10.1 Data sheet iSave 50-70 - (521B1378)) ....................................................23
10.2 Start and stop procedures (180R9213). ..................................................45
10.3 Membrane cleaning of the RO system with iSave unit (180R9214) . ......................51
10.4 APP pumps and iSave overload protection(180R9372)...................................57
10.5 Hose assembly and installation (180R9084) .............................................67
10.6 iSave part list 50-70 (521B1428) .........................................................75
10.7 Operating- and maintenance instruction, electric motor (180R9230).....................87
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
3
Operating guide | iSave 50 - 70
1. ValidityDocument information and copyright
Installation, Operation and Maintenance
Manual.
Danfoss can accept no responsibility for possible
errors in the manual and instructions. Danfoss
reserves the right to alter its products without
notice. This also applies to products already on
order provided that such alterations can be
made without subsequential changes being
necessary in specifications already agreed.
All rights reserved. Contents provided herein
must neither be distributed, copied, reproduced,
edited or processed for any other purpose, nor
otherwise translated or published without
Danfoss’ express written consent.
PUMP
Type iSave 50 ERD
Code no. 180FXXXX
Serial no. XXXXXX02-XXX
MADE IN DENMARK
Danfoss A/S, 6430 Nordborg, Denmark
This manual is valid for iSave 50 -70
Code No./DescriptionSerial no.
180F7020
iSave 50 without motor
180F7021
iSave 70 without motor
180F7038
iSave 50 Vertical
(IEC motor)
180F7023
iSave 50 horizontal
(IEC motor)
180F704 0
iSave 70 vertical
(IEC motor)
180F7025
iSave 70 horizontal
(IEC motor)
XXXXXX02-XXX
XXXXXX02-XXX
XXXXXX02-XXX
XXXXXX02-XXX
XXXXXX02-XXX
XXXXXX02-XXX
The serial number is referring to the Serial no. on
the product label. The digits shown (02) indicate
the version number of the pump.
This document is only valid for ERD version 2
and upwards.
4
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Operating guide | iSave 50 - 70
2.Introduction2.1 General
iSave is manufactured by Danfoss A/S, and is sold
and marketed by a net of authorised distributors
world wide.
This manual contains the necessary instructions
for the installation, operation and service of the
iSave.
All personnel who are responsible for the
operation and maintenance of the iSave unit
must read and fully understand these
instructions, especially the section “Safety”
before:
• Transporting of the iSave unit.
• Lifting the unit.
• Installing the iSave unit on a frame.
• Connecting the iSave unit to the fluid
system.
• Connecting the electrical motor and
instrumentation.
• Commissioning the unit.
• Servicing the iSave unit, mechanics and
electrics.
• Decommissioning the iSave unit.
Ensure that these instructions are always readily
available to all personnel concerned.
2.3 Symbols
Indicates something to be noted by
the reader.
Indicates a situation which will or
couldresult in damage to the iSave
and its function.
Indicates a situation which will or
could result in personal injury and/or
damage to the iSave.
Electrical hazard. Indicates a high-voltage
warning
This manual is intended for use by personnel
with qualified training and experience in the
operation and maintenance of a Sea Water
Reverse Osmosis (SWRO) or Brackish Water
Reverse Osmosis (BWRO) system.
2.5 Country specific information
2.5.1 United Kingdom
Danfoss Ltd.
22 Wycombe End
HP9 1NB Beaconsfield
United Kingdom
2.6 Additional technical documents
Below documents are not present in this Operating guide. Please contact Danfoss.
Document nameContent
Service guide: 180R9387
Disassembling and assembling
Design guide: 180R9367
Pipe connection
Guide line: 180R9371
Pressure safety valve in SWRO systems
Guide line: 180R9370
Review sheet P&ID
Description of how to disassemble and assemble the iSave
Design guide on how to make har piping
with Victaulic clamps
Guide line on how to evaluate if a safty
valve is needed in a SWRO system
Detailed description about the need for
each individual component in the preferred
P&ID
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
5
Operating guide | iSave 50 - 70
3. Safety3.1 General
The iSave must not be used for other
purposes than those recommended and
specified without first consulting your local
iSave distributor.
This manual must be read and completely
understood by the responsible specialist
personnel prior to installation and
commissioning.
Use of this manual does not relieve operation
and maintenance personnel of the responsibility
of applying normal good judgment in the
operation and care of this product and its
components.
This manual must be available to all personnel
concerned at the site at all time.
An iSave must always be installed and used
in accordance with existing national and local
sanitary and safety regulations and laws. It is the
responsibility of the safety officer or the chief
operator to assure compliance with all local
regulations that are not taken into account in this
manual.
The iSave is a rotating machine that typically
operates at high pressure.
• Improper installation can cause fatal
injuries.
• The iSave must not operate outside the
application range.
• During the initial start-up, slowly raise the
pressure of the system and adjust the
over-pressure protection equipment for
proper limit settings.
• Make sure that the pressure is released
from the iSave before the iSave is
disconnected from any pipe or hose
connections.
• Make sure that the iSave can be drained
without injuring anyone and without
contaminating nearby equipment or the
environment.
• Before intervening in the iSave/system,
the power must be shut off and the
starting device must be locked. When
intervening in the iSave unit, follow the
instructions for Service/Maintenance,
chapter 8.
• A failure not to follow the instructions can
result in personal injury and/or damage to
the iSave. It will also invalidate the
warranty.
Always wear suitable safety and lifting
equipment when handling the iSave.
• Bolt the iSave properly to the base before
start-up to avoid personal injury and/or
damage to the iSave.
• The pipe connections to the iSave must be
stress-free mounted, securely fastened to
the iSave and well supported. Improper
installation will or could result in personal
injury and/or damage to the iSave.
• Proper installation and care of shutdown
devices and over-pressure protection
equipment is essential.
• All electrical installation work must be
carried out by authorised personnel in
accordance with EN60204-1 and/or local
regulations.
• Install a lockable circuit breaker to avoid
inadvertent starting. Protect the motor and
other electrical equipment from overloads
with suitable
• equipment.
• The electric motors must be supplied with
adequate cooling ventilation.
• The iSave must never run dry. Dry running
produces heat and will cause damage to
internal parts.
• If the iSave does not function satisfactorily, contact your local iSave distributor.
Use of this manual does not relieve
operation and maintenance personnel of
the responsibility of applying normal
good judgment in the operation and care
of this product.
3.2 Intended use
The iSave is designed for use as energy recovery
device in Sea Water Reverse Osmosis (SWRO) or
Brackish Water Reverse Osmosis (BWRO) system.
The iSave must not be used for other purposes
than recommended and quoted for without
consulting your local iSave distributor.
3.3 Application range
For application range see data sheet 521B1378
available in appendix 10.1.
Applications not suitable for the iSave
can cause damages to the iSave unit,
with risk of personal injury.
6
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Operating guide | iSave 50 - 70
3.4 Preferred system design
Danfoss recommends building systems with
a high degree of safety. Our preferred system
design can be found in the data heet in appendix
10.1.
• It is always the system builders’
responsibility that the system design does
not cause any form of hazard and are
adapted to local regulations.
• Proper installation and care of shutdown
devices and over-pressure protection
equipment is essential.
4. Arrival inspection,
handling and storage
4.1 Arrival inspection
The iSave is packed in a wood container.
The iSave ports connector are protected by
plastic caps that protect the iSave against dust
and particles. Do not remove the caps before the
system have been flushed and the iSave can be
installed.
Remove all packing materials immediately after
delivery. Immediately check the shipment for
damage on arrival and make sure that the name
plate/type designation is in accordance with the
packing slip and your order.
In case of damage and/or missing parts, a report
should be drawn up and presented o the carrier
at once.
The identification label on the iSave states the
specific type, the serial number and the code
number of the iSave; see fig. below.
The last three digits of the Serial No. indicate the
week and year of production.
PUMP
Type iSave 50 ERD
Code no. 180FXXXX
Serial no. XXXXXX02-XXX
4.2 Return to the supplier
Flush the iSave with clean water. Drain the iSave
and plug the port connections with a cap/cover.
MADE IN DENMARK
Danfoss A/S, 6430 Nordborg, Denmark
4.3 Transport and Handling
•
• Personnel involved in lifting and
transportation of the equipment must be
trained in proper handling and safety
procedures.
• Observe the local regulations regarding
lifting.
• Use suitable, permitted lifting equipment.
• The iSave (set) could slip the lifting
arrangement.
• Be aware of individuals located in the
operation area while lifting the
component.
The weight of the iSave including electric
motor can be found in the datasheet.
All parts weighing more than 20 kg (44 lb)
must be lifted using lifting slings and suitable
lifting devices, e.g. an overhead crane
or fork lift.
Do not use connections/nozzles for
lifting. Do not use only one sling! Make
sure that the load is balanced before
attempting the lift.
Pack the iSave into a suitable container and make
sure that it is suitably fastened to the container.
Please coordinate the shipment with your local
authorized distributor or contact anfoss direct to
obtain a return shipping address.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
When lifting the ERD without motor use
the lifting eye
s.
When you have finished using the lifting eyes,
remove them to prevent corrosion.
7
Operating guide | iSave 50 - 70
When the iSave is mounted with an electric
motor (horizontal), it must not be lifted in the
lifting eye. An iSave assembled with motor
(horizontal) must be handled by using two slings
around the unit. One sling must be attached to
the electric motor and one sling
around the iSave. Make sure that the unit/load is
balanced before lifting. The centre of the mass
may vary.
Some motors and pumps have specific lifting
eyes.
Do not use connections/nozzles for lifting!
