Danfoss M46 User guide

Technical Information
Axial Piston Pumps
Series 40 M46
powersolutions.danfoss.com
Technical Information
Series 40 M46 Pumps
Revision history Table of revisions
Date Changed Rev
March 2017 Minor updates - FNR Control options 0209
October 2016 Minor updates 0208
May 2015 more corrections to tandem pumps model code BG
January 2015 minor edits BE
January 2015 added port callouts - HC EDC drawings BD
November 2014 corrections to shaft options BC
July 2014 Edits to HC EDC Schematic BB
April 2014 Danfoss layout BA
2 | © Danfoss | March 2017 L1001029 | BC00000176en-US0209
Technical Information
Series 40 M46 Pumps

Contents

Specifications
General Information
Features and Options
Operating Parameters
System Design Parameters
Model Code - Single Pumps
Model Code - Tandem Pumps
Options
Design Specifications......................................................................................................................................................................5
Technical Specifications.................................................................................................................................................................5
Operating Parameters.....................................................................................................................................................................5
Options.................................................................................................................................................................................................6
Fluid specifications.......................................................................................................................................................................... 6
M46 Pumps.........................................................................................................................................................................................7
M46 Variable Pumps........................................................................................................................................................................7
System Circuit Diagram..................................................................................................................................................................8
Schematic Diagram..........................................................................................................................................................................8
Features................................................................................................................................................................................................9
Options.................................................................................................................................................................................................9
Fluids.................................................................................................................................................................................................. 10
Viscosity........................................................................................................................................................................................10
Temperature...............................................................................................................................................................................10
Charge Pressure..............................................................................................................................................................................10
Control Pressure............................................................................................................................................................................. 10
Case Pressure...................................................................................................................................................................................11
System Pressure..............................................................................................................................................................................11
Speed Ratings..................................................................................................................................................................................11
Inlet Pressure................................................................................................................................................................................... 12
Sizing Equations............................................................................................................................................................................. 13
Filtration............................................................................................................................................................................................ 13
Suction Filtration.......................................................................................................................................................................14
Charge Pressure Filtration..................................................................................................................................................... 14
Redundant Braking System Requirement.............................................................................................................................15
Loop Flushing..................................................................................................................................................................................15
Reservoir............................................................................................................................................................................................15
Case Drain Usage for Tandem Pumps.................................................................................................................................... 15
Bearing Life and External Shaft Loading................................................................................................................................16
Hydraulic Unit Life......................................................................................................................................................................... 17
Mounting Flange Loads...............................................................................................................................................................17
Shaft Torques...................................................................................................................................................................................19
Shaft selection........................................................................................................................................................................... 19
Shaft torque and spline lubrication................................................................................................................................... 19
Shaft torque for tapered shafts............................................................................................................................................19
Single Pumps...................................................................................................................................................................................20
Tandem Pumps...............................................................................................................................................................................24
Shaft options....................................................................................................................................................................................28
Single pumps............................................................................................................................................................................. 28
Tandem pumps......................................................................................................................................................................... 30
Charge Pump...................................................................................................................................................................................31
Charge Pump Output Flow...................................................................................................................................................32
Charge Pump Power Requirements.................................................................................................................................. 32
Charge Relief Valve........................................................................................................................................................................32
High Pressure Relief Valve (HPRV) and Charge Check......................................................................................................33
Bypass Function..............................................................................................................................................................................34
Displacement Limiters................................................................................................................................................................. 34
©
Danfoss | March 2017 L1001029 | BC00000176en-US0209 | 3
Technical Information
Series 40 M46 Pumps
Contents
Auxiliary Mounting Pads and Auxiliary Pumps................................................................................................................... 35
Manual Displacement Control (MDC) - Options AB, AC, AK, AW, and GB..................................................................36
Hydraulic Displacement - Options BA, BB and BC..............................................................................................................38
Electrical Displacement Control- Options CE, CG, CM, and CN..................................................................................... 41
High Current Electric Displacement Control - Options HA (12Vdc) and HB (24Vdc).............................................44
Response times..........................................................................................................................................................................46
Manual OverRide (MOR).............................................................................................................................................................. 46
Three-position Electrical Control - Options DA and DB................................................................................................... 47
Port Locations
Single Pump.....................................................................................................................................................................................50
Tandem Pump.................................................................................................................................................................................51
Installation Drawings - Single Pump Dimensions
Auxiliary Mounting Flanges....................................................................................................................................................... 52
Pump, filtration/charge pump options, MDC, displacement limiter...........................................................................53
Installation Drawings - Tandem Pump Dimensions
Auxiliary mounting flange..........................................................................................................................................................54
Rear mounting boss......................................................................................................................................................................55
Pumps, filtration/charge pump options, MDC, displacement limiters.......................................................................56
Control Options - Installation Drawings
Control options, AC, AK............................................................................................................................................................... 57
Option GB......................................................................................................................................................................................... 57
Options AB, AW...............................................................................................................................................................................58
HC EDC Control...............................................................................................................................................................................59
Hydraulic displacement control (HDC).................................................................................................................................. 60
Option CE..........................................................................................................................................................................................61
Options CG, CN............................................................................................................................................................................... 61
Options DA, DB............................................................................................................................................................................... 62
Reference Literature
Literature...........................................................................................................................................................................................63
4 | © Danfoss | March 2017 L1001029 | BC00000176en-US0209
Technical Information
Series 40 M46 Pumps

