Danfoss MCA 105 Operating guide

MAKING MODERN LIVING POSSIBLE
Installation Guide
VLT® CANopen MCA 105
VLT® AutomationDrive FC 301/302
Contents Installation Guide
Contents
1 Introduction
1.1 Purpose of the Manual
1.2 Additional Resources
1.3 Product Overview
1.4 Approvals and Certications
1.5 Disposal
1.6 Symbols, Abbreviations, and Conventions
2 Safety
2.1 Safety Symbols
2.2 Qualied Personnel
2.3 Safety Precautions
3 Installation
3.1 Safety Instructions
3.2 EMC-compliant Installation
3.3 Grounding
3.4 Cable Routing
2
2
2
2
2
3
3
4
4
4
4
6
6
6
6
6
3.5 Mounting
3.6 Setting Address Switches
3.7 Electrical Installation
3.8 Reassembling Cover
3.9 Applying Power
3.10 Checking Network Cabling
4 Troubleshooting
4.1 Warnings and Alarms
4.2 Troubleshooting
4.2.1 LED Status 11
4.2.2 No Communication with the Frequency Converter 11
Index
7
8
8
10
10
10
11
11
11
12
MG33J402 Danfoss A/S © 05/2015 All rights reserved. 1
Introduction
VLT® CANopen MCA 105
11
1 Introduction
1.1 Purpose of the Manual
This installation guide provides information for quick instal-
lation of a VLT® CANopen MCA 105 interface in the VLT frequency converter. The installation guide is intended for use by qualied
personnel. Users are assumed to be familiar with the VLT frequency converter, with CANopen technology, and with the PC or PLC that is used as a master in the system. Read the instructions before installation and ensure that instructions for safe installation are observed.
VLT® is a registered trademark.
1.2 Additional Resources
Resources available for the frequency converters and optional equipment:
The VLT® AutomationDrive FC 301/FC 302
Operating Instructions provide the necessary information for getting the frequency converter up and running.
®
®
Product Overview
1.3
1.3.1 Intended Use
This installation guide relates to the CANopen interface. Ordering numbers:
130B1103 (uncoated)
130B1205 (coated)
CANopen is a low-level network that standardises only communications between industrial devices (sensors, limit switches, motor controls) and high-level devices (controllers). Congure CANopen systems to operate in a master-slave or in a distributed control architecture using peer-to-peer communication. The CANopen interface is designed to communicate with any master abiding by the CANopen standard.
VLT® CANopen MCA 105 is intended for use with VLT AutomationDrive FC 301/FC 302.
®
The VLT® AutomationDrive FC 301/FC 302 Design
Guide provides detailed information about capabilities and functionality to design motor control systems.
The VLT® AutomationDrive FC 301/FC 302
Programming Guide provides greater detail on working with parameters and many application examples.
The VLT® CANopen MCA 105 Installation Guide
provides information about installing the CANopen and troubleshooting.
The VLT® CANopen MCA 105 Programming Guide
provides information about conguring the system, controlling the frequency converter, parameter access, programming, troubleshooting, as well as some typical application examples.
Supplementary publications and manuals are available from Danfoss. See vlt-drives.danfoss.com/Support/Technical- Documentation/ for listings.
1.3.2 Items Supplied
When the eldbus option is not factory mounted, the following items are supplied:
Fieldbus option and connector.
LCP cradle.
Front covers (in various sizes).
Stickers.
Accessories bag (including EMC bracket).
Installation guide.
Approvals and Certications
1.4
More approvals and certications are available. For more information, contact a Danfoss local partner.
2 Danfoss A/S © 05/2015 All rights reserved. MG33J402
Introduction Installation Guide
1.5 Disposal
Do not dispose of equipment containing
electrical components together with
domestic waste.
Collect it separately in accordance with
local and currently valid legislation.
