Danfoss Managing Harmonic Distortion Application guide

Managing Harmonic Distortion with Quasi 12-pulse
■■
Conventional Reduction Techniques
■■
For many years, the most commonly used method for reducing harmonic distortion caused by Variable Fre­quency Drives in electrical systems has been to add AC line reactors at the drives' input terminals. This re­duces the harmonic distortion to a level which will be sufficient in most installations. There is however a practical limit to the size of the reactors which can be installed and therefore also to the possible reduction in harmonics which can be obtained by using this technique.
The reason is that the drives' ability to supply full out­put torque is reduced as a result of voltage drop across the reactors. The only way to compensate for this is to increase the current supplied to the mo­tor. This means that the motors must be able to manage higher currents at the same torque require­ment. Larger drives may also be required. However, this causes a waste of resources as a result of in­creased generation of heat. This must be considered when dimensioning the system in order to avoid over­heating.
Managing Harmonic Distortion with Quasi 12-pulse
Another well-known technique is to implement DC reactors in the intermediate circuit. This is however not very practical if large reactors are needed, since these reactors would produce a lot of heat in the drives and reduce the drives' efficiency.
In order to avoid the unfortunate side effects of AC or DC reactors in installations where high require­ments to the reduction of harmonic distortion exist, it has become the norm in certain markets to utilise 12 pulse drives. These drives consist of two 6 pulse rectifiers and either a phase shifting transformer in front of one of the rectifiers or a three winding trans­former in front of the combined rectifier. See Figure 1 for schematic.
Figure 1: 12 Pulse Drives with Rectifiers in Parallel and in Series
This design provides excellent harmonic perform­ance. The 5 celled almost completely. The two rectifiers and either a phase shifting transformer and an interface reactor (left solution in Figure 1) or a three winding transformer
th
and 7th harmonic currents are can-
(right solution in Figure 1) makes this solution at least 50% more expensive than a standard drive with built-in DC reactors. Therefore a more wide spread use of it would mean a drastic increase in the cost per drive installed.
MN.90.J2.02 - VLT is a registered Danfoss trademark
■■
The alternative solution
■■
Managing Harmonic Distortion with Quasi 12-pulse
An alternative solution would be to use phase shift­ing transformers in front of 50% of the drive load and then leave the other drives connected to the normal mains.
The cost of this solution is only about 16% higher than the cost of a standard Danfoss VLT frequency converter. Since a transformer is only required on every second drive, the total impact on the fre­quency converter cost is reduced to 8%. This is, however, compared to a standard solution without any additional harmonic filtering.
When considering this type of harmonic filtering, a comparison with a solution where a 5% AC line re­actor is used would be more realistic. This will not nearly give the performance of the quasi 12 pulse, but it is the largest AC line reactor which can be rec­ommended installed in front of a Danfoss VLT Fre­quency Converter. A 5% AC line reactor will increase
Managing Harmnic Distortion with Quasi 12-pulse
the drive cost by approx. 2%. This means that the ac­tual additional cost to a project would come to approx. 6%.
The argument against this solution compared to a true 12-pulse solution is that the balance of the load is important to the performance, because the improved performance is a result of the cancellation of the 5 phase shift.
When the load is not balanced, the harmonics on the drives with high load are not cancelled. This is because the whole basis for the cancellation is that the current vectors are of equal amplitude and that the angle between them is 180°. The angle is main­tained by the phase shifting transformer, but the amplitude varies as the load decreases. When the load only decreases on one of the drives, the length of the vectors becomes unequal and full cancellation is not achieved.
Figure 2 shows the system configuration for an instal­lation using quasi 12-pulse. Please notice that stand­ard 6 pulse frequency converters are used and that the estimated load on each drive group should be as close to equal as possible to achieve the best effect. See the following sections to get a general impression of the performance of quasi 12 pulse on the 2 drive groups.
th
and 7th harmonic current due to the 30°
Figure 2: System Configuration for Quasi 12 Pulse
■■
Simulation of the Effects of Varying Load
■■
The research at Danfoss Drives into the significance of load variations has revealed that there is a signifi­cant advantage to be obtained by using quasi 12 Pulse as long as all drives are above 20% load. Whether or not the load is the same is less impor­tant.
Table 1 and Figure 3 on the following page show the results of a simulation of the Total Harmonic Current Distortion (THCD) as a function of the load on two drive groups.
MN.90.J2.02 - VLT is a registered Danfoss trademark
Loading...
+ 2 hidden pages