Specifications

Design Specifications

Technical Specifications

Product line Pump type Direction rotation Installation position Filtration configuration Other system requirements
Model Displacement Shaft Speed Minimum
Rated Maximum
System Pressure Maximum working*
Maximum
Minimum low loop Weight (MDC without aux pad) Mass moment of inertia of the rotating
components Charge Pressure Minimum
Maximum Control Pressure
Case Pressure Continuous
Inlet Pressure Rated
Minimum @ corner
power
Maximum (cold
start)
Minimum
Series 40 Pumps
In-line, axial piston, variable, positive displacement pumps
Clockwise (CW) or counterclockwise (CCW) available
Discretionary, the housing must be filled with hydraulic fluid
Suction or charge pressure filtration
Independent braking system, suitable reservoir and heat exchanger
Unit M46 Single Pump M46 Tandem Pump
cm3/rev [in3/rev] 45.9 [2.80] 45.9 x 2 [2.80 x 2]
min-1 (rpm)
min-1 (rpm) 4000
min-1 (rpm) 4100
bar [psi] 345 [5000]
385 [5585]
10 [145]
kg [lb] 33 [73] 59 [131]
kg ·m2 [slug·ft2] 0.0050 [0.0037] 0.0100 [0.0073]
bar [psi] 6 [87]
31 [450]
bar [psi] 21.5 [312]
bar [psi] 1.7 [25]
5.2 [75]
bar absolute [inches of Mercury vacuum]
0.8 [6]
6 [9.2 Maximum]
* Operation above maximum working pressure is permissible with Danfoss application approval.

Operating Parameters

Fluid Viscosity
©
Danfoss | March 2017 L1001029 | BC00000176en-US0209 | 5
Minimum mm2/s (cSt) [SUS] 7 [49]
Continuous Maximum (cold start) Intermittent
1
12-16 [70-278]
1600 [7500]
6 [46]
Technical Information
Series 40 M46 Pumps
Specifications

Options

Fluid Temperature
(1) Intermittent equals a short period of time at less than one minute per incident and not exceeding two percent of duty cycle based on load life.
Mounting Flange Input Shaft Ø 25.4 mm [1.000 in] straight keyed
Auxillary Mounting Flange
Main Port Configuration
Minimum (intermittent cold start)
Continuous Maximum Intermittent
SAE - B X X
Ø 25.4 mm [1.000 in] 1:8 taper (SAE J501) 13-tooth, 16/32 pitch (ANSI B92.1 1970 - Class 5) 15-tooth, 16/32 pitch (ANSI B92.1 1970 - Class 5) 19-tooth, 16/32 pitch (ANSI B92.1 1970 - Class 5) 9-tooth internal spline, 16/32 pitch (SAE A) 11-tooth internal spline, 16/32 pitch (SAE A) 13-tooth internal spline, 16/32 pitch (SAE B) 15 - tooth internal spline, 16/32 pitch (SAE BB)
1-5/16 - 12 SAE A straight thread O-ring Ports (SAE J514) X X
degrees C [degrees F] - 40° C [- 40° F]
82.2° C [180° F]
1
104.4° C [220° F]
Single Tandem
X X
X X
X -
X X
- X
X X
X X
X X
- X