Always use two slings.
Lifting the iSave with electric motor (vertical):
The two lifting belts around the bell housing
before lifting the unit.
Lift the iSave unit with only one fastening point.
Incorrect lifting can result in personal injury and/
or damage of the unit.
4.4 Assembly iSave to electric motor
A: Elastic coupling
B: Bell housing
C: iSave shaft
D. iSave flange
1. Mount the coupling flush or maximum 1
mm offset from the iSave shaft end. Ensure
an air gap between coupling parts of 3-5
mm (0.12-0.2 inch).
2. Mount the bell housing on iSave. Secure
nuts with the right torque.
3. Measure the longest distance “A” from top
of bell housing to the button of coupling
claw.
4. Mount the coupling on motor shaft. Ensure
the coupling and motor flange are not in
contact with each other.
5. Measure from motor flange to the top of the
coupling. That measurement “B” shall be 3-5
mm (0.12-0.2 inch) shorter than the measure
me nt “A”.
(“A” and “B” can be found on the next page).
8
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
6. Adjust respectively, verify the measure ment, and secure both couplings with the
right torques on the locking screws (see
coupling operation & mounting instruc
tion).
7. Mount the elastic gear ring and mount
the bell housing/iSave on the motor.
After mounting it must be possible to
move the elastic gear ring 3-5 mm (0.12 -
0.2 inch) axial “C”. The check can be done
through the inspection hole of bell
housing. Secure flange bolts with the
right torque.
231
If alternative mounting is desired, please contact
Danfoss High Pressure Pumps.
Choose proper tolerances to ensure an easy
mounting of the elastic coupling without use of
tools.
Please take care to observe the recommended
length tolerances of the chosen coupling, as an
axial force on the pump will damage the pump.
(“C” can be found on the drawing below).
Thread sizeM5M6M8M10
Torque (Nm)24.81017
Details on how to install iSave 50/70 on Danfoss
vertical and horizontal frame can be found in the
Service guide 180R9387.
4.5 Storage
When each iSave is tested before shipment in
demineralized water. When tested the iSave is
emptied and “plugged”, this will prevent frost
damages.
The storage temperature is is:
-40 °C to +70 °C (-40°F to 158 °F) –
provided that the iSave is drained of fluid and
stored “plugged”.
Frost protection is required if the iSave is not
completely drained of fluids at temperatures
below 1 °C .
Storage of iSave that have been in operation:
For shorter periods of storage flush the iSave
with permeate and store.
For long term storage (more than 2 months)
Danfoss recommends servicing the product
and clean any biological growth of the
surfaces. Store the pump dry witout water
inside.
3-5 mm
Danfoss recommends using DOWFROST from
DOW Chemical Company or Chillsafe mono
propylene glycol from Arco Chemical Company.
For further information on anti-freeze media,
please contact Danfoss High Pressure Pumps.
The iSave is NOT delivered frost-protected
from the factory.
Only remove caps from the openings of the
iSave at the time of installation.
4.6 Outdoor Storage
For outdoor storage cover the iSave (set) with
waterproof material.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
9
Operating guide | iSave 50 - 70
5. Technical data and
design review
1: 3” Victaulic connections
2: Shaft
3: Low pressure shaft seal
4: Port flange
6: Valve plate
7: Cylinder drum
9: Port plate (brine)
10: Port pllate (sea water)
11: Vanes
12: Coupling
13: Intermediate flange
14: Rotor
15: Rotor element
16: Sealing plate
17: Stator
18: Motor end flange
5.1 Design details
5.2 Sound level of the iSave
The A-weighted sound pressure level @ 1m,
L
is for the iSave including the iSave motor.
PA, 1M
Measurement are according to EN ISO
3744:2010. The test is made under following
conditions:
1. iSave and electrical motor mounted on
Danfoss base plate.
2. Baseplate is isolated from concrete ground
by rubber vibration dampers.
3. Flexible hoses are used on high pressure
and low pressure sides of the iSave.
4. Rotation speed is max. rpm
5. System pressure max. allowable working
pressure and a booster pressure of 3 barg.
Influences
Since the iSave is mounted on a base plate and
connected to the electromotor by a bell housing,
the noise level can only be determined for the
complete unit (system).
It is therefore important that the iSave unit is
mounted correctly on a frame with dampers
to minimise vibrations and noise.
Alternativamente, emplee acoplamientos Victaulic®
flexibles en la tubería rígida.
The noise level is influenced by:
• The speed of the iSave. High speed creates
more noise than low speed.
• Rigid mounting of the iSave baseplate
generates more noise than flexible
mounting
• Pipe mounting directly to the iSave
increases the noise level compared to
flexible hoses.
• Higher pressure provides higher sound
level.
5.3 Materials
All critical parts of the iSave are made of
super-duplex 1.4410/UN S32750/1.4462/
UN S32205/S31803 or the like.
Non-critical parts that are not in contact with sea
water are made of AISI 316.
The shaft to the electrical motor is sealed by
a standardised mechanical seal.
It is also strongly recommended to use highpressure flexible hoses between the hard piping
in the RO plant and the iSave.
See “Hose assembly and installation” 180R9084 in chapter10.5 and Guide line Pipe
connections 180R9367.
Alternative use multiple flexible Victaulic®
couplings on the hard piping.
10
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Operating guide | iSave 50 - 70
5.4 Temperature and corrosion
The chart below illustrates the corrosive
resistance of different types of stainless steel
related to NaCl concentration and temperature.
º
80
C
Duplex
70
60
50
316L
40
30
20
100
1000
1601600
Depending on the NaCl concentration, the fluid
temperature must be between:
+2 °C y 50 °C (35,6 °F y 122°F).
Super Duplex
10 000
16000
100 000
160000
CI
ppm
NaCI
ppm
-
In order to minimise the risk of crevice
corrosion, always flush the iSave
according to the specified start/stop
procedure.
5.5 Dimensions and weights
For dimensions and weights please refer to the
iSave datasheet. See appendix 10.1
5.6 Electrical motor data
See datasheet in appendix 10.1 and “Operating
and Maintenance instructions, electric motor” in
appendix 10.7
5.7 How does the iSave work?
Figure 5.1 shows a section view of the iSave.
The iSave consists of a rotating isobargic
pressure exchanger and a positive
displacement pump, also called booster
pump. The rotation speed of the pressure
exchanger and the pump is exactly the
same, as they are driven by the same electric
motor.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
11
Operating guide | iSave 50 - 70
5.8 Seawater quality
5.81 Pre-filtration
It is important that the incoming water is filtered
properly to assure optimum service life of the
iSave. A true graded density melt-blown depth
filter cartridge rated at 3 μm is therefore
recommended. Poor pre-filtration of the feed
water will result in reduced service life of the
iSave.
The iSave may request a different pre-filter of the
seawater than the HP pump and other
omponents in the RO system.
It is important to use a proper filter housing that
allows a good seal between housing and filter
cartridge. If there is a high risk of water by-pass it
is recommended to use a second stage filter
solution.
As the various filters on the market differ greatly,
Danfoss High Pressure Pumps recommends using
cartridges with consistent, reliable performance
and high efficiency, in which fibres are blown
continuously onto a central support core.
Danfoss High Pressure Pumps does not
recommend cartridges requiring any type of
binders or resins.
Filters can be purchased from Danfoss High
Pressure Pumps.
5.8.3 Chemicals
The iSave can be flushed with biocide like the
membranes. The biocide must be compatible
with the materials used in the iSave.
iSave material can be found in the parts list,
appendix 10.6.
5.8.4 Initial start up and flushing
Prior to the initial start-up, all piping associated
with the iSave unit should be thoroughly flushed
to assure that no impurities enter the iSave.
Inadequate pre-flushing will strongly affect the
life of the iSave and may lead to its eventual
breakdown.
It is essential that the water used for the final
pre-flush is pre-filtered to a level described in
chapter 5.8
It is recommended to disconnect all connections
to the iSave and to thoroughly flush the piping
before the iSave is connected to the inlet and
outlet connections.It is recommended to install
temporary basket strainers at both inlets to
the iSave during the initial start-up and
commissioning.
Strainers do not eliminate the need for
thoroughly pipe flushing before commissioning.
Also see “Instruction for start and stop of
the SWRO with iSave unit” - 180R9213 in
appendix 10.2.
5.9 Initial start up and settings of safety
equipment
The system designer is responsible to design the
equipment according to the local regulations where
the equipment is running. According to PED
2014/68/ EU a risk assessment must be made to
identify and evaluate hazards which apply to his
equipment on account of pressure.
For more information on the importance of
proper filtration, please consult our
publication “Filtration”,
AI317041322125en-000201 which also will
provide you with an explanation of filtration
definitions and guidance on how to select the
right filter.
5.8.2 A ir bubbles
Large bubbles in a pressurised RO system can
result in damage to piping and equipment. All air
must be bleed from both the LP and HP before
the RO system is pressurised. Special
consideration should also be given to air bubbles
in feed flow, continuously fed into the HP pump
and iSave.
Where under reasonable foreseeable conditions, the
allowable limits could be exceeded, the pressure
equipment must be fitted with, or provision made
for fitting of a suitable protective device.
Dischage pressure on the pump is generated only
by the restriction in the pipelines, valves and
membranes.
The pump can build up pressure that will exceed
the mechanical strength of the membrane
vessels, pipes and other accessories.
The pressure rise can be fast and may exceed the
response time for electrical safety equipment,
like pressure switch and control loop.
12
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Operating guide | iSave 50 - 70
To prevent such over-pressurisation, appropriate relief valves should be used and procedures should be implemented to safeguard
the HP and LP sides of the iSave and/or the
RO system.
