Danfoss MCA 104 Programming guide

MAKING MODERN LIVING POSSIBLE

Programming Guide VLT® DeviceNet MCA 104

VLT® Frequency Converter Series • FC 102 • FC 202 • FC 301/302

vlt-drives.danfoss.com

Danfoss MCA 104 Programming guide

Contents

Programming Guide

 

 

Contents

1 Introduction

3

1.1 Purpose of the Manual

3

1.2 Additional Resources

3

1.3 Document and Software Version

3

1.4 Product Overview

3

1.5 Approvals and Certi€cations

4

1.6 Symbols, Abbreviations and Conventions

4

2 Safety

5

2.1 Safety Symbols

5

2.2 Quali€ed Personnel

5

2.3 Safety Precautions

5

3 Configuration

7

3.1 Con€gure the DeviceNet Network

7

3.2 Con€gure the Master

8

3.3 Con€gure the Frequency Converter

8

4 Control

9

4.1 DeviceNet Process Control Modes

9

4.2 I/O Assembly Instances

10

4.3 Process Data

10

4.4 ODVA Control Pro€le

11

4.5 FC Control Pro€le

13

5 Parameter Access

17

5.1 Explicit Messages

17

5.2 Object Classes

17

5.3 DeviceNet Object Classes

18

5.4 Danfoss Object Classes

27

6 Parameters

28

6.1 Parameter Description

28

6.2 Parameter List

36

6.3 Data Types Supported

37

7 Application Examples

38

7.1 Example: Working with Instance 101/151 Process

38

8 Troubleshooting

40

8.1 LED Status

40

8.2 No Communication with the Frequency Converter

41

MG92F102

Danfoss A/S © 12/2015 All rights reserved.

1

Contents

VLT® DeviceNet MCA 104

8.3 Frequency Converter Does Not Respond to Control Signals

41

8.4 Warnings and Alarms

44

Index

46

2

Danfoss A/S © 12/2015 All rights reserved.

MG92F102

Introduction Programming Guide

1 Introduction

1

1

 

 

 

 

 

1.1 Purpose of the Manual

The VLT® DeviceNet MCA 104 Programming Guide provides information about con€guring the system, controlling the frequency converter, parameter access, programming, troubleshooting, and some typical application examples. The programming guide is intended for use by quali€ed personnel who are familiar with the VLT® frequency converter, with DeviceNet technology, and with the PC or PLC that is used as a master in the system.

Read the instructions before programming and follow the procedures in this manual.

VLT® is a registered trademark.

1.2 Additional Resources

Resources available for the VLT® frequency converter and optional equipment:

The VLT® Operating Instructions provide the necessary information for getting the VLT® frequency converter up and running.

The VLT® Design Guide provides detailed information about capabilities and functionality to design motor control systems.

The VLT® Programming Guide provides greater detail on working with parameters and many application examples.

The VLT® DeviceNet MCA 104 Installation Guide provides information about installing the DeviceNet and troubleshooting.

The VLT® DeviceNet MCA 104 Programming Guide provides information about con€guring the system, controlling the VLT® frequency converter, parameter access, programming, troubleshooting, and some typical application examples.

Supplementary publications and manuals are available from Danfoss. See vlt-drives.danfoss.com/Support/Technical- Documentation/ for listings.

1.3 Document and Software Version

This manual is regularly reviewed and updated. All suggestions for improvement are welcome. Table 1.1 shows the document version and the corresponding software version.

Edition

Remarks

Software version

 

 

 

MG92F1xx

First edition.

4.4x

 

 

 

Table 1.1 Document and Software Version

1.4 Product Overview

This programming guide relates to the DeviceNet interface. Ordering number:

130B1102 (non-coated version).

130B1210 (conformal coated version).

DeviceNet is a low-level network that standardizes communications between industrial devices (sensors, limit switches, motor controls) and high-level devices (controllers). DeviceNet follows the Open Systems Interconnection (OSI) model and is based on CAN technology for media access control and physical signaling.

