Installation guide
Heavy duty pressure switch
Types MBC 5000 and MBC 5100
Electrical connection
061R 9318
AC 15:
DC 13:
Dimensions
0.5A
12W
250V
125V
Terminal Wire colour
1: Inpu t Black
2: Normally closed (NC) Brown
3: Normally open (NO) Blue
Ground Shield
061R 9318
Mounting and pressure connection
Danfoss
93Z268.10
Thread
In environments that have excessive vibrations such as fast running
engines, gears and similar, Danfoss recommends that the product is
mounted on a heavy solid base, like the engine frame. It is also strongly
recommended that the inlet pressure tube is secured to the same solid
base in order to avoid inlet tube vibrations.
Flange
© Danfoss A/S (AC-MCP / jmn), 2014-10 IC.PI.P10.D1.02 / 520B6479 1
Operation
temperature
-40 °C – 85 °C Bellows and piston version
-10 °C – 85 °C Diaphragm version
One full turn (360°) of the MBC setting screw is approx.
equal to 7% of the full setting range.
Mechanical dierential
2 IC.PI.P10.D1.02 / 520B6479 © Danfoss A/S (AC-MCP / jmn), 2014-10