5.12 High pressure remains after shutdown
The HP line of the RO system equipped with an iSave
can remain pressurised for a long time after
shutdown. Pressure decreases as water slowly leaks
through the iSave. If more rapid system
depressurisation is required, the system should be
bled through a suitable valve on the HP concentrate
line.
trado HP.
5.10 Flushing
RO membranes require periodic flushing to
limit biological fouling.
There are two types of flushing: feed water
(Seawater) flush and fresh water (Permeate)
flush.
Regardless of the flush water used, the water
must be pre-filtered to the level described
in chapter 5.8. All parts of the iSave must be
flushed, i.e. LP- and HP flow channels.
Follow the guide line 180R9213 “Start and stop of
the SWRO with iSave in appendix 10.2.
It is required to flush with permeate:
• After chemical treatment
• For stop more than 1 day the iSave must be
rotated during permeate flush
• Before long time shut down
It is required to flush with fresh sea water prior to
every shut down.
Special attention should be given to the
pressure in the HP line (7) as the iSave may
start to cavitate when it runs at high speed
and the pressure in the P line (7) drops below 2
bargs. This can be avoided by reducing the
speed of the iSave and keeping the pressurein
the HP line at the minimum of 2 barg.
At this low pressure the iSave may only
run for a maximum of 10 minutes.
Always check the pressure in the high-pressure
lines before making service in the HP lines or
pressurised equipment.
5.13 Over-pressurisation caused by low
pressure isolation
If the low-pressure side of the iSave is blocked
and the iSave is exposed to high-pressure, there
is a risk that the iSave or the LP piping could be
damaged by over-pressurisation.
To prevent such over-pressurisation, appropriate
relief valves should be used and procedures should
be implemented to assure that the HP of the iSave is
depressurised prior to the isolation of the LP side..
5.14 Over-pressurisation caused by the
high-pressure pump.
Discharge pressure on the pump is generated
only by the restriction in the pipelines, valves
and membranes. The pump can build up
pressure that will exceed the mechanical
strength of the membrane vessels, pipes
and other accessories. The pressure rise can be
fast and may exceed the response time for
electrical safety equipment, like pressure
switch and control loop.
Failing to flush the iSave with fresh water before
extended shutdowns may result in extensive
biological growth and cause corrosion in the
iSave and other equipment in the RO system.
5.11 CIP or membrane cleaning
The purpose of membrane cleaning is to reduce
scaling and fouling in the membranes. For optimal
performance specific chemicals are required,
depending on the cause of the pollution. After
chemical treatment the system must be
flushed with permeate.
The flush water coming out of the membranes may
consist of a large amount of suspended inorganic
particles. It is important to assure that hese particles
must not enter the iSave as the waste product of
flushing exceed the iSave filtration.
Also see instruction “Membrane cleaning of
RO system with iSave unit” in appendix 10.3.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
To prevent such over-pressurisation, appropriate
relief valves should be used and procedures should
be implemented to assure that the HP of
the iSave is protected against excess pressure.
5.15 Explanation of P&ID set-up
See data sheet in appendix 10.1.
13
Operating guide | iSave 50 - 70
!
6. On-site installation6.1 Design details
For safety instruction see chapter 3.
6.2 Installation and alignment
The figure below illustrates the major iSave
components.
An unlocked bolt can result in personal injury
and/or damage to the iSave
Misalignment of the base frame to the iSave may
cause stress and/or damage.
6.3 Orientation
The iSave can be mounted horizontally and
vertically.
When mounted vertically, the electric motor
must be placed above the iSave.
6.4 Piping and joints
Piping material and schedule is of high
importance. The strength of the Victaulic®
connections is influenced by the material used
for both the Victaulic® clamps and the hard
piping.
The hard piping and connections used must
be of proper design and must be installed in
accordance with the manufacturer’s
recommendations.
Hard piping to the iSave must be properly
aligned to avoid stress on the iSave port
connections.
Pipe connection must be aligned as
shown in the figures next page. Don’t use the
iSave as a strain for hard piping.
The iSave is connected to the electric motor
by the bell housing and a flexible coupling.
If not using Danfoss base frame both the
iSave and the motor must be supported
without applying stress/load to the bell
housing.
Danfoss provides the iSave with a base
frame and support brackets. Although the
base frame is of a sturdy design, it can flex
or bend when it is bolted to the foundation.
The base frame thus requires a solid
foundation such as concrete or rigid steel
frame. The base frame itself must be aligned
to avoid bending caused by bolting to an
uneven foundation.
Incorrect piping alignment
A rigid foundation for the iSave assembly is
important, and must fulfil Eurocode 2:
EN1992-1-1, and the iSave assembly must
be bolted to the foundation with M12 bolts.
The bolts used must be of proper design
and must be installed in accordance with
bolt manufacturer’s recommendations.
To reduce noise it is recommended to use
resilient mounts between the baseplate and
The hard piping and connections used must
be of proper design and must be installed in
accordance with the manufacturer’s recom-
mendations.
the foundation. Make sure that the bolts are
properly locked and will stay locked over time.
A failure to comply with this will or may result
in personal injury and/or damage the iSave.
14
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Operating guide | iSave 50 - 70
Misalignment of the hard pipes may place
stress on the iSave port connections and may
damage the iSave.
6.5 Mounting of coupling
The figure below illustrates how to mount the
flexible coupling between the iSave and to
connect it to the electric motor..
100 NM ± 10 NM
Min. 3 -5 mm air space
A
PUMP
Type iSave 50 ERD
Code no. 180FXXXX
Serial no. XXXXXX02-XXX
MADE IN DENMARK
Danfoss A/S, 6430 Nordborg, Denmark
When connecting to the power supply, check the
direction of rotation. The rotation can only be
checked with water connected and iSave
bleeded. This can be made by:
1. Looking at the fan in the end of the electric
motor.
2. Removing the plug in the bell housing and
watch the rotation of coupling.
3. Before assembling the iSave on the electric
motor, check the rotation of the shaft on the
electric motor.
C
B
A: Flexible coupling
40 NM ± 4 NM
B: Bell housing
C: Motor shaft
Any axial and radial load on the shaft must be
avoided.
6.6 Accessibility
With respect to the service and replacement
of the complete iSave unit, it is recommended to
maintain sufficient space around the unit.
The space must be sufficient enough to allow for
safe lifting of the equipment, with no risk for
personal injury and/or damage to the iSave.
6.7 Drives
6.7.1 Electric motor
The iSave must only be driven by an electric
motor.
Special attention has to be on NON
PROTECTED - FREE ROTATING shaft on
the electric motor. Ignorance will or
could result in personal injury.
Running the iSave in the wrong direction for
more than a few minutes can cause unintended wear on the iSave. If the electric
motor is running at a lower speed, extra care
must be taken to ensure that the electric
motor is NOT overheated. External cooling
may be necessary.
6.7.3 Starting torque for the iSave
Because of the inertia and stick-slip friction of the
iSave internal parts, the torque may exceed the
maximum allowable operation torque for the
iSave when the speed is ramped up from zero to
maximum.
It is required to use a VFD. See Danfoss guide line
180R9372 “APP pumps and iSave overload
protection”.
Using anything other than an electric motor
can lead to an irreparable fracture of the
iSave’s internal parts.
6.7.2 Speed control
The rotation speed on the electric motor can
be controlled by a VFD. The VFD must be able to
operate at constant torque over the whole range
of speed. The direction of rotation can be seen
on the identification label.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
15
Operating guide | iSave 50 - 70
7. Commissioning, start-up and shutdown
6.7.4 Torque overload protection on the
iSave
The electric motor and iSave must always be
protected against overload.
As continuously operation the maximum
torque on the iSave must be monitored.
The electric motor must be shut off if the
maximum torque of the iSave exceeds the
defined limit.
If more electric motors are powered by the
same VFD, each electric motor must be
equipped with “torque limit equipment” to
protect the iSave against overload.
Below are examples of equipment which
can measure the load on the electric motor
or limit the torque on the iSave.
7.1 Safety regulations
The operator ensures that all inspection and
installation work is performed by authorised,
qualified specialized personnel who are
thoroughly familiar with the manual..
• Before starting up the iSave and the
high-pressure pump, make sure that the
following requirements are met:
• The iSave has been properly connected to
the electric power supply and is quipped
with all protection devices in accordance
with EN 60204-1
• Check that all motor protections are
properly set.
• All safety equipment, auxiliary equipment
and connection required are properly
connected and operational.
• Check all bolts in all connections and in the
foundation of the iSave and the pumps.
7.2 Support
Danfoss A/S offers commissioning and service at
system manufacturer’s location.
Rated quotes are offered upon request.
1. VFD with integrated current monitoring
relays.
2. External current monitoring relays suitablefor VFD control.
The electric motor and iSave must always be
protected against overload.
See Danfoss guide line 180R9372 “APP pumps
and iSave overload protection” in the appendix
10.4.
If torque exceeds the maximum operation
torque, it may lead to an irreparable fracture of
the iSave’s internal parts.
7.3 Commissioning
Before starting up the iSave and the highpressure pump, make sure the following
requirements are met:
• All pipes are flushed, free from debris and
full of water.
• The iSave has been bled and is full of
water.
• At pressure lower that 10 barg, check the
system for leakage.
Slowly raise the pressure in the system and set
all pressure switches to the correct limit and
continually check all connections.
• If pressure relief valve is present, set
pressure relief valve on both low and
high-pressure at the maximum system
pressure.