DeviceNet systems can be con€gured to operate in a master/slave or a distributed control architecture using peer-to-peer communication. Up to 63 nodes in a multidrop network topology are supported. By using the same cable for communication, communication options can be powered directly from the bus. Nodes can be removed or inserted without powering down the network.

Each node on the network has its own unique media access control identi€er (MAC ID) to distinguish it on the network. The access control is based on the CSMA/CA (carrier sense multiple access/collision avoidance) principle, meaning that all nodes may have access to the network at the same time. When 2 nodes attempt to get control of the network bus simultaneously, the CAN protocol resolves the issue by arbitration. In this way, collisions on the network are avoided.

DeviceNet de€nes device pro€les for devices belonging to speci€c classes. For other devices, de€ne a custom class to make it DeviceNet compatible. All the above enhances the interchangeability and interoperability of the network.

 

24 V

 

<![if ! IE]>

<![endif]>195NA228.10

 

 

 

 

 

Power supply

 

Trunk line

 

 

 

RT

 

 

RT

 

 

 

1

1

1

1

 

Drop lines 1

RT=Termination resistors

Illustration 1.1 Topology

MG92F102

Danfoss A/S © 12/2015 All rights reserved.

3

Introduction

VLT® DeviceNet MCA 104

1 1 VLT® DeviceNet MCA 104 is designed to communicate with any master abiding by the DeviceNet standard. It is intended for use with:

VLT® HVAC Drive FC 102

VLT® AQUA Drive FC 202

VLT® AutomationDrive FC 301/FC 302

1.5 Approvals and Certi€cations

More approvals and certi€cations are available. For more information, contact a local Danfoss partner.

1.6Symbols, Abbreviations and

Conventions

Abbreviation

Definition

 

 

ACK

ACKnowledge

 

 

BOC

Bus o‚ counter

 

 

BOOL

Boolean expression

 

 

CAN

Controller area network

 

 

CSMA/CA

Carrier sense multiple access/collision avoidance

 

 

COS

Change of state

 

 

CTW

Control word

 

 

EDS

Electronic data sheet

 

 

EMC

Electromagnetic compatibility

 

 

ETR

Electronic thermal relay

 

 

FIFO

First in €rst out

 

 

HF

High frequency

 

 

HPFB

High performance €eldbus

 

 

I/O

Input/output

 

 

ISO

International standards organization

 

 

LCD

Liquid crystal display

 

 

LED

Light emitting diode

 

 

LSB

Least signi€cant bit

 

 

MAC ID

Media access control identi€er

 

 

MAV

Main actual value

 

 

MRV

Main reference value

 

 

MSB

Most signi€cant bit

 

 

N/A

Not applicable

 

 

ODVA

Open DeviceNet Vendor Association

 

 

OSI

Open systems interconnection

 

 

PC

Personal computer

 

 

PCD

Process data

 

 

PIW

Peripheral input word

 

 

PLC

Programmable logic control

 

 

PNU

Parameter number

 

 

PPO

Parameter-process data object

 

 

QW

Peripheral output word

 

 

Abbreviation

Definition

 

 

SINT

Signed integer

 

 

STW

Status word

 

 

VSD

Variable speed drive

 

 

UDINT

Unsigned double integer

 

 

UNIT

Unsigned integer

 

 

USINT

Unsigned short integer

 

 

Table 1.2 Symbols and Abbreviations

Conventions

Numbered lists indicate procedures.

Bullet lists indicate other information.

Italicized text indicates:

Cross reference.

Link.

Parameter name.

Parameter group name.

Parameter option.

Footnote.

4

Danfoss A/S © 12/2015 All rights reserved.

MG92F102

Safety

Programming Guide

 

 

2 Safety

2.1 Safety Symbols

The following symbols are used in this manual:

WARNING

Indicates a potentially hazardous situation that could result in death or serious injury.

