Danfoss MBD 1000 Installation guide

Connection and operating instructions Plug-in Display MBD 1000
Introduction
1999 to +9999 digits.
The operating range of the display device can be directly adjusted to the transmitter range by simply entering the maximum and minimum measuring range limits as well as the decimal point position.
Parameters and limit values are entered via three keys which are accessible after removal of the cover. All programmable parameters of the MBD 1000 are stored in an EEPROM; in the event of a current failure they will remain there for at least 10 years. The MBD 1000 is equipped with a self-diagnosis system which continuously monitors the essential parts of the device. Sensor operational performance is continuously monitored. The MBD 1000 is tested and completely calibrated.
The MBD 1000 must be congured to the specic application. Please refer to chapter "Conguration".
In accordance with EN50081-1 and EN50082-2 for unrestricted use in housing and industrial areas
Safety advice
In order to exclude any risk whatsoever for the operator the following points have to be
observed:
a) Immediately switch o the unit in the event of visible damage or obvious malfunction.
b) Always disconnect the MBD 1000 before opening it up. All electrical connections must be securely connected and touch­ proof after installation.
Attention: When running electric devices parts of these devices will always be highly energised. Unless the warnings are observed serious personal injuries or damage to property may result. Skilled personnel only should be allowed to work with this device. For trouble-free and safe operation of the device please ensure professional transport, storage, installation and connection as well as proper operation an mainte­nance.
c) Standard regulations for operation and safety for electrical, light and heavy current equipment have to be observed, with particular attention having to be paid to national safety regulations (e.g. VDE 0100).
IC.PI.P20.E2.02/ 520B1359 © Danfoss A/S 07-2007
MBD 1000 Connection and operating instructions
Electric connection
The MBD 1000 is simpy plugged into a transmit­ter by means of a special adaptor for the cubic plug according to DIN43650.
Electric connection and commissioning of the device must be carried out by trained and skilled personnel.
Terminal assignment:
Use male plugs 1 and 2.
Supply voltage: The display takes power directly from measuring current.
Assembly
Wrong connection may lead to the destruction of the display device. Danfoss cannot assume any responsibility for this !!
Observe the maximum input current rating of 40mA under all circumstances !!
MBS/ AKS/ MBT
Transmitter connector
DIN 43650
2 IC.PI.P20.E2.02
© Danfoss A/S
MBD 1000 Connection and operating instructions
Technical specication
Input signal 4 ... 20 mA (2-wire) Max. allowed input current 40 mA Reverse voltage protection polarized installation Voltage drop across display approx. 3 V Display 10 mm high LCD-display Display range starting and end value freely selectable Maximum display value 9999 digits Minimum display value -1999 digits Decimal point any position Measuring accuracy 0.2% ± 1 digit Temperature drift 100 ppm / °C Measuring interval approx. 5 measurements / sec. Filter 3 stages can be switched on Nominal temperature 25°C Amibent temperature 0 to 50°C Relative atmospheric humidity 0 to 80% (non condensing) Eletromagnetic compatibility: Additional error: Housing ABS. Front screen made of polycarbonate.
Connection specially designed adaptor for cubic plug
IP rating front side IP65
Fault codes
In case of unacceptable conditions in the system a fault code will be displayed.
Fault codes have been dened as follows:
In accordance with EN50081-1 and EN50082-2 < 1%
48.5 x 48.5 x 35.5 mm (L x W x D)
DIN43650 for simple connection. Length of screw has to be adjusted.
FE 1: Measuring range has been exceeded
This fault code indicates that the measuring range of the A/D converter has been exceeded. Potential fault cause: transmitter damaged short-circuit in transmitter connection MBD 1000 not/incorrectly congurated Remedies: FE 1 will be reset as soon as the measuring values are back within
their permissible range. Please check your transmitter and transmitter connecting cables.
FE 2: Measuring values have fallen below permissible range
This fault code indicates that the measuring values of the A/D converter have fallen below the permissible range.
Potential fault cause: transmitter damaged transmitter connection interrupted MBD 1000 not/incorrectly congurated Remedies: FE 2 will be reset as soon as the measuring values are back within
their permissible range. Please check your transmitter and transmitter connecting cables.
© Danfoss A/S IC.PI.P20.E2.02 3
MBD 1000 Connection and operating instructions
Conguration
Please note: measuring current should be at least 4 mA during conguration!
1. Press button 1, "dP" (decimal point) will be
displayed. Select decimal point position desired using buttons 2 and 3. Acknowledge decimal point position by pressing button 1. "dP" will be displayed again.
2. Press button 1 once again, "An 4" (display for 4mA) will be displayed. Use buttons 2 and 3 to set value to be displayed on the MBD 1000 for an input signal of 4mA.
Buttons 2 and 3 are equipped with a scrolling function, i.e. the value will be increased respectively decreased by 1 digit when button 2 respectively button 3 is pressed briey (no more than 1 s). When pressing these buttons for a longer time (over 1 s) the values will start „scrolling“ upwards respectively downwards with the scrolling speed being increased after approx. 6s.
Acknowledge value displayed by pressing button 1. "An 4" will be displayed again.
3. Switch over to the next parameter by pressing button 1 once again. "An20" will be displayed (display for 20mA). Use buttons 2 and 3 to set value to be displayed on the MBD 1000 for an input signal of 20mA. Acknowledge value displayed by pressing button 1. "An20" will be displayed again.
4. Press button 1 once again. "LI" (limit) will be displayed. Select measuring range limits desired using buttons 2 and 3.
0 = Values exceeding/falling below limits are acceptable. (FE1, FE2 displayed for hardware limits)
1 = Values exceeding/falling below limits are not acceptable. (FE1, FE2 displayed for area limits)
Acknowledge selection made by pressing button 1. "LI" will be displayed again. For pressure and temperature measuring transducers always enter "LI 0".
5. Press button 1 once again. "FILt" (lter) will be displayed. Select input lter 0, 1, 2 or 3 desired using buttons 2 and 3.
0 = no lter 1 = lter 1 active 2 = lter 2 active 3 = lter 1 and lter 2 active
Filter 1: for ltering short pikes occurring when relays and contactors are switched. Make sure to always activate lter 1 if high loads are switched in the vicinity of the MBD 1000 (wires or sensor or if large spikes are to be expected). Additional display delay: approx. 0.5s
Filter 2: prevents ”jumping” of the last gure, a phenomenon often found with digital displays and controllers. Make sure to always activate lter 2 if the display range exceeds 2000 digits. Additional display delay: approx. 1s
Acknowledge selection made by pressing button
1. "FILt" will be displayed again.
The adjustment of the MBD 1000 to the trans­mitter is now completed. The MBD 1000 can be immediately switched over to display the current measuring vlaue by pressing button 1.
IC.PI.P20.E2.02
© Danfoss A/S (DE-BD) 07-2007
Loading...