• Check high-pressure hoses for proper
assembly and inspect for external leakage
for all connections.
• At low pressure, start the iSave and check
direction of rotation.
• “Start and stop procedure” Guide line
180R9213. - appendix 10.2.
16
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Operating guide | iSave 50 - 70
8. Service/Maintenance8.1 Safety regulations
The operator ensures that all maintenance,
inspection and installation work is performed
by authorised, qualified specialist personnel
who are thoroughly familiar with the manual.
Before intervening in the iSave/system:
• The power must be shut off and the main
switch must be locked.
• The pressure in the high-pressure lines
must be drained to the low-pressure side.
• The water in all connected pipes must be
drained.
Always use suitable safety and lifting equipment when handling the iSave, and follow the
instructions in chapter 4.3.
• Assure correct settings of safety equipment before start-up.
• When the system is re-started after
service and maintenance follow the
instruction in chapter 8 and in “Start and
stop procedures” in guide line 180R9213
in appendix 10.2.
Three months after commissioning:
1. Re-check bolts in the foundation and the
base plate of the iSave and tighten the
bolts to specified torque if necessary.
2. Re-check alignment of the iSave base
plate and iSave.
3. Visually inspect all pipe connections/
couplings for external leakage.
4. Re-check bolts in all pipe connections/
couplings and tighten the bolts to
specified torque if necessary.
1. Replace filters if necessary.
2. Clean the filter housing and install the new
filter. Make sure no debris enters the
system.
3. Audibly inspect the iSave assembly. If there
is irregular sounds or vibration inspect the
internal parts of the iSave and replace if
necessary.
Half year:
1.
For vertical mounted electric motor
lubricate motor bearings.
8.2 Support
Danfoss A/S offers commissioning and service
at the system manufacturer’s location.
Tates/quotes are offered upon request.
8.3 Maintenance schedule
The schedule of preventive maintenance below
will help ensure that the iSave provides years of
trouble-free performance.
One day after commissioning:
1. Re-check bolts in the foundation and the
base plate of the iSave and tighten the
bolts to specified torque if necessary.
2. Visually inspect all pipe connections/
couplings for external leakage.
3. Re-check bolts in all pipe connections/
couplings and tighten the bolts to
specified torque if necessary.
1. Replace filters if necessary.
2. Clean the filter housing and reinstall
filters. Make sure no debris enters the
system.
Annually:
1. Re-check bolts in the foundation and the
baseplate of the iSave and tighten the
bolts to specified torque if necessary.
2. Re-check alignment of iSave base plate
and iSave.
3. Visually inspect all pipe connections/
couplings for external leakage.
4. Re-check bolts in all pipe connections/
couplings and tighten the bolts to
specified torque if necessary.
1. Replace filters if necessary.
2. Clean the filter housing and nstall the new
filter. Make sure no debris enters the
system.
3. Visually inspect iSave coupling and
replace if necessary.
4. Audibly inspect the iSave assembly. If
there is irregular sounds or vibrations
inspect the internals parts of the iSave
and replace if necessary.
5. Check power consumption. If there are
irregular parts of the iSave and replace if
necessary.
6. Lubricate motor bearings.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
17
Operating guide | iSave 50 - 70
8.4 Recommended service intervals on
internal parts
Se below table.
For detailed information on parts see Service
guide 180R9392 Parts list.
Tool kit
Screw and seal kit32.000 hours26.000 hours
Shaft seal kit32.000 hours26.000 hours
Coupling kit56.000 hours56.000 hours
Port plate kit (PE), iSave 50
32.000 hours26.000 hours
Port plate kit (PE), iSave 7032.000 hours26.000 hours
Vane kit (8 pcs)
Valve kit, Pressure exchanger32.000 hours26.000 hours
Rotor element and sealing plates kt32.000 hours26.000 hours
8.5 Lubrication of bearings in electric
motor
Motors with a re-greasing system must be
lubricated with high quality lithium complex
grease, NLGI grade 2 or 3 with a temperature
range between -40 °C to 150 °C.
For electric motors in vertical mount; grease
every 6 months.
For electric motor in horizontal mount;
grease every 12 months.
If the motor has increased vibrations or
sound check the bearings.
Follow manufacturer’s recommendations for
electric motor service and maintenance, see
appendix 10.7.
18
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Operating guide | iSave 50 - 70
9. Trouble-shooting9.1 Safety regulations
Before intervening in the iSave/system:
The operator ensures that all inspection and
installation work is performed by authorised,
qualified specialist personnel who are
thoroughly familiar with the manual.
• The power must be shut off and the
starting device be locked.
• The pressure in the high-pressure lines
must be drained to lowpressure side.
• The water in all connected pipes must be
drained.
The numbers in () correspond to the preferred system design and P&ID (see data sheet)
ProblemPossible causeAction
VFD cannot start the iSave at initial start-up VFD is not designed for constant torque
VFD cannot deliver sufficient start torque
Ramp-up settings in the VFD are not correct. VFD is tilting
Choose a VFD that is designed for constant
torque
Choose a VFD that is designed for sufficient
start torque. See guide line 180R9372
Set ramp-up parameters correct. See guide
line 180R9372
Valve (9) is closedOpen valve (9)
Start the iSave only when the pressure in
the HP line is low
Clean or change membranes
Torque on iSave is too high during operation
Pressure in the HP line (5) is too high
Pressure difference from HP-out (5) to HPin (10) is too high
Debris in the booster pump or iSaveClean the system
Wear in the booster pump or iSaveRepair or change the parts
Design of the basic plant does not fit the
performance of the iSave
Change design to fit the iSave performance
Permeate production is too low (17)Valves (6), (7), (8) or (16) are leakingRepair or change valve(s)
Internal leakage in iSaveRepair iSave
HP pump flow (2) is too smallCorrect speed on the HP pump
Check the HP pump and repair if necessary
Pressure on the membranes (5) is too high
Fouling on the membranesClean the membranes
Mixing in the iSave is too highCheck flow on LP-in (12) and adjust flow
Flow out of the iSave is too low and causes
a recovery rate that is too high
Check speed on iSave and change if necessary
Booster pump in the iSave is worn out.
Perform service on the VP
Pressure on the membranes (5) is too low
Valves (6), (7), (8) or (16) are leakingRepair or change valve (s)
Internal leakage in iSaveRepair iSave
Pressure on the membranes (5) is too lowIncorrect speed on the HP pump
Check the HP pump and repair, if necessary
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
19
Operating guide | iSave 50 - 70
20
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Appendices
Energy Recovery Device
iSave 50-70
Appendices - Installation, Operation
and Maintenance Manual
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Data sheet | iSave 50 and iSave 70
1. General informationEnergy Recovery Devices (ERD) are used in
reverse osmosis (RO) systems to recycle the
energy held in discharged brine from the
membranes. Thus, iSave 50 and iSave 70 are
designed for use with low viscosity and corrosive
fluid such as sea water.
The Danfoss iSave Energy Recovery Devices all
consist of an isobaric pressure exchanger and a
positive displacement pump combined into one
compact unit. The high-pressure booster pump
is based on the vane pump principle enabling a
very light and compact design. The vane pumps
are fixed displacement pumps in which the flow
is proportional to the number of revolutions
(rpm) of the driving shaft – enabling flow control.
Speed control is made by a VFD. The iSave design
ensures lubrication of the moving parts by the
fluid itself.
1. 3” Victaulic connections
2. Shaft
3. Low pressure shaft seal
4. Port flange
6. Valve plate
7. Cylinder barrel
9. Port plate (brine)
10. Port plate (sea water)
11. Vane s
12. Coupling
13. Intermediate flange
14. Rotor
15. Rotor element
16. Sealing plate
17. Sta t or
18. Motor end flange
All parts included in the iSave 50 & 70 are
designed to provide long service life with a
constant high efficiency and minimum service
required.
Unlike a centrifugal pump, it produces a similar
flow at a given speed no matter what discharge
pressure.
2. Benefits• Corrossion resistance (all wetted parts are made
• Significant power savings and low specific
energy consumption (SEC)
• Simple and space-saving installation with
both pump and pressure exchanger in one
of high corrosion-resistant materials e.g. Super
Duplex or Duplex)
• Fewer components
unit
• Simple system design and monitoring
without requirement for high-pressure flow
meters
• Simple operation with design that prevents
overspin/overflushing
• Easy modular service
3. Applications
Danfoss iSave ERDs are built into a broad range
of RO desalination plant around the world.
