Status and Fault Logic.....................................................................................................................................................................6
Status Logic...................................................................................................................................................................................6
Relationship Between Function Block Input and Output Signals...................................................................................7
Function Block Connections.........................................................................................................................................................8
MC Controller—Input Configuration........................................................................................................................................ 8
Configure the MFIn.....................................................................................................................................................................9
Configure the DigAn..................................................................................................................................................................9
Configure the MFIn..................................................................................................................................................................10
Configure the DigAn................................................................................................................................................................11
Status and Fault Logic..................................................................................................................................................................13
Status Logic.................................................................................................................................................................................13
Relationship Between Function Block Input and Output Signals................................................................................ 14
Function Block Connections...................................................................................................................................................... 15
MC Controller—Input Configuration......................................................................................................................................15
Configure the MFIn..................................................................................................................................................................16
Configure the DigAn................................................................................................................................................................16
Configure the MFIn..................................................................................................................................................................17
Configure the DigAn................................................................................................................................................................18
Status and Fault Logic..................................................................................................................................................................20
Status Logic.................................................................................................................................................................................20
Relationship Between Function Block Input and Output Signals................................................................................ 21
Function Block Connections...................................................................................................................................................... 22
MC Controller—Input Configuration......................................................................................................................................22
Configure the MFIn..................................................................................................................................................................23
Configure the DigAn................................................................................................................................................................23
Configure the MFIn..................................................................................................................................................................24
Configure the DigAn................................................................................................................................................................25
Status and Fault Logic..................................................................................................................................................................27
Status Logic.................................................................................................................................................................................27
Relationship Between Function Block Input and Output Signals................................................................................ 28
Function Block Connections...................................................................................................................................................... 29
MC Controller—Input Configuration......................................................................................................................................29
Configure the MFIn..................................................................................................................................................................30
Configure the DigAn................................................................................................................................................................30
Configure the MFIn..................................................................................................................................................................31
Configure the DigAn................................................................................................................................................................32
Status and Fault Logic..................................................................................................................................................................34
Status Logic.................................................................................................................................................................................34
Relationship Between Function Block Input and Output Signals................................................................................ 35
Function Block Connections...................................................................................................................................................... 36
MC Controller—Input Configuration......................................................................................................................................36
Configure the MFIn..................................................................................................................................................................37
Configure the DigAn................................................................................................................................................................37
Configure the MFIn..................................................................................................................................................................38
Configure the DigAn................................................................................................................................................................39
Status and Fault Logic..................................................................................................................................................................41
Status Logic.................................................................................................................................................................................41
Relationship Between Function Block Input and Output Signals................................................................................ 42
Function Block Connections...................................................................................................................................................... 43
MC Controller—Input Configuration......................................................................................................................................43
Configure the MFIn..................................................................................................................................................................44
Configure the DigAn................................................................................................................................................................44
Configure the MFIn..................................................................................................................................................................45
Configure the DigAn................................................................................................................................................................46
Status and Fault Logic..................................................................................................................................................................48
Status Logic.................................................................................................................................................................................48
Relationship Between Function Block Input and Output Signals................................................................................ 49
Function Block Connections...................................................................................................................................................... 50
MC Controller—Input Configuration......................................................................................................................................50
Configure the MFIn..................................................................................................................................................................51
Configure the DigAn................................................................................................................................................................51
Configure the MFIn..................................................................................................................................................................52
Configure the DigAn................................................................................................................................................................53
Status and Fault Logic..................................................................................................................................................................55
Status Logic.................................................................................................................................................................................55
Relationship Between Function Block Input and Output Signals................................................................................ 56
Function Block Connections...................................................................................................................................................... 57
MC Controller—Input Configuration......................................................................................................................................57
Configure the MFIn..................................................................................................................................................................58
Configure the DigAn................................................................................................................................................................58
Configure the MFIn..................................................................................................................................................................59
Configure the DigAn................................................................................................................................................................60
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr40b Function Block
This function block configures the output of MBS 1250 pressure sensors with a nominal 0–40 bar [4000
kPa/580 PSI] range.
Inputs
Find out how the function block uses a reference voltage and a changing input voltage to produce PSI,
kPa, dBar and Pct outputs.
Function Block Inputs
InputTypeRangeDescription
Snsr PwrU160–5250 mVInputs a reference voltage that the PLUS+1® controller also applies to the Pin 1 (+ Supply) on the pressure
transmitter.
InputU160–5250 mVThe function block compares the changing Input voltage with the constant Snsr Pwr reference voltage to produce
PSI, kPa, dBar and Pct outputs.
The function block’s nominal operating range is between 10.00% and 90.00% of Snsr Pwr voltage.
When the Input voltage reaches:
•
10.00% of the Snsr Pwr voltage, the function block’s output starts rising above zero.
•
90.00% of the Snsr Pwr voltage, the function block outputs its maximum nominal outputs of PSI and kPa. The
maximum nominal output is specified by Bar and is limited to 2200.
•
100.00% of the Snsr Pwr voltage, the function block outputs its maximum over-pressure outputs of PSI and kPa
at 112.50% of the output defined by Bar.
The maximum over-pressure output equals 112.50% of the maximum nominal output. The generic function
block allows you to specify the pressure range allowed.
Outputs
Learn how the outputs of the general function block work.
Function Block Outputs
OutputTypeRangeDescription
StatusU16——Indicates if the Flt Pct value is within range or is set too high.
The Flt Pct sets the percentage that the Input voltage can rise above or fall below the function block’s operating range
without setting a fault condition.
You can change the Flt Pct value (1000 = 10.00%) on the inner page of the Prs_Snsr function block.
