The VLT® PROFIBUS DP MCA 101 Programming Guide
provides information about:
Conguring the system.
•
Controlling the frequency converter.
•
Parameter access.
•
Programming.
•
Troubleshooting.
•
Typical application examples.
•
The programming guide is intended for use by qualied
personnel familiar with the VLT® frequency converter, with
PROFIBUS technology, and with the PC or PLC used as a
master in the system.
Read the instructions before programming and follow the
procedures in this manual.
VLT® is a registered trademark.
1.2 Additional Resources
Resources available for the frequency converters and
optional equipment:
The VLT® Operating Instructions provide the
•
necessary information for getting the frequency
converter up and running.
®
The VLT
•
information about capabilities and functionality
to design motor control systems.
The VLT® Programming Guide provides greater
•
detail on working with parameters and many
application examples.
The VLT® PROFIBUS DP MCA 101 Installation Guide
•
provides information about installing the
PROFIBUS and troubleshooting.
The VLT® PROFIBUS DP MCA 101 Programming
•
Guide provides information about conguring the
system, controlling the frequency converter,
parameter access, programming, troubleshooting,
and some typical application examples.
Supplementary publications and manuals are available
from Danfoss. See vlt-drives.danfoss.com/Support/Technical-
Documentation/ for listings.
Design Guide provides detailed
Document and Software Version
1.3
This manual is regularly reviewed and updated. All
suggestions for improvement are welcome. Table 1.1 shows
the document version and the corresponding software
version.
EditionRemarksSoftware
version
MG37G2xx
Table 1.1 Document and Software Version
Information about VLT® DriveMotor
•
FCP 106/FCM 106 added.
New feature for fast PCD communi-
•
cation for MCO 305.
5.20
1.4 Product Overview
1.4.1 Features of PROFIBUS DP-V1
2 dierent state machines can be selected:
•
PROFIdrive prole or Danfoss FC prole.
Communication using PROFIBUS DP-V1, master
•
class 1, and master class 2.
Backward compatibility: New protocol extensions
•
retain all the functions of the previous versions.
PROFIBUS is an international standard for eldbus
communication in automation technology (IEC 61158 and
IEC 61784). The member companies of the PROFIBUS
International User Community support the standard.
For information about PROFIBUS and downloads for
PROFIBUS DP and the PROFIdrive prole, refer to
www.Probus.com.
PROFIBUS DP-V1
The PROFIBUS DP protocol enables communication
between PROFIBUS masters and slaves.
Congure communication via MCT 10 Set-up Software.
Cyclic/acyclic communication
PLC communicates with telegrams of constant
•
length.
Fits time-critical requirements.
•
Cyclic transmission via PPO types.
•
Extended diagnosis.
•
for general parameter access as an alternative to the PCV
parameter channel.
Illustration 1.2 PROFIBUS DP-V1
The PROFIBUS DP extension DP-V1 allows acyclic as well as
cyclic data communication. This feature can be used by a
DP master class 1, for example PLC, as well as a DP master
class 2, for example PC tool.
Illustration 1.1 PROFIBUS DP-V0
Features of a master class 1 connection:
Cyclic data exchange (DP-V0).
•
The acyclic connection is xed and cannot be changed
during operation.
Features of a master class 2 connection:
The acyclic connection can be established (initiated) or
removed (aborted) dynamically even when a master class 1
is active on the network. Use the DP-V1 acyclic connection
Acyclic read/write on parameters.
•
•
•
•
Extended diagnosis.
Initiate/abort acyclic connection.
Acyclic read/write on parameters.
Approvals and Certications
1.5
More approvals and certications are available. For more
information, contact a local Danfoss partner.
Indicates a potentially hazardous situation that could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could
result in minor or moderate injury. It can also be used to
alert against unsafe practices.
NOTICE
Indicates important information, including situations that
can result in damage to equipment or property.
