MAKING MODERN LIVING POSSIBLE
Programming Guide
VLT® PROFIBUS DP MCA 101
VLT® Frequency Converter Series FC 102 • FC 103 • FC 202
FC 301/302 • FCD 302 • FCP 106 • FCM 106
vlt-drives.danfoss.com
Contents |
Programming Guide |
|
|
Contents
1 Introduction |
3 |
1.1 Purpose of the Manual |
3 |
1.2 Additional Resources |
3 |
1.3 Document and Software Version |
3 |
1.4 Product Overview |
3 |
1.5 Approvals and Certifications |
4 |
1.6 Symbols, Abbreviations, and Conventions |
5 |
2 Safety |
6 |
2.1 Safety Symbols |
6 |
2.2 Qualified Personnel |
6 |
2.3 Safety Precautions |
6 |
3 Configuration |
8 |
3.1 Configure the PROFIBUS Network |
8 |
3.2 Configure the Master |
9 |
3.2.1 GSD File |
9 |
3.3 Configure the Frequency Converter |
11 |
3.3.1 Frequency Converter Parameters |
11 |
3.3.2 LEDs |
12 |
4 Control |
13 |
4.1 PPO Types |
13 |
4.2 Process Data |
15 |
4.2.1 Process Control Data |
15 |
4.2.2 Process Status Data |
15 |
4.2.3 Reference Handling |
15 |
4.2.4 Process Control Operation |
16 |
4.2.5 Influence of the Digital Input Terminals on FC Control Mode |
16 |
4.3 Control Profile |
16 |
4.4 PROFIdrive Control Profile |
17 |
4.4.1 Control Word According to PROFIdrive Profile (CTW) |
17 |
4.4.2 Status Word According to PROFIdrive Profile (STW) |
18 |
4.4.3 PROFIdrive State Transition Diagram |
20 |
4.5 Danfoss FC Control Profile |
21 |
4.5.1 Control Word According to FC Profile (CTW) |
21 |
4.5.2 Status Word According to FC Profile (STW) |
22 |
4.6 Synchronize and Freeze |
23 |
4.6.1 Sync/Unsync |
23 |
4.6.2 Freeze/Unfreeze |
24 |
MG37G202 |
Danfoss A/S © 01/2016 All rights reserved. |
1 |
Contents |
VLT® PROFIBUS DP MCA 101 |
5 Parameter Access |
25 |
5.1 Parameter Access in General |
25 |
5.2 DP-V1 Parameter Access |
25 |
5.3 PCV Parameter Access |
31 |
5.4 PROFIBUS DP Parameter and Data Type |
33 |
6 Parameters |
36 |
6.1 8-** PROFIBUS Parameters |
36 |
6.2 9-** and 16-** PROFIBUS Parameters |
39 |
6.3 PROFIBUS-specific Parameter List |
46 |
7 Application Examples |
48 |
7.1 Example 1: Process Data with PPO Type 6 |
48 |
7.2 Example 2: Control Word Telegram using PPO Type |
49 |
7.3 Example 3: Status Word Telegram using PPO Type |
50 |
7.4 Example 4: PLC Programming |
51 |
8 Troubleshooting |
53 |
8.1 Diagnosis |
53 |
8.2 No Response to Control Signals |
53 |
8.3 Warnings and Alarms |
56 |
8.4 Fault Messages via DP Diagnosis |
58 |
8.5 Extended Diagnosis |
59 |
Index |
60 |
2 |
Danfoss A/S © 01/2016 All rights reserved. |
MG37G202 |
Introduction Programming Guide
1 Introduction |
1 |
1 |
|
|
|
|
|
|
1.1 Purpose of the Manual
The VLT® PROFIBUS DP MCA 101 Programming Guide provides information about:
•Configuring the system.
•Controlling the frequency converter.
•Parameter access.
•Programming.
•Troubleshooting.
•Typical application examples.
The programming guide is intended for use by qualified personnel familiar with the VLT® frequency converter, with PROFIBUS technology, and with the PC or PLC used as a master in the system.
Read the instructions before programming and follow the procedures in this manual.
1.3 Document and Software Version
This manual is regularly reviewed and updated. All suggestions for improvement are welcome. Table 1.1 shows the document version and the corresponding software version.
Edition |
|
Remarks |
Software |
|
|
|
version |
|
|
|
|
MG37G2xx |
• |
Information about VLT® DriveMotor |
5.20 |
|
|
FCP 106/FCM 106 added. |
|
|
• |
New feature for fast PCD communi- |
|
|
|
cation for MCO 305. |
|
|
|
|
|
Table 1.1 Document and Software Version
1.4 Product Overview
VLT® is a registered trademark.
1.2 Additional Resources
Resources available for the frequency converters and optional equipment:
•The VLT® Operating Instructions provide the necessary information for getting the frequency converter up and running.
•The VLT® Design Guide provides detailed information about capabilities and functionality to design motor control systems.
•The VLT® Programming Guide provides greater detail on working with parameters and many application examples.
•The VLT® PROFIBUS DP MCA 101 Installation Guide provides information about installing the PROFIBUS and troubleshooting.
•The VLT® PROFIBUS DP MCA 101 Programming Guide provides information about configuring the system, controlling the frequency converter, parameter access, programming, troubleshooting, and some typical application examples.
Supplementary publications and manuals are available from Danfoss. See vlt-drives.danfoss.com/Support/Technical- Documentation/ for listings.
1.4.1 Features of PROFIBUS DP-V1
•2 different state machines can be selected: PROFIdrive profile or Danfoss FC profile.
•Communication using PROFIBUS DP-V1, master class 1, and master class 2.
•Backward compatibility: New protocol extensions retain all the functions of the previous versions.
•Intelligent base for future technologies such as OPC, FDT/DTM, PROFINET.
•Bus timeout reaction.
•PLC/CPU stop reaction.
•8 PPO types available.