The Status output uses the bitwise scheme.
Danfoss | March 201811062069 | AQ00000100en-US0401 | 5
User Manual
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr40b Function Block
Function Block Outputs (continued)
FaultU16——Indicates if the voltage on the function block’s Input pin is too low or too high.
The Flt Pct sets the percentage that the Input voltage can rise above or fall below the function block’s operating range
without setting a fault condition.
You can change the Flt Pct value (1000 = 10.00%) on the inner page of the Prs_Snsr function block.
The Fault output uses the bitwise scheme.
•
0x0000 = Block is OK.
•
0x8001 = Input value is too low.
•
0x8002 = Input value is too high.
PSIU160–35896Indicates pressure in pounds per square inch (PSI).
1 = 1 PSI.
kPaU160–247500 Indicates pressure in kilopascals (kPa).
1 = 1 kPa.
dBarU160–24750
PctU160–11250Indicates pressure as a percent of the function block’s operating range.
Indicates pressure in decibars (dBar).
1 = 1 dBar.
10000 = 100.00%.
Status and Fault Logic
This topic describes how status logic and fault logic are indicated for the function block.
Status Logic
The status code indicates the calibration state of the function block.
Danfoss | March 201811062069 | AQ00000100en-US0401 | 7
User Manual
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr40b Function Block
Function Block Connections
Connections you can make with the function block are described.
Function block connections
ItemDescription
1Sensor voltage (varies with pressure).
2Sensor reference power voltage.
3Function block status.
4Function block faults.
5Pressure in PSI.
6Pressure in kPa.
7Pressure in decibar (dBar)
8Pressure in % of range.
MC Controller—Input Configuration
Configure MFIn and DigAn to accept the input of the function block.
For MC Controllers, you route the function block’s Input through an MFIn or a DigAn.
You must change the MFIn and DigAn default configurations to accept this input.
Danfoss | March 201811062069 | AQ00000100en-US0401 | 9
User Manual
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr40b Function Block
3. Make the changes that are shown in the following figure.
SC Controller—Input Configuration
Configure MFIn and DigAn to accept the input of the function block.
You route the function block’s Input through an MFIn or a DigAn. You must change the MFIn and
DigAn default configurations to accept this input.
Configure the MFIn
Learn how to configure MFIn to accept input from the function block.
1. In the GUIDE template, enter the Inputs page.
2. Enter the page that receives the input.
3. Make the changes that are shown in the following figure.
Danfoss | March 201811062069 | AQ00000100en-US0401 | 11
User Manual
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr160b Function Block
This function block configures the output of MBS 1250 pressure sensors with a nominal 0–160 bar [16000
kPa/2320 PSI] range.
Inputs
Find out how the function block uses a reference voltage and a changing input voltage to produce PSI,
kPa, dBar and Pct outputs.
Function Block Inputs
InputTypeRangeDescription
Snsr Pwr——0–5250 mVInputs a reference voltage that the PLUS+1 controller also applies to the Pin 1 (+ Supply) on the Pressure
Transmitter.
Input——0–5250 mVThe function block compares the changing Input voltage with the constant Snsr Pwr reference voltage to produce
PSI, kPa, dBar, and Pct outputs.
The function block’s nominal operating range is between 10.00% and 90.00% of Snsr Pwr voltage.
When the Input voltage reaches:
•
10.00% of the Snsr Pwr voltage, the function block’s output starts rising above zero.
•
90.00% of the Snsr Pwr voltage, the function block outputs its maximum nominal outputs of 2320 PSI/16000
kPa/10000 (100.00%).
•
100.00% of the Snsr Pwr voltage, the function block outputs its maximum over-pressure outputs of 2610 PSI/
18000 kPa/11250 (112.50%).
The maximum over-pressure output equals 112.50% of the maximum nominal output (16000 kPa x 112.50% =
18000 kPa).
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr160b Function Block
Outputs
Learn about the outputs of the Prs_Snsr160b function block.
Function Block Outputs
Output TypeRangeDescription
StatusU16——Indicates if the Flt Pct value is within range or is set too high.
The Flt Pct sets the percentage that the Input voltage can rise above or fall below the function block’s operating range
without setting a fault condition.
You can change the Flt Pct value (1000 = 10.00%) on the inner page of the Prs_Snsr function block.
The Status output uses the bitwise scheme.
•
0x0000 = Block is OK.
•
0x8008 = Flt Pct value is too high.
FaultU16——Indicates if the voltage on the function block’s Input pin is too low or too high.
The Flt Pct sets the percentage that the Input voltage can rise above or fall below the function block’s operating range
without setting a fault condition.
You can change the Flt Pct value (1000 = 10.00%) on the inner page of the Prs_Snsr function block.
The Fault output uses the bitwise scheme.
•
0x0000 = Block is OK.
•
0x8001 = Input value is too low.
•
0x8002 = Input value is too high.
PSIU160–2610Indicates pressure in pounds per square inch (PSI).
1 = 1 PSI.
kPaU160–18000Indicates pressure in kilopascals (kPa).
1 = 1 kPa.
dBarU160–1800
PctU160–11250Indicates pressure as a percent of the function block’s operating range.
Indicates pressure in decibars (dBar).
1 = 1 dBar.
10000 = 100.00%.
Status and Fault Logic
This topic describes how status logic and fault logic are indicated for the function block.
Status Logic
The status code indicates the calibration state of the function block.
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr160b Function Block
Drops below 300 mV, the function block outputs an input too low fault. (500 mV – 5% of the 4000 mV
•
nominal input voltage range = fault at 300 mV)
Rises above 4700 mV, the function block outputs an input too high fault. (4500 mV + 5% of the 4000
•
mV nominal input voltage range = fault at 4700 mV)
Function Block Connections
Connections you can make with the function block are described.