1.6 Symbols, Abbreviations, and Conventions
Abbreviation Denition
CAN Controller area network
CiA CAN in automation
COB Communication object
COB-ID Communication object identier
CTW Control word
EDS Electronic data sheet
EMC Electromagnetic compatibility
EMCY Emergency message
I/O Input/output
LCP Local control panel
LED Light emitting diode
LSB Least signicant bit
MAV Main actual value (actual output)
MRV Main reference value
MSB Most signicant bit
NMT Network management
N/A Not applicable
OD Object directory
PCD Process data
PDO Process data object
PLC Programmable logic controller
PNU Parameter number
RPDO Receive process data object
RPM Revolutions per minute; unit for the speed of a
revolving motor
RTR Remote transmission request frame
RX Receive data
STW Status word
SDO Service data object
SYNC Object for synchronisation of process data
TPDO Transmit process data object
TX Transmit data
Conventions
Numbered lists indicate procedures. Bullet lists indicate other information and descriptions of illustrations. Italicised text indicates:
Cross-reference.
Link.
Parameter name.
Footnote.
Parameter group.
Parameter option.
Alarms/warnings.
1 1
Table 1.1 Symbols and Abbreviations
MG33J402 Danfoss A/S © 05/2015 All rights reserved. 3
Safety
VLT® CANopen MCA 105
2 Safety
22
2.1 Safety Symbols
WARNING
The following symbols are used in this manual:
WARNING
Indicates a potentially hazardous situation that could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could result in minor or moderate injury. It can also be used to alert against unsafe practices.
NOTICE
Indicates important information, including situations that can result in damage to equipment or property.
2.2 Qualied Personnel
Correct and reliable transport, storage, installation, operation, and maintenance are required for the trouble­free and safe operation of the frequency converter. Only qualied personnel are allowed to install and operate this equipment.
Qualied personnel are dened as trained sta, who are authorised to install, commission, and maintain equipment, systems, and circuits in accordance with pertinent laws and regulations. Additionally, the qualied personnel must be familiar with the instructions and safety measures described in these operating instructions.
Safety Precautions
2.3
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation, start-up, and maintenance by qualied personnel can result in death or serious injury.
Only qualied personnel must perform instal-
lation, start-up, and maintenance.
UNINTENDED START
When the frequency converter is connected to AC mains, DC supply, or load sharing, the motor may start at any time. Unintended start during programming, service, or repair work can result in death, serious injury, or property damage. The motor can start with an external switch, a eldbus command, an input reference signal from the LCP or LOP, via remote operation using MCT 10 Set-up Software, or after a cleared fault condition. To prevent unintended motor start:
Disconnect the frequency converter from the
mains.
Press [O/Reset] on the LCP before
programming parameters.
Completely wire and assemble the frequency
converter, motor, and any driven equipment before connecting the frequency converter to AC mains, DC supply, or load sharing.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors that can remain charged even when the frequency converter is not powered. Failure to wait the specied time after power has been removed before performing service or repair work, can result in death or serious injury.
Stop the motor.
Disconnect the AC mains and remote DC-link
supplies, including battery back-ups, UPS, and DC-link connections to other frequency converters.
Disconnect or lock the PM motor.
Wait for the capacitors to discharge fully before
performing any service or repair work. The duration of waiting time is specied in the relevant frequency converter operating instructions, Chapter 2 Safety.
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the frequency converter properly can result in death or serious injury.
Ensure the correct grounding of the equipment
by a certied electrical installer.
4 Danfoss A/S © 05/2015 All rights reserved. MG33J402
Safety Installation Guide
WARNING
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment can result in death or serious injury.
Ensure that only trained and qualied personnel
perform installation, start-up, and maintenance.
Ensure that electrical work conforms to national
and local electrical codes.
Follow the procedures in this manual.
CAUTION
INTERNAL FAILURE HAZARD
An internal failure in the frequency converter can result in serious injury, when the frequency converter is not properly closed.
Ensure that all safety covers are in place and
securely fastened before applying power.
2 2
MG33J402 Danfoss A/S © 05/2015 All rights reserved. 5
130BD866.10
≥ 200mm
2
1
Installation
3 Installation
VLT® CANopen MCA 105
3.1 Safety Instructions
33
See chapter 2 Safety for general safety instructions.