Fluid specifications

Ratings and data are based on operation with premium petroleum-based hydraulic fluids reftaining oxidation, rust, and foam inhibitors.
Parameter Unit Minimum reftinuous Maximum
Viscosity mm /sec (cSt)
Temperature °C [°F] -40 [-40] 82 [180] 104 [220] Cleanliness ISO 4406 Class 18/13 or better Filtration
efficiency
suction filtration β charge filtration β
[SUS]
7 [47] 12-60 [70-278] 1600 [7500]
=75 (β10≥1.5)
35-44
=75 (β10≥10)
15-20
6 | © Danfoss | March 2017 L1001029 | BC00000176en-US0209
Input
shaft
Auxiliary
pad
Control
Charge check/
high pressure relief
valve
Charge relief valve
Charge
pump
Valve plate
Piston
Cylinder
block
Cradle swashplate
Ball
bearing
P100 585E
Technical Information
Series 40 M46 Pumps

General Information

M46 Pumps

M46 Variable Pumps

M46 pumps are designed for medium power applications with maximum loads of 345 bar [5000 psi]. These pumps can be combined with other products in a system to transfer and control hydraulic power.
M46 pumps provide an infinitely variable speed range between zero and maximum in both forward and reverse modes of operation.
M46 pumps are compact, high power density units. All models use the parallel axial piston / slipper concept in conjunction with a tiltable swashplate to vary the pump’s displacement. Reversing the angle of the swashplate reverses the flow of fluid from the pump, reversing the direction of rotation of the motor output.
M46 pumps may include an integral charge pump to provide system replenishing and cooling fluid flow, as well as servo control fluid flow. M46 pumps feature a range of auxiliary mounting pads to accept auxiliary hydraulic pumps for use in complementary hydraulic systems.
M46 pumps offer proportional controls with either manual, hydraulic, or electronic actuation. An electric three-position control is also available.
©
Danfoss | March 2017 L1001029 | BC00000176en-US0209 | 7
Input shaft
Suction flow
Servo pressure
High pressure
Case flow
Charge pressure
Output shaft
Cylinder block assembly
Filter
Charge
pump
Reservoir
Fixed displacement motor
Cylinder
block
assembly
Heat exchanger
Check valves w/ high pressure relief valve
Variable displacement pump
Heat exchanger bypass
Charge relief valve
Displacement control valve
Control handle
Bypass
valve
Loop flushing
module
P100586
B
M2
M1
A
E
L1
L2
M5
M4
S
M3
B N A
P100587
Technical Information
Series 40 M46 Pumps
General Information

System Circuit Diagram

Schematic Diagram

8 | © Danfoss | March 2017 L1001029 | BC00000176en-US0209
Technical Information
Series 40 M46 Pumps

Features and Options

Features

Options

Efficient Axial Piston Design
Compact, Lightweight Pumps
Worldwide Support
Low Noise
Single and Tandem Integrated Tandem Configurations
Manual, Hydraulic or Electric Control
High Pressure Relief Valve (HPRV) - A high pressure relief valve limits the system pressure to protect the system from over-pressure.
Charge Relief Valve - The charge pressure relief valve regulates charge pressure. Displacement Limiters - Optional displacement limiters allow maximum displacement adjustment to
allow for fine tuning of the propel system.
Auxiliary Mounting Pads - Several auxiliary mounting pad options allow for adding a second pump. Control Options - Control options include manual displacement control (MDC), hydraulic displacement
control (HDC), electric displacement control (EDC), and threeposition electric displacement control (FNR). Input Shafts - Straight keyed, tapered keyed, and several splined shaft options are available.
©
Danfoss | March 2017 L1001029 | BC00000176en-US0209 | 9
Technical Information
Series 40 M46 Pumps

Operating Parameters

Fluids

Ratings and performance data are based on operating with premium hydraulic fluids containing oxidation, rust, and foam inhibitors. These include premium turbine oils, API CD engine oils per SAE J183, M2C33F or G automatic transmission fluids (ATF), Dexron II (ATF) meeting Allison C-3 or Caterpillar T02 requirements, and certain specialty agricultural tractor fluids. For more information on hydraulic fluid selection, see Danfoss publications: Hydraulic Fluids and Lubricants, Technical Information, 520L0463 and,
Experience with Biodegradable Hydraulic Fluids, Technical Information,520L465.

Viscosity

For maximum efficiency and bearing life, ensure the fluid viscosity remains in the recommended range. The minimum viscosity should be encountered only during brief occasions. Maximum temperature is based on material properties. Measure maximum temperature at the hottest
point in the system. This is usually the case drain. The maximum viscosity should be encountered only at cold start, and is merely a reflection of a viscosity condition supporting an engine start, at idle. Normal vehicle operation and performance should not occur until the fluid viscosity improves with increrased temperature. For more information on viscosity, see Danfoss publication, Hydraulic Fluids and Lubricants,
Technical Information 520L0463.

