverse
Control
Parameter441 Process PID
Data range0.01 – 9999.990.01 – 10000.00
Table 5.168 Conversion of Parameter 441
Parameter442 Process PID
Data range0.00 – 10.000.00 – 10.00
Table 5.169 Conversion of Parameter 442
Parameter443 Process PID diff.
Data range5.0 – 50.00.00 – 10.00
Table 5.170 Conversion of Parameter 443
Parameter444 Process PID
VLT 5000 seriesFC 302 series
7-34 Process PID
integral time
VLT 5000 seriesFC 302 series
differentiation time
VLT 5000 seriesFC 302 series
gain limit
VLT 5000 seriesFC 302 series
lowpass filter time
integral time
7-35 Process PID
Differentiation Time
7-36 Process PID
Diff. Gain Limit
Not supported
Table 5.171 Conversion of Parameter 444
Table 5.164 Conversion of Parameter 437
32MG34N202 - Rev. 2013-10-15
Parameter Mapping Lists
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
Parameter445 Flying start1-73 Flying Start
Options[0] Off[0] Disable
Table 5.172 Conversion of Parameter 445
Parameter446 Switching
Options[0] 60 AVM[0] 60 AVM
Table 5.173 Conversion of Parameter 446
Parameter447 Torque
Table 5.174 Conversion of Parameter 447
VLT 5000 seriesFC 302 series
[1] On[1] Enable
VLT 5000 seriesFC 302 series
14-00 Switching
pattern
[1] SFAVM[1] SFAVM
VLT 5000 seriesFC 302 series
compensation
Pattern
Not supported
Parameter455 Frequency
Table 5.180 Conversion of Parameter 455
Parameter457 Phase loss
Options[0] Trip[0] Trip
Table 5.181 Conversion of Parameter 457
Parameter483 Dynamic DC
Table 5.182 Conversion of Parameter 483
VLT 5000 seriesFC 302 series
Not supported
range monitor
VLT 5000 seriesFC 302 series
14-12 Function at
functions
[1] Warning[1] Warning
VLT 5000 seriesFC 302 series
link compensation
Mains Imbalance
Not supported
55
Parameter448 Gear ratioNot supported
Table 5.175 Conversion of Parameter 448
Parameter449 Friction lossNot supported
Table 5.176 Conversion of Parameter 449
Parameter450 Mains voltage
Range180 – 690 V100 – 800 V
Table 5.177 Conversion of Parameter 450
Parameter453 Gear ratio,
Range0.01 – 100.000.0001 – 32.0000
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
14-11 Mains Voltage
at mains fault
VLT 5000 seriesFC 302 series
speed close loop
at Mains Fault
7-07 Speed PID
Feedback Gear Ratio
Table 5.178 Conversion of Parameter 453
Parameter454 Dead time
Table 5.179 Conversion of Parameter 454
VLT 5000 seriesFC 302 series
compensation
Not supported
MG34N202 - Rev. 2013-10-1533
Parameter Mapping Lists
5.6
VLT® 5000 Parameter Group 5
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
Parameter500 Address8-31 Address
Range0 - 1260 - 126
Table 5.183 Conversion of Parameter 500
Parameter501 Baud rate8-32 FC Port Baud Rate
Options[0] 300Not supported
Parameter 780 Dead time compensationNot supported
Options[0] Off
Table 5.266 Conversion of Parameter 780
Parameter781 Program IDNot supported
Options0 – 65000
Table 5.267 Conversion of Parameter 781
Parameter 795 - 799 User defined
OptionsUser definedUser defined
Table 5.268 Conversion of Parameters 795 to 799
VLT 5000 seriesFC 302 series
[1] On
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
19-95 -19-99 User
(read only)
defined (read only)
38MG34N202 - Rev. 2013-10-15
Parameter Mapping Lists
5.9
VLT® 5000 Parameter Group 8
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
Parameter800 PROFIBUS DPNot converted
Table 5.269 Conversion of Parameter 800
Parameter801 Baud rate selectionNot converted
Table 5.270 Conversion of Parameter 801
Parameter802 Minimum station delayNot converted
Table 5.271 Conversion of Parameter 802
Parameter 803 Time out after bus
Range1 – 990.1 – 18000.0
Table 5.272 Conversion of Parameter 803
Parameter 804 Response after bus
Range[0] Off[0] Off
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
8-03 Control Word Timeout
error
VLT 5000 seriesFC 302 series
time out
[1] Freeze output
frequency
[2] Stop[2] Stop
[3] Jogging[3] Jogging
[4] Max speed[4] Max speed
[5] Stop and trip[5] Stop and trip
[6] No com. option
control
[7] Select set up 4[10] Select set up 4
Reference
[219] Catch up/slow Down
Value
[207] Ramp 1 Ramp up
Time
[208] Ramp 1 Ramp Down
Time
[209] Ramp 2 Ramp up
Time
[210] Ramp 2 Ramp down
Time
[211] Jog Ramp Time[380] Jog Ramp Time
[212] Quick Stop Ramp
Time
[201] Motor Low Limit [Hz] [412] Motor Speed Low
[202] Motor High Limit [Hz] [414] Motor Speed High
[221] Torque Limit Motor
Mode
[222] Torque Limit
Generator Mode
[509] Bus Jog 1 Speed[890] Bus Jog 1 Speed
[510] Bus Jog 2 Speed[891] Bus Jog 2 Speed
VLT® 5000 supports more write signals. If a notsupported signal is written then the corresponding
signal is set to [0] None.