2.2 Qualied Personnel
Correct and reliable transport, storage, installation,
operation, and maintenance are required for the troublefree and safe operation of the frequency converter. Only
qualied personnel are allowed to install and operate this
equipment.
Qualied personnel are dened as trained sta, who are
authorized to install, commission, and maintain equipment,
systems, and circuits in accordance with pertinent laws and
regulations. Also, the qualied personnel must be familiar
with the instructions and safety measures described in
these operating instructions.
Safety Precautions
2.3
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when
connected to AC mains input, DC supply, or load sharing.
Failure to perform installation, start-up, and maintenance
by qualied personnel can result in death or serious
injury.
Only qualied personnel must perform instal-
•
lation, start-up, and maintenance.
WARNING
UNINTENDED START
When the frequency converter is connected to AC mains,
DC supply, or load sharing, the motor may start at any
time. Unintended start during programming, service, or
repair work can result in death, serious injury, or
property damage. The motor can start with an external
switch, a eldbus command, an input reference signal
from the LCP or LOP, via remote operation using MCT 10
Set-up Software, or after a cleared fault condition.
To prevent unintended motor start:
Press [O/Reset] on the LCP before
•
programming parameters.
Disconnect the frequency converter from the
•
mains.
Completely wire and assemble the frequency
•
converter, motor, and any driven equipment
before connecting the frequency converter to
AC mains, DC supply, or load sharing.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors,
which can remain charged even when the frequency
converter is not powered. High voltage can be present
even when the warning LED indicator lights are o.
Failure to wait the specied time after power has been
removed before performing service or repair work can
result in death or serious injury.
Stop the motor.
•
Disconnect AC mains and remote DC-link power
•
supplies, including battery back-ups, UPS, and
DC-link connections to other frequency
converters.
Disconnect or lock PM motor.
•
Wait for the capacitors to discharge fully. The
•
minimum duration of waiting time is specied
in the chapter Safety in the operatinginstructions supplied with the frequency
converter.
Before performing any service or repair work,
•
use an appropriate voltage measuring device to
make sure that the capacitors are fully
discharged.
2.Set the DIP switch to 126 or 127 (factory switch
setting).
3.Set the address via parameter 9-18 Node Address
or the PROFIBUS SSA-command.
4.The address change comes into eect at the next
power-up.
130BC915.10
130BC913.11
CongurationProgramming Guide
Setting the PROFIBUS address with set station address
command
1.Switch o the supply.
2.Set the DIP switch to 126 or 127 (factory switch
setting).
3.Set the address via the set station address
command. Use the set station address command
to lock the programmed address and to change
the address. To unlock the address setting,
change parameter 9-18 Node Address or the
address switch, followed by a power cycle. A new
address is eective immediately after applying
the set station address command.
3.2 Congure the Master
3.2.1 GSD File
To congure a PROFIBUS master, the conguration tool
needs a GSD le for each type of slave on the network.
The GSD le is a PROFIBUS DP standard text le containing
the necessary communications set-up data for a slave.
Download the GSD
converter series vlt-drives.danfoss.com/products/engineering-software/software-download/eldbus/.
le for the relevant frequency
33
Illustration 3.3 Install GSD File
PROFIBUS SW version
(parameter 15-61 Option SW
Version)
1.xda01040A.GSD
2.xda02040A.GSD
FCD 302da01040B.GSD
Table 3.2 GSD File
The following example shows the procedure of
a PROFIBUS master for FC 301/FC 302, but the procedure is
also valid for other frequency converter series.
1.Import the GSD
2.Import the GSD le to the Simatic Manager
software tool. Import a GSD le once only for
each frequency converter series, following the
initial installation of the software tool. See
Illustration 3.3.
3.Use the browser for the GSD le, install all les,
and import both a GSD le and a bitmap for the
device into the hardware catalog. See
Illustration 3.4 and Illustration 3.5.
4.Import and access the FC 301/FC 302 GSD le via
the path in the hardware catalog, see
Illustration 3.6.