CAUTION

Indicates a potentially hazardous situation that could result in minor or moderate injury. It can also be used to alert against unsafe practices.

NOTICE

Indicates important information, including situations that can result in damage to equipment or property.

2.2 Quali€ed Personnel

Correct and reliable transport, storage, installation, operation, and maintenance are required for the troublefree and safe operation of the frequency converter. Only quali€ed personnel are allowed to install and operate this equipment.

Quali€ed personnel are de€ned as trained sta‚, who are authorized to install, commission, and maintain equipment, systems, and circuits in accordance with pertinent laws and regulations. Additionally, the quali€ed personnel must be familiar with the instructions and safety measures described in these operating instructions.

2.3 Safety Precautions

WARNING

HIGH VOLTAGE

Frequency converters contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation, start-up, and maintenance by qualified personnel can result in death or serious injury.

Only qualified personnel must perform installation, start-up, and maintenance.

2 2

WARNING

UNINTENDED START

When the frequency converter is connected to AC mains, DC supply, or load sharing, the motor may start at any time. Unintended start during programming, service, or repair work can result in death, serious injury, or property damage. The motor can start with an external switch, a fieldbus command, an input reference signal from the LCP or LOP, via remote operation using MCT 10 Set-up Software, or after a cleared fault condition.

To prevent unintended motor start:

Press [Off/Reset] on the LCP before programming parameters.

Disconnect the frequency converter from the mains.

Completely wire and assemble the frequency converter, motor, and any driven equipment before connecting the frequency converter to AC mains, DC supply, or load sharing.

WARNING

DISCHARGE TIME

The frequency converter contains DC-link capacitors that can remain charged even when the frequency converter is not powered. Failure to wait the specified time after power has been removed before performing service or repair work can result in death or serious injury.

Stop the motor.

Disconnect the AC mains and remote DC-link supplies, including battery back-ups, UPS, and DC-link connections to other frequency converters.

Disconnect or lock the PM motor.

Wait for the capacitors to discharge fully before performing any service or repair work. The waiting time is specified in the relevant frequency converter operating instructions,

Chapter 2 Safety.

WARNING

LEAKAGE CURRENT HAZARD

Leakage currents exceed 3.5 mA. Failure to ground the frequency converter properly can result in death or serious injury.

Ensure the correct grounding of the equipment by a certified electrical installer.

MG92F102

Danfoss A/S © 12/2015 All rights reserved.

5

Safety VLT® DeviceNet MCA 104

WARNING

EQUIPMENT HAZARD

2 2 Contact with rotating shafts and electrical equipment can result in death or serious injury.

Ensure that only trained and qualified personnel perform installation, start-up, and maintenance.

Ensure that electrical work conforms to national and local electrical codes.

Follow the procedures in this guide.

CAUTION

INTERNAL FAILURE HAZARD

An internal failure in the frequency converter can result in serious injury when the frequency converter is not properly closed.

Ensure that all safety covers are in place and securely fastened before applying power.

6

Danfoss A/S © 12/2015 All rights reserved.

MG92F102

Configuration

Programming Guide

 

 

3 Con€guration

3.1 Con€gure the DeviceNet Network

All DeviceNet stations that are connected to the same bus network must have a unique station address. Select the DeviceNet address of the frequency converter via:

Address switches (default 63).

Parameter 10-02 MAC ID (default 63).

Class code 0X03, instance 1, attribute 1.

Illustration 3.1 VLT® DeviceNet MCA 104 Interface

3.1.1Setting the DeviceNet Address using the Address Switches

NOTICE

Switch off the power supply before changing the address switches. The address change comes into effect at the next power-up, and can be read in parameter 10-02 MAC ID.

Set the address switches to give the option a unique ID. Select an address range from 0–63 (factory setting 63) according to Table 3.1.