Typical applications for iSave 50 - 70 will be:
• Containerized solutions for hotels and
resorts on islands as well as coastal regions
• Onboard systems for ships
• Offshore platforms for the oil and gas
industry
• Municipal and private waterworks
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
25
Data sheet | iSave 50 and iSave 70
4. Technical data4.1 iSave without motor
iSave sizeiSave 50iSave 70
Code number180F7020180F7021
Pressure
Max. differential pressure (HP out - HP in)
Min. pressure HP out (min. allowable working
pressure)
Max. pressure HP out (Max. allowable working
pressure, MAWP)
Min. pressure on HP in,
intermittent
Max. pressure LP in (MAWP)
Max. pressure LP in, peak
Min. allowable working pressure LP in
Max. differential pressure (LP in - LP out)
Max. static test pressure (HP in and HP out)
Max. static test pressure (LP in and LP out)
Speed
Min. speedrpm525625
Max. speedrpm650875
Typical flow
Flow at min. speed, HP out
Flow at max. speed. HP out
Max. lubrication flow at 60 barg (871 psig)
Peak flow, LP in
Max. allowable working flow, LP in
1)
2) 3)
4)
10)
barg55
psig7272
barg4040
psig580580
barg8383
psig120 0120 0
barg22
psig2929
1)
barg55
psig7272
barg1010
psig145145
barg22
psig2929
barg0.530.79
psig7. 6911.46
barg108108
psig15661566
barg1313
psig189189
m³/h4250
gpm184220
m³/h5270
gpm228308
l/min2525
gpm6.66.6
m³/h120120
gpm528528
7)
m³/h57. 270
gpm252308
26
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Data sheet | iSave 50 and iSave 70
Technical specifications
Media temperature
Ambient temperature
Filtration requirements (nominal)
Salinity increase at membrane at 40% recovery rate at
balanced flow
Weight (dry)
Weight (operation with water)
Noise
Sound pressure level L
Torque data
Max. allowable working torque
Max. starting torque (stick/slip)
o
5)
6)
9)
C2-352-35
o
F36-9536-95
o
C0-500-50
o
F32-12232-122
3 micron melt-blown
2-3%
kg164164
lb362362
kg172172
lb379379
8)
PA
1 m
dB(A)8386
Nm17019 0
lbf-ft12 5140
Nm18 0180
lbf-ft132132
1)
Max. allowable working pressure of continous operation. For lower and higher pressure, please
contact Danfoss.
2)
Typical pressure level at start-up and permeate
flush.
3)
Intermittent pressure is acceptable for less than 10
minutes within a period of 6 hours.
4)
Typical average flow at 60 barg and 3 barg
differential pressure
5)
Dependent on NaCI concentation.
6)
Please see section 7.4 filtration.
7)
Continuous operation: iSave can operate
continuously with up to 10% over flush with the
limitation that the flow rate at LP inlet shall not
exceed 70 m3/h.
8)
A-weighted sound pressure level at 1 m from the
pump unit surfaces (reference box) acc. to EN ISO
20361 section 6.2. The noise measurements are
performed acc. to EN ISO 3744:2010 on a motor-
pump-unit at max. pressure and rpm.
9)
Balanced flow: The mixing rate is defined at balanced flow when HP-out is equal to LP-in.
10)
At system start-up: iSave can run for up to 10 min.
with 150% of max. rated flow at LP inlet. The time
where max. rated flow is exceeded should be kept
as short as possible to minimize wear.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
27
Data sheet | iSave 50 and iSave 70
4.2 iSave with IEC motor
i
iSave sizeiSave 50iSave 70
Code number (vertical)180F7038180F7040
Code number (horizontal)180F7023180F7025
Pressure, Speed, Flow, Temperature and Torwue are identical with 180F7020 and 180F7021
Efficiency
Efficiency at max. speed at 60 barg (871 psig)%93.792.4
Technical specifications
Media temperature
Filtration requirements (nominal)
Weight (dry) vertical/horizontal
Weight (operation with water) vertical/
horizontal
Noise
Sound pressure level L
Footprint
Footprint (vertical position)
Footprint (horizontal position)
Torque data
Max. allowable working torque
Max. starting torque (stick/slip)
Motor data
Nominal speedrpm985985
Rated current at 400VA3737
Motor size
Frame size
Rated motor torque at nominal speed
Rated motor ambient temperature
Motor insulationClassBB
Motor degrees of protectionIP5555
5)
°C2-352-35
°F36-9536-95
6)
3 micron melt-blown
kg441/463441/463
lb972/1021972/1021
kg470/471470/471
lb1036/10381036/1038
2)
PA
1 m
3)
dB(A)8386
m²0.440.44
foot²4.714.71
3)
m²0.760.76
foot²8.148.14
Nm170177
lbf-ft125130.5
Nm180180
lbf-ft132132
kW18. 518.5
HP30.030.0
IEC200 L200 L
Poles66
Nm177177
lbf-ft130.5130.5
4)
°C4040
°F104104
28
2)
A-weighted sound pressure level at 1 m from the ERD
unit surfaces (reference box) acc. to EN ISO 20361
section 6.2. The noise measurement are performed
acc. to EN ISO 3744:2010 on an ERD with motor
(motor pump unit) from min. to max. pressure and
speed.
3
Area covered with recommended IE3 motor
configurations (excl. of space to service the ERD)
4)
For higher temperature, contact Danfoss.
5)
Dependent on NaCI concentation.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
)
6)
Please see section 7.4 Filtration
7)
Typical efficiency for pressure exchanger, ..
booster pump, electrical motor and VFD at 3
barg differential pressure after a system has ...
been commissioned and run in.
Data sheet | iSave 50 and iSave 70
4.3 iSave with NEMA motor
iSave sizeiSave 50iSave 70
Code number (vertical)180U0062180U0064
Code number (horizontal)180U0003180U0005
Pressure, Speed, Flow, Temperatue and Torque are identical with180F7020180 F7021
Efficiency
Efficiency at max. speed at 60 barg (871 psig)
Technical specifications
Media temperature
Filtration requirements (nominal)
Weight (dry) vertical/horizontal
Weight (operation with water) vertical/
horizontal
Noise
Sound pressure level L
Footprint
Footprint (vertical position)
Footprint (horizontal position)
Torque data
Max. allowable working torque
Max. starting torque (stick/slip)
Motor data
Nominal speedrpm118 0118 0
Rated current at 400VA36.236.2
Motor size
Frame size
Rated motor torque at nominal speed
Rated motor ambient temperature
Motor insulationClassBB
Motor degrees of protectionIP5555
2)
A-weighted sound pressure level at 1 m from the ERD
unit surfaces (reference box) acc. to EN ISO 20361
section 6.2. The noise measurement are performed
acc. to EN ISO 3744:2010 on an ERD with motor
(motor pump unit) from min. to max. pressure and
speed.
3
Area covered with recommended IE3 motor
configurations (excl. of space to service the ERD)
4)
For higher temperature, contact Danfoss.
5)
Dependent on NaCI concentation.
7)
%93.792.4
5
)
6)
°C2-352-35
°F36-9536-95
3 micron melt-blown
kg484/506484/506
lb10 67/111610 67/1116
kg513/535513/535
lb1131/11791131/ 1179
2)
PA
1 m
3)
dB(A)8386
m²0.440.44
foot²4.714.71
3)
m²0.760.76
foot²8.148.14
Nm170177
lbf-ft125130.5
Nm18 0180
lbf-ft132132
kW22.522.5
HP30.030.0
NEMA324/6T324/6T
Poles66
Nm179179
lbf-ft132132
4)
°C4040
°F104104
6)
Please see section 7.4 Filtration
7)
Typical efficiency for pressure exchanger, ..
booster pump, electrical motor and VFD at 3
barg differential pressure after a system has ...
been commissioned and run in.
)
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
29
Data sheet | iSave 50 and iSave 70
0
10
20
30
40
50
60
525650
Flow [GPM]
Flow [m
3
/h]
Motor speed [rpm]
Flow curve iSave50®
5 bar
2
bar
220
176
0,0
10,0
20,0
30,0
40,0
50,0
60,0
70,0
80,0
625875
Flow [GPM]
Flow [m
3
/h]
Motor speed [rpm]
Flow curve iSave70®
2
bar
5 bar
220
308
5. Performance curves5.1 Flow at different rpm
The diagram shows that the HP flow can be
changed by changing the rotation speed of the
iSave. The flow/rpm ratio is constant, the
required flow is obtainable by changing the
rotation speed to a required value.
5.2 iSave 50 flow curves
For accurate data and advise, please contact
Danfoss High Pressure Pumps.
The iSave is delivered with a 3.1 performance
certificate according to EN10204.
5.3 iSave 70 flow curves
30
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Data sheet | iSave 50 and iSave 70
5.4 Torque curve for iSave 50 and iSave 70
Below curve illustrates typical values.
Torque [Nm]
200
180
160
140
120
100
80
60
40
Torque on iSave50 and iSave70
Starting torque
delta-P: 5 bar
delta-P: 4 bar
delta-P: 3 bar
delta-P: 2 bar
delta-P: 1 bar
20
0
5.5 Mixing curve
525645765875
Motor speed [rpm]
Volumetric mixing versus flushing
14,0
12,0
10,0
8,0
6,0
Volumetric mixing [%]
4,0
2,0
0,0
-10-50510
Flush ratio (larger than 0 means overflush) [%]
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
31
Data sheet | iSave 50 and iSave 70
6. Temperature and
corrosion
6.1 Operation
The chart below illustrates the corrosive
resistance of different types of stainless steel
related to NaCl concentration and temperature.
All critical parts of the iSave is made of
Super Duplex 1.4410/UNS 32 750 or Duplex
1.4462/UNS 32803.
º
80
C
Duplex
70
60
50
316L
40
30
20
100
1000
1601600
Always flush the iSave with fresh water at
operation stop in order to minimize the risk of
crevice corrosion.
Super Duplex
-
10 000
16000
100 000
160000
CI
ppm
NaCI
ppm
7. Installation
7.1 Operation and mounting7.2 Horizontal mount
The iSave 50 and iSave 70 can be mounted
horizontally and vertically. When mounted
vertically, the electric motor must be placed at
the top of the iSave
The iSave is delivered with a standard port
orientation. The port orientation can be changed
by the customer by rotating the combined iSave
and bell housing around the center of the motor
shaft.
32
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Data sheet | iSave 50 and iSave 70
See example below on how to mount the pump
and connect it to an electrical motor.
A: Flexible coupling
B: Bell housing
C: Motor shaft
7.3 Connection to inlet or discharge ports:
• When using hard piping, it is important to
follow the Guideline 180R9367 - Pipe
connection.