Function block connections
ItemDescription
1Sensor voltage (varies with pressure).
2Sensor reference power voltage.
3Function block status.
4Function block faults.
5Pressure in PSI.
6Pressure in kPa.
7Pressure in decibar (dBar)
8Pressure in % of range.
MC Controller—Input Configuration
Configure MFIn and DigAn to accept the input of the function block.
For MC Controllers, you route the function block’s Input through an MFIn or a DigAn.
You must change the MFIn and DigAn default configurations to accept this input.
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr160b Function Block
3. Make the changes that are shown in the following figure.
SC Controller—Input Configuration
Configure MFIn and DigAn to accept the input of the function block.
You route the function block’s Input through an MFIn or a DigAn. You must change the MFIn and
DigAn default configurations to accept this input.
Configure the MFIn
Learn how to configure MFIn to accept input from the function block.
1. In the GUIDE template, enter the Inputs page.
2. Enter the page that receives the input.
3. Make the changes that are shown in the following figure.
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr250b Function Block
This function block configures the output of MBS 1250 pressure sensors with a nominal 0–250 bar [25000
kPa/3626 PSI] range.
Inputs
Learn how the function block uses a reference voltage and a changing input voltage to produce PSI, Kpa,
dBar and Pct outputs.
Function Block Inputs
InputTypeRangeDescription
Snsr Pwr——0–5250 mVInputs a reference voltage that the PLUS+1 controller also applies to the Pin 1 (+ Supply) on the Pressure
Transmitter.
Input——0–5250 mVThe function block compares the changing Input voltage with the constant Snsr Pwr reference voltage to produce
PSI, kPa, dBar , and Pct outputs.
The function block’s nominal operating range is between 10.00% and 90.00% of Snsr Pwr voltage.
When the Input voltage reaches:
•
10.00% of the Snsr Pwr voltage, the function block’s output starts rising above zero.
•
90.00% of the Snsr Pwr voltage, the function block outputs its maximum nominal outputs of 3626 PSI/25000
kPa/10000 (100.00%).
•
100.00% of the Snsr Pwr voltage, the function block outputs its maximum over-pressure outputs of 4080 PSI/
28125 kPa/11250 (112.50%).
The maximum over-pressure output equals 112.50% of the maximum nominal output. (25000 kPa x 112.50% =
28125 kPa)
Danfoss | March 201811062069 | AQ00000100en-US0401 | 19
User Manual
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr250b Function Block
Outputs
Learn about the outputs of the Prs_Snsr250b function block.
Function Block Outputs
OutputTypeRangeDescription
StatusU16——Indicates if the Flt Pct value is within range or is set too high.
The Flt Pct sets the percentage that the Input voltage can rise above or fall below the function block’s operating
range without setting a fault condition.
You can change the Flt Pct value (1000 = 10.00%) on the inner page of the Prs_Snsr function block.
The Status output uses the bitwise scheme.
•
0x0000 = Block is OK.
•
0x8008 = Flt Pct value is too high.
FaultU16——Indicates if the voltage on the function block’s Input pin is too low or too high.
The Flt Pct sets the percentage that the Input voltage can rise above or fall below the function block’s operating
range without setting a fault condition.
You can change the Flt Pct value (1000 = 10.00%) on the inner page of the Prs_Snsr function block.
The Fault output uses the bitwise scheme.
•
0x0000 = Block is OK.
•
0x8001 = Input value is too low.
•
0x8002 = Input value is too high.
PSIU160–4080Indicates pressure in pounds per square inch (PSI).
1 = 1 PSI.
kPaU160–28125Indicates pressure in kilopascals (kPa).
1 = 1 kPa.
dBarU160–2812
PctU160–11250Indicates pressure as a percent of the function block’s operating range.
Indicates pressure in decibars (dBar).
1 = 1 dBar.
10000 = 100.00%.
Status and Fault Logic
This topic describes how status logic and fault logic are indicated for the function block.
Status Logic
The status code indicates the calibration state of the function block.
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr250b Function Block
Fault Logic
Learn how fault logic can indicate problems, causes of problems, and solutions.
Fault logic
ConditionHex
Input value is too low.0x80010001
Input value is too high.0x80020010
*
Bit 16 set to 1 identifies a standard Danfoss status or fault code.
*
Binary CauseResponseCorrection
Volt(age) is less than [10% of
Snsr Pwr] - [Flt Pct of nominal
signal range (which is 80% of
Snsr Pwr)].
Snsr Pwr less than 0.Ensure correct software input is
Volt(age) is greater than [90% of
Snsr Pwr] + [Flt Pct of nominal
signal range (which is 80% of
Snsr Pwr)].
Snsr Pwr greater than 5250.
Output = 0.
Output is extrapolated beyond
the maximum value up to 11250
(112.50%).
Output = 0.
Inspect for open circuit in wire
connections to sensor.
made in the application.
Inspect for short circuit in wire
•
connections to sensor.
Verify the correct pressure
•
sensor is used for the
application.
Ensure correct software input is
made in the application.
Relationship Between Function Block Input and Output Signals
Use the plot to find out the relationships between the function block's Input voltages and its kPa and Pct
outputs.
This function block’s:
Flt Pct value = 500 (5.00%) and its Snsr Pwr value = 5000 mV.
•
Nominal Input voltage ranges between 10.00% (500 mV) and 90.00% (4500 mV) of the Snsr Pwr
•
voltage.
Nominal pressure output ranges between zero with the Input voltage at 500 mV and a maximum
•
nominal 25000 kPa/100.00% with the Input voltage at 4500 mV.