Switch

8

7

6

5

4

3

2

1

 

 

 

 

 

 

 

 

 

Address value

+32

+16

+8

+4

+2

+1

 

 

 

 

 

 

 

 

 

5

OFF

OFF

OFF

ON

OFF

ON

 

 

 

 

 

 

 

 

 

20

OFF

ON

OFF

ON

OFF

OFF

 

 

 

 

 

 

 

 

 

35

ON

OFF

OFF

OFF

ON

ON

 

 

 

 

 

 

 

 

 

Table 3.1 Settings for the Address Switches

3.1.2 Setting the DeviceNet Address via

 

 

Parameter 10-02 MAC ID

3

3

 

Set the address via parameter 10-02 MAC ID if the hardware switches are set to 63 (factory setting). The address change comes into e‚ect at the next power-up.

3.1.3Setting the DeviceNet Address with the Object Class Code 0x03, Instance 1, Attribute 1

Set the address via the DeviceNet object class code 0x03 attribute 1 command when the address switch is set to 63 (factory setting). A new address becomes e‚ective immediately after the class code 0x03, instance 1, attribute 1 command.

3.1.4 Setting the Baud Rate

All DeviceNet stations connected to the same bus network must have the same baud rate. Select the baud rate of the frequency converter via:

Address switches.

Parameter 10-01 Baud Rate Select (default 125 kBd).

Object class code 0x03, instance 1, attribute 2.

3.1.5Setting the DeviceNet Baud Rate using the Address Switches

NOTICE

Switch off the power supply before changing the address switches. The baud rate change comes into effect at the next power-up, and can be read in parameter 10-01 Baud Rate Select.

Use the address switches to select a baud rate of 125 k baud (factory setting), 250 k baud, or 500 k baud, see

Table 3.2:

Baud rate switch

8

7

 

 

 

Parameter 10-01 Baud Rate Select

1

1

 

 

 

125 kBd

0

0

 

 

 

250 kBd

0

1

 

 

 

500 kBd

1

0

 

 

 

Table 3.2 Address Switches

MG92F102

Danfoss A/S © 12/2015 All rights reserved.

7

Configuration

VLT® DeviceNet MCA 104

3.1.6Setting the DeviceNet Baud Rate via Parameter 10-01 Baud Rate Select

Set the baud rate via parameter 10-01 Baud Rate Select if the address switches 1 and 2 are set to ON (factory

3 3 setting). The baud rate change comes into e‚ect at the next power-up.

3.1.7Setting the DeviceNet Baud Rate with the Object Class Code 0x03, Attribute 2

Set the baud rate via the DeviceNet object class code 0x03 attribute 2 command, when the address switches 1 and 2 are set to ON (factory setting). A new baud rate becomes e‚ective immediately after the class code 0x03 attribute 2 command.

3.2 Con€gure the Master

3.2.1 EDS File

A large part area of the system con€guration is the setting of application-related parameters. EDS (Electronic Data Sheet) €les simplify the setting up of most of the DeviceNet con€gurable parameters. For o‚-line con€guration, Danfoss provides a generic English EDS €le covering all voltage and power sizes. Download the EDS €le from www.danfoss.com/drives.

NOTICE

The EDS file does not contain all parameters. It contains only a selected, limited number of parameters with generic minimum, maximum, and default values.

3.3Con€gure the Frequency Converter

3.3.1Frequency Converter Parameters

Note the following parameters when con€guring the frequency converter with a DeviceNet interface. Refer to chapter 6 Parameters for more details of each parameter.

Parameter 0-40 [Hand on] Key on LCP.

If the Hand key on the frequency converter is activated, control of the frequency converter via the DeviceNet interface is disabled. After initial power-up the frequency converter automatically detects whether a €eldbus option is installed in slot A, and sets parameter 8-02 Control Word Source to [3] Option A. If an option is added to, changed in, or removed from an already commissioned frequency converter, it does not change parameter 8-02 Control Word Source but enters trip mode, and the frequency converter shows an error.

