Installation Guide
VLT® PROFIBUS DP MCA 101
VLT® AutomationDrive FC 361
1 Introduction
1.1 Purpose of this Installation Guide
This installation guide provides information for quick replacement of a VLT® PROFIBUS DP MCA 101 in the VLT® AutomationDrive FC
361.
The installation guide is intended for use by qualified personnel. Users are assumed to know the VLT® drive, with PROFIBUS
technology, and with the PC or PLC used as a master in the system.
Read the instructions before installation and ensure that instructions for safe installation are observed.
1.2 Trademarks
VLT® is a registered trademark for Danfoss A/S.
Danfoss A/S © 2019.03
AN274235331989en-000101 / 130R0855 | 1
Installation Guide | VLT® PROFIBUS DP MCA 101
2 Safety
2.1 Safety Precautions
WARNING
DISCHARGE TIME
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be
present even when the warning indicator lights are off.
Failure to wait the specified time after power has been removed before performing service or repair work could result in death
or serious injury.
Stop the motor.
-
Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and
-
DC-link connections to other drives.
Wait for the capacitors to discharge fully. The minimum waiting time is specified in table Discharge time and is also visible
-
on the nameplate on top of the drive.
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors
-
are fully discharged.
Safety
Table 1: Discharge Time
Voltage [V] Power range [kW (hp)] Minimum waiting time (minutes)
380–480 90–315 kW (125–450 hp) 20
2 | Danfoss A/S © 2019.03