Danfoss JS120 2Pt Operating guide

Page 1
PLUS+1™ GUIDE Software

PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual

142.0 mm [5.59]
97.0 mm [3.82]
144.5 mm
5.69
158.2 mm
6.23
PIN #1 INDICATED
2x 25.2 mm [1.0]
2x ∅7.0 [.28] MOUNTING DIRECTION #2
LED INDICATO R LIGHTS
TM
COMPLIANT
CONNECTOR MATES WITH DEUTCH CONNECTOR #D TM-06-125A
51.6 mm
47.1 mm [1.85]
[2.03]
1
12
6
7
1
6
12
7
CONNECTOR MATES WITH DEUTCH CONNECTOR #DTM-06-125A
Page 2
PLUS+1 Compliant JS120 2Pt Joystick Function Block
T
User Manual
About this Manual
Organization and Headings
o help you quickly find information in this manual, the material is divided into sections, topics, subtopics, and details, with descriptive headings set in red type. Section titles appear at the top of every page in large red type.
In the PDF version of this document, clicking an item underlined in blue italic type you to the referenced page in the document.
Special Text Formatting Controls and indicators are set in bold black type.
Table of Contents
A Table of Contents (TOC) appears on the next page. In the PDF version of this document, the TOC entries are hyperlinked.
Revision History
Revision Date Comment
Rev BA September 2011
jumps
©2011 Sauer-Danfoss. All rights reserved.
Sauer-Danfoss accepts no responsibility for possible errors in catalogs, brochures and other printed material.
Sauer-Danfoss reserves the right to alter its products without prior notice. This also applies to products already
ordered provided that such alterations can be made without affecting agreed specifications.
All trademarks in this material are properties of their respective owners.
PLUS+1, GUIDE, and Sauer-Danfoss are trademarks of the Sauer-Danfoss Group. The PLUS+1 GUIDE, PLUS+1
Compliant, and Sauer-Danfoss logotypes are trademarks of the Sauer-Danfoss Group.
2
11007136 · Rev BA · September 2011
Page 3
PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual

Contents

JS120_2Pt Function Block ............................................................................................................................. 4
Overview..................................................................................................................................................... 4
Inputs ........................................................................................................................................................... 4
Outputs ....................................................................................................................................................... 5
Connections and Signals Overview ................................................................................................... 5
Status and Fault Logic ............................................................................................................................ 6
Configuration Settings .......................................................................................................................... 7
About Calibration Windows and Default Calibration Values .................................................. 10
About Calibration Values and Deadbands .................................................................................... 12
MC Controller—Input Configuration .............................................................................................. 14
MC Controller—How to Configure a MFIn............................................................................ 14
MC Controller—How to Configure an AnIn ......................................................................... 15
MC Controller—How to Configure a DigAn ......................................................................... 16
SC Controller—Input Configuration ............................................................................................... 17
SC Controller—How to Configure a MFIn ............................................................................. 17
SC Controllers—How to Configure a DigAn......................................................................... 18
About the Para Input ............................................................................................................................ 19
About the Name Space Feature ....................................................................................................... 21
How to Enter a Name Space Value .......................................................................................... 21
11007136 · Rev BA · September 2011
3
Page 4

Overview

PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual

JS120_2Pt Function Block

The JS120_2Pt function block configures the output of a Sauer-Danfoss JS120 Single Axis Fingertip Joystick. This joystick has a single two-point y-axis in its base.
The JS120 Joystick uses a spring to return its lever to one end of its travel.
Using the default values supplied in this function block, an input equal to:
10% of sensor power voltage causes this joystick to output a value of 0%.
90% of sensor power voltage causes this joystick to output a value of 100%.
See:
Connections and Signals Overview on page 5 for an overview of this function block’s
connections and signals.
About the Name Space Feature on page 21 if you are using more than one of these
function blocks in your application.

Inputs

JS120_2Pt Function Block Inputs
Input Type Range Description
Para —— —— Allows common parameters to be applied to multiple joystick function blocks.
See About the Para Input on page 19 for more information.
Snsr Pwr —— 0–5260 mV Inputs the sensor power voltage (reference voltage) that the controller applies to the joystick’s sensor power pin.
Y —— 0–5260 mV The voltage on this input indicates the position of the joystick on its y-axis.
The default: – CalLow calibration value for Y is 10% of the SnsrPwr voltage. A Y input at 10% of the SnsrPwr voltage
outputs a Y_Axis_Psn signal of 0%.
CalHi calibration value for Y is 90% of the SnsrPwr voltage. A Y input at 90% of the SnsrPwr voltage outputs
a Y_Axis_Psn signal of 100%.
4
11007136 · Rev BA · September 2011
Page 5
PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual
JS120_2Pt Function Block