3.2 EMC-compliant Installation
To obtain an EMC-compliant installation, follow the instructions provided in the relevant frequency converter operating instructions and design guide. Refer to the eldbus master manual from the PLC supplier for further installation guidelines.
3.3 Grounding
Ensure that all stations connected to the eldbus
network are connected to the same ground potential. When there are long distances between the stations in a eldbus network, connect the individual station to the same ground potential. Install equalising cables between the system components.
Establish a grounding connection with low HF
impedance, for example by mounting the frequency converter on a conductive back plate.
Keep the ground wire connections as short as
possible.
Establish electrical contact between the cable
screen and the frequency converter enclosure by using metal cable glands or by using the clamps provided on the equipment.
Use high-strand wire to reduce electrical
interference.
Cable Routing
3.4
NOTICE
EMC INTERFERENCE
Use screened cables for motor and control wiring, and separate cables for eldbus communication, motor wiring, and brake resistor. Failure to isolate eldbus communication from motor and brake resistor cables can result in unintended behaviour or reduced performance. Minimum 200 mm (7.9 in) clearance between power, motor, and control cables is required. For power sizes above 315 kW, it is recommended to increase the minimum distance to 500 mm (20 in).
NOTICE
When the eldbus cable crosses a motor cable or a brake resistor cable, ensure that the cables cross at an angle of 90°.
1 Fieldbus cable
2 90° crossing
6 Danfoss A/S © 05/2015 All rights reserved. MG33J402
Illustration 3.1 Cable Routing
130BD876.10
1
2
4
3
130BD862.10
130BD863.10
Installation Installation Guide
3.5 Mounting
1. Check whether the eldbus option is already mounted in the frequency converter. If already mounted, go to step 6. If not mounted, go to step 2.
2. Remove the LCP or blind cover from the frequency converter.
3. Use a screwdriver to remove the front cover and the LCP cradle.
4. Mount the eldbus option. Mount the option with the connector facing up for top cable entry (see Illustration 3.3), or with the connector facing down for bottom cable entry (see Illustration 3.4). If an MCB option is installed, only top cable entry is possible.
5. Remove the knock-out plate from the new LCP cradle.
6. Mount the new LCP cradle.
3 3
1 LCP
2 LCP cradle
3 Fieldbus option
4 Connector
Illustration 3.2 Exploded View
Illustration 3.3 Top Cable Entry: Option Mounted with
Connector Facing Up
MG33J402 Danfoss A/S © 05/2015 All rights reserved. 7
Illustration 3.4 Bottom Cable Entry: Option Mounted with
Connector Facing Down
130BD877.10
1
2
Installation
VLT® CANopen MCA 105
3.6 Setting Address Switches
NOTICE
Switch o the power supply before changing the address switches. The address change comes into eect at the
33
next power-up.
The address switches enable setting of baudrate and node ID:
Switches 8 and 7 arefor setting the baudrate for
either: 125, 250, or 500 Kbps.
Switches 6–1 are for setting the node address in
the range 1–62.
3.7.2 Wiring Procedures
Wiring procedure for enclosure sizes A1–A3
1. Mount the eldbus connector on the eldbus option (CAN_L, Drain, CAN_H). For top cable entry, mount the supplied EMC bracket on top of the frequency converter with 2 screws.
2. Prepare the eldbus cable by stripping a section of the cable insulation, so that the cable screen contacts the EMC bracket. Keep the unshielded wire as short as possible. For cable specications, refer to chapter 3.7.1 Cable Specications.
3. Connect the eldbus cable wires to the terminals according to the colour code of the wires, see
Switch Baudrate
8 7
On On Parameter 10-01 Bau
d Rate Select
On O 500 kbps
On On 250 kbps
On O 125 kbps
Table 3.1 Switches 8 and 7
Illustration 3.6.
4. To establish mechanical xation and electrical contact between cable screen and ground, position the stripped cable between the spring loaded metal clamps.
