The VLT® PROFIBUS DP MCA 101 Programming Guide
provides information about:
Conguring the system.
•
Controlling the frequency converter.
•
Parameter access.
•
Programming.
•
Troubleshooting.
•
Typical application examples.
•
The programming guide is intended for use by qualied
personnel familiar with the VLT® frequency converter, with
PROFIBUS technology, and with the PC or PLC used as a
master in the system.
Read the instructions before programming and follow the
procedures in this manual.
VLT® is a registered trademark.
1.2 Additional Resources
Resources available for the frequency converters and
optional equipment:
The VLT® Operating Instructions provide the
•
necessary information for getting the frequency
converter up and running.
®
The VLT
•
information about capabilities and functionality
to design motor control systems.
The VLT® Programming Guide provides greater
•
detail on working with parameters and many
application examples.
The VLT® PROFIBUS DP MCA 101 Installation Guide
•
provides information about installing the
PROFIBUS and troubleshooting.
The VLT® PROFIBUS DP MCA 101 Programming
•
Guide provides information about conguring the
system, controlling the frequency converter,
parameter access, programming, troubleshooting,
and some typical application examples.
Supplementary publications and manuals are available
from Danfoss. See vlt-drives.danfoss.com/Support/Technical-
Documentation/ for listings.
Design Guide provides detailed
Document and Software Version
1.3
This manual is regularly reviewed and updated. All
suggestions for improvement are welcome. Table 1.1 shows
the document version and the corresponding software
version.
EditionRemarksSoftware
version
MG37G2xx
Table 1.1 Document and Software Version
Information about VLT® DriveMotor
•
FCP 106/FCM 106 added.
New feature for fast PCD communi-
•
cation for MCO 305.
5.20
1.4 Product Overview
1.4.1 Features of PROFIBUS DP-V1
2 dierent state machines can be selected:
•
PROFIdrive prole or Danfoss FC prole.
Communication using PROFIBUS DP-V1, master
•
class 1, and master class 2.
Backward compatibility: New protocol extensions
•
retain all the functions of the previous versions.
PROFIBUS is an international standard for eldbus
communication in automation technology (IEC 61158 and
IEC 61784). The member companies of the PROFIBUS
International User Community support the standard.
For information about PROFIBUS and downloads for
PROFIBUS DP and the PROFIdrive prole, refer to
www.Probus.com.
PROFIBUS DP-V1
The PROFIBUS DP protocol enables communication
between PROFIBUS masters and slaves.
Congure communication via MCT 10 Set-up Software.
Cyclic/acyclic communication
PLC communicates with telegrams of constant
•
length.
Fits time-critical requirements.
•
Cyclic transmission via PPO types.
•
Extended diagnosis.
•
for general parameter access as an alternative to the PCV
parameter channel.
Illustration 1.2 PROFIBUS DP-V1
The PROFIBUS DP extension DP-V1 allows acyclic as well as
cyclic data communication. This feature can be used by a
DP master class 1, for example PLC, as well as a DP master
class 2, for example PC tool.
Illustration 1.1 PROFIBUS DP-V0
Features of a master class 1 connection:
Cyclic data exchange (DP-V0).
•
The acyclic connection is xed and cannot be changed
during operation.
Features of a master class 2 connection:
The acyclic connection can be established (initiated) or
removed (aborted) dynamically even when a master class 1
is active on the network. Use the DP-V1 acyclic connection
Acyclic read/write on parameters.
•
•
•
•
Extended diagnosis.
Initiate/abort acyclic connection.
Acyclic read/write on parameters.
Approvals and Certications
1.5
More approvals and certications are available. For more
information, contact a local Danfoss partner.
Indicates a potentially hazardous situation that could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could
result in minor or moderate injury. It can also be used to
alert against unsafe practices.
NOTICE
Indicates important information, including situations that
can result in damage to equipment or property.
2.2 Qualied Personnel
Correct and reliable transport, storage, installation,
operation, and maintenance are required for the troublefree and safe operation of the frequency converter. Only
qualied personnel are allowed to install and operate this
equipment.
Qualied personnel are dened as trained sta, who are
authorized to install, commission, and maintain equipment,
systems, and circuits in accordance with pertinent laws and
regulations. Also, the qualied personnel must be familiar
with the instructions and safety measures described in
these operating instructions.
Safety Precautions
2.3
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when
connected to AC mains input, DC supply, or load sharing.
Failure to perform installation, start-up, and maintenance
by qualied personnel can result in death or serious
injury.
Only qualied personnel must perform instal-
•
lation, start-up, and maintenance.
WARNING
UNINTENDED START
When the frequency converter is connected to AC mains,
DC supply, or load sharing, the motor may start at any
time. Unintended start during programming, service, or
repair work can result in death, serious injury, or
property damage. The motor can start with an external
switch, a eldbus command, an input reference signal
from the LCP or LOP, via remote operation using MCT 10
Set-up Software, or after a cleared fault condition.
To prevent unintended motor start:
Press [O/Reset] on the LCP before
•
programming parameters.
Disconnect the frequency converter from the
•
mains.
Completely wire and assemble the frequency
•
converter, motor, and any driven equipment
before connecting the frequency converter to
AC mains, DC supply, or load sharing.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors,
which can remain charged even when the frequency
converter is not powered. High voltage can be present
even when the warning LED indicator lights are o.
Failure to wait the specied time after power has been
removed before performing service or repair work can
result in death or serious injury.
Stop the motor.
•
Disconnect AC mains and remote DC-link power
•
supplies, including battery back-ups, UPS, and
DC-link connections to other frequency
converters.
Disconnect or lock PM motor.
•
Wait for the capacitors to discharge fully. The
•
minimum duration of waiting time is specied
in the chapter Safety in the operatinginstructions supplied with the frequency
converter.
Before performing any service or repair work,
•
use an appropriate voltage measuring device to
make sure that the capacitors are fully
discharged.
2.Set the DIP switch to 126 or 127 (factory switch
setting).
3.Set the address via parameter 9-18 Node Address
or the PROFIBUS SSA-command.
4.The address change comes into eect at the next
power-up.
130BC915.10
130BC913.11
CongurationProgramming Guide
Setting the PROFIBUS address with set station address
command
1.Switch o the supply.
2.Set the DIP switch to 126 or 127 (factory switch
setting).
3.Set the address via the set station address
command. Use the set station address command
to lock the programmed address and to change
the address. To unlock the address setting,
change parameter 9-18 Node Address or the
address switch, followed by a power cycle. A new
address is eective immediately after applying
the set station address command.
3.2 Congure the Master
3.2.1 GSD File
To congure a PROFIBUS master, the conguration tool
needs a GSD le for each type of slave on the network.
The GSD le is a PROFIBUS DP standard text le containing
the necessary communications set-up data for a slave.
Download the GSD
converter series vlt-drives.danfoss.com/products/engineering-software/software-download/eldbus/.
le for the relevant frequency
33
Illustration 3.3 Install GSD File
PROFIBUS SW version
(parameter 15-61 Option SW
Version)
1.xda01040A.GSD
2.xda02040A.GSD
FCD 302da01040B.GSD
Table 3.2 GSD File
The following example shows the procedure of
a PROFIBUS master for FC 301/FC 302, but the procedure is
also valid for other frequency converter series.
1.Import the GSD
2.Import the GSD le to the Simatic Manager
software tool. Import a GSD le once only for
each frequency converter series, following the
initial installation of the software tool. See
Illustration 3.3.
3.Use the browser for the GSD le, install all les,
and import both a GSD le and a bitmap for the
device into the hardware catalog. See
Illustration 3.4 and Illustration 3.5.
4.Import and access the FC 301/FC 302 GSD le via
the path in the hardware catalog, see
Illustration 3.6.
8.Set up the peripheral input and output data. Data
set up in the peripheral area is transmitted
cyclically via PPO types. Drag and drop a PPO
type 6 word consistent to the rst slot, see
Illustration 3.8. See the PPO types in
chapter 4 Control for more information.
33
Illustration 3.6 Import and Access the GSD File
Illustration 3.8 Drag and Drop PPO Type 6 Word Consistent to
5.Open a project, set up the hardware, and add a
PROFIBUS master system.
6.Select FC 300, then drag and drop it onto the
PROFIBUS in the hardware diagram.
7.A window for the address of the FC 300 appears.
Select the address from the scroll-down list.
Ensure that the address setting matches the
previous address setting in parameter 9-18 NodeAddress. See Illustration 3.7.
the First Slot
The conguration tool automatically assigns addresses in
the peripheral address area. In this example, the input and
output areas have the following congurations:
Alternative: For PROFIBUS SW version 2.x and higher, autoconguration of process data is supported. This feature
makes it possible to congure the process data
(parameter 9-15 PCD Write Conguration and
parameter 9-16 PCD Read Conguration) from the PLC/
master. To use auto-conguration, make sure to enable the
feature under DP slave properties. See Illustration 3.9.
Illustration 3.9 Enable Feature under DP Slave Properties
NOTICE
DP-V1 diagnosis is supported for PROFIBUS SW version
2.x and higher. The default setting of the VLT® PROFIBUS
DP MCA 101 is DP-V1 diagnosis. If DP-V0 diagnosis is
required, change the setting under DP slave properties.
Congure the Frequency Converter
3.3
3.3.1 Frequency Converter Parameters
The following parameters are important when conguring
the frequency converter with a PROFIBUS interface:
Parameter 0-40 [Hand on] Key on LCP. Pressing
•
[Hand on] disables control of the frequency
converter via PROFIBUS.