8.Set up the peripheral input and output data. Data
set up in the peripheral area is transmitted
cyclically via PPO types. Drag and drop a PPO
type 6 word consistent to the rst slot, see
Illustration 3.8. See the PPO types in
chapter 4 Control for more information.
33
Illustration 3.6 Import and Access the GSD File
Illustration 3.8 Drag and Drop PPO Type 6 Word Consistent to
5.Open a project, set up the hardware, and add a
PROFIBUS master system.
6.Select FC 300, then drag and drop it onto the
PROFIBUS in the hardware diagram.
7.A window for the address of the FC 300 appears.
Select the address from the scroll-down list.
Ensure that the address setting matches the
previous address setting in parameter 9-18 NodeAddress. See Illustration 3.7.
the First Slot
The conguration tool automatically assigns addresses in
the peripheral address area. In this example, the input and
output areas have the following congurations:
Alternative: For PROFIBUS SW version 2.x and higher, autoconguration of process data is supported. This feature
makes it possible to congure the process data
(parameter 9-15 PCD Write Conguration and
parameter 9-16 PCD Read Conguration) from the PLC/
master. To use auto-conguration, make sure to enable the
feature under DP slave properties. See Illustration 3.9.
Illustration 3.9 Enable Feature under DP Slave Properties
NOTICE
DP-V1 diagnosis is supported for PROFIBUS SW version
2.x and higher. The default setting of the VLT® PROFIBUS
DP MCA 101 is DP-V1 diagnosis. If DP-V0 diagnosis is
required, change the setting under DP slave properties.
Congure the Frequency Converter
3.3
3.3.1 Frequency Converter Parameters
The following parameters are important when conguring
the frequency converter with a PROFIBUS interface:
Parameter 0-40 [Hand on] Key on LCP. Pressing
•
[Hand on] disables control of the frequency
converter via PROFIBUS.
Parameter 8-02 Control Word Source. After an
•
initial power-up, the frequency converter
automatically detects whether a eldbus option is
installed in slot A. The frequency converter then
sets parameter 8-02 Control Word Source to [3]Option A. If an option is added to, changed in, or
removed from an already commissioned
frequency converter, it does not change
parameter 8-02 Control Word Source. Instead, the
frequency converter enters trip mode and shows
an error.
Parameter 8-10 Control Word Prole. Select
•
between the Danfoss FC Prole and the
PROFIdrive prole.
Parameter 8-50 Coasting Select to
•
parameter 8-56 Preset Reference Select. Select how
to gate PROFIBUS control commands with digital
input command of the control card.
Parameter 8-03 Control Word Timeout Time to
•
parameter 8-05 End-of-Timeout Function. Set the
reaction in the event of a bus timeout via these
parameters.
Parameter 9-18 Node Address.
•
Parameter 8-07 Diagnosis Trigger.
•
33
NOTICE
The setting in parameter 8-01 Control Site overrides the
settings in parameter 8-50 Coasting Select to
parameter 8-56 Preset Reference Select, and they all act on
bus control.
Illustration 3.10 DP-V1 Diagnosis
Download the congurationle to the PLC. The PROFIBUS
system is able to go online, and it starts to exchange data
when the PLC is set to run mode.
The 2 bicolor LEDs in the VLT® PROFIBUS DP MCA 101
indicate the status of PROFIBUS communication.
33
The LED marked NS (FCD 302: NS2) indicates the network
status, that is, the cyclic communication to the PROFIBUS
master. When this light is a constant green, data exchange
between the master and the frequency converter is active.
The LED marked MS (FCD 302: BUS MS) indicates the
module status, that is, acyclic DP-V1 communication from
either a PROFIBUS master class 1 (PLC) or a master class 2
(MCT 10 Set-up Software, FDT tool). When this light is a
constant green, DP-V1 communication from master classes
1 and 2 is active.
