Danfoss MCA 104 Operating guide

MAKING MODERN LIVING POSSIBLE
Installation Guide
VLT® DeviceNet MCA 104
VLT® Frequency Converter Series FC 102 • FC 202 • FC 301 • FC 302
Contents Installation Guide
Contents
1 Introduction
1.1 Purpose of the Manual
1.2 Additional Resources
1.3 Product Overview
1.4 Approvals and Certications
1.5 Disposal
1.6 Symbols, Abbreviations and Conventions
2 Safety
2.1 Safety Symbols
2.2 Qualied Personnel
2.3 Safety Precautions
3 Installation
3.1 Safety Instructions
3.2 EMC-compliant Installation
3.3 Grounding
3.4 Cable Routing
2 2 2 2 2 2 3
4 4 4 4
6 6 6 6 6
3.5 Mounting
3.6 Setting Address Switches
3.7 Electrical Installation
3.8 Reassembling Cover
3.9 Applying Power
3.10 Checking Network Cabling
4 Troubleshooting
4.1 Warnings and Alarms
4.2 Troubleshooting
4.2.1 LED Status 12
4.2.2 No Communication with the Frequency Converter 13
Index
7 8
8 11 11 11
12 12 12
14
MG33D502 Danfoss A/S © Rev. 03/2015 All rights reserved. 1
Introduction
VLT® DeviceNet MCA 104
1
1 Introduction
1.1 Purpose of the Manual
This installation guide provides information for quick instal­lation of a VLT® DeviceNet MCA 104 interface in the VLT
frequency converter. The installation guide is intended for use by qualied
personnel. Users are assumed to be familiar with the VLT frequency converter, with DeviceNet technology, and with the PC or PLC that is used as a master in the system. Read the instructions before installation and ensure that instructions for safe installation are observed.
VLT® is a registered trademark.
1.2 Additional Resources
Resources available for the frequency converters and optional equipment:
The VLT® Operating Instructions provide the
necessary information for getting the frequency converter up and running.
®
The VLT
information about capabilities and functionality to design motor control systems.
The VLT
detail on working with parameters and many application examples.
The VLT® DeviceNet MCA 104 Installation Guide
provides information about installing the DeviceNet and troubleshooting.
The VLT® DeviceNet MCA 104 Programming Guide
provides information about conguring the system, controlling the frequency converter, parameter access, programming, troubleshooting, as well as some typical application examples.
Supplementary publications and manuals are available from Danfoss. See www.danfoss.com/BusinessAreas/DrivesSo-
lutions/Documentations/VLT+Technical+Documentation.htm
for listings.
1.3
Product Overview
Design Guide provides detailed
®
Programming Guide provides greater
®
®
DeviceNet is a low-level network that standardises communications between industrial devices (sensors, limit switches, motor controls) and high-level devices (controllers). DeviceNet systems can be congured to operate in a master-follower or a distributed control architecture using peer-to-peer communication. The DeviceNet interface is designed to communicate with any master abiding by the DeviceNet standard.
VLT® DeviceNet MCA 104 is intended for use with:
VLT® HVAC Drive FC 102
VLT® AQUA Drive FC 202
VLT® AutomationDrive FC 301
VLT® AutomationDrive FC 302
Items Supplied
1.3.2
When the eldbus option is not factory mounted, the following items are supplied:
Fieldbus option and connector
LCP cradle
Front covers (in various sizes)
Stickers
Accessories bag (including EMC bracket)
Installation Guide
1.4
Approvals and Certications
More approvals and certications are available. For more information, contact a Danfoss local partner.
1.5
Disposal
1.3.1 Intended Use
Do not dispose of equipment containing
This installation guide relates to the DeviceNet interface. Ordering number:
130B1102 (non coated version)
130B1202 (conformal coated version)
2 Danfoss A/S © Rev. 03/2015 All rights reserved. MG33D502
electrical components together with domestic waste. Collect it separately in accordance with local and currently valid legislation.