Maximum over-pressure output = 28125 kPa with the Input voltage at 5000 mV. (25000 maximum
•
nominal pressure x 112.50% = 28125 kPa maximum over-pressure)
Danfoss | March 201811062069 | AQ00000100en-US0401 | 21
User Manual
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr250b Function Block
•
Drops below 300 mV, the function block outputs an input too low fault. (500 mV – 5% of the 4000 mV
nominal input voltage range = fault at 300 mV)
•
Rises above 4700 mV, the function block outputs an input too high fault. (4500 mV + 5% of the 4000
mV nominal input voltage range = fault at 4700 mV)
Function Block Connections
Connections you can make with the function block are described.
Function block connections
ItemDescription
1Sensor voltage (varies with pressure).
2Sensor reference power voltage.
3Function block status.
4Function block faults.
5Pressure in PSI.
6Pressure in kPa.
7Pressure in decibar (dBar)
8Pressure in % of range.
MC Controller—Input Configuration
Configure MFIn and DigAn to accept the input of the function block.
For MC Controllers, you route the function block’s Input through an MFIn or a DigAn.
You must change the MFIn and DigAn default configurations to accept this input.
Danfoss | March 201811062069 | AQ00000100en-US0401 | 23
User Manual
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr250b Function Block
3. Make the changes that are shown in the following figure.
SC Controller—Input Configuration
Configure MFIn and DigAn to accept the input of the function block.
You route the function block’s Input through an MFIn or a DigAn. You must change the MFIn and
DigAn default configurations to accept this input.
Configure the MFIn
Learn how to configure MFIn to accept input from the function block.
1. In the GUIDE template, enter the Inputs page.
2. Enter the page that receives the input.
3. Make the changes that are shown in the following figure.
Danfoss | March 201811062069 | AQ00000100en-US0401 | 25
User Manual
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr400b Function Block
This function block configures the output of MBS 1250 pressure sensors with a nominal 0–400 bar [40000
kPa/5800 PSI] range.
Inputs
Learn how the function block uses a reference voltage and a changing input voltage to produce PSI, kPa,
dBar and Pct outputs.
Function Block Inputs
InputTypeRangeDescription
Snsr Pwr——0–5250 mVInputs a reference voltage that the PLUS+1 controller also applies to the Pin 1 (+ Supply) on the Pressure
Transmitter.
Input——0–5250 mVThe function block compares the changing Input voltage with the constant Snsr Pwr reference voltage to produce
PSI, kPa, dBar , and Pct outputs.
The function block’s nominal operating range is between 10.00% and 90.00% of Snsr Pwr voltage.
When the Input voltage reaches:
•
10.00% of the Snsr Pwr voltage, the function block’s output starts rising above zero.
•
90.00% of the Snsr Pwr voltage, the function block outputs its maximum nominal outputs of 5800 PSI/40000
kPa/10000 (100.00%).
•
100.00% of the Snsr Pwr voltage, the function block outputs its maximum over-pressure outputs of 6525 PSI/
45000 kPa/11250 (112.50%).
The maximum over-pressure output equals 112.50% of the maximum nominal output. (40000 kPa x 112.50% =
45000 kPa)
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr400b Function Block
Outputs
Learn about the outputs of the Prs_Snsr400b function block.
Function Block Outputs
Output TypeRangeDescription
StatusU16——Indicates if the Flt Pct value is within range or is set too high.
The Flt Pct sets the percentage that the Input voltage can rise above or fall below the function block’s operating
range without setting a fault condition.
You can change the Flt Pct value (1000 = 10.00%) on the inner page of the Prs_Snsr function block.
The Status output uses the bitwise scheme.
•
0x0000 = Block is OK.
•
0x8008 = Flt Pct value is too high.
FaultU16——Indicates if the voltage on the function block’s Input pin is too low or too high.
The Flt Pct sets the percentage that the Input voltage can rise above or fall below the function block’s operating
range without setting a fault condition.
You can change the Flt Pct value (1000 = 10.00%) on the inner page of the Prs_Snsr function block.
The Fault output uses the bitwise scheme.
•
0x0000 = Block is OK.
•
0x8001 = Input value is too low.
•
0x8002 = Input value is too high.
PSIU160–6525Indicates pressure in pounds per square inch (PSI).
1 = 1 PSI.
kPaU160–45000Indicates pressure in kilopascals (kPa).
1 = 1 kPa.
dBarU160–4500
PctU160–111250Indicates pressure as a percent of the function block’s operating range.
Indicates pressure in decibars (dBar).
1 = 1 dBar.
10000 = 100.00%.
Status and Fault Logic
This topic describes how status logic and fault logic are indicated for the function block.
Status Logic
The status code indicates the calibration state of the function block.
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr400b Function Block
Drops below 300 mV, the function block outputs an input too low fault.
•
(500 mV – 5% of the 4000 mV nominal input voltage range = fault at 300 mV)
Rises above 4700 mV, the function block outputs an input too high fault.
•
(4500 mV + 5% of the 4000 mV nominal input voltage range = fault at 4700 mV)
Function Block Connections
Connections you can make with the function block are described.
Function block connections
ItemDescription
1Sensor voltage (varies with pressure).
2Sensor reference power voltage.
3Function block status.
4Function block faults.
5Pressure in PSI.
6Pressure in kPa.
7Pressure in decibar (dBar)
8Pressure in % of range.
MC Controller—Input Configuration
Configure MFIn and DigAn to accept the input of the function block.
For MC Controllers, you route the function block’s Input through an MFIn or a DigAn.
You must change the MFIn and DigAn default configurations to accept this input.
