Danfoss KDC 65-200 Data sheet

Data Sheet
Pressure control valve Type KDC 65-200
Ecient control of excessive discharge pressure
The KDC valve is a pressure control valve . The valve controls the discharge pressure of the compressor to ensure fast build-up of pressure and lubrication pressure. The valve also acts as a check valve in the discharge line of the compressor.
The KDC valve is force-controlled so that when pressure in the oil separator becomes 2 bar (29 psi) higher than the suction pressure, the spring is compressed and the valve opens. In lowpressure units (boosters), the spring requires a dierential pressure of 0.5 bar (7 psi) for the valve to open.
Features
• Applicable to HCFC, HFC, R717(Ammonia) and R744 (CO2).
• Each valve type is clearly marked with type, size and performance range
• Angle valves with weld connections
• Fast build-up of oil pressure in oil separator during start-up.
• High closing force on the cone during standstill, even without dierential pressure across the valve
• Very low pressure drop because of spring force
• Low part-load without risk of valve chattering
• Stainless steel bolts
• Housing and bonnet material is in low temperature steel according to requirements of the Pressure Equipment Directive and other international classication authorities
• Pressure range: 40 bar (580 psig)
• Temperature range: -50 °C / +150 °C (-58 °F / +302 °F)
Classication: DNV, CRN, BV, EAC etc. To get an updated list of certication on the products please contact your local Danfoss Sales Company.
AI225686433549en-001001
Pressure control valve, type KDC 65-200
Functions
The KDC valve opens in a 3 step sequence. The sequence of steps depends on the start-up situation (see Figure 1:
KDC valve).
Step 1
The valve is always closed by a minimum dierential pressure of 1.5 to 2.0 bar (0.3 to 0.5 bar in a booster system). Step 1 will occur when the compressor is stopped and the discharge pressure has equalized to the top of the valve through the suction side of the compressor.
pc – p1 < 2 bar (0.5 bar for booster) and pc > p
2
Step 2
Step 2 will occur as soon as the condensing pressure becomes higher than the pressure in the oil separator, and when the dierential pressure between suction side and condensing pressure is bigger than the spring force.
pc – p1 > 2 bar (0.5 bar for booster) and pc > p
2
When the compressor starts the valve will either be in step 1 or step 2 position, depending on the pressure dierence between the oil separator and the condensing pressure.
Start up situation 1
Condensing pressure is lower than oil separator pressure.
Start up will occur from step 1 position and go to step 3 as soon as a dierential pressure between suction side and oil separator that can overcome the spring force is present.
Start up situation 2
Condensing pressure is higher than oil separator pressure but the dierential pressure is lower than the spring force.
Start up will occur from step 1 and go to step 2 when dierential pressure between suction side and condensing pressure is bigger than the spring force. When oil separator pressure comes close to the condensing pressure the valve will start opening and the small spring will open the valve completely. The valve will then be in step 3 position.
Start up situation 3
Condensing pressure is higher than oil separator pressure + spring force pressure. Start up will occur from step 2 position.
When oil separator pressure comes close to the condensing pressure the valve will start opening and the small spring will open the valve completely. The valve will then be in step 3 position.
When the compressor stops, the valve will be in step 3 position and as soon as the condensing pressure has equalized to the suction side the spring force will close the valve. The valve will be in step 1 position until enough dierential pressure between condensing pressure and oil separator/suction side pressure occurs for the valve to enter into step 2 position.
NOTE:
The KDC valve cannot be used on compressor units where the non-return valve is placed between compressor and oil separator instead of on the suction side of the compressor. The reason for this is that the KDC valve needs to have the pilot pipe connected to a point on the compressor unit, where the pressure is low during running and high during standstill.
© Danfoss | Climate Solutions | 2021.02 AI225686433549en-001001 | 2
Step 1 Step 2 Step 3
System with KDC valve
System without KDC valve
Time
Pressure difference (p -p)
Pressure control valve, type KDC 65-200
Figure 1: KDC valve
Figure 2: Time and Pressure dierence graph
© Danfoss | Climate Solutions | 2021.02 AI225686433549en-001001 | 3
KDC valve
p
c
Screw
compressor
Oil separator
p
1
p
2
Pressure control valve, type KDC 65-200
Applications
Example
Figure 3: Compressor discharge line after oil separator
© Danfoss | Climate Solutions | 2021.02 AI225686433549en-001001 | 4
Pressure control valve, type KDC 65-200
Media
Refrigerants
Applicable to HCFC, HFC, R717(Ammonia) and R744 (CO2).
For further information please see installation instruction for KDC.
New refrigerants
Danfoss products are continually evaluated for use with new refrigerants depending on market requirements.
When a refrigerant is approved for use by Danfoss, it is added to the relevant portfolio, and the R number of the refrigerant (e.g. R513A) will be added to the technical data of the code number. Therefore, products for specic refrigerants are best checked at store.danfoss.com/en/, or by contacting your local Danfoss representative.
© Danfoss | Climate Solutions | 2021.02 AI225686433549en-001001 | 5
Loading...
+ 11 hidden pages