Parameter 8-10 Control Word Profile (see

chapter 4 Control). Select between the Danfoss FC Pro€le and the ODVA pro€le. Select the desired DeviceNet instance in parameter 10-10 Process Data Type Selection.

Parameter 8-50 Coasting Select to parameter 8-56 Preset Reference Select (see

chapter 6 Parameters). Selection of how to gate the DeviceNet control commands with digital input command of the control card.

NOTICE

When parameter 8-01 Control Site is set to [2] Control word only, the settings in parameter 8-50 Coasting Select to parameter 8-56 Preset Reference Select is overruled, and all act on bus control.

Parameter 8-03 Control Word Timeout Time to parameter 8-05 End-of-Timeout Function. The reaction in the event of a bus timeout is set via these parameters.

Parameter 10-10 Process Data Type Selection. Default is 125 kbps.

Parameter 10-02 MAC ID. Default is 63.

8

Danfoss A/S © 12/2015 All rights reserved.

MG92F102

Control

Programming Guide

 

 

4 Control

4.1 DeviceNet Process Control Modes

This section describes 2 of 3 possible process control modes:

Polling.

Change of state (COS).

The 3rd FC control mode uses the acyclic mode explicit messaging via the standard DeviceNet control supervisory object class 29H. The control supervisory object is described in chapter 5.3 DeviceNet Object Classes.

4.1.2 Change of State, COS

4.1.1 Polling

Table 4.1 is a classic master/slave connection and the standard DeviceNet operating mode. The master controls the data exchange by sending cyclic poll-requests to the

connected slave, and the slave answers by sending a poll- 4 4 response to the master. The master can control and

monitor the frequency converter by polling the DeviceNet or Danfoss objects (I/O instances).

Master

 

Slave

 

 

 

CTW

MRV

 

Slave

 

Master

 

 

 

 

 

 

STW

MAV

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 4.1 Standard DeviceNet Operation Mode - Polled I/O

COS is an event-controlled operating mode used to minimize network traffic. Messages are transmitted only if a de€ned state or value has changed. The condition for triggering a COS message is determined by the insertion of COS-€lters (parameter 10-20 COS Filter 1 to parameter 10-23 COS Filter 4), for each bit in the di‚erent PCD words. The €lter acts like a logical AND function: If a bit in the €lter is set to 1, the COS function triggers after a change to the corresponding bit for the PCD word.

Illustration 4.1 Different PCDs and the Corresponding Filter Parameters

Parameter 10-20 COS Filter 1 to parameter 10-23 COS Filter 4 can be used to €lter out undesired events for COS. If a €lter bit is set to 0, the corresponding I/O instance bit is unable to produce a COS message. By default, all bits in the COS €lters are set to 0.

To signal that the connection has not been interrupted, or the device is not powered o‚, a heartbeat message is transmitted within a speci€ed time interval (heartbeat interval). This interval is de€ned in attribute heartbeat time of the connection object, class code 0x05.

To prevent the device from producing heavy network traffic if a value changes frequently, the production inhibit time (an attribute of the connection object) is de€ned. This parameter de€nes the minimum time between 2 COS messages.

MG92F102

Danfoss A/S © 12/2015 All rights reserved.

9

Control

VLT® DeviceNet MCA 104

The attribute expected package rate de€nes the maximum time between 2 COS messages even when the value is unchanged. In the event of COS connection, the explicit package rate is identical with the heartbeat interval mentioned above. This timer is used both as transmission trigger and inactivity watchdog, depending on whether the connection is producer or consumer.

4.2 I/O Assembly Instances

I/O assembly instances are several de€ned process control objects with de€ned content comprising control and status

information. Illustration 4.2 shows the I/O assembly instance options for controlling and monitoring the frequency converter.

4 4

Illustration 4.2 I/O Assembly Instance Options

4.3 Process Data

Process data comprises the control and status data in the I/O assembly instances.