Introduction
Installation Guide
1.6 Symbols, Abbreviations and Conventions
Abbreviation Denition
ACK Acknowledge BOC Bus o counter BOOL Boolean expression CAN Controller area network CSMA/CA Carrier sense multiple access/collision avoidance COS Change of state CTW Control word EDS Electronic data sheet EMC Electromagnetic compatibility ETR Electronic thermal relay FIFO First In rst out HF High frequency HPFB High performance eld bus I/O Input/output ISO International standards organization LCD Liquid crystal display LED Light emitting diode LSB Least signicant bit MAC ID Media access control identier MAV Main actual value MRV Main reference value MSB Most signicant bit N/A Not applicable ODVA Open deviceNet vendor association OSI Open systems interconnection PC Personal computer PCD Process data PIW Peripheral input word PLC Programmable logic control PNU Parameter number PPO Parameter-process data object QW Peripheral output word SINT Signed integer STW Status word VSD Variable speed drive UDINT Unsigned double integer UNIT Unsigned integer USINT Unsigned short integer
1
1
Table 1.1 Symbols and Abbreviations
Conventions
Numbered lists indicate procedures. Bullet lists indicate other information and description of illustrations. Italicised text indicates:
Cross reference
Link
Parameter name
MG33D502 Danfoss A/S © Rev. 03/2015 All rights reserved. 3
2
Safety
VLT® DeviceNet MCA 104
2 Safety
2.1 Safety Symbols
The following symbols are used in this manual:
WARNING
Indicates a potentially hazardous situation that could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could result in minor or moderate injury. It can also be used to alert against unsafe practices.
NOTICE
Indicates important information, including situations that can result in damage to equipment or property.
2.2 Qualied Personnel
Correct and reliable transport, storage, installation, operation, and maintenance are required for the trouble­free and safe operation of the frequency converter. Only qualied personnel are allowed to install or operate this equipment.
Qualied personnel are dened as trained sta, who are authorised to install, commission, and maintain equipment, systems, and circuits in accordance with pertinent laws and regulations. Additionally, the qualied personnel must be familiar with the instructions and safety measures described in these operating instructions.
2.3
Safety Precautions
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation, start-up, and maintenance by qualied personnel can result in death or serious injury.
Installation, start-up, and maintenance must be
performed by qualied personnel only.
WARNING
UNINTENDED START
When the frequency converter is connected to AC mains, DC supply, or load sharing, the motor may start at any time. Unintended start during programming, service, or repair work can result in death, serious injury, or property damage. The motor can start with an external switch, a eldbus command, an input reference signal from the LCP or LOP, via remote operation using MCT 10 Set-up Software, or after a cleared fault condition. To prevent unintended motor start:
Disconnect the frequency converter from the
mains. Press [O/Reset] on the LCP before
programming parameters. The frequency converter, motor, and any driven
equipment must be fully wired and assembled when the frequency converter is connected to AC mains, DC supply, or load sharing.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors that can remain charged even when the frequency converter is not powered. Failure to wait the specied time after power has been removed before performing service or repair work, can result in death or serious injury.
Stop the motor.
Disconnect the AC mains and remote DC-link
power supplies, including battery back-ups, UPS, and DC-link connections to other frequency converters.
Disconnect or lock the PM motor.
Wait for the capacitors to discharge fully before
performing any service or repair work. The duration of waiting time is specied in the relevant frequency converter operating instructions, Chapter 2 Safety.
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the frequency converter properly can result in death or serious injury.
Ensure the correct grounding of the equipment
by a certied electrical installer.
4 Danfoss A/S © Rev. 03/2015 All rights reserved. MG33D502
Safety Installation Guide
WARNING
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment can result in death or serious injury.
Ensure that only trained and qualied personnel
perform installation, start-up, and maintenance. Ensure that electrical work conforms to national
and local electrical codes. Follow the procedures in this manual.
CAUTION
INTERNAL FAILURE HAZARD
An internal failure in the frequency converter can result in serious injury, when the frequency converter is not properly closed.
Ensure that all safety covers are in place and
securely fastened before applying power.
2
2
MG33D502 Danfoss A/S © Rev. 03/2015 All rights reserved. 5
130BD866.10
≥ 200mm
2
1
Installation
3 Installation
VLT® DeviceNet MCA 104
3.1 Safety Instructions
33
See chapter 2 Safety for general safety instructions.
3.2 EMC-compliant Installation
To obtain an EMC-compliant installation, follow the instructions provided in the relevant frequency converter operating instructions and design guide. Refer to the eldbus master manual from the PLC supplier for further installation guidelines.