Parameter 8-02 Control Word Source. After an
•
initial power-up, the frequency converter
automatically detects whether a eldbus option is
installed in slot A. The frequency converter then
sets parameter 8-02 Control Word Source to [3]Option A. If an option is added to, changed in, or
removed from an already commissioned
frequency converter, it does not change
parameter 8-02 Control Word Source. Instead, the
frequency converter enters trip mode and shows
an error.
Parameter 8-10 Control Word Prole. Select
•
between the Danfoss FC Prole and the
PROFIdrive prole.
Parameter 8-50 Coasting Select to
•
parameter 8-56 Preset Reference Select. Select how
to gate PROFIBUS control commands with digital
input command of the control card.
Parameter 8-03 Control Word Timeout Time to
•
parameter 8-05 End-of-Timeout Function. Set the
reaction in the event of a bus timeout via these
parameters.
Parameter 9-18 Node Address.
•
Parameter 8-07 Diagnosis Trigger.
•
33
NOTICE
The setting in parameter 8-01 Control Site overrides the
settings in parameter 8-50 Coasting Select to
parameter 8-56 Preset Reference Select, and they all act on
bus control.
Illustration 3.10 DP-V1 Diagnosis
Download the congurationle to the PLC. The PROFIBUS
system is able to go online, and it starts to exchange data
when the PLC is set to run mode.
The 2 bicolor LEDs in the VLT® PROFIBUS DP MCA 101
indicate the status of PROFIBUS communication.
33
The LED marked NS (FCD 302: NS2) indicates the network
status, that is, the cyclic communication to the PROFIBUS
master. When this light is a constant green, data exchange
between the master and the frequency converter is active.
The LED marked MS (FCD 302: BUS MS) indicates the
module status, that is, acyclic DP-V1 communication from
either a PROFIBUS master class 1 (PLC) or a master class 2
(MCT 10 Set-up Software, FDT tool). When this light is a
constant green, DP-V1 communication from master classes
1 and 2 is active.
For details of the full range of communications status
indicated by the LEDs, refer to chapter 8 Troubleshooting.
The PROFIBUS prole for frequency converters species a
number of communication objects (parameter process data
objects, PPO). The PROFIBUS prole for frequency
converters is suitable for data exchange between a process
controller (for example PLC) and a frequency converter. All
PPOs are dened for cyclic data transfer (DP-V0) for
transferring process data (PCD) and parameters (PCA) from
the master to the slave, and conversely.
Pure process data objects
PPO types 3, 4, 6, 7, and 8 are pure process data objects
for applications requiring no cyclic parameter access. The
PLC sends out process control data, and the frequency
converter then responds with a PPO of the same length,
containing process status data.
Illustration 4.1 shows the available PPO types:
PCD 1: The
•
(PCD 1) comprise a xed part present in all PPO
types.
PCD 2: The next 2 bytes are
•
entries (see parameter 9-15 PCD Write Congu-
ration [1]), but congurable for PCD read entries
(see parameter 9-16 PCD Read Conguration [1]).
PCD 3–10: In the remaining bytes, the process
•
data can be parameterized with process signals,
see parameter 9-23 Parameters for Signals.
The setting in parameter 9-15 PCD Write Conguration
determines the signals for transmission (request) from the
master to the frequency converter.
rst 2 bytes of the process data area
xed for PCD write
The setting in parameter 9-16 PCD Read Conguration
determines the signals for transmission (response) from the
frequency converter to the master.
Parameter channel and process data
PPO types 1, 2, and 5 consist of a parameter channel and
process data. Use the parameter channel for reading
and/or updating of parameters (successively). Alternatively,
for better utilization of I/O and PLC capacity, access
parameters via DP-V1. To access via DP-V1, select a pure
process data object (PPO type 3, 4, 6, 7, or 8).
Select the PPO type in the master conguration. The
selection is automatically recorded in the frequency
converter. No manual setting of PPO types in the
frequency converter is required. Read the current PPO type
in parameter 9-22 Telegram Selection. The setting [1]Standard telegram 1 is equivalent to PPO type 3.
In addition, all PPO types can be set up as word-consistent
or module-consistent. The process data area can be wordor module-consistent, whereas the parameter channel
must always be module-consistent.
Word-consistent data is transmitted as individual,
•
independent words between the PLC and the
frequency converter.
Module-consistent data is transmitted as sets of
•
interrelated words transferred simultaneously
between the PLC and the frequency converter.
Use the process data part of the PPO to control and
monitor the frequency converter via the PROFIBUS.
4.2.1 Process Control Data
Process control data (PCD) is the process data sent from
the PLC to the frequency converter.
Master/slave
123.......10
CTWMRVPCD.......PCD
PCD write
Table 4.1 Process Control Data
PCD 1 contains a 16-bit control word, and each bit controls
specic function of the frequency converter, see
a
chapter 4.3 Control Prole.
PCD 2 contains a 16-bit speed setpoint in percentage
format. See chapter 4.2.3 Reference Handling.
The settings in parameter 9-15 PCD Write Conguration and
parameter 9-16 PCD Read Conguration dene the content
of PCD 3 to PCD 10.
4.2.3 Reference Handling
The reference handling is an advanced mechanism that
sums up references from dierent sources, as shown in
Illustration 4.2.
For more information on reference handling, refer to the
design guide of the relevant frequency converter.
44
Illustration 4.2 Reference
The reference, or speed setpoint, is sent via PROFIBUS and
is always transmitted to the frequency converter in
percentage format as integers shown in hexadecimal (0–
4000 hex).
4.2.2 Process Status Data
Process status data is the process data sent from the
frequency converter and contains information about the
current state.
Slave/master
123......10
STWMAVPCD......PCD
PCD read
Table 4.2 Process Status Data
PCD 1 contains a 16-bit status word, and each bit contains
information regarding a possible state of the frequency
converter.
PCD 2 contains per default the value of the current speed
of the frequency converter in percentage format (see
chapter 4.2.3 Reference Handling). PCD 2 can be congured
to contain other process signals.
The settings in parameter 9-16 PCD Read Congurationdene the content of PCD 3 to PCD 10.
The reference (MRV) and feedback (MAV) are always scaled
equally. The setting of parameter 3-00 Reference Range
determines the scaling of the reference and feedback
(MAV), see Illustration 4.3.
Illustration 4.3 Reference (MRV) and Feedback (MAV), Scaled
NOTICE
When parameter 3-00 Reference Range is set to [0] Min Max, a negative reference is handled as 0%.
The actual output of the frequency converter is limited by
the speed limit parameters Motor Low/High Speed Limit
[RPM/Hz] in parameter 4-11 Motor Speed Low Limit [RPM] to
parameter 4-14 Motor Speed High Limit [Hz].
The nal speed limit is set in parameter 4-19 Max Output
Frequency.
Table 4.3 lists the reference (MRV) and the feedback (MAV)
formats.
MRV is the process setpoint.
•
MAV expresses the actual process feedback (range
•
±200%).
4.2.5 Inuence of the Digital Input
MRV/MAVInteger in hexInteger in decimal
100%400016384
44
75%300012288
50%20008192
25%10004096
0%00
-25%F000-4096
-50%E000-8192
-75%D000-12288
-100%C000-16384
Table 4.3 Reference/Feedback (MRV/MAV) Format
NOTICE
Negative numbers are formed as complement of 2.
NOTICE
The data type for MRV and MAV is an N2 16-bit
standardized value, expressing a range from -200% to
+200% (8001 to 7FFF).
Example
The following settings determine the speed, as shown in
Table 4.4:
Parameter 1-00 Conguration Mode set to [0]
•
Speed open loop.
Parameter 3-00 Reference Range set to [0] Min-Max.
•
Parameter 3-02 Minimum Reference set to 100
•
RPM.
Parameter 3-03 Maximum Reference set to 3000
•
RPM.
Terminals on FC Control Mode
In parameter 8-50 Coasting Select to parameter 8-56 PresetReference Select, set the inuence of the digital input
terminals on the control of the frequency converter.
NOTICE
The setting of parameter 8-01 Control Site overrules the
settings in parameter 8-50 Coasting Select to
parameter 8-56 Preset Reference Select. The setting of
terminal 37 coast stop (safe) overrules any other
parameter.
Program each of the digital input signals to logic AND,
logic OR, or to have no relation to the corresponding bit in
the control word. In this way, the following signal sources
initiate a specic control command, for example stop/
coast:
Fieldbus only.
•
Fieldbus AND digital input.
•
Either eldbus OR digital input terminal.
•
NOTICE
To control the frequency converter via PROFIBUS, set
parameter 8-50 Coasting Select to either [1] Bus or [2]
Logic AND. Then set parameter 8-01 Control Site to [0]
Digital and ctrl.word or [2] Controlword only.
For more detailed information and examples of logical
relationship options, see chapter 8 Troubleshooting.
Control Prole
4.3
MRV/MAVActual speed [RPM]
0%0 hex100
25%1000 hex825
50%2000 hex1550
75%3000 hex2275
100%4000 hex3000
Table 4.4 Actual Speed for MRV/MAV
Control the frequency converter according to:
The PROFIdrive prole, see chapter 4.4 PROFIdrive
•
Control Prole, or
The Danfoss FC control, see chapter 4.5 Danfoss
•
FC Control Prole.
Select the control prole in parameter 8-10 Control WordProle. The choice of proleaects the control word and
status word only.
4.2.4 Process Control Operation
Chapter 4.4 PROFIdrive Control Prole and
In process control operation, parameter 1-00 CongurationMode is set to [3] Process.
The reference range in parameter 3-00 Reference Range is
always [0] Min - Max.
chapter 4.5 Danfoss FC Control Prole provide a detailed
description of control and status data.