• When using flexible hoses, it is recommened
to use Hose Whip Restraint. Also follow the
guideline 180R9084 - Right and Wrong Hose
assembly.
Note: Any axial and radial load on the shaft
must be avoided.
min. 3 - 5 mm air space
A B C
7.4 Filtration
High quality water extends the service life of the
whole system.
Water to the iSave must be filtered to 3 μm
nominal, using melt-blown depth filter with
good end sealings. Consult Danfoss for correct
choice of filter.
It is important with selection of a proper filter
and filter housing to ensure good cartridge end
sealing.
If there is a high risk of water by-pass it is
recommended to use a second stage filter
solution.
7.5 Noise
Since the iSave is mounted on a bell housing and
electric motor, the noise level should be
determined for a complete system. To minimize
vibrations and noise throughout the system, it is
improtant that a horizontal iSave unit is mounted
correctly on a frame with dampeners.
Rigid designs with metal pipes cause vibration
and noise. It is therefore recommended to use
high-pressure flexible hoses between the hard
piping in the RO-plant and the iSave or to used
multiple connections with Victaulic clamps
where possible.
The noise level is influenced by:
Speed:
• High rpm makes more fluid/structure-borne
pulsations/vibrations than low rpm due to
higher frequency.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
As the various filters on the market differ greatly,
Danfoss High Pressure Pumps recommends
using cartridges with consistent, reliable
performance and high efficiency and where
fibres are blown continuously onto a central
support core. High Pressure Pumps does not
recommend cartridges requiring any type of
binders or resins.
Filters can be purchased from Danfoss
High Pressure Pumps. For more information on
the importance of proper filtration, please
consult our publication “Filtration” (code number
521B1009), which also will provide you with an
explanation of filtration definitions and a
guidance on how to select the right filter.
Pressure:
• High pressure makes more noise than low
pressure.
Mounting:
• Rigid mounting makes more noise than flexible mounting due to structure-borne
vibrations.
Connections to iSave:
• Pipes connected directly to the iSave make
more noise than flexible hoses due to structure-borne vibrations.
• Variable frequency drives (VFD):
Motors regulated by VFDs can increase noise
level if the VFD does not have the right
settings.
33
Data sheet | iSave 50 and iSave 70
7.5 RO systems with an iSave
VFD
22
M
4
2
26
Media filter
A
BC
Filter
3 micron
nominel
PI
Fresh water
permeate flush
Filter
10 micron
absolut
PI
F
*
12
PI
PS
21
24
19
*
Second stage filter: If recommended housing des ign and cartridges are not used, a second stage filt er is required
3
LP in
PI
PS
F
1
HP out
11
M
4
26
iSave
HP in
M
VFD
2323
25
18
25
18
HP out
HP in
M
VFD
VFD
5
PI
PS
13
14
PS
PI
6
7
20
F
22
Full flow
cleaning/CIP
1011
PI
15
17
Permeate
F
Flowmeter
8
9
16
28
CIP
27
Drain
Explanation of P&ID setup
D. Inlet flow control and mixing:
A. Inlet filter:
Place inlet filters on LP string in front of the iSave (11). Please see Guide line 521B1009 on
Filtration.
To balance LP flow up against HP flow on the
iSave and control mixing, place a
flowmeter on low-pressure inlet (12) or low
pressure outlet (20) of the iSave.
If recommended housing design and cartridges are not used, a second stage filter is required, see above (*).
Thoroughly clean pipes and flush system
prior to start-up.
E. Outlet pressure control:
In order to control the inlet pressure needed a
back pressure valve (15) must be installed in
the common outlet pipe from the iSaves. The
valve should be designed to control flow.
B. Inlet pressure:Must assure that iSave is running according to
specifications. Refer to iSave data sheet.
It is recommended to use a manual valve with
lock function or an automatic controlled
valve.
Required: Must assure min. pressure to avoid
cavitation.
Recommended: Must assure max. pressure to
avoid hydraulic and mechanical overload.
(13) used for iSave 21 and iSave 40.
(24) used for iSave 50 and iSave 70.
F. Variable speed and overload protection:
Install a VFD to control the speed of the iSave
and protect it against mechanical overload.
See instruction 180R9372 for guidance of VFD
settings.
C. Piping and hoses:Dimension the piping to obtain minimum
G. LP discharge flow control:
See “E”.
pressure loss (large flow, minimum pipe length, minimum number of bends/
connections and fittings to prevent pressure
loss and flow turbulence). Use flexible hoses
to minimize vibrations and noise. Please consult the Danfoss Hoses and Hose Fittings
H. Air venting:
Install an air bleed valve (8) on the highest
point of the high-pressure piping to ensure
the air is purged from the system before
startup.
data sheet (521B0909 ) and Right and wrong
Hose assembly (180R9084) for guidance.
34
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Data sheet | iSave 50 and iSave 70
I. Pressure relief (high pressure): The pressure relief valve (6) protects the whole
system against pressure overload and relieves
the water if the pressure exceeds the maximum set pressure. If the high-pressure pump
is a positive displacement pump, the pump
can built up a very high pressure that will
exceed mechanical strength of the membrane
housing, pipes and other accessories. When
using Danfoss APP pumps with Danfoss VCM
check valves, it is recommended to place a
pressure relief valve or pressure safety valve as
illustrated. In case the Danfoss check valves
are not used, the valve must be placed
between pump and check valve (See
180R9371, Design Guide Pressure saftey valve
in seawater RO sytem for more details).
J. Pressure relief (low pressure): The pressure relief valve or pressure safety
valve (19) protects the low-pressure pipes
against pressure overload and relieves the
water if the pressure exceeds the maximum
allowable pressure.
For a more eleborate description of the P&ID
setup, please consult the Danfoss Design Guide
Piping & Instrumentation Diagram (P&ID)
(180R9370) or contact Danfoss.
The iSave 50 and iSave 70 can be mounted in
parallel. For more information, please see
“Design Guide Parallel-coupled APP and iSave”
-180R9354 or contact Danfoss.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
35
Data sheet | iSave 50 and iSave 70
8. Dimensions and
connections
8.1 iSave 50-70
without electric motor
36
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Data sheet | iSave 50 and iSave 70
8.2 iSave 50-70 with with IE3 motor 18.5 kW
on base frame vertical_front mounted
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
37
Data sheet | iSave 50 and iSave 70
8.3 iSave 50-70 with with IE3 motor 18.5 kW
on base frame vertical_back mounted
38
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Data sheet | iSave 50 and iSave 70
8.4 iSave 50-70
with with IE3 motor 18.5 kW
on base frame horizontal
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
39
Data sheet | iSave 50 and iSave 70
8.4 iSave 50-70 with NEMA motor 30 HP
on base frame vertical - front mounted
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
40
Data sheet | iSave 50 and iSave 70
8.5 iSave 50-70 with NEMA motor 30 HP
on base frame vertical - back mounted
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
41
Data sheet | iSave 50 and iSave 70
8.5 iSave 50-70
with NEMA motor 30 HP
on base frame horizontal
42
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Data sheet | iSave 50 and iSave 70
9. Service9.3 Maintenance
9.1 Warranty
The Danfoss iSave is designed for long operation,
low maintenance and reduced lifecycle costs.
Periodic inspections are required to ensure worn
parts (if any), are replaced in due time. Opera-
tional conditions such as water quality should be
Provided that the iSave has been running
according to the Danfoss specifications, Danfoss
guarantees one year service-free operation,
taken into consideration when determining the
frequency of the inspections. Danfoss recom-
mends yearly inspections.
however, max. 18 months from date of
production.
It is recommended to order the purpose-
designed tool kit.
9.2 Operational conditions of concern
Particular attention should be paid to the
following factors to avoid increased wear and
spare parts costs:
9.4 Repair assistance
In case of irregular function of the Danfoss RO
components, please contact Danfoss High
Pressure Pumps.
- Insufficient filtration
- Insufficient bleeding and venting
- Running at speeds outside specificat
tions
- Wrong direction of rotation
- Insuffi cien t flushing or pe rio ds of s tan ds till with
sea water inside the iSave.
180 R9214Membrane cleaning of the RO system with the iSave
180R9354Parallel coupled APP and iSave
180R9367Pipe connections
180R9371Pressure safety valve in the SWRO system
180R9372APP and iSave overload protection
180R9370Review sheet P&ID
521B1009Filtration
iSave selection tool (hpp.danfoss.com)
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
43
Danfoss A/S
High Pressure Pumps
DK-6430 Nordborg
Denmark
Danfoss ca n accept no respons ibility for pos sible errors in ca talogues, bro chures and other pr inted material. Da nfoss reserve s the right to alter its p roducts with out notice.
This also a pplies to produc ts already on ord er provided that su ch alterations ca n be made without su bsequential cha nges being nece ssary in speci fications alread y agreed.
All trade marks in this mate rial are proper ty of the respec tive companies . Danfoss and the Danf oss logotyp e are trademark s of Danfoss A/S. Al l rights reserv ed.
AI264763692435en-000901 | Data sheet iSave 50-70 | UK | 44
Design guide
iSave Energy Recovery Device
Start and stop of the SWRO with iSave
hpp.danfoss.com
Design guide Start and stop of the SWRO with iSave unit
Table of ContentsPrior to start-up................................................................................................................................................................47
Starting up the system...................................................................................................................................................48
Daily system shutdown.................................................................................................................................................48
More than one day system shut down......................................................................................................................49
46
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Design guide Start and stop of the SWRO with iSave unit
Below procedures are general guidelines for the
start-up and shut-down functions of SWROsystems with the Danfoss iSave Energy Recovery
Device.