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr400b Function Block
3. Make the changes that are shown in the following figure.
SC Controller—Input Configuration
Configure MFIn and DigAn to accept the input of the function block.
You route the function block’s Input through an MFIn or a DigAn. You must change the MFIn and
DigAn default configurations to accept this input.
Configure the MFIn
Learn how to configure MFIn to accept input from the function block.
1. In the GUIDE template, enter the Inputs page.
2. Enter the page that receives the input.
3. Make the changes that are shown in the following figure.
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr500b Function Block
This function block configures the output of MBS 1250 pressure sensors with a nominal 0–500 bar [50000
kPa/7250 PSI] range.
Inputs
Learn how the function block uses a reference voltage and a changing input voltage to produce PSI, kPa,
dBar and Pct outputs.
Function Block Inputs
InputTypeRangeDescription
Snsr Pwr ——0–5250 mVInputs a reference voltage that the PLUS+1® controller also applies to the Pin 1 (+ Supply) on the pressure
transmitter.
Input——0–5250 mVThe function block compares the changing Input voltage with the constant Snsr Pwr reference voltage to produce
PSI, kPa, dBar and Pct outputs.
The function block’s nominal operating range is between 10.00% and 90.00% of Snsr Pwr voltage.
When the Input voltage reaches:
•
10.00% of the Snsr Pwr voltage, the function block’s output starts rising above zero.
•
90.00% of the Snsr Pwr voltage, the function block outputs its maximum nominal outputs of 7250 PSI/50000 kPa/
10000 (100.00%).
•
100.00% of the Snsr Pwr voltage, the function block outputs its maximum over-pressure outputs of 8156 PSI/
56250 kPa/11250 (112.50%).
The maximum over-pressure output equals 112.50% of the maximum nominal output. (50000 kPa x 112.50% =
56250 kPa)
Danfoss | March 201811062069 | AQ00000100en-US0401 | 33
User Manual
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr500b Function Block
Outputs
Learn about the outputs of the Prs_Snsr500b function block.
Function Block Outputs
Output TypeRangeDescription
StatusU16——Indicates if the Flt Pct value is within range or is set too high.
The Flt Pct sets the percentage that the Input voltage can rise above or fall below the function block’s operating range
without setting a fault condition.
You can change the Flt Pct value (1000 = 10.00%) on the inner page of the Prs_Snsr function block.
The Status output uses the bitwise scheme.
•
0x0000 = Block is OK.
•
0x8008 = Flt Pct value is too high.
FaultU16——Indicates if the voltage on the function block’s Input pin is too low or too high.
The Flt Pct sets the percentage that the Input voltage can rise above or fall below the function block’s operating range
without setting a fault condition.
You can change the Flt Pct value (1000 = 10.00%) on the inner page of the Prs_Snsr function block.
The Fault output uses the bitwise scheme.
•
0x0000 = Block is OK.
•
0x8001 = Input value is too low.
•
0x8002 = Input value is too high.
PSIU160–8156Indicates pressure in pounds per square inch (PSI).
1 = 1 PSI.
kPaU160–56250Indicates pressure in kilopascals (kPa).
1 = 1 kPa.
dBarU160–5625
PctU160–11250Indicates pressure as a percent of the function block’s operating range.
Indicates pressure in decibars (dBar).
1 = 1 dBar.
10000 = 100.00%.
Status and Fault Logic
This topic describes how status logic and fault logic are indicated for the function block.
Status Logic
The status code indicates the calibration state of the function block.
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr500b Function Block
Fault Logic
Learn how fault logic can indicate problems, causes of problems, and solutions.
Fault logic
ConditionHex
Input value is too low.0x80010001
Input value is too high.0x80020010
*
Bit 16 set to 1 identifies a standard Danfoss status or fault code.
*
Binary CauseResponseCorrection
Volt(age) is less than [10% of
Snsr Pwr] - [Flt Pct of nominal
signal range (which is 80% of
Snsr Pwr)].
Snsr Pwr less than 0.Ensure correct software input is
Volt(age) is greater than [90% of
Snsr Pwr] + [Flt Pct of nominal
signal range (which is 80% of
Snsr Pwr)].
Snsr Pwr greater than 5250.
Output = 0.
Output is extrapolated beyond
the maximum value up to 11250
(112.50%).
Output = 0.
Inspect for open circuit in wire
connections to sensor.
made in the application.
Inspect for short circuit in wire
•
connections to sensor.
Verify the correct pressure
•
sensor is used for the
application.
Ensure correct software input is
made in the application.
Relationship Between Function Block Input and Output Signals
Use the plot to find out the relationships between the function block's Input voltages and its kPa and Pct
outputs.
This function block’s:
Flt Pct value = 500 (5.00%) and its Snsr Pwr value = 5000 mV.
•
Nominal Input voltage ranges between 10.00% (500 mV) and 90.00% (4500 mV) of the Snsr Pwr
•
voltage.
Nominal pressure output ranges between zero with the Input voltage at 500 mV and a maximum
•
nominal 50000 kPa/100.00% with the Input voltage at 4500 mV.
Maximum over-pressure output = 56250 kPa with the Input voltage at 5000 mV. (50000 maximum
•
nominal pressure x 112.50% = 56250 kPa maximum over-pressure)
Danfoss | March 201811062069 | AQ00000100en-US0401 | 35
User Manual
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr500b Function Block
Drops below 300 mV, the function block outputs an input too low fault.
•
(500 mV – 5% of the 4000 mV nominal input voltage range = fault at 300 mV)
Rises above 4700 mV, the function block outputs an input too high fault.