•Numerous relevant process data (PCD) types available.
•Automatic detection of baud rate and PPO type.
•Extended diagnosis available.
•Alarms and warnings available as text messages within the PLC.
•Configuration via MCT 10 Set-up Software.
•Equally long bus cycle time configurable in PLC system.
•Improved network efficiency, since the cyclic parameter channel is no longer required.
•Short bus cycle times compared to industrial Ethernet.
•Backwards compatibility with DP.
MG37G202 |
Danfoss A/S © 01/2016 All rights reserved. |
3 |
Introduction |
VLT® PROFIBUS DP MCA 101 |
1 |
1 |
1.4.2 Technical Overview |
|
|
|
for general parameter access as an alternative to the PCV parameter channel.
PROFIBUS
PROFIBUS is an international standard for fieldbus communication in automation technology (IEC 61158 and IEC 61784). The member companies of the PROFIBUS International User Community support the standard.
For information about PROFIBUS and downloads for PROFIBUS DP and the PROFIdrive profile, refer to www.Pro€bus.com.
PROFIBUS DP-V1
The PROFIBUS DP protocol enables communication between PROFIBUS masters and slaves.
Configure communication via MCT 10 Set-up Software.
Cyclic/acyclic communication
•PLC communicates with telegrams of constant length.
•Fits time-critical requirements.
•Cyclic transmission via PPO types.
•Extended diagnosis.
|
PLC |
|
|
|
<![if ! IE]> <![endif]>130BA078.11 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PLC |
|
|
|
|
|
|
|
PC tool |
|
|
<![if ! IE]> <![endif]>130BA079.11 |
||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
Master class 1 |
|
Master class 2 |
|
|
|
|
||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Illustration 1.2 PROFIBUS DP-V1
The PROFIBUS DP extension DP-V1 allows acyclic as well as cyclic data communication. This feature can be used by a DP master class 1, for example PLC, as well as a DP master class 2, for example PC tool.
1.5 Approvals and Certifications
More approvals and certifications are available. For more information, contact a local Danfoss partner.
Illustration 1.1 PROFIBUS DP-V0
Features of a master class 1 connection:
•Cyclic data exchange (DP-V0).
•Acyclic read/write on parameters.
•Extended diagnosis.
The acyclic connection is fixed and cannot be changed during operation.
Features of a master class 2 connection:
•Initiate/abort acyclic connection.
•Acyclic read/write on parameters.
The acyclic connection can be established (initiated) or removed (aborted) dynamically even when a master class 1 is active on the network. Use the DP-V1 acyclic connection
4 |
Danfoss A/S © 01/2016 All rights reserved. |
MG37G202 |
Introduction Programming Guide
1.6 |
Symbols, Abbreviations, and |
|
1 |
1 |
|
|
Conventions |
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
CAN |
|
Controller area network |
|
|
|
|
|
|
|
|
|
CTW |
|
Control word |
|
|
|
|
|
|
|
|
|
DP |
|
Distributed periphery |
|
|
|
|
|
|
|
|
|
DTM |
|
|
|
|
|
|
|
|
|
|
|
DU |
|
Data unit |
|
|
|
|
|
|
|
|
|
EEPROM |
Electrical erasable programmable read-only memory |
|
|
|
|
|
|
|
|
|
|
EMC |
|
Electromagnetic compatibility |
|
|
|
|
|
|
|
|
|
FDT |
|
Field device tool |
|
|
|
|
|
|
|
|
|
HMI |
|
|
|
|
|
|
|
|
|
|
|
IND |
|
Sub index |
|
|
|
|
|
|
|
|
|
LCD |
|
Liquid crystal display |
|
|
|
|
|
|
|
|
|
LCP |
|
Local control panel |
|
|
|
|
|
|
|
|
|
LED |
|
Light emitting diode |
|
|
|
|
|
|
|
|
|
MAV |
|
Main actual value |
|
|
|
|
|
|
|
|
|
MC1 |
|
Master class 1 |
|
|
|
|
|
|
|
|
|
MC2 |
|
Master class 2 |
|
|
|
|
|
|
|
|
|
MRV |
|
Main reference value |
|
|
|
|
|
|
|
|
|
OPC |
|
|
|
|
|
|
|
|
|
|
|
PC |
|
Personal computer |
|
|
|
|
|
|
|
|
|
PCD |
|
Process data |
|
|
|
|
|
|
|
|
|
PCA |
|
Parameter characteristics |
|
|
|
|
|
|
|
|
|
PCV |
|
Parameter characteristics value |
|
|
|
|
|
|
|
|
|
PDU |
|
Protocol data unit |
|
|
|
|
|
|
|
|
|
PLC |
|
Programmable logic control |
|
|
|
|
|
|
|
|
|
PNU |
|
Parameter number |
|
|
|
|
|
|
|
|
|
PPO |
|
Parameter-process data |
|
|
|
|
|
|
|
|
|
PVA |
|
Parameter value |
|
|
|
|
|
|
|
|
|
RC |
|
Request/response characteristics |
|
|
|
|
|
|
|
|
|
SAP |
|
Service access point |
|
|
|
|
|
|
|
|
|
SMP |
|
Spontaneous message |
|
|
|
|
|
|
|
|
|
STW |
|
Status word |
|
|
|
|
|
|
|
|
|
Table 1.2 Symbols and Abbreviations
Conventions
Numbered lists indicate procedures.
Bullet lists indicate other information and description of illustrations.
Italicized text indicates:
•
•
•
•
•
•
Cross-reference. Link.
Footnote. Parameter name.
Parameter group name. Parameter option.
* indicates a default setting in a parameter.
MG37G202 |
Danfoss A/S © 01/2016 All rights reserved. |
5 |
Safety |
VLT® PROFIBUS DP MCA 101 |
2 Safety
2 2
2.1 Safety Symbols
The following symbols are used in this manual:
WARNING
Indicates a potentially hazardous situation that could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could result in minor or moderate injury. It can also be used to alert against unsafe practices.