For details of the full range of communications status
indicated by the LEDs, refer to chapter 8 Troubleshooting.
The PROFIBUS prole for frequency converters species a
number of communication objects (parameter process data
objects, PPO). The PROFIBUS prole for frequency
converters is suitable for data exchange between a process
controller (for example PLC) and a frequency converter. All
PPOs are dened for cyclic data transfer (DP-V0) for
transferring process data (PCD) and parameters (PCA) from
the master to the slave, and conversely.
Pure process data objects
PPO types 3, 4, 6, 7, and 8 are pure process data objects
for applications requiring no cyclic parameter access. The
PLC sends out process control data, and the frequency
converter then responds with a PPO of the same length,
containing process status data.
Illustration 4.1 shows the available PPO types:
PCD 1: The
•
(PCD 1) comprise a xed part present in all PPO
types.
PCD 2: The next 2 bytes are
•
entries (see parameter 9-15 PCD Write Congu-
ration [1]), but congurable for PCD read entries
(see parameter 9-16 PCD Read Conguration [1]).
PCD 3–10: In the remaining bytes, the process
•
data can be parameterized with process signals,
see parameter 9-23 Parameters for Signals.
The setting in parameter 9-15 PCD Write Conguration
determines the signals for transmission (request) from the
master to the frequency converter.
rst 2 bytes of the process data area
xed for PCD write
The setting in parameter 9-16 PCD Read Conguration
determines the signals for transmission (response) from the
frequency converter to the master.
Parameter channel and process data
PPO types 1, 2, and 5 consist of a parameter channel and
process data. Use the parameter channel for reading
and/or updating of parameters (successively). Alternatively,
for better utilization of I/O and PLC capacity, access
parameters via DP-V1. To access via DP-V1, select a pure
process data object (PPO type 3, 4, 6, 7, or 8).
Select the PPO type in the master conguration. The
selection is automatically recorded in the frequency
converter. No manual setting of PPO types in the
frequency converter is required. Read the current PPO type
in parameter 9-22 Telegram Selection. The setting [1]Standard telegram 1 is equivalent to PPO type 3.
In addition, all PPO types can be set up as word-consistent
or module-consistent. The process data area can be wordor module-consistent, whereas the parameter channel
must always be module-consistent.
Word-consistent data is transmitted as individual,
•
independent words between the PLC and the
frequency converter.
Module-consistent data is transmitted as sets of
•
interrelated words transferred simultaneously
between the PLC and the frequency converter.
Use the process data part of the PPO to control and
monitor the frequency converter via the PROFIBUS.
4.2.1 Process Control Data
Process control data (PCD) is the process data sent from
the PLC to the frequency converter.
Master/slave
123.......10
CTWMRVPCD.......PCD
PCD write
Table 4.1 Process Control Data
PCD 1 contains a 16-bit control word, and each bit controls
specic function of the frequency converter, see
a
chapter 4.3 Control Prole.
PCD 2 contains a 16-bit speed setpoint in percentage
format. See chapter 4.2.3 Reference Handling.
The settings in parameter 9-15 PCD Write Conguration and
parameter 9-16 PCD Read Conguration dene the content
of PCD 3 to PCD 10.
4.2.3 Reference Handling
The reference handling is an advanced mechanism that
sums up references from dierent sources, as shown in
Illustration 4.2.
For more information on reference handling, refer to the
design guide of the relevant frequency converter.
44
Illustration 4.2 Reference
The reference, or speed setpoint, is sent via PROFIBUS and
is always transmitted to the frequency converter in
percentage format as integers shown in hexadecimal (0–
4000 hex).
4.2.2 Process Status Data
Process status data is the process data sent from the
frequency converter and contains information about the
current state.
Slave/master
123......10
STWMAVPCD......PCD
PCD read
Table 4.2 Process Status Data
PCD 1 contains a 16-bit status word, and each bit contains
information regarding a possible state of the frequency
converter.