[312] Catch up/slow
Down Value
[341] Ramp 1 Ramp up
Time
[342] Ramp 1 Ramp
Down Time
[351] Ramp 2 Ramp up
Time
[352] Ramp 2 Ramp
down Time
[381] Quick Stop Ramp
Time
Limit [Hz]
Limit [Hz]
[416] Torque Limit
Motor Mode
[417] Torque Limit
Generator Mode
Table 5.286 Conversion of Parameter 910
Parameter911 PPO type for FMS readNot converted
Table 5.287 Conversion of Parameter 911
Parameter913 Broadcast indexNot converted
Table 5.288 Conversion of Parameter 913
40MG34N202 - Rev. 2013-10-15
VLT 5000 seriesFC 302 series
VLT 5000 seriesFC 302 series
Parameter Mapping Lists
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
[538] Alarm word[1472] VLT Alarm Word
[540] Warning word[1473] VLT Warning Word
[541] Ext. status word[1474] VLT Ext. status
Word
[600] Operating hours[1500] Operating hours
[601] Running hours[1501] Running hours
[602] kWh Counter[1502] kWh Counter
[539] Control word[1600] Control word
[516] Reference [Unit][1601] Reference [Unit]
[515] Reference %[1602] Reference %
[534] Status word[1603] Status word
[522] Power [kW][1610] Power [kW]
[523] Power [HP][1611] Power [HP]
[524] Motor voltage[1612] Motor voltage
[518] Motor frequency[1613] Motor frequency
[520] Motor current[1614] Motor current
[557] Motor RPM[1617] Motor speed
[526] Motor thermal[1618] Motor thermal
[521] Torque[1622] Torque %
[525] DC link voltage[1630] DC link voltage
[536] Brake energy/s[1632] Brake energy/s
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
Parameter 971 Save data values 9-71 Profibus Save Data Values
OptionsUnsigned 8 (5)Unsigned 8 (5)
Table 5.302 Conversion of Parameter 971
Parameter 980, 981, 982, 990 Modified
55
Table 5.303 Conversion of Parameter 980-990
VLT 5000 seriesFC 302 series
[0] Not active[0] Off
[1] Save active setup [1] Store all setups
[2] Save edit setup[1] Store all setups
[3] Save all setups[1] Store all setups
VLT 5000 seriesFC 302 series
Not converted
parameters
42MG34N202 - Rev. 2013-10-15
Troubleshooting
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
6 Troubleshooting
6.1 Step-by-step Troubleshooting
After copying the station address from the VLT® 5000 to
the VLT® AutomationDrive FC 302, power must be cycled
to the FC 302. The master/PLC should now recognise FC
302 as a VLT® 5000. The NS LED on the MCA 114 option
should now be solid green indicating that communication
between master and slave is established.
If the NS LED flashes, the master/PLC has not recognized
the FC 302:
Check if station address is the same in the FC 302
•
as the replaced VLT® 5000.
Check 9-63 Actual Baud Rate. If the frequency
•
converter has a connection to the master, this
parameter displays the detected baudrate. If no
master has been detected, the parameter
displays: “No baud rate found”.
Check 9-53 Profibus Warning Word.
•
Bit
Warn. Word
[Hex]
00001Connection with DP-master is not OK
10002Unused
20004
30008Clear data command received
40010Actual value is not updated
50020Baudrate search
60040PROFIBUS ASIC is not transmitting
70080Initialising of PROFIBUS is not ok
80100Drive is tripped
90200Internal CAN error
100400Wrong configuration data from PLC
110800Wrong ID sent by PLC
121000Internal error occurred
132000Not configured
144000Timeout active
158000Warning 34 active
FDL (Field-bus Data link Layer) is not
OK
Description
66
Table 6.1 Warning Word
Check 1.3 Constraints for more information on
•
limitations.
MG34N202 - Rev. 2013-10-1543
Index
VLT® AutomationDrive FC 302 PROFIBUS Converter Operating Instructions