ControlProgramming Guide
4.4 PROFIdrive Control Prole
This section describes the functionality of the control word
and status word in the PROFIdrive prole.
4.4.1 Control Word According to
PROFIdrive Prole (CTW)
The control word is used to send commands from a master
(for example a PC) to a slave.
BitBit=0Bit=1
00OFF 1ON 1
01OFF 2ON 2
02OFF 3ON 3
03CoastingNo coasting
04Quick stopRamp
05Hold frequency outputUse ramp
06Ramp stopStart
07No functionReset
08Jog 1 OFFJog 1 ON
09Jog 2 OFFJog 2 ON
10Data invalidData valid
11No functionSlow down
12No functionCatch up
13Parameter set-upSelection lsb
14Parameter set-upSelection msb
15No functionReverse
Table 4.5 Control Word Bits
Explanation of the control bits
Bit 00, OFF 1/ON 1
Normal ramp stops using the ramp times of the actual
selected ramp.
Bit 00=0 stops and activates the output relay 1 or 2 if the
output frequency is 0 Hz, and if [31] Relay 123 is selected
in parameter 5-40 Function Relay.
When bit 0=1, the frequency converter is in state 1,
Switching on inhibited.
Refer to Illustration 4.4.
Bit 01, OFF 2/ON 2
Coast stop.
Bit 01=0 coast stops and activates the output relay 1 or 2
if the output frequency is 0 Hz, and if [31] Relay 123 is
selected in parameter 5-40 Function Relay.
When bit 01=1, the frequency converter is in state 1,
Switching on inhibited. Refer to Illustration 4.4.
Bit 02, OFF 3/ON 3
Quick stop using the ramp time of parameter 3-81 Quick
Stop Ramp Time.
Bit 02=0 quick stops and activates the output relay 1 or 2
if the output frequency is 0 Hz, and if [31] Relay 123 is
selected in parameter 5-40 Function Relay.
When bit 02=1, the frequency converter is in state 1,
Switching on inhibited.
Refer to Illustration 4.4.
Bit 03, coasting/no coasting
Bit 03=0 leads to a coast stop.
When bit 03=1, if the other start conditions are fullled,
the frequency converter can start.
NOTICE
The selection in parameter 8-50 Coasting Select
determines how bit 03 is linked with the corresponding
function of the digital inputs.
Bit 04, quick stop/ramp
Quick stop using the ramp time of parameter 3-81 Quick
Stop Ramp Time.
When bit 04=0, a quick stop occurs.
When bit 04=1, if the other start conditions are fullled,
the frequency converter can start.
NOTICE
The selection in parameter 8-51 Quick Stop Select
determines how bit 04 is linked with the corresponding
function of the digital inputs.
Bit 05, hold frequency output/use ramp
When bit 05=0, the present output frequency is
maintained, even if the reference value is modied.
When bit 05=1, the frequency converter can perform its
regulating function again according to the respective
reference value.
Bit 06, ramp stop/start
Normal ramp stop using the ramp times of the actual
ramp selected. In addition, if [31] Relay 123 is selected in
parameter 5-40 Function Relay, and if the output frequency
is 0 Hz, this bit activates output relay 01 or 04.
Bit 06=0 stops the frequency converter.
When bit 06=1, if the other start conditions are fullled,
the frequency converter can start.
NOTICE
The selection in parameter 8-53 Start Select determines
how bit 06 is linked with the corresponding function of
the digital inputs.
Bit 07, no function/reset
Reset after switching o. Acknowledges event in fault
buer.
When bit 07=0, no reset occurs.
When there is a slope change of bit 07 to 1, a reset occurs
after switching o.
Bit 08, jog 1 OFF/ON
Activation of the pre-programmed speed in
parameter 8-90 Bus Jog 1 Speed. JOG 1 is only possible if bit
04=0 and bits 00–03=1.
Bit 09, jog 2 OFF/ON
Activation of the pre-programmed speed in
parameter 8-91 Bus Jog 2 Speed. JOG 2 is only possible if bit
Tells the frequency converter whether to use or ignore the
control word.
Bit 10=0 ignores the control word, making it possible to
turn o the control word when updating/reading
parameters.
Bit 10=1 uses the control word. This function is relevant,
because the control word is always contained in the
telegram, regardless of which type of telegram is used.
44
Bit 11, no function/slow down
Used to reduce the speed reference value by the amount
given in parameter 3-12 Catch up/slow Down Value.
When bit 11=0, no modication of the reference value
occurs.
When bit 11=1, the reference value is reduced.
Bit 12, no function/catch up
Used to increase the speed reference value by the amount
given in parameter 3-12 Catch up/slow Down Value.
When bit 12=0, no modication of the reference value
occurs.
When bit 12=1, the reference value is increased.
If both slowing down and accelerating are activated (bits
11 and 12=1), slowing down has priority, and the speed
reference value is reduced.
Bits 13/14, set-up selection
Bits 13 and 14 are used to select between the 4 parameter
set-ups according to Table 4.6.
The function is only possible if [9] Multi Set-up has been
selected in parameter 0-10 Active Set-up. The selection in
parameter 8-55 Set-up Select determines how bits 13 and
14 are linked with the corresponding function of the
digital inputs. Changing set-up while running is only
possible if the set-ups have been linked in
parameter 0-12 This Set-up Linked to.
Set-upBit 13Bit 14
100
210
301
411
Table 4.6 Parameter Set-ups
Bit 15, no function/reverse
Bit 15=0 causes no reversing.
Bit 15=1 causes reversing.
NOTICE
In the factory setting, reversing is set to [0] Digital in
parameter 8-54 Reversing Select.
NOTICE
Bit 15 causes reversing only when Ser. communication,
Logic or, or Logic and is selected.
4.4.2 Status Word According to PROFIdrive
Prole (STW)
The status word is used to notify a master (for example a
PC) about the status of a slave.
BitBit=0Bit=1
00Control not readyControl ready
01Drive not readyDrive ready
02CoastingEnable
03No errorTrip
04OFF 2ON 2
05OFF 3ON 3
06Start possibleStart not possible
07No warningWarning
08
09Local operationBus control
10Out of frequency limit Frequency limit ok
11No operationIn operation
12Drive OKStopped, auto start
13Voltage OKVoltage exceeded
14Torque OKTorque exceeded
15Timer OKTimer exceeded
Table 4.7 Status Word Bits
Explanation of the status bits
Bit 00, control not ready/ready
When bit 00=0, bit 00, 01, or 02 of the control word is 0
(OFF 1, OFF 2, or OFF 3) - or the frequency converter is
switched
When bit 00=1, the frequency converter control is ready,
but power is not necessarily supplied to the unit (in the
event of 24 V external supply of the control system).
Bit 01, VLT not ready/ready
Same signicance as bit 00, however, power is supplied to
the unit. The frequency converter is ready when it receives
the necessary start signals.
Bit 02, coasting/enable
When bit 02=0, bit 00, 01, or 02 of the control word is 0
(OFF 1, OFF 2, or OFF 3 or coasting) - or the frequency
converter is switched o (trip).
When bit 02=1, bit 00, 01, or 02 of the control word is 1,
and the frequency converter has not tripped.
Bit 03, no error/trip
When bit 03=0, no error condition exists in the frequency
converter.
When bit 03=1, the frequency converter has tripped and
requires a reset signal before it can start.
Bit 04, ON 2/OFF 2
When bit 01 of the control word is 0, bit 04=0.
When bit 01 of the control word is 1, bit 04=1.
Bit 05, ON 3/OFF 3
When bit 02 of the control word is 0, bit 05=0.
When bit 02 of the control word is 1, bit 05=1.
If [1] PROFIdrive has been selected in
parameter 8-10 Control Word Prole, bit 06 is 1 after a
switch-o acknowledgement, after activation of OFF2 or
OFF3, and after switching on the mains voltage. To reset
Start not possible, set bit 00 of the control word to 0, and
bits 01, 02, and 10 to 1.
Bit 07, no warning/warning
Bit 07=0 means that there are no warnings.
Bit 07=1 means that a warning has occurred.
Bit 08, speed≠reference/speed=reference
When bit 08=0, the current speed of the motor deviates
from the set speed reference value. The deviation may
occur, for example, when the speed is being changed
during start/stop through ramp up/down.
When bit 08=1, the current speed of the motor
corresponds to the set speed reference value.
Bit 09, local operation/bus control
Bit 09=0 indicates that the frequency converter has been
stopped with [Stop] on the LCP, or that [0] Linked to hand
or [2] Local has been selected in parameter 3-13 ReferenceSite.
When bit 09=1, the frequency converter can be controlled
through the serial interface.
Bit 10, out of frequency limit/frequency limit OK
When bit 10=0, the output frequency is outside the limits
set in parameter 4-52 Warning Speed Low and
parameter 4-53 Warning Speed High.
When bit 10=1, the output frequency is within the
indicated limits.
Bit 11, no operation/operation
When bit 11=0, the motor does not turn.
When bit 11=1, the frequency converter has a start signal,
or the output frequency is higher than 0 Hz.
Bit 12, drive OK/stopped, auto start
When bit 12=0, there is no temporary overload of the
inverter.
When bit 12=1, the frequency converter has stopped due
to overload. However, the frequency converter has not
switched o (tripped) and starts again after the overload
has ended.
Bit 13, voltage OK/voltage exceeded
When bit 13=0, the voltage limits of the frequency
converter are not exceeded.
When bit 13=1, the direct voltage in the DC link of the
frequency converter is too low or too high.