Charge Pressure

Temperature

Maintain fluid temperature within the limits shown in the table. Minimum temperature relates to the physical properties of the component materials. Cold oil will not affect the durability of the pump components. However, it may affect the ability of the pump to transmit power.
Maximum temperature is based on material properties. Measure maximum temperature at the hottest point in the system. This is usually the case drain.
Ensure fluid temperature and viscosity limits are concurrently satisfied.
An internal charge relief valve regulates charge pressure. Charge pressure supplies the control with pressure to operate the swashplate and to maintain a minimum pressure in the low side of the transmission loop.
The charge pressure setting listed in the order code is the set pressure of the charge relief valve with the pump in neutral, operating at 1800 min-1 [rpm], and with a fluid viscosity of 32 mm2/s [150 SUS]. Pumps configured with no charge pump (external charge supply) are set with a charge flow of 19 l/min [5 US gal/ min] (single pumps), 38 l/ min [10 US gal/min] (tandem pumps), and a fluid viscosity of 32 mm2/s [150 SUS].
The charge pressure setting is referenced to case pressure. Charge pressure is the differential pressure above case pressure.
Minimum charge pressure is the lowest pressure allowed in order to maintain a safe working condition in the low side of the loop. Minimum control pressure requirements are a function of speed, pressure, and swashplate angle, and may be higher than the minimum charge pressure shown in the Specifications section.
Maximum charge pressure is the highest charge pressure allowed by the charge relief adjustment, and which provides normal component life. Elevated charge pressure can be used as a secondary means to reduce the swashplate response time.

Control Pressure

Control pressure is the pressure in the servo system needed to position and hold the pump on stroke. Servo pressure depends on system pressure and speed.
10 | © Danfoss | March 2017 L1001029 | BC00000176en-US0209
C
Technical Information
Series 40 M46 Pumps
Operating Parameters

Case Pressure

System Pressure

At minimum control pressure, the pump will run at reduced stroke depending on speed and pressure. Minimum control pressure at corner power holds the pump on full stroke at maximum speed and
maximum pressure. Maximum control pressure is the highest pressure typically given by the charge pressure setting.
Under normal operating conditions, do not exceed rated case pressure. During cold start, keep case pressure below maximum intermittent case pressure.
CAUTION
Operating outside of charge and case pressure limits will damage the pump. To minimize this risk, use full size inlet and case drain plumbing, and limit line lengths.
System pressure is the differential pressure between high pressure system ports. It is the dominant operating variable affecting hydraulic unit life. High system pressure, which results from high load, reduces expected life. Hydraulic unit life depends on the speed and normal operating, or weighted average, pressure that can only be determined from a duty cycle analysis.
Application pressure is the high pressure relief or pressure limiter setting normally defined within the order code of the pump. This is the applied system pressure at which the driveline generates the maximum calculated pull or torque in the application.
Maximum Working pressure is the highest recommended application pressure. Maximum working pressure is not intended to be a continuous pressure. Propel systems with application pressures at, or below, this pressure should yield satisfactory unit life given proper component sizing.
Maximum pressure is the highest allowable application pressure under any circumstance. Application pressures above maximum working pressure will only be considered with duty cycle analysis and factory approval.
Minimum low loop pressure must be maintained under all operating conditions to avoid cavitation.
All pressure limits are differential pressures referenced to low loop (charge) pressure. Subtract low loop pressure from gauge readings to compute the differential.

Speed Ratings

Minimum speed is the lowest input speed recommended during engine idle condition. Operating below
minimum speed limits the pump’s ability to maintain adequate flow for lubrication and power transmission.
Rated speed is the highest input speed recommended at full power condition. Operating at or below this speed should yield satisfactory product life.
Maximum speed is the highest operating speed permitted. Exceeding maximum speed reduces product life and can cause loss of hydrostatic power and braking capacity. Never exceed the maximum speed limit under any operating conditions.
Operating conditions between rated speed and maximum speed should be restricted to less than full power and to limited periods of time. For most drive systems, maximum unit speed occurs during downhill braking or negative power conditions.
For more information consult Pressure and Speed Limits BLN-9884, when determining speed limits for a particular application.
©
Danfoss | March 2017 L1001029 | BC00000176en-US0209 | 11
W
Technical Information
Series 40 M46 Pumps
Operating Parameters

