User Manual
PLUS+1® GUIDE Software
PLUS+1 Compliant KEP 3-Pt Foot Pedal
Function Block
www.danfoss.com
User Manual
PLUS+1 Compliant KEP 3-Pt Foot Pedal Function Block User Manual
Revision history |
Table of revisions |
|
|
|
|
|
|
|
Date |
Changed |
Rev |
|
|
|
|
|
August 2021 |
Fixed the version numbers |
0202 |
|
|
|
|
|
June 2021 |
First release of the user manual |
0201 |
|
|
|
|
2 | © Danfoss | August 2021 |
AQ152886481726en-0202 |
User Manual |
|
PLUS+1 Compliant KEP 3-Pt Foot Pedal Function Block User Manual |
|
Contents |
|
Introduction |
|
Inputs, Outputs, and Signals |
|
Inputs.................................................................................................................................................................................................... |
5 |
Outputs................................................................................................................................................................................................ |
5 |
Diagnostics Signals.......................................................................................................................................................................... |
6 |
Status Outputs................................................................................................................................................................................... |
6 |
Fault Outputs..................................................................................................................................................................................... |
6 |
Configuration |
|
Configuration Parameters............................................................................................................................................................. |
8 |
Setup Configuration Parameter Inputs............................................................................................................................ |
10 |
NV Page............................................................................................................................................................................................. |
11 |
Configuring Inputs with Legacy MC Controllers................................................................................................................ |
11 |
Configure a Multifunction Input with Legacy Controllers......................................................................................... |
12 |
Configure an Analog Input with Legacy Controllers................................................................................................... |
12 |
Configure a Digital/Analog Input for Legacy Controllers.......................................................................................... |
13 |
Configuring Inputs with SC Controllers and Non-Legacy MC Controllers................................................................ |
13 |
Configure a Multifunction Input......................................................................................................................................... |
13 |
Configure a Digital/Analog Input....................................................................................................................................... |
14 |
Using Namespaces........................................................................................................................................................................ |
15 |
Change Namespace Value..................................................................................................................................................... |
15 |
Calibration |
|
Calibrate the Foot Pedal.............................................................................................................................................................. |
16 |
Calibration Windows and Default Calibration Values....................................................................................................... |
16 |
Calibration Values and Deadbands......................................................................................................................................... |
17 |
Customizable Service Screens |
|
Add Service Screens to the Service Tool................................................................................................................................ |
19 |
KEP Foot Pedal Service Screen.................................................................................................................................................. |
19 |
Calibration Service Screen.......................................................................................................................................................... |
21 |
Pedal Reusable Panel.................................................................................................................................................................... |
22 |
© Danfoss | August 2021 |
AQ152886481726en-0202 | 3 |
User Manual
PLUS+1 Compliant KEP 3-Pt Foot Pedal Function Block User Manual
The KEP 3Pt Foot Pedal Function Block provides parameters and logic used to integrate a KEP 3Pt Foot Pedal into your application.
•The SnsrPwr input receives the sensor power voltage applied to the pedal sensor. This voltage remains constant.
•The Pedal input receives the voltage output by the pedal sensor. The position of the pedal varies this voltage.
The function block makes ratiometric comparisons of the Pedal and SnsrPwr inputs. This comparison produces Out values that range from ±10000 (±100.00%).