Switch Node ID
6 5 4 3 2 1
On On On On On On Parameter
10-02 MAC
ID
On On On On On O 62
O O O O O On 1
Table 3.2 Switches 6–1
When both switch 8 and 7are set to ON, select baudrates via parameter 10-01 Baud Rate Select: 10, 20, 50, 100, 125, 250, or 500 kbps.
When switches 6–1 are set to ON, select node ID via parameter 10-02 MAC ID in the range: 1–127
Electrical Installation
3.7
3.7.1 Cable Specications
Baudrate
[kbps]
500 100 <60 0.34–0.6
250 250
125 500
50 1000
10 5000
Maximum
cable
length [m]
Resistance
[m/m]
<40 0.5–0.6
<26 0.75–0.820 2500
Cable cross-
section
[mm2]
Termination
resistor []
120
1 Cable screen
2 EMC bracket (used for top cable entry only)
Illustration 3.5 Wiring for Enclosure Sizes A1–A3
Table 3.3 Cable Specications
8 Danfoss A/S © 05/2015 All rights reserved. MG33J402
130BD864.10
Installation Installation Guide
Pin no. Terminal Colour Name
1 Not used
2 CAN_L Blue CAN LOW
3 Drain (bare) Screen
4 CAN_H White CAN HIGH
5 Not used
Wiring procedure for enclosure sizes A4–A5, B1–B4, and C1–C4
1. Push the cable through cable glands.
2. Mount the eldbus connector on the eldbus option ( CAN_L, Drain, CAN_H).
3. Prepare the eldbus cable by stripping a section of the cable insulation. Keep the unshielded wire as short as possible. For cable specications, refer to chapter 3.7.1 Cable Specications.
4. Connect the eldbus cable wires to the terminals according to the colour code of the wires, see Illustration 3.6.
5. Fix the cable screen to the metal base plate using cable clamp or cable tie, see Illustration 3.8.
6. Tighten cable glands securely.
3 3
Illustration 3.6 Fieldbus Cable Terminal Connections
CANopen termination
Install the termination resistors at each end of the bus line. Mount the resistor between terminal 2 (CAN_L) and terminal 4 (CAN_H). The resistors have the following specication:
121 Ω
1% Metal
1/4 W
Illustration 3.7 Termination Resistor Mounted
lm
Illustration 3.8 Wiring for Enclosure Sizes A4–A5, B1–B4, and
C1–C4
MG33J402 Danfoss A/S © 05/2015 All rights reserved. 9
130BC527.10
Installation
VLT® CANopen MCA 105
Wiring procedure for enclosure sizes D, E, and F
1. Mount the eldbus connector on the eldbus option (CAN_L, Drain, CAN_H).
2. Prepare the eldbus cable by stripping a section of the cable insulation. Keep unshielded wire as
33
short as possible. For cable specications, refer to chapter 3.7.1 Cable Specications.
3. Connect the eldbus cable wires to the terminals according to the colour code of the wires, see Illustration 3.6.
4. Fix the cable screen to the metal base plate using cable clamp or cable tie, see Illustration 3.9.
5. Tie down the cable and route it with other control wires inside the unit, see Illustration 3.9.
Reassembling Cover
3.8
1. Mount the new front cover and the LCP.
2. Attach the sticker with the correct product name to the front cover.
3.9 Applying Power
Follow the instructions in the frequency converter operating instructions to commission the frequency converter. The frequency converter automatically detects the CANopen interface. A new parameter group (Group 10) appears.
3.10 Checking Network Cabling
1. If the address has not been set via the address switches, go to parameter 10-02 MAC ID to set the address.
2. Connect to a running CANopen master.
3. Check that network cabling is correct or not.
Illustration 3.9 Wiring for Enclosure Sizes D, E, and F
10 Danfoss A/S © 05/2015 All rights reserved. MG33J402
Troubleshooting Installation Guide
4 Troubleshooting
4.1 Warnings and Alarms
NOTICE
Refer to the relevant operating instructions for an overview of warning and alarm types and for the full list of warnings and alarms.