3.3 Grounding
Ensure that all stations connected to the eldbus
network are connected to the same ground potential. When there are long distances between the stations in a eldbus network, connect the individual station to the same ground potential. Install equalising cables between the system components.
Establish a grounding connection with low HF
impedance, for example by mounting the frequency converter on a conductive back plate.
Keep the ground wire connections as short as
possible. Establish electrical contact between the cable
screen and the frequency converter enclosure by using metal cable glands or by using the clamps provided on the equipment.
Use high-strand wire to reduce electrical
interference.
3.4
Cable Routing
NOTICE
EMC INTERFERENCE
Use screened cables for motor and control wiring, and separate cables for eldbus communication, motor wiring, and brake resistor. Failure to isolate eldbus communication, motor, and brake resistor cables can result in unintended behaviour or reduced performance. Minimum 200 mm (7.9 in) clearance between power, motor, and control cables is required. For power sizes above 315 kW, it is recommended to increase the minimum distance of 500 mm (20 in).
NOTICE
When the eldbus cable crosses a motor cable or a brake resistor cable, ensure that the cables cross at an angle of 90°.
1 Fieldbus cable 2 90° crossing
Illustration 3.1 Cable Routing
6 Danfoss A/S © Rev. 03/2015 All rights reserved. MG33D502
130BD260.10
1
2
4
3
130BD862.10
130BD863.10
Installation Installation Guide
3.5 Mounting
1. Check whether the eldbus option is already mounted in the frequency converter. If already mounted, go to step 6. If not mounted, go to step 2.
2. Remove the LCP or blind cover from the frequency converter.
3. Use a screwdriver to remove the front cover and the LCP cradle.
4. Mount the eldbus option. Mount the option with the connector facing up for top cable entry (see Illustration 3.3), or with the connector facing down for bottom cable entry (see Illustration 3.4). If an MCB option is installed, only top cable entry is possible.
5. Remove the knock-out plate from the new LCP cradle.
6. Mount the new LCP cradle.
3 3
Illustration 3.3 Top Cable Entry: Option Mounted with Connector Facing Up
Illustration 3.4 Bottom Cable Entry: Option Mounted with Connector Facing Down
1 LCP 2 LCP cradle 3 Fieldbus option 4 Connector
Illustration 3.2 Exploded View
MG33D502 Danfoss A/S © Rev. 03/2015 All rights reserved. 7
Installation
VLT® DeviceNet MCA 104
3.6 Setting Address Switches
NOTICE
Switch o the power supply before changing the address switches. The address change comes into eect at the next power-up.
33
Set the address switches to give the option a unique ID. Select an address range from 0 to 63 (factory setting 63) according to Table 3.1.
Switch 8 7 6 5 4 3 2 1
Address value 5 - - OFF OFF OFF ON OFF ON 20 - - OFF ON OFF ON OFF OFF
35 - - ON OFF OFF OFF ON ON
Table 3.1 Settings for the Address Switches
Alternatively, assign a unique ID from parameter 10-02 MAC ID. For setting the address from parameter 10-02 MAC ID,
ensure that all address switches are set to “ON”. When the address is already set using address hardware switches, the address value shown in parameter 10-02 MAC ID is ‘read only’.
- - +32 +16 +8 +4 +2 +1
3.7 Electrical Installation
3.7.1 Cable Specications
Baud rate [kBaud] Max. per drop [m] Cumulative
125 500
250 250 78 500 100 39
Table 3.2 Cable Lengths
Max. total cable length [m]
Use the cables according to ODVA
Note that the ODVA “Flat Cable” is an unscreened
cable type, and is not suited for use with frequency converters.
Drop length
6
specications.
max. [m]
156
Illustration 3.6 ODVA “Thin Cable” Cross-section
Illustration 3.5 Location and Sequence of the Address Switches
8 Danfoss A/S © Rev. 03/2015 All rights reserved. MG33D502
130BD877.10
1
2
5 4 3 2 1
130BE259.10
Installation Installation Guide
3.7.2 Wiring Procedures
Wiring Procedure for Enclosure Types A1-A3
1. Mount the eldbus connector on the eldbus option (terminal V-, CAN_L, Drain, CAN_H, V+). For top cable entry, mount the supplied EMC bracket on top of the frequency converter with 2 screws.
