This installation guide provides information for quick replacement of a VLT® PROFIBUS DP MCA 101 in the VLT® AutomationDrive FC
361.
The installation guide is intended for use by qualified personnel. Users are assumed to know the VLT® drive, with PROFIBUS
technology, and with the PC or PLC used as a master in the system.
Read the instructions before installation and ensure that instructions for safe installation are observed.
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be
present even when the warning indicator lights are off.
Failure to wait the specified time after power has been removed before performing service or repair work could result in death
or serious injury.
Stop the motor.
-
Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and
-
DC-link connections to other drives.
Wait for the capacitors to discharge fully. The minimum waiting time is specified in table Discharge time and is also visible
-
on the nameplate on top of the drive.
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors
-
are fully discharged.
Safety
Table 1: Discharge Time
Voltage [V]Power range [kW (hp)]Minimum waiting time (minutes)
•Terminate the nodes at the physical ends of each segment. If the bus segment is branched, the device furthest from the segment
connector represents the end of the segment.
•Terminals 66 and 67 provide a 5 V DC supply, available for external termination.
NOTICE
The PROFIBUS D-sub 9 adapter also features a termination switch. When the D-sub 9 adapter is used, set the termination switch
on the fieldbus option to OFF to avoid double termination.
NOTICE
When the fieldbus is extended with a repeater, terminate the extension at both ends.
NOTICE
To avoid impedance mismatch, use the same cable type throughout the entire network.
3.2 Cable Specifications
Table 2: Cable Specifications
Impedance at a measuring frequency from 3–20 MHz135–165 Ω
Resistance<110 Ω/km
Capacitance<30 pF/m
Damping (total wire length)Maximum 9 dB over the whole wire length.
Cross-section
Cable typeTwisted in pairs, 1 x 2, 2 x 2, or 1 x 4 wires.
ShieldingCopper-braided shield, or braided shield and foil shield.
1. Make sure that the power to the drive is disconnected.
2. Remove the front cover from the drive.
3. Remove the LCP (Local Control Panel) or blind cover, and then remove the LCP cradle from the drive.
4. Disconnect the communication cables from the existing MCA option card.
5. Remove the existing MCA option card from the drive.
6. Fit the new VLT® PROFIBUS DP MCA 101 option card into slot A. Mount the option with the connector facing up for top cable entry ,
or with the connector facing down for bottom cable entry. If an MCB option is installed, only top cable entry is possible.
7. Connect the communication cables.
8. Set the termination switch (shown in the illustration in
is the last station on the segment.
9. Set the address switches if needed.
10. Fit the LCP cradle.
11. Fit the LCP or blind cover in the LCP cradle.
12. Fit the front cover on the drive.
13. Connect power to the drive.
4.2 Setting Address Switches) on the fieldbus option to ON, when the drive
4.2 Setting Address Switches
Set the address switches to give the option a unique ID. Select an address range from 0–125 (factory setting 127) according to table 3.
Table 3: Settings for the Address Switches
Switch87654321
Address valueNot used+64+32+16+8+4+2+1
5Not usedOFFOFFOFFOFFONOFFON
35Not usedOFFONOFFOFFOFFONON
82Not usedONOFFONOFFOFFONOFF
Alternatively, assign a unique ID from parameter 9-18 Node Address. For setting the address from parameter 9-18 Node Address,
ensure that all address switches are set to ON. When the address is already set using address hardware switches, the address value
shown in parameter 9-18 Node Address is read-only.
4. Fix the cable screen to the metal base plate using cable clamp or cable tie.
5. Tie down the cable and route it with other control wires inside the unit.