The CTW, MRV, STW, and MAV have de€ned formats and functions, depending on the I/O instance selected. PCD 3 and PCD 4 are freely con€gurable, for instance 101/151 via parameter 10-11 Process Data Config Write and parameter 10-12 Process Data Config Read.

All PCDs are freely con€gurable for instance 102/152.

DeviceNet provides a flexible way to customize the number of process data (I/O words) and the functionality of each word. To activate the user de€nable process data, select the I/O instance 101/151 in parameter 10-10 Process Data Type Selection. This changes the I/O size to 4 words in the input and output area. This selection uses the Danfoss-speci€c pro€le for the control word and status word as well as for the main reference value/main actual value.

The €rst 2 words are €xed on the DeviceNet, whereas PCD 3 and PCD 4 are user con€gurable. The number of PCDs active in a system is €xed to 2 words.

NOTICE

To select [1] Instance 101/151 in parameter 10-10 Process Data Type Selection, set parameter 8-10 Control Word Pro€le to [0] FC pro€le.

To enable use of PCD data from the DeviceNet, con€gure the contents of each single PCD word in parameter 10-11 Process Data Config Write and parameter 10-12 Process Data Config Read. Changes to parameter 10-11 Process Data Config Write and parameter 10-12 Process Data Config Read are e‚ected immediately in the PCD data.

10

Danfoss A/S © 12/2015 All rights reserved.

MG92F102

Control

Programming Guide

 

 

Instanc e

Originator (PLC) --> Target (Drive)

 

 

Instanc e

Target (Drive) --> Originator (PLC)

 

 

 

 

 

 

 

 

 

 

 

 

 

20

CTW

REF

 

 

 

70

STW

MA V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21

CTW

REF

 

 

 

71

STW

MA V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

CTW

REF

 

 

 

150

STW

MA V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

101

CTW

REF

 

PCD 2

PCD 3

151

STW

MA V

 

PCD 2

PCD 3

 

write

write

 

read

read

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<![if ! IE]>

<![endif]>130BE709.10

4 4

Byte #

1

 

 

2

3

 

 

4

5

 

 

6

7

 

 

8

 

Byte #

1

 

 

2

3

 

 

4

5

 

 

6

7

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Word #

 

 

 

 

 

 

 

 

Word #

 

1

 

2

 

3

 

 

4

 

 

1

 

2

 

3

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fixed contents

 

 

 

 

 

 

 

 

 

 

User de ned contents

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Illustration 4.3 Process Data

4.4 ODVA Control Pro€le

4.4.1Control Word under Instances 20/70 and 21/71

Set parameter 8-10 Control Word Profile to ODVA and select the instance in parameter 10-10 Process Data Type Selection.

Illustration 4.4 The Control Word in Instances 20 and 21

NOTICE

The bits 00 and 02 in instance 20 are identical with bits 00 and 02 in the more extensive instance 21.

Bit

Instance 20

 

Instance 21

 

 

 

 

 

 

 

Bit = 0

Bit = 1

Bit = 0

Bit = 1

 

 

 

 

 

00

Stop

Run Fwd

Stop

Run Fwd

 

 

 

 

 

01

Stop

Run Rev

 

 

 

 

 

02

No function

Fault reset

No function

Fault reset

 

 

 

 

 

03

 

 

 

 

 

04

 

 

 

 

 

05

Net Ctrl

 

 

 

 

 

06

Net Ref

 

 

 

 

 

07–15

 

 

 

 

 

Table 4.2 Bits in Instances 20 and 21

Explanation of the bits: Bit 0, Run Fwd

Bit 0 = 0: The frequency converter has a stop command. Bit 0 = 1: Leads to a start command, and the frequency converter runs the motor clockwise.

Bit 1, Run Rev

Bit 1 = 0: Leads to a stop of the motor.

Bit 1 = 1: Leads to a start reverse of the motor, and the frequency converter runs the motor counterclockwise.

Bit 2, Fault Reset

Bit 2 = 0: There is no reset of a trip. Bit 2 = 1: A trip is reset.