Outputs

JS120_2Pt Function Block Outputs
Output Type Range Description
Status Reports the function block status.
This output uses the standard bitwise scheme described in the Basic Function Blocks Library User’s Manual.
Status_Y U16 —— Indicates the calibration and setup condition of the Y input.
0x0000 = Block is OK. 0x8001 = Block is not calibrated. 0x8002 = Block is partially calibrated. 0x8008 = Invalid setup/calibration.
Fault Reports function block faults.
This output uses the standard bitwise scheme described in the Basic Function Blocks Library User’s Manual.
Fault_Y U16 —— Indicates the operating condition of the Y input.
0x0000 = Block is OK. 0x8001 = Input value is too low. 0x8002 = Input value is too high. 0x8004 = Short circuit. 0x8008 = Open circuit.
Out Outputs a bus with a Psn signal.
Y_Axis_Psn S16 0–10000 Indicates the position of the joystick base’s y-axis.
0 = 0%. 10000 = 100.00%.

Connections and Signals Overview

11007136 · Rev BA · September 2011
5
Page 6

Status and Fault Logic

PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual
JS120_2Pt Function Block
The following table shows how:
The Status output indicates the calibration conditions of the inputs.
During calibration, the related Psn signal on the Out pin is zero.
Status Logic
Condition Status Psn Signal Comment
Block is OK. 0x0000 0–10000 Normal output of all Psn signals.
Block is not calibrated. 0x8001
Block is partially calibrated. 0x8002
Invalid setup/calibration. 0x8008
The following table shows how:
0*/0–10000**
*Calibration of an input sets its related Psn signal
to 0.
**A valid input has a related Psn signal of 0–10000.
The Fault output indicates fault conditions.
Any fault condition sets its related Psn signal on the Out pin to zero.
Fault Logic
Condition Fault Psn Signal Comment
Block is OK. 0x0000 0–10000 Normal output of all Psn signals.
Input value is too low. 0x8001
Input value is too high. 0x8002
0*/0–10000**
Short circuit. 0x8004
Open circuit. 0x8008
*Calibration of an input sets its related Psn signal
to 0.
**A valid input has a related Psn signal of 0–
10000.
6
11007136 · Rev BA · September 2011
Page 7

