Danfoss KP 15, KP 15A, KP 17W, KP 17B, KP 17WB Installation guide

Installation guide
Pressure switch
KP 15, KP 15A, KP 17W, KP 17B, KP 17WB
Refrigerants:
R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D, R448A, R449A, R450A, R452A, R507A, R513A, R717*)
060R 9753
For complete list of approved refrigerants, go to http://products.danfoss.com/all-products/
*) only for KP 15A
Ambient temperatures / Mounting requirements
t1 min. KP 15: -40 °C (-40 °F) t1 min. KP 17: - 25 °C (-13 °F) t1 max.: 65 °C (149 °F)
Relative humidity RH: 30 – 98% Vibrations resistance: 4 g (10 – 1000 Hz)
KP 15, KP 17 KP 15, KP 17 KP 15A
Test pressure (P
Typ e
KP 15
KP 15 LP man. reset
KP 17
Regulation range
)
test
LP: -0.2 – 7.5 bar
HP: 8 – 32 bar
LP: -0.9 – 7 bar
HP: 8 – 32 bar
LP: -0.2 – 7.5 bar
HP: 8 – 32 bar
p
max.
test
35 bar (510 psig)
PS/MWP
p
max.
test
20 bar (285 psig)
PS/MWP
Max. working pressure PS/MWP
17 bar/245 psig 35 bar/510 psig
17 bar/245 psig 35 bar/510 psig
17 bar/245 psig 35 bar/510 psig
060R 9753
12 (⁄in)
15% Ag
KP 15, KP 17KP 15A
17 m m (⁄in)
14 mm (⁄in)
14 mm (⁄in)
Max. 100 °C (212 ° F)
Enclosure
A: 8 – 32 UNC (M4)
C: Enclosure IP44
(EN 60529)
B: Enclosure IP30
(EN 60529)
max. 3 mm (⁄in)
© Danfoss | Climate Solutions | 2021.05 AN211686434433en-000701 | 1
CAUTION:
Disconnect power supply before wiring connections are made or service to avoid possible electrical shock or damage to equipment. Do never touch live parts with your ngers or with any tool.
LP side: A-C opens on pressure drop HP side: A-C opens on pressure rise
Electrical rating - General When used acc. to UL regulations
AC 1: 16 A
LR 112A
AC 3: 16 A 12 W
AC 15: 10 A 220 V
Short circuit protection:
Fuse 16 Amp
400 V
AC
DC 13
Listed refrigeration controller
Contacts
A - B A - C
A - D 240 5 0 VA
Use copper wire only Tightening torque 20 lb. in
Voltage FL LR
AC DC A A
240 8 48 8 A
120 16 96 16 A
240 12 W
LP = Low Pressure LP = Low Pressure HP = High Pressure
-1 bar (Pe)(30 inHg) -1 bar (Pe)(30 inHg)
LP, aut. reset LP, man. reset HP
Manual trip function
Convertible reset
KP 15: LP/HP convertible, KP 17WB: HP convertible
61B5
Resist .
load
Pilot duty
3 A
TRIP: use FINGERS ONLY! (Do NOT use screwdriver)
Adjustment
0.7 bar (10 psi)/rev.
2 | AN211686434433en- 000701
0.15 bar (2 psi)/rev.
6 mm (⁄ in)
2.3 bar (33.5 psi)/rev.
Insert a screwdriver into the slot on the lock disc and turn it to desired reset conguration. Do not turn the screw on the lock disc as it may damage theconvertible reset mechanism.
Reset options
LP man. LP auto. LP auto. LP man.
HP man HP man HP auto. HP auto.
Note: Do not select automatic reset if safety of the system
requires manual reset. Note: Selected reset conguration may be protected against unauthorized actions applying a seal.
© Danfoss | Climate Solutions | 2021.05