•
(4500 mV + 5% of the 4000 mV nominal input voltage range = fault at 4700 mV)
Function Block Connections
Connections you can make with the function block are described.
Function block connections
ItemDescription
1Sensor voltage (varies with pressure).
2Sensor reference power voltage.
3Function block status.
4Function block faults.
5Pressure in PSI.
6Pressure in kPa.
7Pressure in decibar (dBar)
8Pressure in % of range.
MC Controller—Input Configuration
Configure MFIn and DigAn to accept the input of the function block.
For MC Controllers, you route the function block’s Input through an MFIn or a DigAn.
You must change the MFIn and DigAn default configurations to accept this input.
Danfoss | March 201811062069 | AQ00000100en-US0401 | 37
User Manual
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr500b Function Block
3. Make the changes that are shown in the following figure.
SC Controller—Input Configuration
Configure MFIn and DigAn to accept the input of the function block.
You route the function block’s Input through an MFIn or a DigAn. You must change the MFIn and
DigAn default configurations to accept this input.
Configure the MFIn
Learn how to configure MFIn to accept input from the function block.
1. In the GUIDE template, enter the Inputs page.
2. Enter the page that receives the input.
3. Make the changes that are shown in the following figure.
Danfoss | March 201811062069 | AQ00000100en-US0401 | 39
User Manual
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr550b Function Block
This function block configures the output of MBS 1250 pressure sensors with a nominal 0–550 bar [55000
kPa/7977 PSI] range.
Inputs
Learn how the function block uses a reference voltage and a changing input voltage to produce PSI, kPa,
dBar and Pct outputs.
Function Block Inputs
InputTypeRangeDescription
Snsr Pwr ——0–5250 mVInputs a reference voltage that the PLUS+1® controller also applies to the Pin 1 (+ Supply) on the pressure
transmitter.
Input——0–5250 mVThe function block compares the changing Input voltage with the constant Snsr Pwr reference voltage to produce
PSI, kPa, dBar and Pct outputs.
The function block’s nominal operating range is between 10.00% and 90.00% of Snsr Pwr voltage.
When the Input voltage reaches:
•
10.00% of the Snsr Pwr voltage, the function block’s output starts rising above zero.
•
90.00% of the Snsr Pwr voltage, the function block outputs its maximum nominal outputs of 7250 PSI/50000 kPa/
10000 (100.00%).
•
100.00% of the Snsr Pwr voltage, the function block outputs its maximum over-pressure outputs of 8156 PSI/
56250 kPa/11250 (112.50%).
The maximum over-pressure output equals 112.50% of the maximum nominal output. (50000 kPa x 112.50% =
56250 kPa)
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr550b Function Block
Outputs
Learn about the outputs of the Prs_Snsr550b function block.
Function Block Outputs
Output TypeRangeDescription
StatusU16——Indicates if the Flt Pct value is within range or is set too high.
The Flt Pct sets the percentage that the Input voltage can rise above or fall below the function block’s operating range
without setting a fault condition.
You can change the Flt Pct value (1000 = 10.00%) on the inner page of the Prs_Snsr function block.
The Status output uses the bitwise scheme.
•
0x0000 = Block is OK.
•
0x8008 = Flt Pct value is too high.
FaultU16——Indicates if the voltage on the function block’s Input pin is too low or too high.
The Flt Pct sets the percentage that the Input voltage can rise above or fall below the function block’s operating range
without setting a fault condition.
You can change the Flt Pct value (1000 = 10.00%) on the inner page of the Prs_Snsr function block.
The Fault output uses the bitwise scheme.
•
0x0000 = Block is OK.
•
0x8001 = Input value is too low.
•
0x8002 = Input value is too high.
PSIU160–8156Indicates pressure in pounds per square inch (PSI).
1 = 1 PSI.
kPaU160–56250Indicates pressure in kilopascals (kPa).
1 = 1 kPa.
dBarU160–5625
PctU160–11250Indicates pressure as a percent of the function block’s operating range.
Indicates pressure in decibars (dBar).
1 = 1 dBar.
10000 = 100.00%.
Status and Fault Logic
This topic describes how status logic and fault logic are indicated for the function block.
Status Logic
The status code indicates the calibration state of the function block.
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr550b Function Block
Flt Pct value = 500 (5.00%) and its Snsr Pwr value = 5000 mV.
•
Nominal Input voltage ranges between 10.00% (500 mV) and 90.00% (4500 mV) of the Snsr Pwr
•
voltage.
Nominal pressure output ranges between zero with the Input voltage at 500 mV and a maximum
•
nominal 50000 kPa/100.00% with the Input voltage at 4500 mV.
Maximum over-pressure output = 50000 kPa with the Input voltage at 5000 mV. (61875 maximum
•
nominal pressure x 112.50% = 18000 kPa maximum over-pressure)
When the Input voltage:
Drops below 300 mV, the function block outputs an input too low fault. (500 mV – 5% of the 4000 mV
•
nominal input voltage range = fault at 300 mV)
Rises above 4700 mV, the function block outputs an input too high fault. (4500 mV + 5% of the 4000
•
mV nominal input voltage range = fault at 4700 mV)
Function Block Connections
Connections you can make with the function block are described.
Function block connections
ItemDescription
1Sensor voltage (varies with pressure).
2Sensor reference power voltage.
3Function block status.
4Function block faults.
5Pressure in PSI.
6Pressure in kPa.
7Pressure in decibar (dBar)
8Pressure in % of range.
MC Controller—Input Configuration
Configure MFIn and DigAn to accept the input of the function block.
For MC Controllers, you route the function block’s Input through an MFIn or a DigAn.
You must change the MFIn and DigAn default configurations to accept this input.