Inlet Pressure

During hydraulic braking and downhill conditions, the prime mover must be capable of providing sufficient braking torque in order to avoid pump over speed. This is especially important to consider for turbocharged and Tier 4 engines.
Warning
Unintended vehicle or machine movement hazard.
The loss of hydrostatic drive line power, in any mode of operation (forward, neutral, or reverse) may cause the system to lose hydrostatic braking capacity. You must provide a braking system, redundant to the hydrostatic transmission, sufficient to stop and hold the vehicle or machine in the event of hydrostatic drive power loss.
Achieving acceptable pump life and performance requires proper charge pump inlet design. A continuous inlet pressure of not less than 0.8 bar absolute (not more than 6.3 inches Hg vacuum) is recommended. Normal pressure less than the minimum inlet pressure of 0.7 bar absolute (greater than
9.2 inches Hg vacuum) indicates inadequate inlet design or a restricted filter. Pressures less than 0.7 bar absolute (greater than 9.2 inches Hg vacuum) during cold start are likely, but should improve quickly as the fluid warms.
12 | © Danfoss | March 2017 L1001029 | BC00000176en-US0209
Based on SI units
= (l/min)
Input torque M = (N•m)
Input power P = = (kW )
Based on US units
= (US gal/min)
Input torque M = (lbf•in)
Input power P = = (hp)
Vg • n • η
v
1000
Vg • p
20 • π • η
m
Q • p
600 • η
t
M • n • π
30 000
Vg • n • η
v
231
Vg • p
2 • π • η
m
Q • p
1714 • η
t
M • n • π 198 000
Flow
Torque
Power
Technical Information
Series 40 M46 Pumps

System Design Parameters

Sizing Equations

Use these equations to help choose the right pump size and displacement for your application.
Variables
SI units [US units] Vg = Displacement per revolution cm3/rev [in3/rev] pO = Outlet pressure bar [psi] pi = Inlet pressure bar [psi] ∆p = pO - pi (system pressure) bar [psi] n = Speed min-1 (rpm) ηv = Volumetric efficiency ηm = Mechanical efficiency ηt = Overall efficiency (ηv • ηm)

Filtration

Ensure fluid entering pump is free of contaminants to prevent damage (including premature wear) to the system. M46 pumps require system filtration capable of maintaining fluid cleanliness at ISO 4406-1999 class 22/18/13 or better.
Consider these factors when selecting a system filter:
Cleanliness specifications
Contaminant ingression rates
Flow capacity
Desired maintenance interval
Locate filter either on the inlet (suction filtration) or discharge (charge pressure filtration) side of the charge pump.
Filter efficiency can be measured with a Beta ratio¹ (βX). For simple suction-filtered closed circuit transmissions and open circuit transmissions with return line filtration, a filter with a β-ratio within the range of β35-45 = 75 (β10 ≥ 2) or better has been found to be satisfactory. Systems with multiple cylinders that are feed from a single reservoir require a more efficient filter. This also applies to systems with gears or clutches using a common reservoir.
For high volume systems, use a charge pressure or return filtration system with a filter β-ratio in the range of β15-20 = 75 (β10 ≥ 10) or better.
Because each system is unique, only a thorough testing and evaluation program can fully validate the filtration system. Please see Design Guidelines for Hydraulic Fluid Cleanliness Technical Information 520L0467 for more information.
©
Danfoss | March 2017 L1001029 | BC00000176en-US0209 | 13
C
Reservoir
Filter
Charge
pump
Charge relief
valve
To pump case
To low pressure
side of loop
and servo control
Strainer
P100588
Technical Information
Series 40 M46 Pumps
System Design Parameters
Cleanliness level and βx-ratio
Filtration (recommended minimum)
1
Filter βx-ratio is a measure of filter efficiency defined by ISO 4572. It is defined as the ratio of the number
Cleanliness per ISO 4406 22/18/13 Efficiency (charge pressure
filtration) Efficiency (suction and
return line filtration) Recommended inlet screen
mesh size
β-ratio β
μm 100 – 125
= 75 (β10 ≥ 10)
15-20
β
= 75 (β10 ≥ 2)
35-45
of particles greater than a given diameter (“x” in microns) upstream of the filter to the number of these particles downstream of the filter.