NOTICE
Indicates important information, including situations that can result in damage to equipment or property.
2.2 Qualified Personnel
Correct and reliable transport, storage, installation, operation, and maintenance are required for the troublefree and safe operation of the frequency converter. Only qualified personnel are allowed to install and operate this equipment.
Qualified personnel are defined as trained staff, who are authorized to install, commission, and maintain equipment, systems, and circuits in accordance with pertinent laws and regulations. Also, the qualified personnel must be familiar with the instructions and safety measures described in these operating instructions.
2.3 Safety Precautions
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation, start-up, and maintenance by qualified personnel can result in death or serious injury.
•Only qualified personnel must perform installation, start-up, and maintenance.
WARNING
UNINTENDED START
When the frequency converter is connected to AC mains, DC supply, or load sharing, the motor may start at any time. Unintended start during programming, service, or repair work can result in death, serious injury, or property damage. The motor can start with an external switch, a fieldbus command, an input reference signal from the LCP or LOP, via remote operation using MCT 10 Set-up Software, or after a cleared fault condition.
To prevent unintended motor start:
•Press [Off/Reset] on the LCP before programming parameters.
•Disconnect the frequency converter from the mains.
•Completely wire and assemble the frequency converter, motor, and any driven equipment before connecting the frequency converter to AC mains, DC supply, or load sharing.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not powered. High voltage can be present even when the warning LED indicator lights are off. Failure to wait the specified time after power has been removed before performing service or repair work can result in death or serious injury.
•Stop the motor.
•Disconnect AC mains and remote DC-link power supplies, including battery back-ups, UPS, and DC-link connections to other frequency converters.
•Disconnect or lock PM motor.
•Wait for the capacitors to discharge fully. The minimum duration of waiting time is specified in the chapter Safety in the operating instructions supplied with the frequency converter.
•Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.
6 |
Danfoss A/S © 01/2016 All rights reserved. |
MG37G202 |
Safety Programming Guide
WARNING
LEAKAGE CURRENT HAZARD |
2 2 |
Leakage currents exceed 3.5 mA. Failure to ground the |
frequency converter properly can result in death or serious injury.
•Ensure the correct grounding of the equipment by a certified electrical installer.
WARNING
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment can result in death or serious injury.
•Ensure that only trained and qualified personnel perform installation, start-up, and maintenance.
•Ensure that electrical work conforms to national and local electrical codes.
•Follow the procedures in this guide.
CAUTION
INTERNAL FAILURE HAZARD
An internal failure in the frequency converter can result in serious injury when the frequency converter is not properly closed.
•Ensure that all safety covers are in place and securely fastened before applying power.
MG37G202 |
Danfoss A/S © 01/2016 All rights reserved. |
7 |
Configuration |
VLT® PROFIBUS DP MCA 101 |
3 Configuration
3.1 Configure the PROFIBUS Network
3 3 Ensure that all PROFIBUS stations connected to the same bus network have a unique station address.
Select the PROFIBUS address of the frequency converter via:
•Hardware switches.
•Parameter 9-18 Node Address.
•The PROFIBUS command SSA (set station address).
3.1.1Setting the PROFIBUS Address using the DIP Switches
<![if ! IE]> <![endif]>130BD878.10 |
ON |
1 |
|
|
||
1 |
2 |
|
PROFIBUS Option A |
|
|
<![if ! IE]> <![endif]>LD201 |
|
<![if ! IE]> <![endif]>S600 |
ON |
Termination SN |
<![if ! IE]> <![endif]>LD202 |
MS |
OFF |
||||
|
|
Code No. 130B1100 |
|
|
<![if ! IE]> <![endif]>LD203 |
NS |
8 7 6 5 4 3 2 1 |
ON |
SW |
<![if ! IE]> <![endif]>LD200 |
|
SW. ver. XX.XX |
<![if ! IE]> <![endif]>S300 |
Address |
OFF |
|
||
|
|
|
|
|
||
|
|
ON |
ON |
|
|
|
|
|
|
|
|
|
2 |
To set the PROFIBUS address using the DIP switches:
1.Switch off the supply.
2.Select an address in the range 0–125. Factory setting is 127.
3.For location of the DIP switches, refer to
Illustration 3.1 and Illustration 3.2.
4.Set the switches according to the address, see
Table 3.1.
Switch |
8 |
7 |
6 |
5 |
4 |
3 |
2 |
1 |
|
|
|
|
|
|
|
|
|
Address |
Not |
+64 |
+32 |
+16 |
+8 |
+4 |
+2 |
+1 |
value |
used |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
5 |
Not |
OFF |
OFF |
OFF |
OFF |
ON |
OFF |
ON |
|
used |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
35 |
Not |
OFF |
ON |
OFF |
OFF |
OFF |
ON |
ON |
|
used |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
82 |
Not |
ON |
OFF |
ON |
OFF |
OFF |
ON |
OFF |
|
used |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Table 3.1 Examples: Setting the PROFIBUS Address using the DIP Switches
NOTICE
Switch off the supply before changing the DIP switches.
1Termination switch
2DIP switches
Illustration 3.1 Location and Sequence of the DIP Switches
The DIP switches in the FCD 302 are placed below the inverter part, see Illustration 3.2.
1 |
2 |
<![if ! IE]> <![endif]>130BB708.10 |
|
3
4 |
5 |
Illustration 3.2 FCD 302 Dip Switches
Setting the PROFIBUS address via parameter 9-18 Node Address
1.Switch off the supply.
2.Set the DIP switch to 126 or 127 (factory switch setting).
3.Set the address via parameter 9-18 Node Address or the PROFIBUS SSA-command.
4.The address change comes into effect at the next power-up.
8 |
Danfoss A/S © 01/2016 All rights reserved. |
MG37G202 |
Configuration |
Programming Guide |
Setting the PROFIBUS address with set station address command
1.Switch off the supply.