4 | © Danfoss | August 2021 |
AQ152886481726en-0202 |
User Manual
PLUS+1 Compliant KEP 3-Pt Foot Pedal Function Block User Manual
|
|
|
|
|
This section provides information on the inputs, outputs, diagnostic signals, and fault and status |
||
|
|
|
|
|
conditions for the KEP 3Pt Foot Pedal Function Block. |
||
Inputs |
|
|
|
|
|
|
|
|
|
|
|
|
The Function Block Inputs table describes the inputs for the KEP 3Pt Foot Pedal Function Block. |
||
Function Block Inputs |
|
|
|
|
|||
|
|
|
|
|
|
|
|
Item |
Type |
|
Range |
|
Description |
||
|
|
|
|
|
|
|
|
Para |
Bus |
|
—— |
|
Allows common configuration parameters to be applied to multiple function blocks. |
||
|
|
|
|
|
|
|
See Setup Configuration Parameter Inputs on page 10 for more information. |
|
|
|
|
|
|
|
|
SnsrPwr |
Bus |
|
0–5250 mV |
|
Inputs a signal with the sensor power voltage (reference voltage) that the controller applies to the |
||
|
|
|
|
|
|
|
sensor power pin of the pedal. |
|
|
|
|
|
|
|
|
Pedal |
Bus |
|
0–5250 mV |
|
Inputs a signal with the voltage output by the pedal sensor. The position of the pedal varies this |
||
|
|
|
|
|
|
|
voltage. |
|
|
|
|
|
|
|
The function block makes a ratiometric comparison of the Pedal and SnsrPwr inputs to produce Out |
|
|
|
|
|
|
|
values from ±10000 (±100.00%). |
|
|
|
|
|
|
|
|
Outputs |
|
|
|
|
|
|
|
|
|
|
|
|
The Outputs table describes the output signals from the function block. |
||
Outputs |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Output |
|
Type |
|
Range |
Description [Unit] |
||
|
|
|
|
|
|
||
Status |
|
U16 |
|
—— |
Indicates the calibration and setup status of the function block. |
||
|
|
|
|
|
|
0x0000: Function block is OK |
|
|
|
|
|
|
|
0x8001: Function block is not calibrated |
|
|
|
|
|
|
|
0x8002: Function block is partially calibrated |
|
|
|
|
|
|
|
0x8008: Invalid setup/calibration |
|
|
|
|
|
|
|
This output uses a bitwise-reporting scheme where multiple items can be reported at a time. |
|
|
|
|
|
|
|
||
Fault |
|
U16 |
|
—— |
Indicates the operating condition of the function block. |
||
|
|
|
|
|
|
0x0000: Function block is OK |
|
|
|
|
|
|
|
0x8001: Input value is too low |
|
|
|
|
|
|
|
0x8002: Input value is too high |
|
|
|
|
|
|
|
0x8004: Short circuit |
|
|
|
|
|
|
|
0x8008: Open circuit |
|
|
|
|
|
|
|
This output uses a bitwise-reporting scheme where multiple items can be reported at a time. |
|
|
|
|
|
|
|
|
|
Out |
|
|
|
|
|
Outputs a bus that contains the Pedal_Psn signal. |
|
|
|
|
|
|
|||
Pedal_Psn |
U16 |
|
0–±10000 |
Indicates the position of the foot pedal. |
|||
|
|
|
|
|
|
Reverse: -10000 (-100.00%) |
|
|
|
|
|
|
|
Neutral: 0 (0%) |
|
|
|
|
|
|
|
Forward: 10000 (100.00%) |
|
|
|
|
|
|
|
[0.01%] |
|
|
|
|
|
||||
Pedal_Pressed |
BOOL |
T/F |
Indicates whether the pedal is pressed. For more information on the PressedThreshold parameter, see |
||||
|
|
|
|
|
|
Configuration Parameters on page 8. |
|
|
|
|
|
|
|
T: Pedal is pressed |
|
|
|
|
|
|
|
F: Pedal is not pressed |
|
|
|
|
|
|
|
|
|
© Danfoss | August 2021 |
AQ152886481726en-0202 | 5 |
User Manual
PLUS+1 Compliant KEP 3-Pt Foot Pedal Function Block User Manual
Inputs, Outputs, and Signals
Diagnostic signals provide indicators of failure states and tools for calibrating the failure indicators. Refer to the following table for more information on diagnostic signals from the KEP 3Pt Foot Pedal Function Block.