PCD 2 contains per default the value of the current speed
of the frequency converter in percentage format (see
chapter 4.2.3 Reference Handling). PCD 2 can be congured
to contain other process signals.
The settings in parameter 9-16 PCD Read Congurationdene the content of PCD 3 to PCD 10.
The reference (MRV) and feedback (MAV) are always scaled
equally. The setting of parameter 3-00 Reference Range
determines the scaling of the reference and feedback
(MAV), see Illustration 4.3.
Illustration 4.3 Reference (MRV) and Feedback (MAV), Scaled
NOTICE
When parameter 3-00 Reference Range is set to [0] Min Max, a negative reference is handled as 0%.
The actual output of the frequency converter is limited by
the speed limit parameters Motor Low/High Speed Limit
[RPM/Hz] in parameter 4-11 Motor Speed Low Limit [RPM] to
parameter 4-14 Motor Speed High Limit [Hz].
The nal speed limit is set in parameter 4-19 Max Output
Frequency.
Table 4.3 lists the reference (MRV) and the feedback (MAV)
formats.
MRV is the process setpoint.
•
MAV expresses the actual process feedback (range
•
±200%).
4.2.5 Inuence of the Digital Input
MRV/MAVInteger in hexInteger in decimal
100%400016384
44
75%300012288
50%20008192
25%10004096
0%00
-25%F000-4096
-50%E000-8192
-75%D000-12288
-100%C000-16384
Table 4.3 Reference/Feedback (MRV/MAV) Format
NOTICE
Negative numbers are formed as complement of 2.
NOTICE
The data type for MRV and MAV is an N2 16-bit
standardized value, expressing a range from -200% to
+200% (8001 to 7FFF).
Example
The following settings determine the speed, as shown in
Table 4.4:
Parameter 1-00 Conguration Mode set to [0]
•
Speed open loop.
Parameter 3-00 Reference Range set to [0] Min-Max.
•
Parameter 3-02 Minimum Reference set to 100
•
RPM.
Parameter 3-03 Maximum Reference set to 3000
•
RPM.
Terminals on FC Control Mode
In parameter 8-50 Coasting Select to parameter 8-56 PresetReference Select, set the inuence of the digital input
terminals on the control of the frequency converter.
NOTICE
The setting of parameter 8-01 Control Site overrules the
settings in parameter 8-50 Coasting Select to
parameter 8-56 Preset Reference Select. The setting of
terminal 37 coast stop (safe) overrules any other
parameter.
Program each of the digital input signals to logic AND,
logic OR, or to have no relation to the corresponding bit in
the control word. In this way, the following signal sources
initiate a specic control command, for example stop/
coast:
Fieldbus only.
•
Fieldbus AND digital input.
•
Either eldbus OR digital input terminal.
•
NOTICE
To control the frequency converter via PROFIBUS, set
parameter 8-50 Coasting Select to either [1] Bus or [2]
Logic AND. Then set parameter 8-01 Control Site to [0]
Digital and ctrl.word or [2] Controlword only.
For more detailed information and examples of logical
relationship options, see chapter 8 Troubleshooting.
Control Prole
4.3
MRV/MAVActual speed [RPM]
0%0 hex100
25%1000 hex825
50%2000 hex1550
75%3000 hex2275
100%4000 hex3000
Table 4.4 Actual Speed for MRV/MAV
Control the frequency converter according to:
The PROFIdrive prole, see chapter 4.4 PROFIdrive
•
Control Prole, or
The Danfoss FC control, see chapter 4.5 Danfoss
•
FC Control Prole.
Select the control prole in parameter 8-10 Control WordProle. The choice of proleaects the control word and
status word only.
4.2.4 Process Control Operation
Chapter 4.4 PROFIdrive Control Prole and
In process control operation, parameter 1-00 CongurationMode is set to [3] Process.
The reference range in parameter 3-00 Reference Range is
always [0] Min - Max.
chapter 4.5 Danfoss FC Control Prole provide a detailed
description of control and status data.