2.Set the DIP switch to 126 or 127 (factory switch setting).
3.Set the address via the set station address command. Use the set station address command to lock the programmed address and to change the address. To unlock the address setting, change parameter 9-18 Node Address or the address switch, followed by a power cycle. A new
address is effective immediately after applying |
Illustration 3.3 Install GSD File |
|
the set station address command. |
||
|
<![endif]>130BC915.10
3 3
3.2 Configure the Master
3.2.1 GSD File
To configure a PROFIBUS master, the configuration tool needs a GSD file for each type of slave on the network. The GSD file is a PROFIBUS DP standard text file containing the necessary communications set-up data for a slave. Download the GSD file for the relevant frequency converter series vlt-drives.danfoss.com/products/engineering- software/software-download/€eldbus/.
PROFIBUS SW version |
GSD file |
(parameter 15-61 Option SW |
|
Version) |
|
|
|
1.x |
da01040A.GSD |
|
|
2.x |
da02040A.GSD |
|
|
FCD 302 |
da01040B.GSD |
|
|
Table 3.2 GSD File |
|
The following example shows the procedure of configuring a PROFIBUS master for FC 301/FC 302, but the procedure is also valid for other frequency converter series.
1.Import the GSD file in the configuration tool.
2.Import the GSD file to the Simatic Manager software tool. Import a GSD file once only for each frequency converter series, following the initial installation of the software tool. See
Illustration 3.3.
3.Use the browser for the GSD file, install all files, and import both a GSD file and a bitmap for the device into the hardware catalog. See
Illustration 3.4 and Illustration 3.5.
Illustration 3.4 Import a GSD File and a Bitmap
Illustration 3.5 Add a GSD File
<![endif]>130BC913.11
MG37G202 |
Danfoss A/S © 01/2016 All rights reserved. |
9 |
3 3
Configuration |
VLT® PROFIBUS DP MCA 101 |
4.Import and access the FC 301/FC 302 GSD file via the path in the hardware catalog, see
Illustration 3.6.
<![if ! IE]><![endif]>130BA564.11
8.Set up the peripheral input and output data. Data set up in the peripheral area is transmitted cyclically via PPO types. Drag and drop a PPO type 6 word consistent to the first slot, see Illustration 3.8. See the PPO types in
chapter 4 Control for more information.
<![if ! IE]><![endif]>130BC911.11
Illustration 3.6 Import and Access the GSD File
5.Open a project, set up the hardware, and add a PROFIBUS master system.
6.Select FC 300, then drag and drop it onto the PROFIBUS in the hardware diagram.
7.A window for the address of the FC 300 appears. Select the address from the scroll-down list. Ensure that the address setting matches the previous address setting in parameter 9-18 Node Address. See Illustration 3.7.
<![if ! IE]><![endif]>130BC912.11
Illustration 3.7 Select the Address
Illustration 3.8 Drag and Drop PPO Type 6 Word Consistent to the First Slot
The configuration tool automatically assigns addresses in the peripheral address area. In this example, the input and output areas have the following configurations:
PPO type 6
PCD word |
1 |
2 |
3 |
4 |
number |
|
|
|
|
|
|
|
|
|
Input |
256–257 |
258–259 |
260–261 |
262–263 |
address |
|
|
|
|
|
|
|
|
|
Set-up |
STW |
MAV |
Parameter 9- |
Parameter 9- |
|
|
|
16 PCD Read |
16 PCD |
|
|
|
Con€gu- |
Read Con€g- |
|
|
|
ration.2 |
uration.3 |
|
|
|
|
|
Table 3.3 PCD Read (Frequency Converter to PLC)
PCD word |
1 |
2 |
3 |
4 |
number |
|
|
|
|
|
|
|
|
|
Output |
256–257 |
258–259 |
260–261 |
262–263 |
address |
|
|
|
|
|
|
|
|
|
Set-up |
CTW |
MRV |
Parameter 9- |
Parameter 9- |
|
|
|
15 PCD Write |
15 PCD |
|
|
|
Con€gu- |
Write |
|
|
|
ration.2 |
Con€gu- |
|
|
|
|
ration.3 |
|
|
|
|
|
Table 3.4 PCD Write (PLC to Frequency Converter)
10 |
Danfoss A/S © 01/2016 All rights reserved. |
MG37G202 |
Configuration |
Programming Guide |
|
|
Alternative: For PROFIBUS SW version 2.x and higher, autoconfiguration of process data is supported. This feature makes it possible to configure the process data (parameter 9-15 PCD Write Con€guration and
parameter 9-16 PCD Read Con€guration) from the PLC/ master. To use auto-configuration, make sure to enable the feature under DP slave properties. See Illustration 3.9.
<![if ! IE]><![endif]>130BT322.11
Illustration 3.9 Enable Feature under DP Slave Properties
NOTICE
DP-V1 diagnosis is supported for PROFIBUS SW version 2.x and higher. The default setting of the VLT® PROFIBUS
DP MCA 101 is DP-V1 diagnosis. If DP-V0 diagnosis is required, change the setting under DP slave properties.