Bit 14, torque OK/torque exceeded
When bit 14=0, the motor torque is below the limit
selected in parameter 4-16 Torque Limit Motor Mode and
parameter 4-17 Torque Limit Generator Mode.
When bit 14=1, the limit selected in parameter 4-16 Torque
Limit Motor Mode or parameter 4-17 Torque Limit Generator
Mode is exceeded.
Bit 15, timer OK/timer exceeded
When bit 15=0, the timers for the motor thermal
protection and thermal frequency converter protection
have not exceeded 100%.
When bit 15=1, a timer has exceeded 100%.
In the PROFIdrive control prole, the control bits:
0–3 perform the basic start-up/power-down functions.
•
4–15 perform application-oriented control.
•
Illustration 4.4 shows the basic state transition diagram, where control bits 0–3 control the transitions, and the corresponding
status bit indicates the actual state. The black bullets indicate the priority of the control signals, where fewer bullets indicate
44
lower priority, and more bullets indicate higher priority.
Illustration 4.4 PROFIdrive State Transition Diagram
To select Danfoss FC protocol in the control word, set
parameter 8-10 Control Word Prole to [0] Frequency
converter prole. Use the control word to send commands
from a master (PLC or PC) to a slave (frequency converter).
BitBit value=0Bit value=1
00Reference valueExternal selection lsb
01Reference valueExternal selection msb
02DC brakeRamp
03CoastingNo coasting
04Quick stopRamp
05Hold output frequencyUse ramp
06Ramp stopStart
07No functionReset
08No functionJog
09Ramp 1Ramp 2
10Data invalidData valid
11No functionRelay 01 active
12No functionRelay 04 active
13Parameter set-upSelection lsb
14Parameter set-upSelection msb
15No functionReverse
Table 4.8 Bit Values for FC Control Word
Explanation of the control bits
Bits 00/01 reference value
Use bits 00 and 01 to select between the 4 reference
values, which are pre-programmed in parameter 3-10 PresetReference according to Table 4.9.
NOTICE
In parameter 8-56 Preset Reference Select, a selection is
made to dene how bit 00/01 gates with the
corresponding function on the digital inputs.
Bit 01Bit 00Programmed
reference value
001[0]
012[1]
103[2]
114[3]
Table 4.9 Programmed Reference Values for Bits
Parameter
Parameter 3-10 Preset
Reference
Parameter 3-10 Preset
Reference
Parameter 3-10 Preset
Reference
Parameter 3-10 Preset
Reference
Bit 02, DC brake
Bit 02=0 leads to DC braking and stop. Braking current and
duration are set in parameter 2-01 DC Brake Current and
parameter 2-02 DC Braking Time.
Bit 02=1 leads to ramping.
Bit 03, coasting
Bit 03=0 causes the frequency converter immediately to
coast the motor to a standstill.
Bit 03=1 enables the frequency converter to start the
motor if the other starting conditions have been fullled.
NOTICE
In parameter 8-50 Coasting Select, a selection is made to
dene how bit 03 gates with the corresponding function
on a digital input.
Bit 04, quick stop
Bit 04=0 quick stops the frequency converter and ramps
the motor speed down to stop via parameter 3-81 QuickStop Ramp Time.
Bit 04=1 makes the frequency converter ramp the motor
speed down to stop via parameter 3-42 Ramp 1 RampDown Time or parameter 3-52 Ramp 2 Ramp Down Time.
Bit 05, hold output frequency
Bit 05=0 freezes the present output frequency (in Hz). The
frozen output frequency can only be changed with the
digital inputs (parameter 5-10 Terminal 18 Digital Input to
parameter 5-15 Terminal 33 Digital Input) programmed to
[21] Speed up and [22] Speed down.
If freeze output is active, stop the frequency converter
with
Bit 03 coast stop.
•
Bit 02 DC brake.
•
Digital input (parameter 5-10 Terminal 18 Digital
•
Input to parameter 5-15 Terminal 33 Digital
44
Bit 06, ramp stop/start
Bit 06=0 stops the frequency converter and the motor
speed ramps down to stop via the selected ramp-down
parameter.
Bit 06=1 allows the frequency converter to start the motor
if the other starting conditions have been fullled.
Input) programmed to DC braking, coasting stop,
or reset and coasting stop.
Bit 13/14, selection of set-up
Use bits 13 and 14 to select from the 4 menu set-ups
according to Table 4.10:
The function is only possible when [9] Multi Set-ups is
selected in parameter 0-10 Active Set-up.
Set-upBit 14Bit 13
100
201
310
411
Table 4.10 Set-up selection
NOTICE
In parameter 8-55 Set-up Select, dene how bit 13/14
gates with the corresponding function on the digital
inputs.
NOTICE
In parameter 8-53 Start Select, dene how bit 06 ramp
stop/start gates with the corresponding function on a
digital input.
Bit 07, reset
Bit 07=0 does not cause a reset.
Bit 07=1 resets a trip. Reset is activated on the signal’s
leading edge, that is, when changing from logic 0 to logic
1.
Bit 08, jog
Bit 08=0, no function.
Bit 08=1, parameter 3-19 Jog Speed [RPM] determines the
output frequency.
Bit 09, selection of ramp 1/2
Bit 09=0, ramp 1 is active (parameter 3-40 Ramp 1 Type to
parameter 3-47 Ramp 1 S-ramp Ratio at Decel. Start).
Bit 09=1, ramp 2 is active (parameter 3-50 Ramp 2 Type to
parameter 3-57 Ramp 2 S-ramp Ratio at Decel. Start).
Bit 10, data not valid/data valid
Tells the frequency converter to use or ignore the control
word.
Bit 10=0 ignores the control word.
Bit 10=1 uses the control word. This function is relevant,
because the control word is always contained in the
telegram, regardless of which type of telegram is used.
Thus, it is possible to turn o the control word, if it is not
needed when updating or reading parameters.
Bit 11, relay 01
Bit 11=0, relay 01 is not activated.
Bit 11=1, relay 01 is activated, provided control word bit 11
is selected in parameter 5-40 Function Relay.
Bit 12, relay 04
Bit 12=0, relay 04 is not activated.
Bit 12=1, relay 04 is activated, provided [37] Control wordbit 12 is selected in parameter 5-40 Function Relay.
Bit 15 reverse
Bit 15=0 means no reversing.
Bit 15=1 means reversing.
4.5.2 Status Word According to FC Prole
(STW)
The status word is used to inform the master (for example
a PC) of the operating mode of the slave (frequency
converter).
Refer to chapter 7 Application Examples for an example of a
status word telegram using PPO type 3.
Explanation of the status bits
Bit 00, control not ready/ready
Bit 00=0, the frequency converter has tripped.
Bit 00=1, the frequency converter controls are ready, but
the power component is not necessarily receiving any
power (in case of 24 V external supply to controls).
Bit 01, frequency converter ready
Bit 01=0, the frequency converter is not ready for
operation.
Bit 01=1, the frequency converter is ready for operation,
but there is an active coasting command via the digital
inputs or via serial communication.
Bit 02, coasting stop
Bit 02=0, the frequency converter has released the motor.
Bit 02=1, the frequency converter can start the motor
when a start command is given.
Bit 03, no error/trip
Bit 03=0, the frequency converter is not in fault mode.
Bit 03=1, the frequency converter is tripped, and a reset
signal is required to re-establish operation.
Bit 04, no error/error (no trip)
Bit 04=0, the frequency converter is not in fault mode.
Bit 04=1, there is a frequency converter error but no trip.
Bit 05, not used
Bit 05 is not used in the status word.
Bit 06, no error/triplock
Bit 06=0, the frequency converter is not in fault mode.
Bit 06=1, the frequency converter is tripped and locked.
Bit 07, no warning/warning
Bit 07=0, there are no warnings.
Bit 07=1, a warning has occurred.
Bit 08, speed reference/speed = reference
Bit 08=0, the motor runs, but the present speed is dierent
from the preset speed reference. It could, for example, be
the case while the speed ramps up/down during start/stop.
Bit 08=1, the present motor speed matches the preset
speed reference.
Bit 09, local operation/bus control
Bit 09=0, [Stop/Reset] is pressed on the LCP, or [2] Local is
selected in parameter 3-13 Reference Site. It is not possible
to control the frequency converter via serial communication.
Bit 09=1, it is possible to control the frequency converter
via the eldbus/serial communication.
Bit 10, out of frequency limit
Bit 10=0, the output frequency has reached the value in
parameter 4-11 Motor Speed Low Limit [RPM] or
parameter 4-13 Motor Speed High Limit [RPM].
Bit 10=1, the output frequency is within the dened limits.
Bit 11, no operation/in operation
Bit 11=0, the motor does not run.
Bit 11=1, the frequency converter has a start signal or the
output frequency is higher than 0 Hz.
Bit 12, frequency converter OK/stopped, auto start
Bit 12=0, there is no temporary overtemperature in the
frequency converter.
Bit 12=1, the frequency converter has stopped because of
overtemperature, but it has not tripped and resumes
operation once the overtemperature stops.
Bit 13, voltage OK/limit exceeded
Bit 13=0, there are no voltage warnings.
Bit 13=1, the DC voltage in the frequency converter’s DC
link is too low or too high.
Bit 14, torque OK/limit exceeded
Bit 14=0, the motor current is lower than the torque limit
selected in parameter 4-16 Torque Limit Motor Mode or
parameter 4-17 Torque Limit Generator Mode.
Bit 14=1, the torque limits in parameter 4-16 Torque Limit
Motor Mode and parameter 4-17 Torque Limit Generator
Mode are exceeded.
Bit 15, timer OK/limit exceeded
Bit 15=0, the timers for motor thermal protection and
frequency converter thermal protection have not exceeded
100%.