Bit 3, No function

Bit 3: No function.

Bit 4, No function

Bit 4: No function.

Bit 5, Net Control

Bit 5 = 0: The frequency converter is controlled via the standard inputs.

Bit 5 = 1: The DeviceNet controls the frequency converter.

NOTICE

Changes affect parameter 8-50 Coasting Select to parameter 8-56 Preset Reference Select.

Bit 6, Net Reference

Bit 6 = 0: Reference is from the standard inputs. Bit 6 = 1: Reference is from DeviceNet.

MG92F102

Danfoss A/S © 12/2015 All rights reserved.

11

Control

VLT® DeviceNet MCA 104

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTICE

 

 

 

Changes affect parameter 3-15 Reference Resource 1 to

 

 

 

parameter 3-17 Reference Resource 3.

 

 

 

For the speed reference, see chapter 4.4.3 Bus Speed

 

 

 

Reference Value under Instances 20/70 and 21/71.

 

 

 

4.4.2 Status Word under Instances 20/70

4

 

4

 

 

 

and 21/71

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Illustration 4.5 Status Word in Instances 70 and 71

NOTICE

The bits 00 and 02 in instance 70 are identical with bits 00 and 02 in the more extensive instance 71.

Bit

Instance 70

 

Instance 71

 

 

 

 

 

 

 

Bit = 0

Bit = 1

Bit = 0

Bit = 1

 

 

 

 

 

00

Fault

Fault

 

 

 

 

 

01

Warning

 

 

 

 

 

02

Running 1

Running 1

 

 

Fwd

 

Fwd

 

 

 

 

 

03

Running 2

 

 

 

 

Rev.

 

 

 

 

 

04

Ready

 

 

 

 

 

05

Control

 

 

 

 

from Net

 

 

 

 

 

06

Reference

 

 

 

 

from Net

 

 

 

 

 

07

At

 

 

 

 

reference

 

 

 

 

 

08–15

State attribute

 

 

 

 

 

Table 4.3 Bits in Instances 70 and 71

Explanation of the bits: Bit 0, Fault

Bit 0 = 0: There is no fault in the frequency converter. Bit 0 = 1: There is a fault in the frequency converter.

Bit 1, Warning

Bit 0 = 0: There is no unusual situation.

Bit 0 = 1: An abnormal condition has arisen.

Bit 2, Running 1

Bit 2 = 0: The frequency converter is not in the running forward state, or run 1 is not set.

Bit 2 = 1: The frequency converter state attribute is enabled or stopping, or that fault-stop and bit 0 (run 1) of the control word are set at the same time.

Bit 3, Running 2

Bit 3 = 0: The frequency converter is not in the running reverse state, or run 2 is not set.

Bit 3 = 1: The frequency converter state attribute is enabled or stopping, or fault-stop and bit 0 (run 2) of the control word are set at the same time.

Bit 4, Ready

Bit 4 = 0: The state attribute is in another state.

Bit 4 = 1: The state attribute is ready, enabled, or stopping.

Bit 5, Control from net

Bit 5 = 0: The frequency converter is controlled from the standard inputs.

Bit 5 = 1: The DeviceNet has control (start, stop, reverse) of the frequency converter.

Bit 6, Ref from net

Bit 6 = 0: The reference comes from inputs to the frequency converter.

Bit 6 = 1: The reference comes from the DeviceNet.

Bit 7, At reference

Bit 7 = 0: The motor is running, but the present speed is di‚erent from the preset speed reference, for example, the speed is being ramped up/down during start/stop.

Bit 7 = 1: The frequency converter and reference speeds are equal.

Bit 8–15, State attribute

(Instance 71 only)

Represents the state attribute of the frequency converter, as indicated in Table 4.4.

Bit number

Meaning

8(Vendor speci€c)

9Start up

10Not ready

11Ready

12Enabled

13Stopping

14Fault stop

15Faulted

Table 4.4 State Attribute (Instance 71)

For more details of the actual output speed, see

chapter 4.4.4 Actual Output Speed under Instances 20/70 and 21/71.