ControlProgramming Guide
4.4 PROFIdrive Control Prole
This section describes the functionality of the control word
and status word in the PROFIdrive prole.
4.4.1 Control Word According to
PROFIdrive Prole (CTW)
The control word is used to send commands from a master
(for example a PC) to a slave.
BitBit=0Bit=1
00OFF 1ON 1
01OFF 2ON 2
02OFF 3ON 3
03CoastingNo coasting
04Quick stopRamp
05Hold frequency outputUse ramp
06Ramp stopStart
07No functionReset
08Jog 1 OFFJog 1 ON
09Jog 2 OFFJog 2 ON
10Data invalidData valid
11No functionSlow down
12No functionCatch up
13Parameter set-upSelection lsb
14Parameter set-upSelection msb
15No functionReverse
Table 4.5 Control Word Bits
Explanation of the control bits
Bit 00, OFF 1/ON 1
Normal ramp stops using the ramp times of the actual
selected ramp.
Bit 00=0 stops and activates the output relay 1 or 2 if the
output frequency is 0 Hz, and if [31] Relay 123 is selected
in parameter 5-40 Function Relay.
When bit 0=1, the frequency converter is in state 1,
Switching on inhibited.
Refer to Illustration 4.4.
Bit 01, OFF 2/ON 2
Coast stop.
Bit 01=0 coast stops and activates the output relay 1 or 2
if the output frequency is 0 Hz, and if [31] Relay 123 is
selected in parameter 5-40 Function Relay.
When bit 01=1, the frequency converter is in state 1,
Switching on inhibited. Refer to Illustration 4.4.
Bit 02, OFF 3/ON 3
Quick stop using the ramp time of parameter 3-81 Quick
Stop Ramp Time.
Bit 02=0 quick stops and activates the output relay 1 or 2
if the output frequency is 0 Hz, and if [31] Relay 123 is
selected in parameter 5-40 Function Relay.
When bit 02=1, the frequency converter is in state 1,
Switching on inhibited.
Refer to Illustration 4.4.
Bit 03, coasting/no coasting
Bit 03=0 leads to a coast stop.
When bit 03=1, if the other start conditions are fullled,
the frequency converter can start.
NOTICE
The selection in parameter 8-50 Coasting Select
determines how bit 03 is linked with the corresponding
function of the digital inputs.
Bit 04, quick stop/ramp
Quick stop using the ramp time of parameter 3-81 Quick
Stop Ramp Time.
When bit 04=0, a quick stop occurs.
When bit 04=1, if the other start conditions are fullled,
the frequency converter can start.
NOTICE
The selection in parameter 8-51 Quick Stop Select
determines how bit 04 is linked with the corresponding
function of the digital inputs.
Bit 05, hold frequency output/use ramp
When bit 05=0, the present output frequency is
maintained, even if the reference value is modied.
When bit 05=1, the frequency converter can perform its
regulating function again according to the respective
reference value.
Bit 06, ramp stop/start
Normal ramp stop using the ramp times of the actual
ramp selected. In addition, if [31] Relay 123 is selected in
parameter 5-40 Function Relay, and if the output frequency
is 0 Hz, this bit activates output relay 01 or 04.
Bit 06=0 stops the frequency converter.
When bit 06=1, if the other start conditions are fullled,
the frequency converter can start.
NOTICE
The selection in parameter 8-53 Start Select determines
how bit 06 is linked with the corresponding function of
the digital inputs.
Bit 07, no function/reset
Reset after switching o. Acknowledges event in fault
buer.
When bit 07=0, no reset occurs.
When there is a slope change of bit 07 to 1, a reset occurs
after switching o.
Bit 08, jog 1 OFF/ON
Activation of the pre-programmed speed in
parameter 8-90 Bus Jog 1 Speed. JOG 1 is only possible if bit
04=0 and bits 00–03=1.