3.3Configure the Frequency Converter
3.3.1Frequency Converter Parameters
The following parameters are important when configuring |
|
|
|
|
the frequency converter with a PROFIBUS interface: |
3 |
|
3 |
|
• |
Parameter 0-40 [Hand on] Key on LCP. Pressing |
|
||
|
[Hand on] disables control of the frequency |
|
|
|
|
converter via PROFIBUS. |
|
|
|
• |
Parameter 8-02 Control Word Source. After an |
|
|
|
|
initial power-up, the frequency converter |
|
|
|
|
automatically detects whether a fieldbus option is |
|
|
|
|
installed in slot A. The frequency converter then |
|
|
|
|
sets parameter 8-02 Control Word Source to [3] |
|
|
|
|
Option A. If an option is added to, changed in, or |
|
|
|
|
removed from an already commissioned |
|
|
|
|
frequency converter, it does not change |
|
|
|
|
parameter 8-02 Control Word Source. Instead, the |
|
|
|
|
frequency converter enters trip mode and shows |
|
|
|
|
an error. |
|
|
|
• |
Parameter 8-10 Control Word Pro€le. Select |
|
|
|
|
between the Danfoss FC Profile and the |
|
|
|
|
PROFIdrive profile. |
|
|
|
• |
Parameter 8-50 Coasting Select to |
|
|
|
|
parameter 8-56 Preset Reference Select. Select how |
|
|
|
|
to gate PROFIBUS control commands with digital |
|
|
|
|
input command of the control card. |
|
|
|
• |
Parameter 8-03 Control Word Timeout Time to |
|
|
|
|
parameter 8-05 End-of-Timeout Function. Set the |
|
|
|
|
reaction in the event of a bus timeout via these |
|
|
|
|
parameters. |
|
|
|
• |
Parameter 9-18 Node Address. |
|
|
|
• |
Parameter 8-07 Diagnosis Trigger. |
|
|
|
NOTICE
The setting in parameter 8-01 Control Site overrides the settings in parameter 8-50 Coasting Select to
parameter 8-56 Preset Reference Select, and they all act on bus control.
Illustration 3.10 DP-V1 Diagnosis
Download the configuration file to the PLC. The PROFIBUS system is able to go online, and it starts to exchange data when the PLC is set to run mode.
MG37G202 |
Danfoss A/S © 01/2016 All rights reserved. |
11 |
Configuration |
VLT® PROFIBUS DP MCA 101 |
3.3.2 LEDs
The 2 bicolor LEDs in the VLT® PROFIBUS DP MCA 101 indicate the status of PROFIBUS communication.
3 3 The LED marked NS (FCD 302: NS2) indicates the network status, that is, the cyclic communication to the PROFIBUS master. When this light is a constant green, data exchange between the master and the frequency converter is active.
The LED marked MS (FCD 302: BUS MS) indicates the module status, that is, acyclic DP-V1 communication from either a PROFIBUS master class 1 (PLC) or a master class 2 (MCT 10 Set-up Software, FDT tool). When this light is a constant green, DP-V1 communication from master classes 1 and 2 is active.
For details of the full range of communications status indicated by the LEDs, refer to chapter 8 Troubleshooting.
<![if ! IE]><![endif]>130BC259.10
A
Illustration 3.11 FCD 302 LED Panel
12 |
Danfoss A/S © 01/2016 All rights reserved. |
MG37G202 |
Control |
Programming Guide |
|
|
4 Control
4.1 PPO Types
The PROFIBUS profile for frequency converters specifies a number of communication objects (parameter process data objects, PPO). The PROFIBUS profile for frequency converters is suitable for data exchange between a process controller (for example PLC) and a frequency converter. All PPOs are defined for cyclic data transfer (DP-V0) for transferring process data (PCD) and parameters (PCA) from the master to the slave, and conversely.
Pure process data objects
PPO types 3, 4, 6, 7, and 8 are pure process data objects for applications requiring no cyclic parameter access. The PLC sends out process control data, and the frequency converter then responds with a PPO of the same length, containing process status data.
Illustration 4.1 shows the available PPO types:
•PCD 1: The first 2 bytes of the process data area (PCD 1) comprise a fixed part present in all PPO types.
•PCD 2: The next 2 bytes are fixed for PCD write entries (see parameter 9-15 PCD Write Con€guration [1]), but configurable for PCD read entries (see parameter 9-16 PCD Read Con€guration [1]).
•PCD 3–10: In the remaining bytes, the process data can be parameterized with process signals, see parameter 9-23 Parameters for Signals.
The setting in parameter 9-15 PCD Write Con€guration determines the signals for transmission (request) from the master to the frequency converter.
The setting in parameter 9-16 PCD Read Con€guration determines the signals for transmission (response) from the frequency converter to the master.
Parameter channel and process data
PPO types 1, 2, and 5 consist of a parameter channel and 4 4 process data. Use the parameter channel for reading
and/or updating of parameters (successively). Alternatively, for better utilization of I/O and PLC capacity, access parameters via DP-V1. To access via DP-V1, select a pure process data object (PPO type 3, 4, 6, 7, or 8).
Select the PPO type in the master configuration. The selection is automatically recorded in the frequency converter. No manual setting of PPO types in the frequency converter is required. Read the current PPO type in parameter 9-22 Telegram Selection. The setting [1] Standard telegram 1 is equivalent to PPO type 3.
In addition, all PPO types can be set up as word-consistent or module-consistent. The process data area can be wordor module-consistent, whereas the parameter channel must always be module-consistent.
•Word-consistent data is transmitted as individual, independent words between the PLC and the frequency converter.
•Module-consistent data is transmitted as sets of interrelated words transferred simultaneously between the PLC and the frequency converter.