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr550b Function Block
3. Make the changes that are shown in the following figure.
SC Controller—Input Configuration
Configure MFIn and DigAn to accept the input of the function block.
You route the function block’s Input through an MFIn or a DigAn. You must change the MFIn and
DigAn default configurations to accept this input.
Configure the MFIn
Learn how to configure MFIn to accept input from the function block.
1. In the GUIDE template, enter the Inputs page.
2. Enter the page that receives the input.
3. Make the changes that are shown in the following figure.
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr600b Function Block
This function block configures the output of MBS 1250 pressure sensors with a nominal 0–600 bar [60000
kPa/8700 PSI] range.
Inputs
Learn how the function block uses a reference voltage and a changing input voltage to produce PSI, kPa,
dBar and Pct outputs.
Function Block Inputs
InputTypeRangeDescription
Snsr Pwr——0–5250 mVInputs a reference voltage that the PLUS+1 controller also applies to the Pin 1 (+ Supply) on the Pressure
Transmitter.
Input——0–5250 mVThe function block compares the changing Input voltage with the constant Snsr Pwr reference voltage to produce
PSI, kPa, dBar, and Pct outputs.
The function block’s nominal operating range is between 10.00% and 90.00% of Snsr Pwr voltage.
When the Input voltage reaches:
•
10.00% of the Snsr Pwr voltage, the function block’s output starts rising above zero.
•
90.00% of the Snsr Pwr voltage, the function block outputs its maximum nominal outputs of 8700 PSI/60000
kPa/10000 (100.00%).
•
100.00% of the Snsr Pwr voltage, the function block outputs its maximum over-pressure outputs of 9788 PSI/
67500 kPa/11250 (112.50%).
The maximum over-pressure output equals 112.50% of the maximum nominal output. (8700 PSI x 112.50% =
9788 PSI)
Danfoss | March 201811062069 | AQ00000100en-US0401 | 47
User Manual
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr600b Function Block
Outputs
Learn about the outputs of the Prs_Snsr600b function block.
Function Block Outputs
Output TypeRangeDescription
StatusU16——Indicates if the Flt Pct value is within range or is set too high.
The Flt Pct sets the percentage that the Input voltage can rise above or fall below the function block’s operating range
without setting a fault condition.
You can change the Flt Pct value (1000 = 10.00%) on the inner page of the Prs_Snsr function block.
The Status output uses the bitwise scheme.
•
0x0000 = Block is OK.
•
0x8008 = Flt Pct value is too high.
FaultU16——Indicates if the voltage on the function block’s Input pin is too low or too high.
The Flt Pct sets the percentage that the Input voltage can rise above or fall below the function block’s operating range
without setting a fault condition.
You can change the Flt Pct value (1000 = 10.00%) on the inner page of the Prs_Snsr function block.
The Fault output uses the bitwise scheme.
•
0x0000 = Block is OK.
•
0x8001 = Input value is too low.
•
0x8002 = Input value is too high.
PSIU160–9788Indicates pressure in pounds per square inch (PSI).
1 = 1 PSI.
kPaU320–67500Indicates pressure in kilopascals (kPa).
1 = 1 kPa.
dBarU160–6750
PctU160–11250Indicates pressure as a percent of the function block’s operating range.
Indicates pressure in decibars (dBar).
1 = 1 dBar.
10000 = 100.00%.
Status and Fault Logic
This topic describes how status logic and fault logic are indicated for the function block.
Status Logic
The status code indicates the calibration state of the function block.
Danfoss | March 201811062069 | AQ00000100en-US0401 | 49
User Manual
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr600b Function Block
Drops below 300 mV, the function block outputs an input too low fault.
•
(500 mV – 5% of the 4000 mV nominal input voltage range = fault at 300 mV)
Rises above 4700 mV, the function block outputs an input too high fault.
•
(4500 mV + 5% of the 4000 mV nominal input voltage range = fault at 4700 mV)
Function Block Connections
Connections you can make with the function block are described.
Function block connections
ItemDescription
1Sensor voltage (varies with pressure).
2Sensor reference power voltage.
3Function block status.
4Function block faults.
5Pressure in PSI.
6Pressure in kPa.
7Pressure in decibar (dBar)
8Pressure in % of range.
MC Controller—Input Configuration
Configure MFIn and DigAn to accept the input of the function block.
For MC Controllers, you route the function block’s Input through an MFIn or a DigAn.
You must change the MFIn and DigAn default configurations to accept this input.
Danfoss | March 201811062069 | AQ00000100en-US0401 | 51
User Manual
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr600b Function Block
3. Make the changes that are shown in the following figure.
SC Controller—Input Configuration
Configure MFIn and DigAn to accept the input of the function block.
You route the function block’s Input through an MFIn or a DigAn. You must change the MFIn and
DigAn default configurations to accept this input.
Configure the MFIn
Learn how to configure MFIn to accept input from the function block.
1. In the GUIDE template, enter the Inputs page.
2. Enter the page that receives the input.
3. Make the changes that are shown in the following figure.
Danfoss | March 201811062069 | AQ00000100en-US0401 | 53
User Manual
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr_Gen Function Block
This function block configures the output of MBS 1250 pressure sensors with a nominal bar range
specifed by a parameter to scale the output.
Inputs
Learn how the function block uses a parameter to customize the scaling values for output and how it
uses a reference voltage and a changing input voltage to produce PSI, kPa, dBar and Pct outputs.
Function Block Inputs
InputTypeRangeDescription
Snsr PwrU160–5250 mVInputs a reference voltage that the PLUS+1® controller also applies to the Pin 1 (+ Supply) on the pressure
transmitter.
