Data Sheet
Pressure transmitters
Type MBS 33
For industrial applications
The standard pressure transmitters MBS 33 are
designed for use in almost all industrial
applications, and oer reliable pressure
measurements, even under harsh
environmental conditions.
The exible pressure transmitter programme
covers dierent output signals, absolute or
gauge (relative) versions, measuring ranges
from 0 – 1 to 0 – 600 bar and a wide range of
pressure and electrical connections.
Excellent vibration stability, robust
construction, and a high degree of EMC / EMI
protection equip the pressure transmitter to
meet the most stringent industrial
requirements.
Features
• Designed for use in severe industrial
environments
• CE-marked: EMC protected in accordance
with EU EMC Directive
• Enclosure and wetted parts of acid-resistant
stainless steel (AISI 316L)
• Fully digitally compensated
• Output signals:
◦ 0 – 5 V, 1 – 5 V, 1 – 6 V or 0 – 10 V DC
◦ 4 – 20 mA
• A wide range of pressure connections
• Electrical connection: plug or cable
• For use in ATEX Zone 2 explosive
atmospheres
• UL approved
AI308949780206en-000202
Accuracy (incl. non-linearity, hysteresis and repeatability)
≤ ± 0.3% FS (typ.)
Non-linearity BFSL (conformity)
Hysteresis and repeatability
Thermal zero point shift
≤ ± 0.1% FS / 10K (typ.)
Thermal sensitivity (span) shift
≤ ± 0.1% FS / 10K (typ.)
Liquids with viscosity < 100 cSt
Overload pressure (static)
Durability, P: 10 – 90% FS
Nom. output signal
(short-circuit protected)
Supply voltage [UB], polarity protected
Supply – current consumption
Supply voltage dependency
0-5 V: 5.75 V
1-5 V: 5.6 V
1-6 V: 6.75 V
Load [RL] (load connected to 0 V)
Sensor operating temperature
Normal
Ambient temperature range (depending on electrical connection)
See Electrical connections
Compensated temperature range
Transport / storage temperature range
Vibration stability
Sinusoidal
IEC 60068-2-6
20 g, 25 Hz – 2 kHz
Enclosure (depending on electrical connection)
See Electrical connections
Pressure transmitters, type MBS 33
Product specication
Technical data
Table 1: Performance (EN 60770)
Table 2: Electrical specications
Table 3: Environmental conditions
Table 4: Explosive atmospheres
(1)
(1)
When used in ATEX Zone 2 areas at low temperatures the cable and plug must be protected against impact.
When used in ATEX Zone 2 areas at low temperatures the cable and plug must be protected against impact.
© Danfoss | Climate Solutions | 2021.06 AI308949780206en-000202 | 2