MG37G202 |
Danfoss A/S © 01/2016 All rights reserved. |
13 |
Control |
VLT® PROFIBUS DP MCA 101 |
Standard telegram |
|
|
|
1 |
|
|
|
CTW/STW |
REF/MAV |
(The old PPO type 3) |
|
|
|
|
|
Danfoss telegram |
|
|
|
<![endif]>130BD911.10
4 |
4 |
PPO 1 |
PCV |
CTW/STW |
REF/MAV |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PCD 2 |
PCD 3 |
|
|
|
|
|
|
|
|
PPO 2 |
PCV |
CTW/STW |
REF/MAV |
Read/ |
Read/ |
|
|
|
|
|
|
|
|
|
|
|
|
Write |
Write |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PPO 3 |
|
CTW/STW |
REF/MAV |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PPO 4 |
PCV |
CTW/STW |
REF/MAV |
PCD 2 |
PCD 3 |
PCD 4 |
PCD 5 |
|
|
|
|
|
|
Read/ |
Read/ |
Read/ |
Read/ |
|
|
|
|
||||
|
|
|
|
|
|
Write |
Write |
Write |
Write |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PCD 2 |
PCD 3 |
PCD 4 |
PCD 5 |
|
|
|
|
|
|
PPO 6 |
|
CTW/STW |
REF/MAV |
Read/ |
Read/ |
Read/ |
Read/ |
|
|
|
|
|
|
|
|
|
|
Write |
Write |
Write |
Write |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PCD 2 |
PCD 3 |
PCD 4 |
PCD 5 |
PCD 6 |
PCD 7 |
|
|
|
|
PPO 7 |
|
CTW/STW |
REF/MAV |
Read/ |
Read/ |
Read/ |
Read/ |
Read/ |
Read/ |
|
|
|
|
|
|
|
|
Write |
Write |
Write |
Write |
Write |
Write |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PCD 2 |
PCD 3 |
PCD 4 |
PCD 5 |
PCD 6 |
PCD 7 |
PCD 8 |
PCD 9 |
|
|
PPO 8 |
|
CTW/STW |
REF/MAV |
Read/ |
Read/ |
Read/ |
Read/ |
Read/ |
Read/ |
Read/ |
Read/ |
|
|
|
|
|
|
Write |
Write |
Write |
Write |
Write |
Write |
Write |
Write |
Illustration 4.1 Available PPO Types
14 |
Danfoss A/S © 01/2016 All rights reserved. |
MG37G202 |
Control |
Programming Guide |
|
|
4.2 Process Data
Use the process data part of the PPO to control and monitor the frequency converter via the PROFIBUS.
4.2.1 Process Control Data
Process control data (PCD) is the process data sent from the PLC to the frequency converter.
Master/slave |
|
|
|
|
|
|
|
|
|
1 |
2 |
3 |
....... |
10 |
|
|
|
|
|
CTW |
MRV |
PCD |
....... |
PCD |
|
|
|
|
|
|
|
|
PCD write |
|
|
|
|
|
|
Table 4.1 Process Control Data |
|
|
PCD 1 contains a 16-bit control word, and each bit controls a specific function of the frequency converter, see
chapter 4.3 Control Pro€le.
PCD 2 contains a 16-bit speed setpoint in percentage format. See chapter 4.2.3 Reference Handling.
The settings in parameter 9-15 PCD Write Con€guration and parameter 9-16 PCD Read Con€guration define the content of PCD 3 to PCD 10.
4.2.2 Process Status Data
Process status data is the process data sent from the frequency converter and contains information about the current state.
Slave/master |
|
|
|
|
|
|
|
|
|
1 |
2 |
3 |
...... |
10 |
|
|
|
|
|
STW |
MAV |
PCD |
...... |
PCD |
|
|
|
|
|
|
|
|
PCD read |
|
|
|
|
|
|
Table 4.2 Process Status Data |
|
|
4.2.3 Reference Handling
The reference handling is an advanced mechanism that sums up references from different sources, as shown in
Illustration 4.2.
For more information on reference handling, refer to the
design guide of the relevant frequency converter.
4 4
Illustration 4.2 Reference
The reference, or speed setpoint, is sent via PROFIBUS and is always transmitted to the frequency converter in percentage format as integers shown in hexadecimal (0– 4000 hex).
The reference (MRV) and feedback (MAV) are always scaled equally. The setting of parameter 3-00 Reference Range determines the scaling of the reference and feedback (MAV), see Illustration 4.3.
PCD 1 contains a 16-bit status word, and each bit contains information regarding a possible state of the frequency converter.
PCD 2 contains per default the value of the current speed of the frequency converter in percentage format (see chapter 4.2.3 Reference Handling). PCD 2 can be configured to contain other process signals.
The settings in parameter 9-16 PCD Read Con€guration define the content of PCD 3 to PCD 10.
Illustration 4.3 Reference (MRV) and Feedback (MAV), Scaled
NOTICE
When parameter 3-00 Reference Range is set to [0] Min - Max, a negative reference is handled as 0%.
The actual output of the frequency converter is limited by the speed limit parameters Motor Low/High Speed Limit [RPM/Hz] in parameter 4-11 Motor Speed Low Limit [RPM] to parameter 4-14 Motor Speed High Limit [Hz].
MG37G202 |
Danfoss A/S © 01/2016 All rights reserved. |
15 |
Control |
VLT® PROFIBUS DP MCA 101 |
The final speed limit is set in parameter 4-19 Max Output Frequency.
Table 4.3 lists the reference (MRV) and the feedback (MAV) formats.
|
|
|
|
MRV/MAV |
Integer in hex |
Integer in decimal |
|
|
|
|
|
|
|
|
|
|
|
|
|
100% |
4000 |
16384 |
|
4 |
|
4 |
|
||||
|
|
|
|
|
|||
75% |
3000 |
12288 |
|||||
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
50% |
2000 |
8192 |
|
|
|
|
|
|
|
|
|
|
|
|
|
25% |
1000 |
4096 |
|
|
|
|
|
|
|
|
|
|
|
|
|
0% |
0 |
0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
-25% |
F000 |
-4096 |
|
|
|
|
|
|
|
|
|
|
|
|
|
-50% |
E000 |
-8192 |
|
|
|
|
|
|
|
|
|
|
|
|
|
-75% |
D000 |
-12288 |
|
|
|
|
|
|
|
|
|
|
|
|
|
-100% |
C000 |
-16384 |
|
|
|
|
|
|
|
|
Table 4.3 Reference/Feedback (MRV/MAV) Format
NOTICE
Negative numbers are formed as complement of 2.
NOTICE
The data type for MRV and MAV is an N2 16-bit standardized value, expressing a range from -200% to +200% (8001 to 7FFF).