Suction Filtration

The filter is located between the reservoir and the charge pump inlet, as shown in the accompanying illustration.
CAUTION
Operating outside of charge and case pressure limits will damage the pump. To minimize this risk, use full size inlet and case drain plumbing, and limit line lengths.
Suction filtration

Charge Pressure Filtration

The filter is mounted remotely after the charge pump outlet, as shown in the accompanying illustration. For charge pressure filtration, use a filter that is rated to at least 34.5 bar [500 psi] pressure. Use a 100 -
125 μm screen in the reservoir or charge inlet line. A bypass valve is necessary to prevent filter damage and to avoid contaminants from being forced
through the filter by high pressure. In the event of high pressure drop associated with a blocked filter or cold start-up conditions, fluid will bypass the filter. Avoid working with an open bypass for an extended period. We recommend a visual or electrical bypass indicator. Proper filter maintenance is mandatory.
14 | © Danfoss | March 2017 L1001029 | BC00000176en-US0209

Reservoir

Filter
with bypass
Charge
pump
Charge relief
valve
To pump case
To Low Pressure
side of loop
and servo control
Strainer
P106102
W
Technical Information
Series 40 M46 Pumps
System Design Parameters
Charge filtration

Redundant Braking System Requirement

Warning
Unintended vehicle or machine movement hazard
The loss of hydrostatic drive line power, in any mode of operation (forward, neutral, or reverse) may cause the system to lose hydrostatic braking capacity. You must provide a braking system, redundant to the hydrostatic transmission, sufficient to stop and hold the vehicle or machine in the event of hydrostatic drive power loss.

Loop Flushing

Closed circuit systems may require loop flushing to meet temperature and cleanliness requirements. A loop flushing valve removes hot fluid from the low pressure side of the system loop for additional cooling and filtering. Ensure the charge pump provides adequate flow for loop flushing and the loop flushing valve does not cause charge pressure to drop below recommended limits.
Reservoir
The reservoir provides clean fluid, dissipates heat, and removes entrained air from the hydraulic fluid. It allows for fluid volume changes associated with fluid expansion and cylinder differential volumes. Minimum reservoir capacity depends on the volume needed to perform these functions. Typically, a capacity of one half the charge pump flow (per minute) is satisfactory for a closed reservoir. Open circuit systems sharing a common reservoir require greater fluid capacity.
Locate the reservoir outlet (suction line) near the bottom, allowing clearance for settling foreign particles. Use a 100 - 125 μm screen covering the outlet port.
Place the reservoir inlet (return lines) below the lowest expected fluid level, as far away from the outlet as possible.
Use a baffle (or baffles) between the reservoir inlet and outlet ports to promote de-aeration and reduce fluid surging.

Case Drain Usage for Tandem Pumps

©
Danfoss | March 2017 L1001029 | BC00000176en-US0209 | 15
The tandem housings are connected through the center section via a drilled hole. The charge relief valve discharges oil into the front housing. In order to provide positive flow through both housings, use a case
Technical Information
Series 40 M46 Pumps
System Design Parameters
drain in the rear housing. The front housing case drain ports should only be used if the pump is used as a common drain manifold for the vehicle where external drain flow is brought into the rear housing and discharged out the front.
Allowable case pressure limits must be satisfied.

Bearing Life and External Shaft Loading

Bearing life is a function of speed, system pressure, charge pressure, and swashplate angle, plus any
external side or thrust loads. Other life factors include oil type and viscosity. The influence of swashplate angle includes displacement as well as direction. External loads are found in applications where the pump is driven with side/thrust load (belt or gear) as well as in installations with misalignment and improper concentricity between the pump and drive coupling.
In vehicle propel drives with no external shaft loads and where the system pressure and swashplate angle are changing direction and magnitude regularly, the normal L20 bearing life (80% survival) will exceed the hydraulic load-life of the unit.
In non propel drives such as vibratory drives, conveyor drives, or fan drives, the operating speed and pressure are often nearly constant and the swashplate angle is predominantly at maximum. These drives have a distinctive duty cycle compared to a propulsion drive. In these types of applications a bearing life review is recommended.
M46 pumps are designed with bearings that can accept some external radial and thrust loads. When external loads are present, the allowable radial shaft loads are a function of the load position relative to the mounting flange, the load orientation relative to the internal loads, and the operating pressures of the hydraulic unit. In applications where external shaft loads can not be avoided, the impact on bearing life can be minimized by proper orientation of the load. Optimum pump orientation is a consideration of the net loading on the shaft from the external load, the pump rotating group, and the charge pump load. A high capacity (cylindrical roller) input shaft bearing is available for applications with high external shaft loads. Contact your Danfoss representative.
In applications where the pump is operated such that nearly equal amounts of forward vs reverse
swashplate operation is experienced; bearing life can be optimized by orientating the external side load to the 0 or 180 deg position (90 deg to rotating group load Fb). See drawing.
In applications where the pump is operated such that the swashplate is predominantly (>75%) on
one side of neutral (e.g. vibratory, conveyor, typical propel); bearing life can be optimized by orientating the external side load generally opposite of the internal rotating group load, Fb. The direction of the internal loading is a function of rotation and system port, which has flow out.
Avoid axial thrust loads in either direction.
The maximum allowable radial loads (Re), based on the maximum external moment (Me) and the distance (L) from the mounting flange to the load, may be determined from the tables below and the cross section drawing.
The maximum allowable radial load is calculated as: Re = Me / L Contact your Danfoss representative for an evaluation of unit bearing life if continuously applied external
radial loads are 25% or more of the maximum allowable, or if thrust loads are known to exist.
Shaft loading parameters
Re Maximum external radial load Me Me Maximum external moment L Distance from mounting flange to point of load Fb Force of cylinder block Te Thrust external load Fcp Force of charge pump
16 | © Danfoss | March 2017 L1001029 | BC00000176en-US0209
L
Re
Te
P100594
270
Re
0
Re
90
Re
180
Re
CW
CCW
F
cp
F
b
Technical Information
Series 40 M46 Pumps
System Design Parameters
Maximum external shaft moments
Standard Bearing
Me/N•m [in·lbf ] 186 [1650]
External radial shaft load