InputU160–5250 mVThe function block compares the changing Input voltage with the constant Snsr Pwr reference voltage to produce
PSI, kPa, dBar and Pct outputs.
The function block’s nominal operating range is between 10.00% and 90.00% of Snsr Pwr voltage.
When the Input voltage reaches:
•
10.00% of the Snsr Pwr voltage, the function block’s output starts rising above zero.
•
90.00% of the Snsr Pwr voltage, the function block outputs its maximum nominal outputs of PSI and kPa. The
maximum nominal output is specified by Bar and is limited to 2200.
•
100.00% of the Snsr Pwr voltage, the function block outputs its maximum over-pressure outputs of PSI and kPa
at 112.50% of the output defined by Bar.
The maximum over-pressure output equals 112.50% of the maximum nominal output. The generic function
block allows you to specify the pressure range allowed.
Para-Bar
U16User defined
range,
0-2200.
The function block uses Bar to rescale the output of the pressure sensor for OEM products. The output of the
function block is expressed in Bar, and has a range that can be defined from 0 to 2200.
Outputs
Learn how the outputs of the general function block work.
Function Block Outputs
OutputTypeRangeDescription
StatusU16——Indicates if the Flt Pct value is within range or is set too high.
The Flt Pct sets the percentage that the Input voltage can rise above or fall below the function block’s operating range
without setting a fault condition.
You can change the Flt Pct value (1000 = 10.00%) on the inner page of the Prs_Snsr function block.
The Status output uses the bitwise scheme.
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr_Gen Function Block
Function Block Outputs (continued)
FaultU16——Indicates if the voltage on the function block’s Input pin is too low or too high.
The Flt Pct sets the percentage that the Input voltage can rise above or fall below the function block’s operating range
without setting a fault condition.
You can change the Flt Pct value (1000 = 10.00%) on the inner page of the Prs_Snsr function block.
The Fault output uses the bitwise scheme.
•
0x0000 = Block is OK.
•
0x8001 = Input value is too low.
•
0x8002 = Input value is too high.
PSIU160–35896Indicates pressure in pounds per square inch (PSI).
1 = 1 PSI.
kPaU160–247500 Indicates pressure in kilopascals (kPa).
1 = 1 kPa.
dBarU160–24750
PctU160–11250Indicates pressure as a percent of the function block’s operating range.
Indicates pressure in decibars (dBar).
1 = 1 dBar.
10000 = 100.00%.
Status and Fault Logic
This topic describes how status logic and fault logic are indicated for the function block.
Status Logic
The status code indicates the calibration state of the function block.
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr_Gen Function Block
Function Block Connections
Connections you can make with the function block are described.
Function block connections
ItemDescription
1Sensor voltage (varies with pressure).
2Sensor reference power voltage.
3Function block status.
4Function block faults.
5Pressure in PSI.
6Pressure in kPa.
7Pressure in decibar (dBar)
8Pressure in % of range.
MC Controller—Input Configuration
Configure MFIn and DigAn to accept the input of the function block.
For MC Controllers, you route the function block’s Input through an MFIn or a DigAn.
You must change the MFIn and DigAn default configurations to accept this input.
PLUS+1® Compliant MBS 1250 Pressure Sensor Function Blocks
Prs_Snsr_Gen Function Block
3. Make the changes that are shown in the following figure.
SC Controller—Input Configuration
Configure MFIn and DigAn to accept the input of the function block.
You route the function block’s Input through an MFIn or a DigAn. You must change the MFIn and
DigAn default configurations to accept this input.
Configure the MFIn
Learn how to configure MFIn to accept input from the function block.
1. In the GUIDE template, enter the Inputs page.
2. Enter the page that receives the input.
3. Make the changes that are shown in the following figure.
2800 East 13th Street
Ames, IA 50010, USA
Phone: +1 515 239 6000
Danfoss
Power Solutions Trading
(Shanghai) Co., Ltd.
Building #22, No. 1000 Jin Hai Rd
Jin Qiao, Pudong New District
Shanghai, China 201206
Phone: +86 21 3418 5200
Products we offer:
Comatrol
www.comatrol.com
Turolla
www.turollaocg.com
Hydro-Gear
www.hydro-gear.com
Daikin-Sauer-Danfoss
www.daikin-sauer-danfoss.com
Bent Axis Motors
•
Closed Circuit Axial Piston
•
Pumps and Motors
Displays
•
Electrohydraulic Power
•
Steering
Electrohydraulics
•
Hydraulic Power Steering
•
Integrated Systems
•
Joysticks and Control
•
Handles
Microcontrollers and
•
Software
Open Circuit Axial Piston
•
Pumps
Orbital Motors
•
PLUS+1® GUIDE
•
Proportional Valves
•
Sensors
•
Steering
•
Transit Mixer Drives
•
Danfoss Power Solutions is a global manufacturer and supplier of high-quality hydraulic and
electronic components. We specialize in providing state-of-the-art technology and solutions
that excel in the harsh operating conditions of the mobile off-highway market. Building on
our extensive applications expertise, we work closely with our customers to ensure
exceptional performance for a broad range of off-highway vehicles.
We help OEMs around the world speed up system development, reduce costs and bring
vehicles to market faster.
Danfoss – Your Strongest Partner in Mobile Hydraulics.
Go to www.powersolutions.danfoss.com for further product information.
Wherever off-highway vehicles are at work, so is Danfoss. We offer expert worldwide support
for our customers, ensuring the best possible solutions for outstanding performance. And
with an extensive network of Global Service Partners, we also provide comprehensive global
service for all of our components.
Please contact the Danfoss Power Solution representative nearest you.
Local address:
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.