Data Sheet
Temperature sensor
Type MBT 5113 and MBT 5116
2 stroke exhaust gas temperature sensors
Heavy-duty sensors used for measuring exhaust gas from diesel engines, turbines and compressors within stationary and marine applications.
MBT 5113 – based on thermocouple technology for media temperatures up to 800 °C.
MBT 5116 – based on a Pt 100 / Pt 1000 element technology for standardised signals, high accuracy and media temperature up to 600 °C.
Features:
• MBT 5113
Up to 800 °C media temperaturesB-head for standard installationsChangeable inserts
Solid drilled protection tube for high resistance to shock and vibrations
1 or 2 x NiCr-Ni, type K
• MBT 5116
Up to 600 °C media temperatures2 or 3 wire connections
Solid drilled protection tube for high resistance to shock and vibrations
Available in 2 versions:
▪ Slim-line for compact installations ▪ B-head for standard installations
Changeable insert
1 or 2 x Pt 100 / Pt 1000
AI215386431660en-000701
Temperature sensor, MBT 5113 and MBT 5116
Product speci€cation
Technical data
MBT 5113
Table 1: General data
Features |
Speci€cations |
Measuring range |
-50 – 800 °C |
Sensing element |
1 × NiCr-Ni, type K or 2 x NiCr-Ni, type K |
Protection tube |
ø24 / ø14, AISI 316 Ti |
|
|
Table 2: Response times
Protection tube |
|
|
Indicative response times |
|
|
|
Water 0.2 m/s |
|
Air 1 m/s |
||
|
|
|
|||
ø24 / ø14 |
t0.5 |
t0.9 |
t0.5 |
t0.9 |
|
30 s |
95 s |
200 s |
700 s |
||
|
|||||
|
|
|
|
|
Table 3: Mechanical and environmental speci€cations
Features |
Speci€cations |
|
|
|
Max. temperature |
Ambient: |
90 |
°C with 800 °C media temperature |
|
85 |
°C with transmitter |
|||
|
|
|||
Vibration stability |
Shock: |
100 g/6 ms |
||
Vibrations: |
4 g sine function, 2 – 100 Hz, measured according to IEC 60068-2-6 |
|||
|
||||
|
|
|
|
|
Enclosure |
IP65 according to IEC 60529 |
|
|
|
Cable entry |
Pg 16 |
|
|
|
|
|
|
|
Figure 1: Sensor tolerance EN 60584-2 class 2 |
|
Max. deviation |
|
Media temperature |
|
NiCr-Ni & Fe-CuNi |
|
© Danfoss | Climate Solutions | 2021.03 |
AI215386431660en-000701 | 2 |
Temperature sensor, MBT 5113 and MBT 5116
MBT 5116
Table 4: General data
Features |
Speci€cations |
Measuring range |
-50 – 600 °C |
Sensing element |
1 or 2 x Pt 100/1 or 2 x Pt 1000 |
Protection tube |
ø24 / ø14, AISI 316 |
|
|
Table 5: Response times
Protection tube |
|
|
Indicative response times |
|
|
|
Water 0.2 m/s |
|
Air 1 m/s |
||
|
|
|
|||
ø24 / ø14 |
t0.5 |
t0.9 |
t0.5 |
t0.9 |
|
30 s |
95 s |
150 s |
450 s |
||
|
|||||
|
|
|
|
|
Table 6: Mechanical and environmental speci€cations
Features |
Speci€cations |
|
|
Max. ambient temperature |
Slim-Line: |
75 °C with 600 °C media temperature |
|
B-Head: |
90 °C with 600 °C media temperature |
||
|
|||
|
|
||
Sensor tolerance |
EN 60751 Class B: ±(0.3 + 0.005 × t) t = temperature of medium, numerical value |
||
Insulation resistance |
Minimum 0.5 M Ohm at 600 °C according to EN60751 |
||
|
|
|
|
Vibration stability |
Shock: |
100 g/6 ms |
|
Vibrations: |
4 g sine function, 2 – 200Hz, measured according to IEC 60068-2-6 |
||
|
|||
|
|
|
|
Enclosure |
IP65 according to IEC 60529 |
|
|
|
|
|
|
Cable entry |
Slim-Line |
Pg 13.5 |
|
B-Head |
Pg 16 |
||
|
|||
|
|
|
Table 7: Material
Type |
Feature |
Material |
Slim-Line |
Housing |
Nickel plated brass |
|
Union |
Nickel plated brass |
|
Cover |
Nickel plated brass |
|
Spring (internal mounted) |
W.no. 1.4568 |
|
Extension length |
AISI 316 |
|
Protection tube in contact with media |
AISI 316 |
|
|
|
B-Head |
Union |
Nickel plated brass |
|
Connection head |
Die cast aluminium |
|
Extension length |
AISI 316 |
|
Protection tube in contact with media |
AISI 316 |
|
|
|
Dimensions
MBT 5113
Figure 2: MBT 5113 |
|
|
|
|
|
|
|
|
A |
B |
C |
|
|
|
|
D |
|
<![if ! IE]> <![endif]>ø15 |
|
|
|
|
|
|
|
|
|
<![if ! IE]> <![endif]>ø24 |
|
|
|
|
|
|
<![if ! IE]> <![endif]>ø14 |
42 |
E |
|
H |
|
|
|
|
|
|
|
|
|
|
|
|
|
F |
|
|
|
|
|
|
G |
|
|
A |
Insertion length |
D |
Process connection |
G |
Pg 16 |
|
B |
Extension length |
E |
Protection tube |
H |
Approx. 50 |
|
C |
Approx. 75 |
|
F |
Connection head, type B |
|
|
© Danfoss | Climate Solutions | 2021.03 |
|
|
|
AI215386431660en-000701 | 3 |