Configuration Settings

PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual
JS120_2Pt Function Block
Enter the JS120_2Pt page to change the JS120_2Pt function block’s configuration
settings.
When working with configuration settings for PLUS+1 compliant joysticks, note that:
Configuration inputs with a _Base suffix configure the joystick base.
Configuration inputs with a _Grip suffix configure the joystick grip.
JS120_2Pt Function Block Configuration Settings
Input Type Range Description
CalMode —— 0–3 Selects the CalMode (Calibration Mode) that sets the CalHi and CalLow values.
0—download values with the PLUS+1 GUIDE Service Tool. 1—capture values using autocalibration or directly download values with the PLUS+1 GUIDE Service Tool.
In autocalibration, you operate the joystick and the block captures values that fall within defined windows.
2—the controller uses the Default calibration values in the Memory page. 3—erases all calibration values.
RturnToNeut BOOL —— RturnToNeut (Return to Neutral) sets when the function block enables its Out signals after a controller startup,
calibration, or a Fault or Status condition. T—the block enables its Out signals only after all its inputs return to neutral. F—the block immediately enables its Out signals.
11007136 · Rev BA · September 2011
7
Page 8
PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual
JS120_2Pt Function Block
JS120_2Pt Function Block Configuration Settings
Input Type Range Description
LatchPFlt BOOL —— The function block sets a Status condition when it receives an invalid setup or calibration parameter.
The block disables the signal on the Out pin that is related to the abnormal parameter.
The LatchPFlt (Latch Parameter Fault) sets when the block enables the signal after the condition clears.
T—the block enables the Out signal only after you repower the controller. F—the block immediately enables the Out signal.
LatchInFlt BOOL —— The function block sets a Fault condition when it receives an invalid input.
The block disables the Out signal that is related to the abnormal input.
The LatchInFlt (Latch Input Fault) sets when the block enables the signal after the condition clears.
T—the block enables the Out signal only after you repower the controller. F—the block immediately enables the Out signal.
CalWindow —— 0–3000 The CalWindow (Calibration Window) sets the width of two calibration windows.
These windows center on the default CalHi and CalLow calibration values.
For more information, see About Calibration Windows and Default Calibration Values on page 10.
The default calibration values are set in the Memory page. They are the Default inputs to the two Non-Volatile
Memory Dynamic with Default components in this page.
During autocalibration, input voltages must be within these windows for the function block to capture them as
valid calibration values.
The CalWindow value is set as percentage of SnsrPwr.
1000 = 10.00%.
CalDetectTm —— 0–65535 The CalDetectTm (Calibration Detect Time) sets the time during autocalibration that input voltages must remain
in each calibration window for the function block to capture them as valid CalHi and CalLow calibration values.
1000 = 1000 ms.
Dband_Hi —— 0–4999 The Dband_Hi (Deadband High) sets the width of an upper deadband.
An input voltage within this band produces a 100% output.
This deadband extends below the CalHi calibration value.
The function block sets the width of the Dband_Hi as a percentage of the difference between the CalHi and
CalLow calibration values.
For more information, see About Calibration Values and Deadbands on page 12.
1000 =10.00%.
8
11007136 · Rev BA · September 2011
Page 9
PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual
JS120_2Pt Function Block
JS120_2Pt Function Block Configuration Settings
Input Type Range Description
Dband_Low —— 0–4999 The Dband_Low (Deadband Low) sets the width of a lower deadband.
This deadband extends above the CalLow calibration value.
An input voltage within this band produces a –100% output.
The function block sets the width of the Dband_Low as a percentage of the difference between the CalHi and
CalLow calibration values.
For more information, see About Calibration Values and Deadbands on page 12.
1000 = 10.00%.
FltDetectTm —— 0–65535 The FltDetectTm (Fault Detect Time) sets the time before an abnormal condition causes the function block to set
a Status or Fault condition.
1000 = 1000 ms.
11007136 · Rev BA · September 2011
9
Page 10
PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual
JS120_2Pt Function Block
About Calibration Windows and Default Calibration Values
The following graph shows the relationship between the default calibration values and the windows in which the function block captures calibration values during autocalibration.
10
The JS120_2Pt function block’s SnsrPwr is 5000 mV.
The JS120_2Pt function block’s default:
CalLow calibration value is 1000, or 10% (500 mV) of SnsrPwr.
CalHi calibration value is 9000, or 90% (4500 mV) of SnsrPwr.
The JS120_2Pt function block’s CalWindow (Calibration window) is 1000, or 500 mV
wide (10% of SnsrPwr).
(The Default values for CalLow and CalHi are set in the Memory page. The CalWindow value is set in the JS120_2Pt page.)
The 500 mV wide calibration windows center on the Default values for CalLow and
CalHi.
11007136 · Rev BA · September 2011
Page 11
PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual
JS120_2Pt Function Block
During autocalibration, an input voltage must be between:
250–750 mV to be captured as a CalLow calibration value.
4250–4750 mV to be captured as a CalHi calibration value.
11007136 · Rev BA · September 2011
11
Page 12
PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual
JS120_2Pt Function Block
About Calibration Values and Deadbands
The following graph shows the:
Formulas used by the function block to calculate low and high deadband width.
Relationship between the calibration values captured during autocalibration and the
width of the deadbands.
12
During autocalibration, the JS120_2Pt function block captured the:
CalLo calibration value at 700 mV.
CalHi calibration value at 4700 mV.
11007136 · Rev BA · September 2011
Page 13
PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual
JS120_2Pt Function Block
An input voltage that falls within the:
Dband_Low deadband produces a 0% output from the function block.
Dband_Hi deadband produces a 100% output from the function block.
11007136 · Rev BA · September 2011
13
Page 14
PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual
JS120_2Pt Function Block

MC ControllerInput Configuration

If you have an SC controller, see SC Controller—Input Configuration on page 17.
You can route the voltage needed by a joystick input though:
A MFIn (Multifunction Input) on your controller.
An AnIn (Analog Input) on your controller.
A DigAn (Digital/Analog input) on your controller.
You must configure the input that you use to accept a voltage input.

MC ControllerHow to Configure a MFIn

1. In the GUIDE template, enter the Inputs page.
2. Enter the MFIn page that routes voltage to the input.
3. Delete the route as shown in the preceding figure.
14
11007136 · Rev BA · September 2011
Page 15
PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual
JS120_2Pt Function Block

MC ControllerHow to Configure an AnIn

1. In the GUIDE template, enter the Inputs page.
2. Enter the AnIn page that routes voltage to the input.
3. Delete the route as shown in the preceding figure.
11007136 · Rev BA · September 2011
15
Page 16
PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual
JS120_2Pt Function Block

MC ControllerHow to Configure a DigAn

1. In the GUIDE template, enter the Inputs page.
2. Enter the DigAn page that routes voltage to the input.
3. Delete the route as shown in the preceding figure.
16
11007136 · Rev BA · September 2011
Page 17
PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual
JS120_2Pt Function Block

SC ControllerInput Configuration

If you have an MC controller, see MC Controller—Input Configuration on page 14.
You can route the voltage needed by a joystick input though:
A MFIn (Multifunction Input) on your controller.
A DigAn (Digital/Analog) input on your controller.
You must configure the input that you use to accept a voltage input.