Procedure details may differ depending on the
system design.
The numbers marked in () refer to the diagram
on page 5.
iSave can be both a single iSave and multiple
iSaves in parallel.
General SWRO system understanding with
ISave
• Basically the permeate flow is the same as the
flow from the high-pressure pump.
• The HP concentrate flow into iSave HP-in and
HP seawater-out is determined by the rpm of
the iSave.
• The iSave (s) HP flow determines the recovery
rate (higher rpm on the iSave gives lower
recovery rate and vice versa).
• Flow on the low-pressure side of the iSave is
determined by feed pump and the pressure
control valve LP-out (15) (not by the rpm of
the iSave).
• The flow on the low-pressure side must be at
least the same as on the high-pressure side
of the iSave (LP in flow = HP in flow; this is
called balanced flow).
• Continuously operation:
• To minimize mixing, the flow on the
low-pressure side can be adjusted up to 10%
higher than the high-pressure flow with the
limitation that the flow rate at LP inlet may not
exceed 70 m³/h.
Prior to start-up
High quality water extends the service life of the
whole system.
Both the APP pump and iSave are sensitive to
hard particles.
Before connecting any APP pump or iSave to
a piping system ALL pipes must be thorough
flushed with high quality pre-filtered water or
mechanical cleaned.
1. Install all filter cartridges in the system.
2. With the iSave(s) and APP pump(s) discon- nected from the piping, the system must be
flushed in order to remove possible
impurities from the system (pipes, hoses,
membranes etc.).
Flushing must run until the system can be ensured clean.
3. Connect the iSave(s) and APP pump(s) to
the pipework. The iSave(s) and APP pump(s)
are now ready for start-up.
Starting up the system
1. Make sure that all valves are set in normal
operating positions.
2. Start the seawater supply pump (A).
3. Make sure all pipework is flushed with water.
Vent all air from the system through air valve
(8) and iSave unit (11). After venting, close
valve (8).
At initial start-up also bleed the iSave(s) and
APP pump(s).
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
47
Design guide Start and stop of the SWRO with iSave unit
4. Start the iSave(s).
In general: Only start the iSaves when the
pressure ”HP in” (10) is below 20 barg/290
psig. Always start the iSave unit before the
high-pressure pump is started.
There are in principle two ways to start multi
ple iSaves:
- Slowly ramp up all the iSaves at the same
time.
- Slowly ramp up one by one.
Starting sequence - one by one:
a) Start iSave #1.
b) After 5 sec. start iSave #2.
c) In a sequence of 5 sec. start the
remaining iSaves.
Comments:
- Ramp up time on iSaves is set between
10 –15 sec.
Starting sequence - Start all iSaves at the
same time.
Comments:
- Ramp up time on iSaves is set between
10 –15 sec.
If the pressure (10) at ”HP in” drops below
3 barg/43.5 psig, the sound will change of
the iSave. This is due to cavitation. ”HP in”
pressure at 3 barg/43.5 psig is acceptable
for less than 10 min. within a period of 6
hours. Run the iSave at its min
allowable speed during this period to reduce cavitation.
“LP-out” pressure (14) is below 1 barg/
14.5 psig, adjust the flow by raising the
flow from the seawater supply pump (A).
3. If the “LP-in” flow (12) is too high, reduce
flow by closing the pressure control
valve (15) or the flow from the seawater
supply pump (A).
10. For iSave 50 and iSave 70:Check the low pressure flow rates (12), and if
required, adjust flow with valve (15) to
achieve balanced flow to the iSave(s).
1. If the “LP-in” flow (12) is too low and the
“LP-in” pressure (21) is higher
than 2 barg/29 psig, increase flow and
decrease pressure by opening the
pressure control valve (15).
2. If the “LP-in” flow (12) is too low and the
“LP-in” pressure (21) is below 2 barg/
29 psig, adjust the flow by raising the
flow from the seawater supply pump
(A).
3. If the “LP-in” flow (12) is too high, reduce
flow by closing the pressure control
valve (15) or the flow from the seawater
supply pump (A).
Daily system shutdown
1. The system is running in normal operation
and producing permeate flow.
2. Stop the high-pressure pump (4).
5. With a pressure control valve (15), adjust the
back pressure of the “LP-out” to fulfill the
minimum presure requested in the Data sheet. (May only be necessary at initial start
up).
6. An “over flush” of the iSave can be done to
bleed any remaining air from the system.
Flush over a period of minimum 2 minutes.
7. Adjust the speed of the iSave unit to desired
flow (rpm). The speed is controlled by a VFD.
8. Start the high-pressure pump(s) (4), and the
system pressure (5) will rise until the
permeate flow (17) almost equals the flow (2)
from the high-pressure pump.
9. For iSave 21 and iSave 40:Check the low pressure flow rates (12), and if
required, adjust flow with valve (15) to
achieve balanced flow to the iSave(s).
1. If the “LP-in” flow (12) is too low and the
“LP-out” pressure (14) is higher
than 1 barg/14.5 psig, increase flow and
decrease pressure by opening the
pressure control valve (15).
2. If the “LP-in” flow (12) is too low and the
3. Keep the iSave(s) (11) running until the
TDS in the high-pressure line is equal to the
TDS in the low-pressure line.
NB! If the pressure (10) at “HP in” drops
below 3 barg/43.5 psig, the sound will
change of the iSave. This is due to
cavitation. “HP in” pressure at
3 barg/43.5 psig is acceptable for less
than 10 minutes within a period of 6
hours. Run the iSave at its min
allowable speed during this period to reduce cavitation.
4. Stop the iSave(s)(11).
5. Stop the seawater supply pump (A).
48
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Design guide Start and stop of the SWRO with iSave unit
More than one day system shutdown
1. Run the “daily system shutdown” procedure.
2. Supply permeate water to the SWRO system
by using fresh water/permeate flush
connection..
3. When the pressure ”HP in” (10) is below 20
barg/ 290 psig start the iSave(s).
NB! If the pressure (10) in “HP in” drops
below 3 barg/43.5 psig, the sound will
change of the iSave. This is due to
cavitation. “HP in” pressure at 3 barg/43.5
psig is acceptable for less than 10 minutes
within a period of 6 hours. Run the iSave
at its minimum allowable speed during
this period to reduce cavitation.
4. Start the APP pump(s) in a period of 5 sec. by
using normal ramp-up settings.
5. Stop the APP pump(s) after 5 sec.
6. Run the iSave(s) until the TDS in the high-
pressure line is equal to the TDS in the low-
pressure line.
7. Stop iSave(s) and permeate water supply.
VFD
22
M
4
2
26
Media filter
A
BC
Filter
3 micron
nominel
PI
Fresh water
permeate flush
Filter
10 micron
absolut
PI
F
*
12
PI
PS
21
24
19
3
PI
PS
F
1
LP in
HP out
11
M
4
26
iSave
HP in
M
VFD
2323
25
18
25
18
HP out
HP in
M
VFD
VFD
5
PI
PS
13
14
PS
PI
6
7
20
F
22
Full flow
cleaning/CIP
1011
PI
15
17
Permeate
F
Flowmeter
8
9
16
28
CIP
27
Drain
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Energy Recovery Device
iSave
Membrane cleaning of RO-system
hpp.danfoss.com
Design guide | Membrane cleaning of the RO-system with iSave ERD
Table of ContentsMembrane cleaning ...............................................................................................................................................................53
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Design guide | Membrane cleaning of the RO-system with iSave ERD
Below procedures are general guidelines for
the membrane cleaning of SWRO-systems with
the Danfoss iSave. Procedure details may differ
depending on the system design.
The numbers marked in () refer to the
diagram’s below.
The purpose of membrane cleaning is to reduce
scaling and fouling in the membranes. For optimal performance specific chemicals are required,
depending on the cause of the contamination.
After chemical treatment the system must be
flushed with fresh water. The flushing water,
coming out of the membranes, may consist of a
large amount of suspended inorganic particles. It
is important to assure that these particles are not
fed into the iSave(s) or pump(s).
NB! It is recommended to disconnect the
piping from the “HP in” of the iSave and flush
the contaminated water from the membranes
directly to drain. By disconnecting the pipes
there will be no accumulation of
contaminations in the HP-piping and
HP-valves. See P&ID no 2.
Membrane cleaning
The procedures below are based on Dow’s
Cleaning and Sanitization: Cleaning steps
described in Dow’s Form No. 609-02090-1005.
Other procedure may be used depending on the
membranes used.
Below procedure is according P&ID no 1.
1. Stop the high-pressure pump(s) (4), and stop
the iSave(s) (11).
2. Stop the seawater supply pump (A).
3. Close valve (9 and 27) and open valve (16 and
28), and feed cleaning solution through valve
(7).
4. Pump mixed cleaning solutions to the vessel
at conditions of low flow rate and low pressure
to displace the process water. Use only
enough pressure to compensate for the
pressure drop from feed to concentrate.
The pressure should be low enough that
essentially no or little permeate is produced.
A low pressure minimizes re-deposition of
dirt on the membrane. Dump the brine/
concentrate to prevent dilution of the
cleaning solution.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
5. Recycle: After the process water is displaced,
cleaning solution will be present in the
concentrate/ brine stream. Recycle the
cleaning solution from the piping to the
cleaning solution tank.
6. Turn of the pump and allow the elements
to soak.
53
Design guide | Membrane cleaning of the RO-system with iSave ERD
7. Feed the cleaning solution at high flow into
the “full flow cleaning” adapter (7). The high
flow rate flushes out the foulants removed
from the membrane surface by the cleaning.
