Data sheet
Pressure transmitter for air and water applications
Type MBS 1900
The pressure transmitter MBS 1900 is designed
for use in air and water applications like Booster
Pumps and Air Compressors.
The semi-exible pressure transmitter
programme covers dierent output signals,
absolute or gauge (relative) versions, measuring
ranges from 0 – 4 bar to 0 – 25 bar and a wide
range of pressure and electrical connections.
Enclosure material is stainless steel AISI 316L.
Features
Approvals
• Designed for use in air and water applications
• Wetted parts of stainless steel (AISI 304)
• Pressure ranges in relative (gauge) or absolute
from 0 – 25 bar
• Output signals: 4 – 20 mA, or ratio metric
UL Approval,
Certicate number: E31024
NSF-61
• Absolute or relative (gauge) sensor element
• A wide range of pressure and electrical
connections
• Digitally compensated
© Danfoss | DCS (im) | 2017.04
IC.PD.P21.K7.02 | 520B7921 | 1
Data sheet | Pressure transmitter for air and water applications, type MBS 1900
Technical data
Performance (EN 60770)
Accuracy (@ 20 °C) (incl. non-linearity, hysteresis and repeatability) ≤ ± 1.0% FS
Non-linearity BFSL (conformity) ≤ ± 0.5% FS
Hysteresis and repeatability ≤ ± 0.1% FS
Total error band inside the compensated temperature range ≤ ± 3.0% FS
Response time < 4 ms
Overload pressure (Static) 3 × FS (max. 75 bar)
Burst pressure 4 × FS (max. 100 bar)
Durability, P: 10 – 90% FS > 10 ×106 cycles
Electrical specications
Nom. output signal
(short-circuit protected)
Supply voltage [UB], polarity protected 9 – 28 V 5 V ± 10%
Supply – current consumption – ≤ 5 mA
Supply voltage dependency ≤ ± 0.1% FS/10 V ≤ ± 0.1% FS/10 V
Load [RL] (load connected to 0 V) RL ≤ (UB -10V)/0.02A RL ≥ 5 KΩ @ 5 V d.c.
Output impedance – < 25 Ω
4 − 20 mA
Ratiometric
(10 – 90% of V
supp.
)
Environmental conditions
Sensor temperature range 0 – 80 °C
Max. media temperature 110 – (0.35 × ambient temperature)
Ambient temperature range (depending on electrical connection) -20 – 80 °C
Compensated temperature range 0 – 80 °C
Transport / Storage temperature range -50 – 85 °C
EMC – Emission EN 61000-6-3
EMC – Immunity EN 61000-6-2
Insulation resistance > 100 MΩ at 500 V
Vibration stability
Shock resistance
Enclosure (depending on electrical connection) see page 4
Sinusoidal 15 g, 5 Hz – 2 kHz IEC 60068-2-6
Random 7.5 g
Shock 200 g/1 ms IEC 60068-2-27
Free fall 1 m IEC 60068-2-32
, 5 Hz – 1 kHz IEC 60068-2-64
rms
2 | 520B7921 | IC.PD.P21.K7.02
Mechanical characteristics
Wetted parts EN 10088-1; 1.4301 (AISI 304)
Materials
Net weight (depending on pressure connection and electrical connection) 0.15 – 0.3 kg
Enclosure EN 10088-1; 1.4404 (AISI 316 L)
Electrical connections see page 4
Mounting instructions
Width across ats 24 mm
Mounting torque max. 20 Nm
© Danfoss | DCS (im) | 2017.04