Bit 15=1, 1 of the timers has exceeded 100%.
Synchronize and Freeze
4.6
The control commands sync/unsync and freeze/unfreeze
are broadcast functions.
Use sync/unsync to synchronize control commands and/or
speed reference to all the connected frequency converters.
Use freeze/unfreeze to freeze the status feedback in the
slaves to obtain synchronized feedback from all connected
slaves.
The synchronize and freeze commands
data (the PCD part of the PPO).
aect only process
4.6.1 Sync/Unsync
To obtain simultaneous reactions such as synchronized
start, stop, or speed change in several slaves, use sync/
unsync.
A sync command freezes the relevant control word and
speed reference. Incoming process data are stored, but not
used, until a new sync command or an unsync command
is received.
An unsync command stops the synchronization mechanism
and enables normal DP data exchange.
Freeze/unfreeze can be used for simultaneous reading of
process data, for example output current, from several
slaves.
A freeze command freezes the actual values and upon
request the slave sends back the value that was present
when the freeze command was received.
44
At the receipt of an unfreeze command, the values once
again are continuously updated and the slave returns a
present value, for example a value generated by current
conditions.
The values are updated when a new freeze or unfreeze
command is received.
In an automated system, frequency converter parameters
can be accessed either from the process controller (that is,
PLC), or from various kinds of HMI equipment.
Parameter access from controllers and HMI
Parameters are located in 4 separate set-ups. Parameter
access in the frequency converter is performed via several
separated parameter channels. Use the separated channels
individually to access a certain parameter set-up. Select the
wanted set-up in parameter 0-11 Edit Set-up or
parameter 9-70 Edit Set-up.
Using the above-mentioned mechanism allows reading or
writing to and from parameters in a certain set-up from a
master class 1, for example a PLC. It is also possible to
access parameters simultaneously in a
a master class 2, for example a PC tool, without interfering
with the set-up selection for the programming sources.
Parameters can be accessed via:
LCP.
•
FC Protocol on RS485 or USB.
•
Cyclic data access on DP-V0 (PCV Channel).
•
PROFIBUS master class 1.
•
PROFIBUS master class 2 (3 connections possible).
•
dierent set-up from
NOTICE
Although the parameter channels are separated, data
conict can occur when writing to parameters from an
HMI unit into a set-up actively in use by the frequency
converter or the process controller (for example a PLC).
5.1.1 Data Store
5.1.2 Read/Write in Double Word Format
The special request IDs 0X51 (read) and 0X52 (write) allow
reading and writing to all parameters containing numeric
values in a general format of double word. The value
element must be right-aligned and unused MSBs lled
with zeros.
Example: Read of a parameter of type U8 is transmitted as
00 00 00 xx, where xx is the value to be transmitted. The
data type signaled by the telegram is 43h (dword).
5.1.3 PROFIBUS DP-V1
The acyclic DP-V1 transmission allows reading and writing
parameter values, as well as reading a number of
descriptive attributes for each parameter. Access to
parameters via DP-V1 is described in chapter 5.2 DP-V1Parameter Access.
5.1.4 PROFIBUS DP V0/PCV Channel
Parameter access via the PCV channel is performed using
PROFIBUS DP V0 cyclic data exchange, where the PCV
channel is part of the PPOs described in chapter 4.1 PPOTypes. Using the PCV channel, it is possible to read and
write parameter values, as well as read a number of
descriptive attributes for each parameter. The functionality
of the PCV channel is described in chapter 5.3 PCVParameter Access.
NOTICE
Object and data types common to both DP-V1 and PCV
parameter access are listed in chapter 5 Parameter Access.
55
Parameters write via the PCV channel (DP V0) is stored in
RAM only. If data has to be stored in non-volatile memory,
use parameter 9-71 Probus Save Data Values for storing 1
or more set-ups.
Using DP-V1 access, store parameters either in RAM or
non-volatile memory by selecting a specic write-request
command. At any time, store non-stored data in nonvolatile memory by activating parameter 9-71 Probus SaveData Values.
This section is useful for the developer with some
experience in:
PLC programs with PROFIBUS master class 1
•
functionality.
PC applications with PROFIBUS master class 2
•
functionality.
For more detailed instructions in use of the DP-V1
function, refer to the PROFIBUS master manual from the
PLC supplier.
Parameter Access
VLT® PROFIBUS DP MCA 101
5.2.1 PROFIBUS DP-V1 Introduction
The PROFIBUS DP extension DP-V1 oers acyclic communication in addition to the cyclic data communication of DP
V0. This feature is possible using a DP master class 1 (for
example, PLC), as well as a DP master class 2 (for example
PC Tool).
Cyclic communication means that data transfer takes place
continuously with a certain refresh rate. This function is the
known DP V0 function normally used for quick updates of
I/O process data.
55
Acyclic communication is a
used for read/write from and to parameters from process
controllers, PC-based tools, or monitoring systems.
5.2.2 Features of a Master Class 1
Connection
Cyclic data exchange (DP-V0).
•
Acyclic read/write from and to parameters.
•
A master class 1 is used as the process controller (either
PLC or PC-based), responsible for commands, speed
reference, status of the application, and so on. The master
class 1 acyclic connection can be used for general
parameter access in the slaves. However, the acyclic
connection is xed and cannot be changed during
operation.
one-o data transfer event,
5.2.4 Services Overview
Master
type
Master
class 1
Master
class 2
Table 5.1 Services Overview
Service
ReadWriteData
trans-
port
Read
Write
data
data to
from
slave
slave
YesYesYes–––
YesYesYesYesYes–
Read
and
write
data
InitiateAbortAlarm
Open a
connec-
tion
Close a
connec-
tion
5.2.5 Principle of Data Exchange by
PROFIBUS DP-V1
In a DP cycle, the master class 1 (MC1) rst updates the
cyclic process data for all slaves in the system. The MC1
then sends 1 acyclic message to 1 slave. If a master class 2
(MC2) is connected, the MC1 hands over the bus rights to
MC2. MC2 is then allowed to send 1 acyclic message to 1
slave. The token is then handed back to the MC1, and a
new DP cycle begins.
5.2.3 Features of a Master Class 2
Connection
Initiate/abort acyclic connection.
•
Acyclic read/write from and to parameters.
•
The master class 2 acyclic connection is typically used for
conguration or commissioning tools for easy access to
each parameter in any slave in the system. The acyclic
connection can be dynamically established (initiated) or
removed (aborted) even when a master class 1 is active on
the network.
Illustration 5.1 DP Cycle
MC: Master class.
•
C1...Cn: Cyclic data.
•
AC1: Acyclic data master class 1.
•
AC2: Acyclic data master class 2.
•
PROFIBUS DP services are activated via specic service
access points (SAP). Table 5.2 shows the SAP specied for
acyclic communication.
50 (32H) 0..48 (0..30H)Master Class 2: Abort, read, write,
51 (33H) 50, 51 (32H,
51 (33H) 51 (33H)Master Class 2: Read, write
Table 5.2 Service Access Points (SAP)
Slave SAPDescription
data transfer
Master Class 2: Alarm
33H)
5.2.6 DP-V1 Features for Parameter Access
This section describes how to use DP-V1 for accessing
frequency converter parameters.
The standard PROFIBUS DP-V1 read and write services are
not sucient for accessing the many parameters and
attributes in the frequency converter. For this reason, the
PROFIdrive parameter channel is dened. Using this
parameter read/write is performed by addressing a single
DP-V1 object in the frequency converter as shown in the
example, Table 5.3.
For a detailed description of the DP-V1 command handling,
refer to the PROFIBUS DP-V1 Design Guide.
Example
Slot=0
Index=47
PROFIBUS
telegram
header
DU0DU1DU2DU3Req./Res.
Table 5.3 General Structure for Telegram
Use the DP-V1 command/response part for the standard
DP-V1 read/write on slot 0, index 47 data block.
Use the PROFIdrive V3 parameter channel to access
parameter data in the frequency converter.
Data unitPROFIBUS
DP-V1
command/response
PROFIdrive V3.0
parameter
channel
Header
telegram
trailer
Data
specic
5.2.7 DP-V1 Read/Write Services
Table 5.4 shows the content of the DP-V1 command/
response headers and their possible attributes.
DU byte ValueMeaningSpecied
0Function
number
0x48
0x51Data transport
0x56Resource manager
0x57Initiate REQ, RES–
0x58Abort REQ–
0x5CAlarm REQ, RES–
0x5ERead REQ, RES–
0x5FWrite REQ, RES–
0xD1Data transport
0xD7Initiate negative
0xDCAlarm negative
0xDERead negative
0xDFWrite negative
1Always zeroSlot numberDP-V1
247IndexDP-V1
3xxData lengthDP-V1
4..nUser dataPNO drive prole
Table 5.4 DP-V1 Command/Response Headers
Idle REQ, RES–
–
REQ, RES
–
REQ
–
negative response
–
response
–
response
–
response
–
response
V3.0
5.2.8 DP-V1 Acyclic Parameter Channel
Use the PROFIdrive parameter channel for read and write
access to parameter values and attributes.
Parameter values of simple variable, array, and
•
visible string.
Parameter description elements such as type and
•
minimum/maximum value.
Descriptive text for parameter values.
•
Access to multiple parameters in 1 telegram is
•
also possible.
Table 5.5 shows the structure of the PROFIdrive parameter
channel.
PROFIBUS DP-V1 telegram for read/write from or to a
frequency converter parameter:
PROFIBUS
telegram
header
DU0DU1DU2DU3Req./Res.
