Danfoss KOVM Data sheet

Data sheet KOVM
3-Way Mixing Valve
Application:
Ordering Information:
The Danfoss KOVM is a linear 3-way mixing valve with a unique bypass design allowing for constant system pressures and flow rates. When the KOVM is combined with either the RAVK non-electric thermostatic operator or the ABV 24VAC thermo-wax actuator the linear actuation of the valve results in the control of hot or chilled water flow to radiators, convectors, fan coil units, etc.
Features:
Unique 3-way bypass design• Linear valve actuation• Provides constant zone or system flow• Designed for use with RAVK/RA 2000 wall•
mount non-electric thermostatic operators or ABV 24VAC thermo-wax electronic actuators
KOVM Valve
Code No. Size Connection Cv
013U3017 ½” NPT
013U301501
1)
013U302001 2.34
Cv is the flow rate allowed by the valve in GPM with a pressure drop of 1 psi.
1)
Rp ½” valves are supplied with compression rings and nuts
2)
Δpc gives the max. differential pressure across the heat exchanger controlled by the valve
Rp ½”
Compression
1.75
Max. Differential Pressure
w/ By pass w/o By pass Δp
12 psi 12 psi
23 psi
(1.6 bar)
(0.8 bar) (0.8 bar)
7.25 psi
(0.5 bar)
2)
c
7.25 psi
(0.5 bar)
Non-Electric Operators
Code No. Size Connection Cv
013U8063 RAVK, thermostatic operator
013G8562
013G8565 16’ (4.9 m)
013G8568 26’ (7.9 m)
RA2000, wall mount operator with
combined remote mounted sensor and
dial
RA2000, wall mount operator with
013G8564
separate remote mounted sensor and
dial
77-149°F
(25-65°C)
45-86°F
(7-30°C)
45-86°F
(7-30°C)
6’6” (2 m)
6’ (1.8 m)
2 x 6’
(2 x 1.8 m)
Electronic Actuators
Code No. Description Typ e Consumption
082F0002
082F0052 Normally closed
ABV, thermo-wax 24VAC electronic
actuator
Normally open
9VA
VDLSB122 © Danfoss 05/09
1
Data sheet KOVM
3-Way Mixing Valve
Spare Parts
Code No. Description
013G4116
013U0070 Packing gland for KOVM
017-4370 ½” Brass sensor well for RAVK
Spare compression fitting for KOVM (consist of compression ring and nut)
Technical Specifications:
Flow Diagram:
Maximum operating pressure 145 psi (10 bar)
Maximum operating temperature 180°F (90°C)
Minimum operating temperature 36°F (2°C)
Allowable fluid For close loop systems
1) 100% water
2) Glycol mixture max. 30%
KOVM
2
VDLSB122 © Danfoss 05/09