2. Prepare the eldbus cable by stripping a section of the cable insulation, so that the cable screen contacts the EMC bracket. Keep the unshielded wire as short as possible. For cable specications, refer to chapter 3.7.1 Cable Specications.
3. Connect the eldbus cable wires to the terminals according to the colour code of the wires, see Illustration 3.8.
4. Position the stripped cable between the spring loaded metal clamps, to establish mechanical xation and electrical contact between cable screen and ground.
3 3
Pin no. Terminal Colour Name
1 V- Black GND 2 CAN_L Blue CAN LOW 3 Drain (bare) Screen 4 CAN_H White CAN HIGH 5 V+ Red +24 V
1 Cable screen 2 EMC bracket (Used for top cable entry only)
Illustration 3.7 Wiring for Enclosure Types A1-A3
Illustration 3.8 Fieldbus Cable Terminal Connections
DeviceNet termination
Install the termination resistors at each end of the bus line. Mount the resistor between terminal 2 (CAN_L) and terminal 4 (CAN_H). The resistors have the following specication: 121 Ohm, 1% Metal lm, 1/4 Watt
Illustration 3.9 Termination Resistor Mounted
MG33D502 Danfoss A/S © Rev. 03/2015 All rights reserved. 9
130BD864.10
Installation
VLT® DeviceNet MCA 104
Drop cable
An alternative to splicing 2 trunk lines in the connector on the control card is to use a DeviceNet connection box or a T-connector. For this installation, a drop cable is available as an option. Drop cable order number: 195N3113. The connector is a micro-style, male, with rotating coupling
33
nut, and ts into a Micro Device port.
Illustration 3.10 Drop Cable
Wiring Procedure for Enclosure Types A4-A5, B1-B4, and C1-C4
1. Push the cable through cable glands.
2. Mount the eldbus connector on the eldbus option (terminal V-, CAN_L, Drain, CAN_H, V+).
3. Prepare the eldbus cable by stripping a section of the cable insulation. Keep the unshielded wire as short as possible. For cable specications, refer to chapter 3.7.1 Cable Specications.
4. Connect the eldbus cable wires to the terminals according to the colour code of the wires, see Illustration 3.8.
5. Fix the cable screen to the metal base plate using cable clamp or cable tie, see Illustration 3.11.
6. Tighten cable glands securely.
Illustration 3.11 Wiring for Enclosure Types A4-A5, B1-B4, and C1-C4
10 Danfoss A/S © Rev. 03/2015 All rights reserved. MG33D502
130BC527.10
Installation Installation Guide
Wiring Procedure for Enclosure Types D, E, and F
1. Mount the eldbus connector on the eldbus option (terminal V-, CAN_L, Drain, CAN_H, V+).
2. Prepare the eldbus cable by stripping a section of the cable insulation. Keep unshielded wire as short as possible. For cable specications, refer to chapter 3.7.1 Cable Specications.
3. Connect the eldbus cable wires to the terminals according to the colour code of the wires, see Illustration 3.8.
4. Fix the cable screen to the metal base plate using cable clamp or cable tie, see Illustration 3.12.
5. Tie down the cable and route it with other control wires inside the unit, see Illustration 3.12.
3.8
Reassembling Cover
1. Mount the new front cover and the LCP.
2. Attach the sticker with the correct product name to the front cover.
3.9 Applying Power
Follow the instructions in the frequency converter Operating Instructions to commission the frequency converter. The frequency converter automatically detects the DeviceNet interface. A new parameter group (Group 10-XX) appears.
3.10 Checking Network Cabling
1. If the address has not been set via the address switches, go to parameter 10-02 MAC ID to set the address.
2. Connect to a running DeviceNet master.
3. Check that network cabling is correct or not.
3 3
Illustration 3.12 Wiring for Enclosure Types D, E, and F
MG33D502 Danfoss A/S © Rev. 03/2015 All rights reserved. 11
Troubleshooting
4 Troubleshooting
VLT® DeviceNet MCA 104
4.1 Warnings and Alarms
NOTICE
Refer to the relevant Operating Instructions for an overview of warning and alarm types and for the full list
44
of warnings and alarms.