Table 5.5 Structure of the PROFIdrive Parameter Channel
55
Table 5.6 shows the principle structure of the PROFIdrive
Data unitPROFIBUS
DP-V1
command/response
PROFIdrive V3.0
parameter
channel
Header
telegram
trailer
Data
parameter channel.
The DP-V1 parameter request telegram consists of 3 data
blocks:
A request header, which denes the request (read
•
or write), and the number of parameters to
access. The master sets the request reference, and
uses this information to evaluate the response.
An address eld where all addressing attributes of
•
the wanted parameters are dened.
A data eld where all parameter data values is
•
placed.
The DP-V1 parameter response telegram consists of 2 data
blocks:
A response header, which indicates:
•
-If the request is performed without
errors (response ID).
-The number of parameters.
-The request reference set by the master
within the corresponding request.
A data eld, where the requested data are placed.
•
If 1 or more internal requests have failed, a fault
code is placed instead of the data values.
DP-V1Parameter responseByte
number
Response headerRequest reference mirrored0
Response ID1
Axis mirrored2
Parameter valuesNumber of parameters3
Format4
Number of values5
Values of error values6
n'th parameter value...
Table 5.7 DP-V1 Parameter Response Telegram
DP-V1Parameter requestByte number
Request
header
Address eld Number of parameters3
Data eldData format4+6*n
Table 5.6 Principle Structure of the PROFIdrive Parameter
Channel
Request reference0
Request ID1
Axis2
Attribute4
Number of elements5
Parameter number6
7
Sub index8
9
n'th parameter number 4+6*(n-1)
...
Number of values(4+6*n)+1
Values(4+6*n)+2
n'th data value...
As the response telegram does not include parameter
addressing information, the master must identify the
structure of the response data from the request telegram.
5.2.9 Request/Response Attributes
Table 5.8 contains an overview of the possible attributes of
the PROFIdrive parameter channel.
0x02 Change parameter (data is NOT stored in non-volatile
memory, lost at power cycle).
0x42 Change parameter non-volatile (data is stored in non-
volatile memory).
0x51 Request parameter value double word. All parameters are
formatted and transferred as double word size, regardless
of the actual data type.
0x52 Change parameter value double word. All parameters
must be formatted and sent as double word size,
regardless of data type.
Table 5.9 Dened Request Identication
5.2.12 Response ID
The response ID indicates if the read or write request was
successfully performed in the frequency converter. If the
response is negative, the request is answered as negative
(rst bit=1), and a fault code is entered per partial
response instead of the value.
5.2.13 Axis
Set the axis attribute to 0.
5.2.14 Number of Parameters
For multi-parameter requests that specify the number of
the parameter address and/or parameter value areas. For a
single request, the number is 1.
5.2.15 Attribute
The attribute determines which data to access. The
frequency converter responds to the attributes value
(10 H), description (20 H), and text (30 H).
55
Table 5.8 Overview: Possible Attributes of the
PROFIdrive Parameter Channel
1) U8 - Unsigned8, U16 - Unsigned16
5.2.16 Attribute Value (10 H)
The attribute value allows reading or writing of parameter
values.
5.2.10 Request Reference
Unique identication of request/response pair for the
master. The master changes the request reference with
each new request. The slave mirrors the request reference
in the response.
Conversion factor for scaling a given parameter value to
The attribute description allows access to the parameter
description. It is possible to read out 1 single description
element, or all elements for 1 parameter in 1 telegram.
Table 5.10 provides an overview of the existing parameter
description, which exists for each parameter in the
frequency converter.
standard SI units.
For example, if the given value is in mV, the standardization factor is 1000, which converts the given value to V.
The standardization factor is in oat format.
Variable attribute
Consists of 2 bytes. The rst byte contains the variable
index, which denes the physical unit of the parameter (for
Subindex DescriptionData type
1Identier IDV2
55
2Number of array
elements or length or
string
3Standardization factorFloat
4Variable attributeOctet string 2
5ReservedOctet string 4
6NameVisible string 16
7Lower limitOctet string 4
8Upper limitOctet string 4
9ReservedOctet string 2
10ID extensionV2
11PCD reference parameter U16
12PCD normalizationV2
0Complete descriptionOctet string 46
Table 5.10 Parameter Description Elements (all Elements are
Read-only)
U16
Table 5.11 explains each description element.
example A, V).
The second byte is the conversion index, which is a scaling
factor for the parameter. All parameters accessible by
PROFIBUS are organized and transmitted as real numbers.
The conversion index denes a factor for conversion of the
actual value to a standard physical unit. A conversion index
of -1 means that the actual value must be divided by 10 to
become a standard physical unit, for example V.
Name
Contains the parameter name, limited to 16 characters, for
example language for parameter 0-01 Language. This text is
available in the language selected in
parameter 0-01 Language.
Lower limit
Contains the minimum value of the parameter. Format is
32 bit signed.
Upper limit
Contains the maximum value of the parameter. Format is
32 bit signed.
ID extension
Not supported.
Identier ID
BitDescription
15Reserved.
14Array.
13Parameter value can be reset only.
12Parameter has been changed from factory setting.
11Reserved.
10Additional text array available.
9Parameter is read-only.
8Standardization factor and variable attribute not
relevant.
0–7Data type.
Table 5.11 Extra Characteristics of a Parameter
PCD reference parameter
Process data may be scaled by a parameter, for example
the maximum reference of 0x4000 (in %) depends on the
setting of parameter X.
To enable the master to calculate the real value of the
process data, it has to know the value of parameter X.
Therefore the process data must deliver a reference to
parameter X.
Field PCD normalization
The eld PCD normalization must express the value that
shows the 100%. Thus, the normalization delivered back
must be the set bit 15 and a value of 0xe (14, 2
14
=0x4000), and the result must be 0x800e.
Complete description
Returns the complete parameter description with the elds
Number of array elements
Contains the number of array elements, if the
•
parameter is an array.
Contains the string length, if the parameter value
•
is a string.
Contains a 0 if the parameter is neither.
•
1–12 in order. Length=46 byte.
5.2.18 Attribute Text (30 H)
For some frequency converter parameters, a descriptive
text is available, which can be read using this attribute. A
bit set in the identier (ID) parameter description element
indicates the availability of a text description for a
parameter. The description element can be read out by the
description attribute (20 H) subindex=1. If bit 10 is set, a
descriptive text exists for each value of the parameter.
As an example, parameter 0-01 Language has settings 0–5.
For each of these values, a specic text exists: 0=English,
2=Deutsch, and so on.
5.2.19 Format
Species the format type for each parameter (word, byte,
and so on), see Table 5.12.
5.2.20 Supported Data types
ValueData type
3Integer16
4Integer32
5Unsigned8
6Unsigned16
7Unsigned32
9Visible string
10Octet string (byte string)
33N2 (standardised value)
35V2 (bit sequence)
44Error
54Time dierence without date indication
Table 5.12 Supported Data Types
5.2.21 Value
The value eld contains the parameter value of the
request. When the response is negative, the eld contains
a corresponding fault code. If the values consist of an odd
number of bytes, a 0-byte is appended to maintain the
word structure of the telegrams.
For a positive partial response, the parameter value
contains the following attributes:
Format = Data type or byte, word, double word.
•
Number of values = Actual number of values.
•
Value = Parameter value.
•
For a negative partial response, the parameter value eld
contains the following:
Format = Error (44H).
•
Number of values = 1.
•
Value = Error value = Error number.
•
eld
5.2.22 Fault Codes for Drive Prole V 3.0
When the parameter request is invalid, the frequency
converter returns a corresponding fault code. Table 5.13
lists the full range of fault codes.
Fault
DescriptionMore Info
code
0x00Unknown parameter.0
0x01Parameter is read-only.Subindex
0x02Value out of range due to maximum/
minimum value.
0x03Wrong subindex.Subindex
0x04Parameter is no array.0
0x05Wrong data type (wrong data length).0
0x06This parameter may not be set, only reset.Subindex
0x07Descriptive element is read-only.Subindex
0x09No description available (only value).0
0x0bProcess control not possible.0
0x0fNo text array available (only value).0
0x11Not possible in current state.0
0x14Value out of range due to frequency
converter state/conguration.
0x15Reply too long (more than 240 bytes).0
0x16Wrong parameter address (unknown or
unsupported value for attribute, element,
parameter number, or subindex, or illegal
combination).
0x17Illegal format (for writing).0
0x18Value amount not consistent.0
0x65Wrong axis: Action not possible with this
axis.
0x66Unknown service request.–
0x67This service is not possible with multi-
parameter access.
0x68Parameter value cannot be read from bus.–
Table 5.13 Fault Codes for DP-V1 Parameter Requests
PCV Parameter Access
5.3
The PROFINET cyclic data exchange performs parameter
access via the PCV channel. The PCV channel forms part of
the PPOs described in chapter 4 Control.
Use the PCV channel to read and write parameter values,
and read status for descriptive attributes of each
parameter.
Subindex
Subindex
0
–
–
55
5.3.1 PCA Handling
The PCA part of PPO types 1, 2, and 5 performs several
tasks. Using PCA, the master controls and supervises
parameters and requests a response from the slave. Then
the slave responds to a request from the master. Requests
and responses are a handshake procedure and cannot be
batched. Therefore, when the master sends out a read/
write request, it must wait for the response before it sends
a new request. The request or response data value is
limited to maximum 4 bytes (see RC characteristics in
Table 5.14), which implies that text strings are not
transferable. For further information, see
chapter 7 Application Examples.
When the slave rejects a request from the master, the RC
word in the PPO-read indicates the rejection by assuming
the value 7. Bytes 7 and 8 in the PVA element carry the
fault number.