Hydraulic Unit Life

Mounting Flange Loads

Hydraulic unit life is defined as the fatigue life expectancy of the hydraulic components. It is a function of speed and system pressure; however, system pressure is the dominant variable. High pressure, which results from high load, reduces expected hydraulic unit life.
System component selection is based on determination of the application maximum loads and speeds. Testing is recommended to secure duty cycle data in which to predict hydraulic unit life. Contact your Danfoss representative for assistance in unit life determination. If duty cycle data is not available, normal input power and maximum pump displacement can be used to determine an application pressure in which to predict life.
M46 pumps will meet most application hydraulic unit life expectancies if applied within the parameters specified in this manual and chosen considering the guidelines within Danfoss publication Selection of Driveline Components BLN-9885. For more detailed information on hydraulic unit life, see Danfoss publication Pressure and Speed Limits BLN-9884.
Shock load moment is the result of an instantaneous jolt to the system. Continuous load moments are generated by the typical vibratory movement of the application. Avoid excessive loading of the mounting flange such as adding tandem mounted auxiliary pumps and/or subjecting pumps to high shock loads. Design pump applications to stay within the allowable shock load moment and allowable continuous load moment.
Use the following formulas to estimate overhung load moment for multiple pump mountings: MS = GS (W1L1 + W2L2 + ... +WnLn) MC = GC (W1L1 + W2L2 + ... +WnLn) Refer to the Installation Drawings section to find pump length (L). Refer to the table Technical
Specifications in the Specifications section, to find pump weight (W). An exact measure of W will depend on the pump’s features.
©
Danfoss | March 2017 L1001029 | BC00000176en-US0209 | 17
Mounting flange
CG Pump 1
CG Pump 2
L1
L2
P100 596E
Technical Information
Series 40 M46 Pumps
System Design Parameters
The tables below show allowable overhung load moment values. If system parameters exceed these values add additional pump support.
Estimated maximum and continuous acceleration factors for some typical Series 40 applications are shown. Applications which experience extreme resonant vibrations may require additional pump support. Typical continuous (vibratory) values can vary significantly due to changes in engine and pump configuration and mounting methods.
Overhung loading parameters
M
s
M
c
G
s
G
c
W
n
L
n
Shock load moment Continuous load moment Maximum shock acceleration (Gs) Continuous (vibratory) acceleration (Gs) Weight of nth pump Distance from mounting flange to center of gravity of nth pump
Allowable overhung parameters
Frame size Continuous load moment (Mc) 107 cycles
N•m [in·lbf]
M46 PV 517 [4600] 832 [7400] M46 PT 517 [4600] 754 [6700]
Shock load moment (Ms) 103 cycles N•m [in·lbf]
Shaft loading parameters
The illustration shows a tandem plus a single pump.
G-factors for sample applications
Application Continuous (vibratory)
acceleration (Gc)
Skid steer loader 4 10 Trencher
(rubber tires) Asphalt paver 2 6 Windrower 2 5 Aerial lift 1.5 4 Turf care vehicle 1.5 4 Vibratory roller 6 10 * Applications which experience extreme resonant vibrations require addition pump support.
3 8
Maximum (shock) acceleration (Gs)
18 | © Danfoss | March 2017 L1001029 | BC00000176en-US0209
Technical Information
Series 40 M46 Pumps
System Design Parameters

Shaft Torques

Shaft selection

Base shaft selection on a review of the maximum torque required by the application and the maximum torque available from the prime mover. Application duty cycle and continuous torque rating of the prime mover are the main variable to consider when selecting a shaft.