Alarm word, warning word, and CANopen warning word are shown on the frequency converter display in hex format. When there is more than 1 warning or alarm, the sum of all warnings or alarms is shown. Alarm word, warning word, and CANopen warning word can also be displayed using the serial bus in:
Parameter 16-90 Alarm Word.
Parameter 16-91 Alarm Word 2.
Parameter 16-92 Warning Word.
Parameter 16-93 Warning Word 2.
4.2 Troubleshooting
4.2.1 LED Status
The 2 bi-colour LEDs on the CANopen card indicate the status of CANopen communication:
The lower LED (NS) indicates the net status.
The upper LED (MS) indicates the module status.
Illustration 4.1 LED Panel VLT® CANopen MCA 105
State Red LED Description
No error O No error.
Warning limit
reached
Error control
event
Sync error Triple ash Sync message has not been
Bus o On Device in bus o-state.
Table 4.1 LED: Module Status (MS)
State Red LED Description
Stopped Single ash Device in stopped state.
Pre-operational Triple ash Device in pre-operational state.
Operational On Device in operational state.
Table 4.2 LED: Network Status (NS)
Single ash CAN error counter has reached/
exceeded warning level.
Double ash Node guard event has occurred.
received within the congured
timeout (object 0x1006).
4.2.2 No Communication with the Frequency Converter
When there is no communication with the frequency converter, proceed with the following checks:
1. Check that cabling is correct. Check that the cables are connected to the correct terminals as shown in Illustration 3.6.
2. Check that the bus connection is terminated at both ends. If not, terminate the bus connection with termination resistors at the initial and
3. Check that each node connected to the CANopen network has a unique node ID (address). If 2 devices have the same node ID, it leads to malfunction in the network.
4. Communication drops out after some time. Check the installation for correct routing of the CANopen cables. Check if the screen of the motor cable is mounted correctly.
5. Communication is unstable. Check
parameter 10-05 Readout Transmit Error Counter and parameter 10-06 Readout Receive Error Counter. These 2 parameters have to be close to 0
most of the time. If they show higher values, check the CANopen cable for interference, wrong termination, and so on.
nal nodes.
4 4
MG33J402 Danfoss A/S © 05/2015 All rights reserved. 11
Index
VLT® CANopen MCA 105
Index
A
Abbreviations........................................................................................... 3
Additional resources.............................................................................. 2
Address switch.................................................................................. 8, 10
Alarm......................................................................................................... 11
Alarm word............................................................................................. 11
Applying power.................................................................................... 10
Approvals................................................................................................... 2
C
Cable specications............................................................................... 8
Cable terminal connections................................................................ 9
CANopen termination........................................................................... 9
Certications............................................................................................. 2
Conventions.............................................................................................. 3
N
Network cabling.................................................................................... 10
P
Power, applying..................................................................................... 10
Q
Qualied personnel................................................................................ 4
S
Safety........................................................................................................... 5
Screened cable......................................................................................... 6
Symbols...................................................................................................... 3
U
Unintended start..................................................................................... 4
D
Discharge time......................................................................................... 4
E
Electrical interference............................................................................ 6
EMC interference..................................................................................... 6
EMC-compliant installation................................................................. 6
Exploded view.......................................................................................... 7
G
Grounding................................................................................................. 6
H
High voltage............................................................................................. 4
I
Intended use............................................................................................. 2
Items supplied.......................................................................................... 2
L
Leakage current....................................................................................... 4
LED panel................................................................................................. 11
LED status................................................................................................ 11
Load sharing............................................................................................. 4
W
Warning.................................................................................................... 11
Warning word........................................................................................ 11
Wiring procedure.................................................................................... 8
M
Motor wiring............................................................................................. 6
Mounting................................................................................................... 7
12 Danfoss A/S © 05/2015 All rights reserved. MG33J402
Index Installation Guide
MG33J402 Danfoss A/S © 05/2015 All rights reserved. 13
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss A/S Ulsnaes 1 DK-6300 Graasten vlt-drives.danfoss.com
130R0067 MG33J402 05/2015
*MG33J402*
Loading...