The content of the RC portion of the PCA word for a
response is listed in Table 5.16.
ResponseFunction
0No response.
1Transfer parameter value (word).
2Transfer parameter value (long word).
3Transfer description element.
4Transfer parameter value (array word).
5Transfer parameter value (array long word).
6Transfer number of array elements.
7Request rejected (including fault number, see
Table 5.17).
8Not serviceable by PCV interface.
9Not used.
10Not used.
11Not used.
12Not used.
13–15Not used.
Table 5.16 Response
size parameter values in bytes 7 and 8,
while long word size values require
bytes 5–8 (32 bits).
-IND: When the response/request
contains array elements, the IND carries
the array subindex. When parameter
descriptions are involved, the IND holds
the record subindex of the parameter
description.
5.3.4 RC Content
Request
The content of the RC portion of the PCA word for a
request is listed in Table 5.15.
RequestFunction
0No request.
1Request parameter value.
2Change parameter value (word).
3Change parameter value (long word).
4Request description element.
5Change description element.
6Request parameter value (array).
7Change parameter value (array word).
8Change parameter value (array long word).
9Request number of array elements.
10–15Not used.
Fault
number
0Illegal PNU.
1Parameter value cannot be changed.
2Upper or lower limit exceeded.
3Subindex corrupted.
4No array.
5Data type false.
6Cannot be set by user (reset only).
7Description element cannot be changed.
8IR required PPO-write not available.
9Description data not available.
10Access group.
11No parameter write access.
12Key word missing.
13Text in cyclic transmission not readable.
14Name in cyclic transmission not readable.
15Text array not available.
16PPO-write missing.
17Request temporarily rejected.
18Other fault.
19Data in cyclic transmission not readable.
130There is no bus access to the parameter called.
131Data change is not possible because factory set-up is
time to 10 s in parameter 3-41 Ramp 1 Ramp Up
Time.
How to command a start and speed reference of
•
50%.
Frequency converter parameter settings:
Parameter 8-50 Coasting Select: [1] Bus.
•
Parameter 8-10 Control Word Prole: [1] PROFIdrive
prole.
5.3.5.1 PCV
PCA parameter characteristics
PCA part (byte 1–2).
The RC part tells what the PCV part must be used for. The
functions available are listed in chapter 5.3.1 PCA Handling.
When a parameter is changed, select value 2 or 3. In this
example, 3 is selected because parameter 3-41 Ramp 1
Ramp Up Time covers a long word (32 bits).
Parameter 3-41 Ramp 1 Ramp Up Time = 155 hex: In this
example, bytes 1 and 2 are set to 3155. See the values for
bytes 1 and 2 in chapter 5.3.5 Example.
IND (bytes 3–4)
Used when reading/changing parameters with subindex,
for example parameter 9-15 PCD Write Conguration. In the
example, bytes 3 and 4 are set to 00 hex. See the values
for bytes 3 and 4 in chapter 5.3.5 Example.
PVA (bytes 5–8)
Change the data value of parameter 3-41 Ramp 1 Ramp Up
Time to 10.00 s. The value transmitted must be 1000,because the conversion index for parameter 3-41 Ramp 1
Ramp Up Time is 2. Therefore, the value received by the
frequency converter is divided by 100, such that the
frequency converter perceives 1000 as 10.00. Bytes 5–8 =
1000 = 03E8 hex. See chapter 5.4 PROFIBUS DP Parameter
and Data Type. See the values for bytes 5–8 in
chapter 5.3.5 Example.
These values are for bytes 9 and 10 in
chapter 5.3.5 Example.
Quick stop: 0000 0100 0110 1111=046F hex.
Stop: 0000 0100 0011 1111=043F hex.
5.4 PROFIBUS DP Parameter and Data Type
5.4.1 Parameter Description
PROFIBUS DP has a number of description attributes. Read/
write on parameter description is performed in the PCV
part using the RC commands 4 and 5, and the subindex of
the wanted description element.
55
5.3.5.2 PCD
Control word (CTW ) according to PROFIdrive prole:
Control words consist of 16 bits. The meaning of each bit
is explained in chapter 4.4.1 Control Word According to
PROFIdrive Prole (CTW ) and chapter 4.4.2 Status Word
According to PROFIdrive Prole (STW). The following bit
Find the size index and the conversion index for each
parameter from the parameter list in the respective
operating instructions. See also size and conversion indices
in Table 5.18.
Physical
quantity
55
Time4
Energy8
Power9
Rotation11Rotation per
Torque16
Tempera-
ture
Voltage21
Current22
Resistance23
Ratio24Percent%01
Relative
change
Frequency28
Size
SI unit nameSI unit
index
0No dimension
Seconds01
Millisecondms-30.001
Minutemin7060
Hourh743600
Dayd7786400
Watt hourWh01
Kilowatt hourkWh31000
Megawatt hourMWh6
MilliwattmW-30.001
WattW01
KilowattkW31000
MegawattMW6
minute
Newton meterNm01
Kilo newton
meter
17Degree celsiusºC01
MillivoltmV-30.001
VoltV01
KilovoltkV31000
MilliamperemA-30.001
AmpereA01
Kilo amperekA31000
Milliohm
Ohm
Kiloohm
27Percent%01
HertzHz01
KilohertzkHz31000
MegahertzMHz6
GigahertzGHz9
symbol
RPM671
kNm31000
mΩ
Ω
kΩ
Conver-
sion
index
-10.1
-20.01
-30.001
01
31000
Conver-
sion
factor
6
10
6
10
6
10
9
10
5.4.3 Object and Data Types Supported
Data typeShort nameDescription
3I2Integer 16
4I4Integer 32
5–Unsigned 8
6O2Unsigned 16
7O4Unsigned 32
9–Visible string
10–Byte string
33N2Standardized value (16 bit)
35V2Bit sequence
54–Time dierence without date
indication
Table 5.19 Supported Data Types
5.4.4 Standardized Value
The frequency reference value transmits to the frequency
converter in the form of a 16-bit word. The value transmits
in integers (0–32767). The value 16384 (4000 hex)
corresponds to 100%. Negative numbers are formed with
the aid of the 2s complement.
0%=0 (0h), 100%=214 (4000 h)
This chapter describes the general parameters relating to
PROFIBUS and the communication settings of the
frequency converter.
Not all product series support all parameters, just as the
parameter settings may vary between the product series.
For details of the parameters in parameter groups 8-**
Comm. and Options, 9-** PROFIBUS, and 16-** Data
Readouts, refer to the programming guide of the
specic
product series.
8-01 Control Site
Option:Function:
The setting in this parameter overrides the
settings in parameter 8-50 Coasting Select to
parameter 8-56 Preset Reference Select.
[0] Digital and
ctrl.word
[1] Digital onlyControl by using digital inputs only.
[2] Controlword
only
Control by using both digital input and
control word.
Control by using control word only.
8-02 Control Word Source
Option:Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Select the source of the control word: 1 of 2
serial interfaces or 4 installed options. During
initial power-up, the frequency converter
automatically sets this parameter to [3] Option
A if it detects a valid
in slot A. When the option is removed, the
frequency converter detects a conguration
change, sets parameter 8-02 Control Word
Source to default setting [1] FC RS485, and
trips. If an option is installed after initial
power-up, the setting of
parameter 8-02 Control Word Source does not
change, but the frequency converter trips and
shows: Alarm 67, Option Changed.
When retrotting a bus option into a
frequency converter that did not have a bus
option installed earlier, change the control to
bus-based. This change is required for safety
reasons to avoid an unintended change.
[0]None
[1]FC RS485
[2]FC USB
eldbus option installed
8-02 Control Word Source
Option:Function:
[3]Option A
[4]Option B
[5]Option C0
[6]Option C1
[30] External Can
8-03 Control Word Timeout Time
Range:Function:
1 s* [ 0.1 -
18000 s]
Enter the maximum time expected to pass
between the reception of 2 consecutive
telegrams. If this time is exceeded, it indicates
that the telegram communication has stopped.
The function selected in parameter 8-04 Control
Word Timeout Function is then carried out. A
valid control word triggers the timeout counter.
8-04 Control Word Timeout Function
Select the timeout function. The timeout function activates when
the control word fails to be updated within the time period
specied in parameter 8-03 Control Word Timeout Time.
Option:Function:
NOTICE
To change the set-up after a timeout,
congure as follows:
1.Set parameter 0-10 Active Set-up to [9] Multi set-up.
2.Select the relevant link in
parameter 0-12 This Set-up
Linked to.
[0]OResumes control via eldbus(eldbus or
standard), using the most recent control word.
[1]Freeze
output
[2]StopStops with auto restart when communication
[3]JoggingRuns the motor at jog frequency until
[4]Max. speed Runs the motor at maximum frequency until
This example shows how to work with PPO type 6, which consists of control word/status word and reference/main actual
value. The PPO also has 2 extra words, which can be programmed to monitor process signals:
The application requires monitoring of the motor torque
and digital input, so PCD 3 is set up to read the current
motor torque. PCD 4 is set up to monitor the state of an
external sensor via the process signal digital input. The
sensor is connected to digital input 18.
An external device is also controlled via control word bit
11 and the built-in relay of the frequency converter.
Reversing is allowed only when the reversing bit 15 in the
control word and the digital input 19 are set to high.