Example
The following settings determine the speed, as shown in
Table 4.4:
•Parameter 1-00 Con€guration Mode set to [0] Speed open loop.
•Parameter 3-00 Reference Range set to [0] Min-Max.
•Parameter 3-02 Minimum Reference set to 100 RPM.
•Parameter 3-03 Maximum Reference set to 3000 RPM.
MRV/MAV |
|
Actual speed [RPM] |
|
|
|
0% |
0 hex |
100 |
|
|
|
25% |
1000 hex |
825 |
|
|
|
50% |
2000 hex |
1550 |
|
|
|
75% |
3000 hex |
2275 |
|
|
|
100% |
4000 hex |
3000 |
|
|
|
Table 4.4 Actual Speed for MRV/MAV
4.2.4 Process Control Operation
In process control operation, parameter 1-00 Con€guration Mode is set to [3] Process.
The reference range in parameter 3-00 Reference Range is always [0] Min - Max.
•MRV is the process setpoint.
•MAV expresses the actual process feedback (range
±200%).
4.2.5Influence of the Digital Input Terminals on FC Control Mode
In parameter 8-50 Coasting Select to parameter 8-56 Preset Reference Select, set the influence of the digital input terminals on the control of the frequency converter.
NOTICE
The setting of parameter 8-01 Control Site overrules the settings in parameter 8-50 Coasting Select to
parameter 8-56 Preset Reference Select. The setting of terminal 37 coast stop (safe) overrules any other parameter.
Program each of the digital input signals to logic AND, logic OR, or to have no relation to the corresponding bit in the control word. In this way, the following signal sources initiate a specific control command, for example stop/ coast:
•Fieldbus only.
•Fieldbus AND digital input.
•Either fieldbus OR digital input terminal.
NOTICE
To control the frequency converter via PROFIBUS, set parameter 8-50 Coasting Select to either [1] Bus or [2] Logic AND. Then set parameter 8-01 Control Site to [0] Digital and ctrl.word or [2] Controlword only.
For more detailed information and examples of logical relationship options, see chapter 8 Troubleshooting.
4.3 Control Profile
Control the frequency converter according to:
•The PROFIdrive profile, see chapter 4.4 PROFIdrive Control Pro€le, or
•The Danfoss FC control, see chapter 4.5 Danfoss FC Control Pro€le.
Select the control profile in parameter 8-10 Control Word Pro€le. The choice of profile affects the control word and status word only.
Chapter 4.4 PROFIdrive Control Pro€le and
chapter 4.5 Danfoss FC Control Pro€le provide a detailed description of control and status data.
16 |
Danfoss A/S © 01/2016 All rights reserved. |
MG37G202 |
Control |
Programming Guide |
|
|
4.4 PROFIdrive Control Profile
This section describes the functionality of the control word and status word in the PROFIdrive profile.
4.4.1Control Word According to PROFIdrive Profile (CTW)
The control word is used to send commands from a master (for example a PC) to a slave.
Bit |
Bit=0 |
Bit=1 |
|
|
|
00 |
OFF 1 |
ON 1 |
|
|
|
01 |
OFF 2 |
ON 2 |
|
|
|
02 |
OFF 3 |
ON 3 |
|
|
|
03 |
Coasting |
No coasting |
|
|
|
04 |
Quick stop |
Ramp |
|
|
|
05 |
Hold frequency output |
Use ramp |
|
|
|
06 |
Ramp stop |
Start |
|
|
|
07 |
No function |
Reset |
|
|
|
08 |
Jog 1 OFF |
Jog 1 ON |
|
|
|
09 |
Jog 2 OFF |
Jog 2 ON |
|
|
|
10 |
Data invalid |
Data valid |
|
|
|
11 |
No function |
Slow down |
|
|
|
12 |
No function |
Catch up |
|
|
|
13 |
Parameter set-up |
Selection lsb |
|
|
|
14 |
Parameter set-up |
Selection msb |
|
|
|
15 |
No function |
Reverse |
|
|
|
Table 4.5 Control Word Bits
Explanation of the control bits Bit 00, OFF 1/ON 1
Normal ramp stops using the ramp times of the actual selected ramp.
Bit 00=0 stops and activates the output relay 1 or 2 if the output frequency is 0 Hz, and if [31] Relay 123 is selected in parameter 5-40 Function Relay.
When bit 0=1, the frequency converter is in state 1, Switching on inhibited.
Refer to Illustration 4.4.
Bit 01, OFF 2/ON 2
Coast stop.
Bit 01=0 coast stops and activates the output relay 1 or 2 if the output frequency is 0 Hz, and if [31] Relay 123 is selected in parameter 5-40 Function Relay.
When bit 01=1, the frequency converter is in state 1, Switching on inhibited. Refer to Illustration 4.4.
Bit 02, OFF 3/ON 3
Quick stop using the ramp time of parameter 3-81 Quick Stop Ramp Time.
Bit 02=0 quick stops and activates the output relay 1 or 2 if the output frequency is 0 Hz, and if [31] Relay 123 is selected in parameter 5-40 Function Relay.
When bit 02=1, the frequency converter is in state 1, Switching on inhibited.
Refer to Illustration 4.4.
Bit 03, coasting/no coasting
Bit 03=0 leads to a coast stop.
When bit 03=1, if the other start conditions are fulfilled, the frequency converter can start.
NOTICE
The selection in parameter 8-50 Coasting Select
determines how bit 03 is linked with the corresponding 4 4 function of the digital inputs.
Bit 04, quick stop/ramp
Quick stop using the ramp time of parameter 3-81 Quick Stop Ramp Time.
When bit 04=0, a quick stop occurs.
When bit 04=1, if the other start conditions are fulfilled, the frequency converter can start.
NOTICE
The selection in parameter 8-51 Quick Stop Select determines how bit 04 is linked with the corresponding function of the digital inputs.