Bit 09, jog 2 OFF/ON
Activation of the pre-programmed speed in
parameter 8-91 Bus Jog 2 Speed. JOG 2 is only possible if bit
Tells the frequency converter whether to use or ignore the
control word.
Bit 10=0 ignores the control word, making it possible to
turn o the control word when updating/reading
parameters.
Bit 10=1 uses the control word. This function is relevant,
because the control word is always contained in the
telegram, regardless of which type of telegram is used.
44
Bit 11, no function/slow down
Used to reduce the speed reference value by the amount
given in parameter 3-12 Catch up/slow Down Value.
When bit 11=0, no modication of the reference value
occurs.
When bit 11=1, the reference value is reduced.
Bit 12, no function/catch up
Used to increase the speed reference value by the amount
given in parameter 3-12 Catch up/slow Down Value.
When bit 12=0, no modication of the reference value
occurs.
When bit 12=1, the reference value is increased.
If both slowing down and accelerating are activated (bits
11 and 12=1), slowing down has priority, and the speed
reference value is reduced.
Bits 13/14, set-up selection
Bits 13 and 14 are used to select between the 4 parameter
set-ups according to Table 4.6.
The function is only possible if [9] Multi Set-up has been
selected in parameter 0-10 Active Set-up. The selection in
parameter 8-55 Set-up Select determines how bits 13 and
14 are linked with the corresponding function of the
digital inputs. Changing set-up while running is only
possible if the set-ups have been linked in
parameter 0-12 This Set-up Linked to.
Set-upBit 13Bit 14
100
210
301
411
Table 4.6 Parameter Set-ups
Bit 15, no function/reverse
Bit 15=0 causes no reversing.
Bit 15=1 causes reversing.
NOTICE
In the factory setting, reversing is set to [0] Digital in
parameter 8-54 Reversing Select.
NOTICE
Bit 15 causes reversing only when Ser. communication,
Logic or, or Logic and is selected.
4.4.2 Status Word According to PROFIdrive
Prole (STW)
The status word is used to notify a master (for example a
PC) about the status of a slave.
BitBit=0Bit=1
00Control not readyControl ready
01Drive not readyDrive ready
02CoastingEnable
03No errorTrip
04OFF 2ON 2
05OFF 3ON 3
06Start possibleStart not possible
07No warningWarning
08
09Local operationBus control
10Out of frequency limit Frequency limit ok
11No operationIn operation
12Drive OKStopped, auto start
13Voltage OKVoltage exceeded
14Torque OKTorque exceeded
15Timer OKTimer exceeded
Table 4.7 Status Word Bits
Explanation of the status bits
Bit 00, control not ready/ready
When bit 00=0, bit 00, 01, or 02 of the control word is 0
(OFF 1, OFF 2, or OFF 3) - or the frequency converter is
switched
When bit 00=1, the frequency converter control is ready,
but power is not necessarily supplied to the unit (in the
event of 24 V external supply of the control system).
Bit 01, VLT not ready/ready
Same signicance as bit 00, however, power is supplied to
the unit. The frequency converter is ready when it receives
the necessary start signals.
Bit 02, coasting/enable
When bit 02=0, bit 00, 01, or 02 of the control word is 0
(OFF 1, OFF 2, or OFF 3 or coasting) - or the frequency
converter is switched o (trip).
When bit 02=1, bit 00, 01, or 02 of the control word is 1,
and the frequency converter has not tripped.
Bit 03, no error/trip
When bit 03=0, no error condition exists in the frequency
converter.
When bit 03=1, the frequency converter has tripped and
requires a reset signal before it can start.
Bit 04, ON 2/OFF 2
When bit 01 of the control word is 0, bit 04=0.
When bit 01 of the control word is 1, bit 04=1.
Bit 05, ON 3/OFF 3
When bit 02 of the control word is 0, bit 05=0.
When bit 02 of the control word is 1, bit 05=1.