For safety reasons, the frequency converter stops the
motor if:
Parameter 4-10 Motor Speed Direction[2] Both directions
Parameter 5-10 Terminal 18 Digital Input[0] No operation
Parameter 5-11 Terminal 19 Digital Input[10] Reversing
Parameter 5-40 Function Relay[36/37] Control word bit 11/12
Parameter 8-03 Control Word Timeout Time1 s
Parameter 8-04 Control Word Timeout Function[2] Stop
Parameter 8-10 Control Word Prole[0] FC Prole
Parameter 8-50 Coasting Select[1] Bus
Parameter 8-51 Quick Stop Select[1] Bus
Parameter 8-52 DC Brake Select[1] Bus
Parameter 8-53 Start Select[1] Bus
Parameter 8-54 Reversing Select[2] Logic AND
Parameter 8-55 Set-up Select[1] Bus
Parameter 8-56 Preset Reference Select[1] Bus
Parameter 9-16 PCD Read Conguration[2] Sub index parameter 16-16 Torque [Nm]
[3] Sub index parameter 16-60 Digital Input
Parameter 9-18 Node AddressSet the address
77
Table 7.2 Parameter Settings
Example 2: Control Word Telegram using PPO Type
7.2
This example shows how the control word telegram relates to the PLC and the frequency converter, using FC control prole.
The PLC sends the control word telegram to the frequency converter. In the example, PPO Type 3 demonstrates the full
range of modules. All the values shown are arbitrary and are provided for demonstration purposes only.
Table 7.3 indicates the bits contained within the control word, and how they are presented as process data in PPO type 3 for
this example.
PCVPCD
123456
PCAINDPVACTWMRVPCDPCDPCDPCD
047C2000
PQW256258260262264266268270272274
master slaveCTWMRV
Bit
number
000001000111110 0
047C
Table 7.3 Example: Control Word Telegram using PPO Type
Table 7.4 indicates the bit functions and corresponding bit values which are active for this example.
BitBit value=0Bit value=1Bit value
00Reference valueExternal selection lsb0
01Reference valueExternal selection msb0
02DC brakeRamp1
03CoastingEnable1
04Quick stopRamp1
05Freeze outputRamp enable1
06Ramp stopStart1
07No functionReset0
08No functionJog0
09Ramp 1Ramp 20
10Data not validValid1
11No functionRelay 01 active0
12No functionRelay 02 active0
13Parameter set-upSelection lsb0
77
14Parameter set-upSelection msb0
15No functionReversing0
Function active
Function inactive
C
7
4
0
Table 7.4 Active Bit Functions for Control Word Telegram using PPO Type
Example 3: Status Word Telegram using PPO Type
7.3
This example shows how the control word telegram relates to the PLC and the frequency converter, using FC control prole.
The PLC sends the control word telegram to the frequency converter. In the example, PPO type 3 demonstrates the full
range of modules. All the values shown are arbitrary and are provided for demonstration purposes only.
Table 7.5 indicates the bits contained within the status word, and how they are presented as process data in PPO type 3 for
this example.
PCVPCD
123456
PCAINDPVACTWMRVPCDPCDPCDPCD
0F072000
PIW256258260262264266268270272274
master slaveSTWMAV
Bit
number
000001000111110 0
047C
Table 7.5 Example: Status Word Telegram using PPO Type
This network sends a start command (047C hex) and a
This network activates relay 02.
reference (2000 hex) of 50% to the frequency converter.
Illustration 7.7 Network Activates Relay 02
Illustration 7.3 Network Sends a Start Command and a
Reference of 50% to the Frequency Converter.
This network reads the motor torque from the frequency
converter. A new reference is sent to the frequency
converter because the motor torque (86.0%) is higher than
77
the compared value.
Illustration 7.4 Network Reads the Motor Torque from the
Frequency Converter
This network reads the status on the digital inputs from
the frequency converter. If digital input 18 is On, it stops
the frequency converter.
Illustration 7.5 Network Reads the Status on the Digital Inputs
from the Frequency Converter
This network reverses the motor when digital input 19 is
ON, because parameter 8-54 Reversing Select is
programmed to Logic AND.
Illustration 7.6 Network Reverses the Motor When Digital
VLT® PROFIBUS DP MCA 101 provides a exible way of
performing diagnosis of slave units, based on diagnosis
messages.
During normal cyclic data exchange:
1.The slave sets a diagnosis bit, which requests the
master to send a diagnosis message during the
next scan cycle, instead of the normal data
exchange.
2.The slave answers the master with a diagnosis
message consisting of standard diagnosis
information, 6 bytes, and possibly extended,
vendor-specic, diagnosis information. The
standard diagnosis messages cover a limited
range of general diagnosis possibilities, whereas
the extended diagnosis function oers detailed
messaging specic to the frequency converter.
See chapter 8.3 Warnings and Alarms for the extended
diagnosis messages for the frequency converter.
A master or a network analyzing tool is able to translate
these diagnosis words into real text messages using the
GSD le.
NOTICE
DP-V1 diagnosis is supported for PROFIBUS SW version
2.X and later versions. The default setting of the
PROFIBUS option is DP-V1 diagnosis.
When DP-V0 diagnosis is required, change the setting
under DP slave Properties.
8.2 No Response to Control Signals
Check that:
The control word is valid.
•
When bit 10=0 in the control word, the frequency
converter does not accept the control word. The
default setting is bit 10=1. Set bit 10=1 via the
PLC.
The relationship between bits in the control word
•
and the terminal I/Os is correct.
Check the logical relationship in the frequency
converter. Set the logic to bit 3=1 and digital
input=1 to achieve a successful start.
Select the FC control mode, digital input, and/or serial
communication, using parameter 8-50 Coasting Select to
parameter 8-56 Preset Reference Select.
Selecting control mode for parameter 8-50 Coasting
Select, parameter 8-51 Quick Stop Select, and
parameter 8-52 DC Brake Select:
If [0] Digital input is selected, the terminals control the
coast and DC brake functions.
NOTICE
Coasting, quick stop, and DC brake functions are active
for logic 0.
TerminalBit 02/03/04Function
00Coast/DC brake/Q-stop
01Coast/DC brake/Q-stop
10No coast/DC brake/Q-stop
11No coast/DC brake/Q-stop
Table 8.1 [0] Digital Input
If [1] Serial communication is selected, commands are
activated only when given via serial communication.
TerminalBit 02/03/04Function
00Coast/DC brake/Q-stop
01No coast/DC brake/Q-stop
10Coast/DC brake/Q-stop
11No coast/DC brake/Q-stop
Table 8.2 [1] Serial Communication
If [2] Logic AND is selected, activate both signals to perform
the function.
TerminalBit 02/03/04Function
00Coast/DC brake/Q-stop
01No coast/DC brake/Q-stop
10No coast/DC brake/Q-stop
11No coast/DC brake/Q-stop
Table 8.3 [2] Logic AND
If [3] Logic OR is selected, activation of 1 signal activates
the function.
Refer to the relevant operating instructions for an overview of warning and alarm types, and for the full list of warnings
and alarms.
Alarm word, warning word, and PROFIBUS warning word are shown on the frequency converter display in hex format. When
there is more than 1 warning or alarm, the sum of all warnings or alarms is shown. Alarm word, warning word, and
PROFIBUS warning word can also be shown using the eldbus in parameter 16-90 Alarm Word, parameter 16-92 WarningWord, and parameter 9-53 Probus Warning Word.
Receive the extended diagnosis function, alarm, and
warning information from the frequency converter. The
setting of parameter 8-07 Diagnosis Trigger determines
which frequency converter events trigger the extended
diagnosis function:
When parameter 8-07 Diagnosis Trigger is set to [0]
•
Disable, no extended diagnosis data is sent
regardless of whether it appears in the frequency
converter or not.
When parameter 8-07 Diagnosis Trigger is set to [1]
•
Alarms, extended diagnosis data is sent when 1
or more alarms arrive in the alarm
parameter 16-90 Alarm Word or
parameter 9-53 Probus Warning Word.
When parameter 8-06 Reset Control Word Timeout is set to
[2] Alarms/Warnings, extended diagnosis data is sent if 1 or
more alarms/warnings arrive in the alarm
parameter 16-90 Alarm Word or parameter 9-53
Warning Word, or in the warning parameter 16-92 Warning
Word.
The extended diagnosis sequence is as follows:
If an alarm or warning appears, the frequency converter
sends a high-priority message to the master via the output
data telegram. The master then sends a request for
extended diagnosis information, to which the frequency
converter replies. When the alarm or warning disappears,
the frequency converter again sends a message to the
master, and on the following request from the master,
returns a standard DP diagnosis frame (6 bytes).
Probus
ByteBit
number
0–5–Standard DP diagnosis data.
6–PDU length.
70–7Status type=0x81.
88–15Slot=0.
916–23Status information.
1024–31Parameter 16-90 Alarm Word.
1132–39Parameter 16-90 Alarm Word.
1240–47Parameter 16-90 Alarm Word.
1348–55Parameter 16-90 Alarm Word.
1456–63Reserved for future use.
1564–71Reserved for future use.
1672–79Reserved for future use.
1780–87Reserved for future use.
1888–95Parameter 16-92 Warning Word.
1996–103Parameter 16-92 Warning Word.
20104–111 Parameter 16-92 Warning Word.
21112–119 Parameter 16-92 Warning Word.
22120–127 Reserved for future use.
23128–135 Reserved for future use.
24136–143 Reserved for future use.
25144–151 Reserved for future use.
26152–159 Parameter 9-53 Probus Warning Word.
27160–167 Parameter 9-53 Probus Warning Word.
28168–175 Reserved for future use.
29176–183 Reserved for future use.
30184–191 Reserved for future use.
31192–199 Reserved for future use.
Table 8.18 Content of the Extended Diagnosis Frame
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to
products already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed. All trademarks in this material are property
of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.