SC ControllerHow to Configure a MFIn

1. In the GUIDE template, enter the Inputs page.
2. Enter the MFIn page that routes voltage to the input.
3. Delete the routes as shown in the preceding figure.
11007136 · Rev BA · September 2011
17
Page 18
PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual
JS120_2Pt Function Block

SC ControllersHow to Configure a DigAn

1. In the GUIDE template, enter the Inputs page.
2. Enter the DigAn page that routes voltage to the input.
18
3. Delete the routes as shown in the preceding figure.
11007136 · Rev BA · September 2011
Page 19
About the Para Input
PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual
JS120_2Pt Function Block
Use the Para input to apply a common set of parameters to multiple function blocks.
The preceding figure shows a Parameters page that outputs common, shared parameters to identical function blocks.
The preceding figure shows the contents of the Parameters page that applies the common, shared parameters to the function blocks.
You create this Parameters page yourself. How you implement parameter sharing determines the inputs, outputs, contents, and name of this page.
11007136 · Rev BA · September 2011
19
Page 20
PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual
JS120_2Pt Function Block
The preceding figure shows the changes made to a JS120_2Pt page to enable this page to accept common parameters through its Para input.
20
11007136 · Rev BA · September 2011
Page 21
PLUS+1 Compliant JS120 2Pt Joystick Function Block User Manual
JS120_2Pt Function Block
About the Name Space Feature
If you use this function block more than once in an application, you must change each

function block’s Name Space value to avoid compiler errors.

These function blocks allocate memory using memory names (“aliases”). Identical function
blocks have identical memory names. Identical memory names will cause a compiler error.
The Name Space value adds a unique prefix to each memory name to avoid memory allocation errors.
How to Enter a Name Space Value
1. In the PLUS+1 GUIDE menu bar, click the Query/Change button.
2. Click the function block’s page name to display the Edit Page window.
3. In the Edit Page window, enter a meaningful Name Space value.
4. Press /.
5. Repeat these steps to enter unique Name Space values for other identical function blocks.
11007136 · Rev BA · September 2011
21
Page 22
p
Products we offer:
Bent Axis Motors
Closed Circuit Axial Piston Pumps
and Motors
Displays
Electrohydraulic Power Steering
Electrohydraulics
Hydraulic Power Steering
Integrated Systems
Joysticks and Control Handles
Microcontrollers and Software
Open Circuit Axial Piston Pumps
Orbital Motors
PLUS+1™ GUIDE
Proportional Valves
Sensors
Steering
Sauer-Danfoss is a global manufacturer and supplier of high­quality hydraulic and electronic components. We specialize in providing state-of-the-art technology and solutions that excel in the harsh operating conditions of the mobile off-highway market. Building on our extensive applications expertise, we work closely with our customers to ensure exceptional performance for a broad range of off-highway vehicles.
We help OEMs around the world speed up system development, reduce costs and bring vehicles to market faster. Sauer-Danfoss—Your Strongest Partner in Mobile Hydraulics.
Go to www.sauer-danfoss.com for further product information.
Wherever off-highway vehicles are at work, so is Sauer-Danfoss.
We offer expert worldwide support for our customers, ensuring the best possible solutions for outstanding performance. And with an extensive network of Global Service Partners, we also provide comprehensive global service for all of our components.
Transit Mixer Drives
Members of the Sauer-Danfoss Group:
Comatrol
www.comatrol.com
Schwarzmüller-Inverter www.schwarzmueller-inverter.com
Turolla www.turollaocg.com
Hydro-Gear www.hydro-gear.com
Sauer-Danfoss-Daikin www.sauer-danfoss-daikin.com
Please contact the Sauer-Danfoss re
Local address: Sauer-Danfoss Inc. 3500 Annapolis Lane North Minneapolis, MN 55447, USA Phone: +1 763 509-2000 Fax: +1 763 559-5769
Sauer-Danfoss (US) Company 2800 East 13th Street Ames, IA 50010, USA Phone: +1 515 239-6000 Fax: +1 515 239-6618
Sauer-Danfoss GmbH & Co. OHG Postfach 2460, D-24531 Neumünster Krokamp 35, D-24539 Neumünster, Germany Phone: +49 4321 871-0 Fax: +49 4321 871 122
resentative nearest you.
Sauer-Danfoss ApS DK-6430 Nordborg, Denmark Phone: +45 7488 4444 Fax: +45 7488 4400
Sauer-Danfoss-Daikin LTD Shin-Osaka TERASAKI 3rd Bldg. 6F 1-5-28 Nishimiyahara, Yodogawa-ku Osaka 532-0004, Japan Phone: +81 6 6395 6066 Fax: +81 6 6395 8585
11007136 ● Rev BA ● September 2011
www.sauer-danfoss.com