Alarm word, warning word, and DeviceNet warning word are shown on the frequency converter display in hex format. When there is more than 1 warning or alarm, the sum of all warnings or alarms is shown. Alarm word, warning word, and DeviceNet warning word can also be displayed using the serial bus in parameter 16-90 Alarm
Word, parameter 16-92 Warning Word, and parameter 16-05 Main Actual Value [%].
4.2 Troubleshooting
4.2.1 LED Status
The 2 bi-colour LEDs on the DeviceNet card indicate the status of DeviceNet communication:
The lower LED (NS) indicates the net status.
The upper LED (MS) indicates the module status.
MS Upper left LED NS Lower left LED
Illustration 4.1 LED Panel DeviceNet MCA 104
State Bi-colour LED Status
No Power O There is no power applied to the option. Device operational
Standby Green The DeviceNet option needs commis-
Minor fault Red Recoverable fault.
Unrecov­erable fault
Self test Green The DeviceNet option is in Self-test
Table 4.1 LED: Module Status (MS)
Green The DeviceNet option is operating in
normal condition.
sioning due to conguration missing, incomplete or incorrect.
Red Unrecoverable fault, may need replacing.
mode.
Red
12 Danfoss A/S © Rev. 03/2015 All rights reserved. MG33D502
Troubleshooting Installation Guide
State Bi-colour LED Status
No Power/Not on-line On-line, not connected
On-line and connected
Connection time-out
Critical link failure
Table 4.2 LED: Network Status (NS)
4.2.2
O The option has not completed “Duplicate
MAC ID” test yet or may not be powered.
Green The option is on-line, but not allocated
to a master.
Green The DeviceNet option is on-line and
connected to a master.
Red One or more I/O connections are in time-
out state.
Red
No Communication with the Frequency Converter
When there is no communication with the frequency converter, proceed with the following checks:
4 4
1. Check that cabling is correct. Check that the cables are connected to the correct terminals as shown in Illustration 3.8.
2. Check that the bus connection is terminated at both ends. If not, terminate the bus connection with termination resistors at the initial and nal nodes.
MG33D502 Danfoss A/S © Rev. 03/2015 All rights reserved. 13
Index
VLT® DeviceNet MCA 104
Index
A
Abbreviation............................................................................................. 3
Additional resources.............................................................................. 2
Address switch.................................................................................. 8, 11
Alarm......................................................................................................... 12
Alarm word............................................................................................. 12
Applying power.................................................................................... 11
Approvals................................................................................................... 2
M
Motor wiring............................................................................................. 6
Mounting................................................................................................... 7
N
Network cabling.................................................................................... 11
Q
Qualied personnel................................................................................ 4
C
Cable length.............................................................................................. 8
Cable specications............................................................................... 8
Cable terminal connections................................................................ 9
Certications............................................................................................. 2
Convention................................................................................................ 3
D
DeviceNet termination.......................................................................... 9
Discharge time......................................................................................... 4
Drop cable............................................................................................... 10
E
Electrical installation.............................................................................. 8
Electrical interference............................................................................ 6
EMC interference..................................................................................... 6
EMC-compliant installation................................................................. 6
Exploded view.......................................................................................... 7
S
Safety........................................................................................................... 5
Screened cable......................................................................................... 6
Symbol........................................................................................................ 3
U
Unintended start..................................................................................... 4
W
Warning.................................................................................................... 12
Warning word........................................................................................ 12
Wiring procedure.................................................................................... 9
G
Grounding................................................................................................. 6
H
High voltage............................................................................................. 4
I
Intended use............................................................................................. 2
Items supplied.......................................................................................... 2
L
Leakage current....................................................................................... 4
LED............................................................................................................... 3
LED panel................................................................................................. 12
LED status................................................................................................ 12
Load sharing............................................................................................. 4
14 Danfoss A/S © Rev. 03/2015 All rights reserved. MG33D502
Index Installation Guide
MG33D502 Danfoss A/S © Rev. 03/2015 All rights reserved. 15
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss A/S Ulsnaes 1 DK-6300 Graasten vlt-drives.danfoss.com
130R0303 MG33D502 Rev. 03/2015
*MG33D502*
Loading...