Data Sheet
Pressure switch
Type KP
The KP pressure switches can be used as safety
switches against too low a suction pressure
and / or too high a discharge pressure in
refrigeration and air conditioning systems. They
can also be used to start / stop compressors
and fans for air-cooled condensers.
They are available in both single and dual
versions and include a single pole double
throw (SPDT) switch.
Features:
• Ultra-short bounce time thanks to snapaction function (reduces wear to a minimum
and increases reliability)
• Available with gold-plated contacts
• SPDT switch design Oers open or close
switching action on pressure rise or fall
• Fail safe double bellows Prevent refrigerant
loss and system contamination - standard on
KP 7 and KP 17 pressure switches
• Convenient manual trip feature To test
electrical contact function - no tools needed
• Pressure wire connectors For easy electrical
wiring
• No spade or lug terminals required
• Integral 1⁄2 NPSM swivel cable connector
Allows direct attachment of 1⁄2 in male pipe
thread connector
• Lockplate Prevents tampering with range and
dierential settings
• Universal mounting hole patterns
AI216886432258en-001101
SPDT - signal pole double throw
-40 – 149 °F (175 °F for maximum 2 hours)
Maximum working pressure
LP: MWP = 245 psig
Maximum test pressure
LP: pe = 285 psig
Single pole changeover switch (SPDT)
240 V DC: 12 W pilot duty
Terminal D, dual switches
KP 1, KP 2, KP 5, KP 7, KP 15, KP 17, KP 25
Tin bronze, no. CW452K, EN 1652 Nickel plated free cutting steel, no. 1.0737 /
1.0718 to EN 10277
Copper SF-Cu, no. 2.0090 to DIN 1787
Bellows movement on pressure rise
Bellows movement on pressure drop
Pressure switch, Type KP
Product specication
Technical data
Table 1: Technical data
Cable entry
Integral 1⁄2 in female NPSM swivel cable connector allows direct attachment of 1⁄2 in male pipe thread connector.
Enclosure
~NEMA 1
This grade of enclosure is obtained when the units without top cover are mounted on a at surface or bracket.
The bracket must be xed to the unit so that all unused holes are covered.
~ NEMA 2
This grade of enclosure is obtained when the units with top cover are mounted on a at surface or bracket.
The bracket must be xed to the unit so that all unused holes are covered
Table 2: Materials in contact with the medium
Electrical wiring
Table 3: Electrical wiring
Figure 1: Low or high pressure
© Danfoss | Climate Solutions | 2021.02 AI216886432258en-001101 | 2
Dual (low and high) pressure, LP signal
Dual (low and high) pressure, LP and HP signal
Low pressure, LP: KP 1 and KP 2
High pressure, HP: KP 5, KP 7W and KP 7B
Dual (low and high) pressure: KP 15, KP 17W, KP 17B and KP 25
Dual (low and high) pressure: KP 15, KP 17W, KP 17B and KP 25
Pressure switch, Type KP
Metric conversions
1 psi = 0.07 bar
5⁄9 (t1 °F - 32) = t2 °C
© Danfoss | Climate Solutions | 2021.02 AI216886432258en-001101 | 3