Shaft torque and spline lubrication

The rated torque is a measure of tooth wear and is the torque level at which a normal spline life of 1 x 107 shaft revolutions can be expected. The rated torque presumes a regularly maintained minimum level of lubrication via a moly-disulfide grease in order to reduce the coefficient of friction and to restrict the presence of oxygen at the spline interface. It is also assumed that the mating spline has a minimum hardness of Rc 55 and full spline depth. The rated torque is proportional to the minimum active spline length.
However, a spline running in oil-flooded environment provides superior oxygen restriction in addition to contaminant flushing. The rated torque of a flooded spline can increase to that of the maximum published rating. A flooded spline would be indicative of a pump driven by a pump drive or plugged into an auxiliary pad of a pump.
Maximum torque ratings are based on torsional fatigue strength considering 1 x 105 full load reversing cycles.
Maintaining a spline engagement at least equal to the pitch diameter will also maximize spline life. Spline engagements of less than ¾ pitch diameter are subject to high contact stress and spline fretting.

Shaft torque for tapered shafts

The rated torque is based on the contact pressure between the shaft and hub surfaces with poor contact areas. With increased quality of the contact areas, the contact pressure between shaft and hub is increased, allowing higher torque to be transmitted.
A key is intended as an installation aid only. Any torque carried by the key as a result of poor contact area or mis-alignment will limit the torque carrying capability of the shaft significantly.
Maximum torque rating is based on an ideal contact area of 100% and the retaining nut properly torqued. This allows for the highest contact pressure between the shaft and the mating hub.
©
Danfoss | March 2017 L1001029 | BC00000176en-US0209 | 19
C D E F G H J L N
P
R
T Z
K
M
S
Product Frame
Type
MPV 046
C
Technical Information
Series 40 M46 Pumps

Model Code - Single Pumps

Single Pumps

C Swashplate
Description Code Remarks
Standard B
D - Seal Group
Description Code Remarks
Seal group for MDC A Must select an MDC control Seal group for EDC/HDC/FNR B Must select an EDC/HDC/FNR control
E - Input Shaft/Auxiliary Spline
Description Code Remarks
13T 16/32 Spline / None A Requires S: None aux.. pad 13T 16/32 Spline / 9T 16/32 SplineR B Requires S: SAE-A aux.. pad 13T 16/32 Spline / 11T 16/32 Spline L Requires S: SAE-A aux.. pad 13T 16/32 Spline / 13T 16/32 Spline D Requires S: SAE-B aux.. pad 15T 16/32 Spline / None G Requires S: None aux.. pad 15T 16/32 Spline / 9T 16/32 Spline H Requires S: SAE-A aux.. pad 15T 16/32 Spline / 11T 16/32 Spline J Requires S: SAE-A aux.. pad 15T 16/32 Spline / 13T 16/32 Spline K Requires S: SAE-B aux.. pad Tapered, 1 inch dia., 1.5 in/foot, square key/9T 16/32 Spline P Requires S: SAE-A aux.. pad. Includes key and nut Tapered, 1 inch dia., 1.5 in/foot, square key/ 13T 16/32 Spline S Requires S: SAE-B aux.. pad. Includes key. Nut is customer supplied Straight key, 1 inch diamater / None V Requires S: None aux.. pad. Includes key. Straight key, 1 inch diameter / 9T 16/32 Spline W Requires S: SAE-A aux.. pad, includes key.
F - Rotation and valve plate
Description Code Remarks
CW, Quiet (Standard) S CP15; 3 deg. index. Requires charge pressure > 19.5 bar. CCW, Quiet (Standard) T CP15; 3 deg. index. Requires charge pressure > 19.5 bar.
G - Charge pump
Description Code Remarks
None A Charge relief set at 19 l/min, external supply
13.9 cc [0.85 in./cu] B Charge relief set at 1800 rpm
20 | © Danfoss | March 2017 L1001029 | BC00000176en-US0209
Loading...
+ 44 hidden pages