4.4.3Bus Speed Reference Value under Instances 20/70 and 21/71

The speed reference value is transmitted to the frequency converter as a 16-bit word. The value is transmitted as a whole number. Negative €gures are formatted by 2’s complement.

12

Danfoss A/S © 12/2015 All rights reserved.

MG92F102

Control

Programming Guide

 

 

Illustration 4.6 Speed Reference Value

The bus speed reference has the following format:

Parameter 3-00 Reference Range = 0 [refMIN to refMAX] 0 (0000 hex) [RPM] to + 32767 (7FFF hex) [RPM]

Parameter 3-00 Reference Range = 1 [-refMAX to +refMAX] -32767 (8001 hex ) to +32767 [RPM] (7FFF hex)

The actual reference [Ref. %] in the frequency converter depends on the settings in the following parameters:

Parameter 1-23 Motor Frequency Parameter 1-25 Motor Nominal Speed Parameter 3-03 Maximum Reference

NOTICE

When the bus speed reference is negative, and the control word contains a run reverse signal, the frequency converter runs clockwise (- - is +).

Example:

Parameter 1-25 Motor Nominal Speed = 1420 RPM Parameter 1-23 Motor Frequency = 50 Hz Parameter 3-03 Maximum Reference = 1420 RPM

To run the motor at 25%, the reference transmitted must be: (1420x0.25) = 355 = 16.3 hex

163 hex 25% Fout = 12.5 Hz

4.4.4Actual Output Speed under Instances 20/70 and 21/71

Illustration 4.7 Actual Output Speed Value

The value of the actual speed of the motor, is transmitted in the form of a 16-bit word.

The value is transmitted as a whole number (negative €gures are formed with 2's complement).

-32767 (8000 hex) [RPM] to +32767 [RPM] (7FFF hex) [RPM]

4.5 FC Control Pro€le

4.5.1 Control Word under Instances 100/150, 101/151, and 102/152

To select FC protocol in the control word, set

 

 

parameter 8-10 Control Word Profile to [0] FC profile. The

 

 

control word is used to send commands from a master

 

 

(PLC or PC) to a slave (frequency converter).

4

4

 

Illustration 4.8 Control Words in Instances 100, 101, and 102

Bit

Bit value = 0

Bit value = 1

 

 

 

00

Reference value

External selection lsb

 

 

 

01

Reference value

External selection msb

 

 

 

02

DC brake

Ramp

 

 

 

03

Coasting

No coasting

 

 

 

04

Quick stop

Ramp

 

 

 

05

Hold output frequency

Use ramp

 

 

 

06

Ramp stop

Start

 

 

 

07

No function

Reset

 

 

 

08

No function

Jog

 

 

 

09

Ramp 1

Ramp 2

 

 

 

10

Data invalid

Data valid

 

 

 

11

No function

Relay 01 active

 

 

 

12

No function

Relay 04 active

 

 

 

13

Parameter set-up

Selection lsb

 

 

 

14

Parameter set-up

Selection msb

 

 

 

15

No function

Reverse

 

 

 

Table 4.5 Bits in Instances 100, 101, and 102

Explanation of the control bits: Bits 00/01

Bits 00 and 01: Select between the 4 reference values, which are pre-programmed in parameter 3-10 Preset Reference according to Table 4.6.

Programmed

Parameter

Bit 01

Bit 00

reference

 

 

 

 

value

 

 

 

 

 

 

 

 

 

1

3-10

[0]

0

0

 

 

 

 

 

2

3-10

[1]

0

1

 

 

 

 

 

3

3-10

[2]

1

0

 

 

 

 

 

4

3-10

[3]

1

1

 

 

 

 

 

Table 4.6 Reference Values

MG92F102

Danfoss A/S © 12/2015 All rights reserved.

13

Loading...
+ 35 hidden pages