Bit 05, hold frequency output/use ramp
When bit 05=0, the present output frequency is maintained, even if the reference value is modified. When bit 05=1, the frequency converter can perform its regulating function again according to the respective reference value.
Bit 06, ramp stop/start
Normal ramp stop using the ramp times of the actual ramp selected. In addition, if [31] Relay 123 is selected in parameter 5-40 Function Relay, and if the output frequency is 0 Hz, this bit activates output relay 01 or 04.
Bit 06=0 stops the frequency converter.
When bit 06=1, if the other start conditions are fulfilled, the frequency converter can start.
NOTICE
The selection in parameter 8-53 Start Select determines how bit 06 is linked with the corresponding function of the digital inputs.
Bit 07, no function/reset
Reset after switching off. Acknowledges event in fault buffer.
When bit 07=0, no reset occurs.
When there is a slope change of bit 07 to 1, a reset occurs after switching off.
Bit 08, jog 1 OFF/ON
Activation of the pre-programmed speed in
parameter 8-90 Bus Jog 1 Speed. JOG 1 is only possible if bit 04=0 and bits 00–03=1.
Bit 09, jog 2 OFF/ON
Activation of the pre-programmed speed in
parameter 8-91 Bus Jog 2 Speed. JOG 2 is only possible if bit 04=0 and bits 00–03=1.
MG37G202 |
Danfoss A/S © 01/2016 All rights reserved. |
17 |
Control |
VLT® PROFIBUS DP MCA 101 |
Bit 10, data invalid/valid
Tells the frequency converter whether to use or ignore the control word.
Bit 10=0 ignores the control word, making it possible to turn off the control word when updating/reading parameters.
Bit 10=1 uses the control word. This function is relevant, because the control word is always contained in the telegram, regardless of which type of telegram is used.
4 4 Bit 11, no function/slow down
Used to reduce the speed reference value by the amount given in parameter 3-12 Catch up/slow Down Value.
When bit 11=0, no modification of the reference value occurs.
When bit 11=1, the reference value is reduced.
Bit 12, no function/catch up
Used to increase the speed reference value by the amount given in parameter 3-12 Catch up/slow Down Value.
When bit 12=0, no modification of the reference value occurs.
When bit 12=1, the reference value is increased.
If both slowing down and accelerating are activated (bits 11 and 12=1), slowing down has priority, and the speed reference value is reduced.
Bits 13/14, set-up selection
Bits 13 and 14 are used to select between the 4 parameter set-ups according to Table 4.6.
The function is only possible if [9] Multi Set-up has been selected in parameter 0-10 Active Set-up. The selection in parameter 8-55 Set-up Select determines how bits 13 and 14 are linked with the corresponding function of the digital inputs. Changing set-up while running is only possible if the set-ups have been linked in
parameter 0-12 This Set-up Linked to.
Set-up |
Bit 13 |
Bit 14 |
|
|
|
1 |
0 |
0 |
|
|
|
2 |
1 |
0 |
|
|
|
3 |
0 |
1 |
|
|
|
4 |
1 |
1 |
|
|
|
Table 4.6 Parameter Set-ups
Bit 15, no function/reverse
Bit 15=0 causes no reversing.
Bit 15=1 causes reversing.
NOTICE
In the factory setting, reversing is set to [0] Digital in parameter 8-54 Reversing Select.
NOTICE
Bit 15 causes reversing only when Ser. communication, Logic or, or Logic and is selected.
4.4.2Status Word According to PROFIdrive Profile (STW)
The status word is used to notify a master (for example a PC) about the status of a slave.
Bit |
Bit=0 |
Bit=1 |
|
|
|
00 |
Control not ready |
Control ready |
|
|
|
01 |
Drive not ready |
Drive ready |
|
|
|
02 |
Coasting |
Enable |
|
|
|
03 |
No error |
Trip |
|
|
|
04 |
OFF 2 |
ON 2 |
|
|
|
05 |
OFF 3 |
ON 3 |
|
|
|
06 |
Start possible |
Start not possible |
|
|
|
07 |
No warning |
Warning |
|
|
|
08 |
Speed ≠ reference |
Speed = reference |
09 |
Local operation |
Bus control |
|
|
|
10 |
Out of frequency limit |
Frequency limit ok |
|
|
|
11 |
No operation |
In operation |
|
|
|
12 |
Drive OK |
Stopped, auto start |
|
|
|
13 |
Voltage OK |
Voltage exceeded |
|
|
|
14 |
Torque OK |
Torque exceeded |
|
|
|
15 |
Timer OK |
Timer exceeded |
|
|
|
Table 4.7 Status Word Bits
Explanation of the status bits Bit 00, control not ready/ready
When bit 00=0, bit 00, 01, or 02 of the control word is 0 (OFF 1, OFF 2, or OFF 3) - or the frequency converter is switched off (tripped).
When bit 00=1, the frequency converter control is ready, but power is not necessarily supplied to the unit (in the event of 24 V external supply of the control system).
Bit 01, VLT not ready/ready
Same significance as bit 00, however, power is supplied to the unit. The frequency converter is ready when it receives the necessary start signals.
Bit 02, coasting/enable
When bit 02=0, bit 00, 01, or 02 of the control word is 0 (OFF 1, OFF 2, or OFF 3 or coasting) - or the frequency converter is switched off (trip).
When bit 02=1, bit 00, 01, or 02 of the control word is 1, and the frequency converter has not tripped.
Bit 03, no error/trip
When bit 03=0, no error condition exists in the frequency converter.
When bit 03=1, the frequency converter has tripped and requires a reset signal before it can start.
Bit 04, ON 2/OFF 2
When bit 01 of the control word is 0, bit 04=0. When bit 01 of the control word is 1, bit 04=1.
Bit 05, ON 3/OFF 3
When bit 02 of the control word is 0, bit 05=0. When bit 02 of the control word is 1, bit 05=1.
18 |
Danfoss A/S © 01/2016 All rights reserved. |
MG37G202 |