Diagnostic Signals
Signal |
Type |
|
Range |
Description [Unit] |
|
|
|
|
|
Enabled |
BOOL |
|
T/F |
Indicates that the calibration output is enabled or disabled. |
|
|
|
|
T: Nom_Signal sets the Pedal_Psn output. |
|
|
|
|
F: Pedal_Psn output is set to 0. |
|
|
|
|
|
Pedal_Ratio |
U16 |
|
0-10000 |
The ratio of Pedal_Signal voltage compared to Sensor_Power voltage. |
|
|
|
|
[0.01%] |
|
|
|
|
|
CalLow_Temp |
U16 |
|
0-10000 |
A temporary calibration point stored by the function block. After all points calibrate, the function |
|
|
|
|
block records this value in memory. |
|
|
|
|
[0.01% of Snsr_Pwr] |
|
|
|
|
|
CalHigh_Temp |
U16 |
|
0-10000 |
A temporary calibration point stored by the function block. After all points calibrate, the function |
|
|
|
|
block records this value in memory. |
|
|
|
|
[0.01% of Snsr_Pwr] |
|
|
|
|
|
CalLow_Pt |
U16 |
|
0-10000 |
Identifies the start of a 20% window to validate the low calibration point. |
|
|
|
|
[0.01% of Snsr_Pwr] |
|
|
|
|
|
CalHi_Pt |
U16 |
|
0-10000 |
Identifies the start of a 20% window to validate the high calibration point. |
|
|
|
|
[0.01% of Snsr_Pwr] |
|
|
|
|
|
Input_TL_Pt |
U16 |
|
0-10000 |
The minimum allowed ratio of Pedal_Signal to Snsr_Pwr voltage. If the ratio is below this threshold |
|
|
|
|
for more than the value set in FltDetectTm, the Fault signal will declare 0x8001 (Input value is too |
|
|
|
|
low). |
|
|
|
|
[0.01% of Snsr_Pwr] |
|
|
|
|
|
Input_TH_Pt |
U16 |
|
0-10000 |
The maximum allowed ratio of Pedal_Signal to Snsr_Pwr voltage. If the ratio is above this threshold |
|
|
|
|
for more than the value set in FltDetectTm, the Fault signal will declare 0x8002 (Input value is too |
|
|
|
|
high). |
|
|
|
|
[0.01% of Snsr_Pwr] |
|
|
|
|
|
Status Outputs |
|
|
|
|
|
|
Status outputs indicate calibration settings and setup status for the KEP 3Pt Foot Pedal Function Block. |
||
|
|
During calibration, the Pedal_Psn signal in the Out bus is zero. |
||
|
|
The following table lists all the status conditions output by the KEP 3Pt Foot Pedal Function Block. |
Status Conditions
Condition |
Status |
Pedal_Psn Signal |
Comment |
|
|
|
|
Block is OK. |
0x0000 |
0–±10000 |
Normal output of the Pedal_Psn signal. |
|
|
|
|
Block is not calibrated. |
0x8001 |
|
|
|
|
|
|
Block is partially calibrated. |
0x8002 |
0 |
—— |
|
|
|
|
Invalid setup/calibration. |
0x8008 |
|
|
|
|
|
|
The Fault outputs indicate the operating condition of the KEP 3Pt Foot Pedal Function Block.
All fault conditions set the Pedal_Psn signal in the Out bus to zero.
The following table lists all the fault conditions output by the KEP 3Pt Foot Pedal Function Block.
6 | © Danfoss | August 2021 |
AQ152886481726en-0202 |
User Manual
PLUS+1 Compliant KEP 3-Pt Foot Pedal Function Block User Manual
Inputs, Outputs, and Signals
Fault Conditions
Condition |
Fault |
Pedal_Psn Signal |
Comment |
|
|
|
|
|
|
Block is OK. |
0x0000 |
0–±10000 |
Normal output of the Pedal_Psn signal. |
|
|
|
|
|
|
Input value is too low. |
0x8001 |
|
|
|
|
|
|
|
|
Input value is too high. |
0x8002 |
0 |
—— |
|
|
|
|||
Short circuit. |
0x8004 |
|||
|
|
|||
|
|
|
|
|
Open circuit. |
0x8008 |
|
|
|
|
|
|
|
© Danfoss | August 2021 |
AQ152886481726en-0202 | 7 |