8. Flush RO permeate or deionised water into
the “full flow cleaning” adapter (7).
Flush out the cleaning solution.
It is essential that the water used for the final
pre-flush is pre-filtered to a level described
in the datasheet.
P&ID no. 1
4
2
26
Media filter
A
BC
Filter
3 micron
nominel
PI
Fresh water
permeate flush
10 micron
absolut
PI
F
*
PI
PS
21
24
19
3
Filter
PI
PS
F
1
12
LP in
HP out
11
iSave
HP in
M
VFD
2323
4
26
9. Open valve (9) and continue flushing.
The iSave(s) may start to rotate backward –
this is OK.
10. When flushing is finalised – assure that no
foulants remain in the piping or valve (9).
11. Close the high pressure “full flow cleaning”
valve (7) and close valve (16 and 28).
12. Open valve (27)
VFD
22
M
25
18
M
25
18
HP out
HP in
M
VFD
VFD
22
5
PI
6
PS
Flowmeter
Full flow
cleaning/CIP
7
1011
9
PI
13
14
PS
PI
15
20
F
8
16
28
27
Drain
17
Permeate
F
CIP
*
Second stage filter: If recommended housing design an d cartridges are not used, a second stage filter is required
Below procedure is according P&ID no 2.
1. Stop the high-pressure pump(s) (4), and stop
the iSave (11).
2. Stop the seawater supply pump (A).
3. Disconnect pipe in joint (9) and connect the
pipe to low pressure “Full flow cleaning”
joint (16).
4. Plug pipe in joint (9).
5. Close valve (27) and open valve (28)
6. Pump mixed cleaning solutions through valve
(7) to the vessel at conditions of low flow rate
and low pressure to displace the process
water. Use only enough pressure to
compensate for the pressure drop from feed
to concentrate.
The pressure should be low enough that
essentially no or little permeate is produced.
A low pressure minimizes re-deposition of dirt
on the membrane. Dump the brine/
concentrate to prevent dilution of the
cleaning solution.
7. Recycle: After the process water is displaced,
cleaning solution will be present in the
concentrate stream. Recycle the cleaning
solution from the piping to the cleaning
solution tank.
8. Turn of the pump and allow the elements to
soak.
9. Feed the cleaning solution at high flow into
the “full flow cleaning” adapter (7) on the
feed side of the membrane. The high flow rate
flushes out the foulants removed from the
membrane surface by the cleaning.
54
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Design guide | Membrane cleaning of the RO-system with iSave ERD
P&ID no. 2
10. Flush RO permeate or deionised water into
the “full flow cleaning” adapter (7) on the
feed side of the membrane. Flush out the
cleaning solution.
It is essential that the water used for the final
pre-flush is pre-filtered to a level described in
the datasheet.
M
4
2
26
Media filter
A
BC
Filter
3 micron
nominel
PI
PI
*
PI
PS
21
Fresh water
permeate flush
24
19
3
Filter
PI
10 micron
PS
absolut
F
1
F
12
LP in
HP out
11
HP in
M
VFD
2323
26
iSave
18
M
4
18
M
VFD
11. When flushing is finalised – Close the high
pressure “full flow cleaning” valve (7) and
close valve (28).
12. Connect the high pressure pipe to joint (9)
again.
VFD
22
VFD
25
25
HP out
HP in
5
PI
PS
PS14PI
22
6
Full flow
cleaning/CIP
7
1011
PI
9
13
15
20
F
Flowmeter
8
16
Drain
17
Permeate
F
28
CIP
v
27
*
Second stage filter: If recommended housing design and car tridges are not used, a second stage filter is required
VFD
22
M
4
2
26
Media filter
A
BC
Filter
3 micron
nominel
PI
Fresh water
permeate flush
10 micron
PI
F
*
PI
PS
21
24
19
*
Second stage filter: If recommended housing design and car tridges are not used, a second stage filter is required
3
Filter
PI
PS
absolut
F
1
12
LP in
HP out
11
HP in
M
VFD
2323
4
26
iSave
25
18
M
25
18
HP out
HP in
M
VFD
VFD
22
5
PI
6
PS
Full flow
cleaning/CIP
7
1011
PI
9
13
15
20
PS14PI
F
Flowmeter
8
16
Drain
17
Permeate
F
28
CIP
27
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
5.2 iSave energy recovery device ...........................................................63
5.3 Time delay before start.................................................................64
1. Introduction
This document shows what to consider when
programming a VFD that can protect the APP
pump and the iSave against overloads. It also
shows how to program the Danfoss VLT FC 202
and FC 302 in connection with the APP pump
and iSave.
Similar functions need to be available on other
VFD brands.
There are principal two choiches that can be
made when selecting the torque limits for the
pump and iSave.
1. Protecting the pump or iSave against
maximum allowable load, means maximum
torque at maximum pressure. This choice
may not give the possibility to detect additional critical torque caused by wear of
internal parts. See graph in example #1 in
chapter 2.1.
2. Protecting the pump or iSave against significant change in actual load. This choice
gives you the possibility to detect additional critical torque caused by wear of internal
parts. This means the torque limit typical
will b set lower than maximum Allowable
Operating Torque. See graph in example #2
in chapter 2.1.
Danfoss strongly recommend to use the
possibility to detect significant change
in actual load.
58
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
When protecting the pump and iSave against
overload both the maximum torque and
maximum pressure must be taken into
account.
- Maximum allowable operation torque is the
maximum torque the product can handle in
normal operation.
- Maximum allowable operation torque is the
maximum torque the product need in a
specificl operation.
Example #1
2.1 Maximum torque
Start up:
• Ramp up speed from 0 to set-point
• The starting torque must not exceed maximum Starting Torque according to chapter 5.
Ongoing operating:
• Continuously the torque must not exceed
120% of maximum Allowable Operating
Torque for more than 30 sec.
• Periodically the torque can for a very short
time go up to maximum Starting torque.
Example #2
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
59
Design Guide | APP and iSave overload protection
3. Standard preferred
settings
3.1 VLT FC 202 and VLT FC 302
For detailed information on how to program a
VLT FC 202 or FC 302 we refer to the “Program-
To calculate setting for parameter 4-16 and 4-18
please contact Danfoss.
ming Guide VLT Aqua Drive FC 202 and FC 302”.
vlt-drives.danfoss.com
Programming VLT:
Parameter 0-01“Language”Set language
Parameter 0-02“Motor speed unit”Set to rpm
Parameter 0-20“LCD Display”Choose rom, Amp, kW, Hz, Torque
Parameter 1-03“Torque characteristic”Set to 0 (Constant torque)
Parameter 1-06“Clockwise direction”Set to inverse (Clockwise)
Parameter 1-20“Motor power kW”According to motor name plate
Parameter 1-22“Motor voltage”According to motor name plate
Parameter 1-23“Motor frequency”According to motor name plate
Parameter 1-24“Motor current”According to motor name plate
Parameter 1-25“Motor nominel speed”Rpm according to name plate
Parameter 1-29“Automatic motor adaption
AMA”
Run full AMA. (Remember to fuse terminals 12 and 27. Push hand on. Remove fuse
after AMA)
Parameter 1-71“Start delay”Set in sec. (See chapter 5.3)
Parameter 1-72“Start function”Set to 0. (DC hold/delay/time)
Parameter 2-00“DC hold current”Set in % (please contact Danfoss or see
chapter 5.2 for iSave)
Parameter 3-02“Minimum reference”Set to 0
Parameter 3-03“Maximum reference”Set needed rpm. For application
Parameter 3-41“Ramp 1. Ramp up time”Motor ramp up time.
Pump: 10-60 sec. = 1 barg/sec.
iSave: 10.15 sec.
Parameter 3-42“Ramp 1. Ramp down time” Motor ramp down time.
Pump: 10-60 sec. = 1 barg/sec.
iSave: 10-15 sec.
Parameter 4-11“Motor speed low limit”Set low limit [rpm] for product according
to chapter 5
Parameter 4-13“Motor speed high limit”Set max. limit [rpm] for product according
to chapter 5
Parameter 4-19“Max. output frequency”[Hz] Set max. output for product
Torque limit
Parameter 4-16“Torque limit motor mode”Set in [%] (please contact Danfoss or see
chapter 5.2 for iSave)
Parameter 14-25“Trip delay at torque limit”Set to 30 sec.
Current limit
Parameter 4-18“Current limit”Set in [%] (Par. 4-18 must always be larger
or equal to Par. 4-16), (please contact
Danfoss or see chapter 5.2 for iSave)
60
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Design Guide | APP and iSave overload protection
4. Examples of VLT overload limit settings
Below is two examples of how to calculate the
torque limit settings for an APP pump.
All calculations are made in the Danfoss HPP
calculation tool (please contact Danfoss HPP for
help).
Example 1:
Settings are made according to actual operating
pressure (see graph #2 in chapeter 2.1).
Instruction | Right and wrong - Hose assembly routing tips
HOSES & HOSE COUPLINGS
GS-HYDRO PRODUCT CATALOGUE
Assembly and installation
When hose installation is straight, allow enough slack in hose line to provide for length changes which will occur when pres-sure is applied.
Prevent twisting and distortion by bending hose in same plane as the motion of the boss to which hose is connected.
User proper angle adaptors to avoid sharp twist or bend in hose.Adequate hose length is necessary to distribute movement on
flexing applications and to avoid abrasion.
When radius is below the required minimum, use an angle adap-tor to avoid sharp bends.
Avoid twisting of hose lines bent in two planes by clamping hose at change of plane.
Hose assembly routing tips
HOSES & HOSE COUPLINGS
GS-HYDRO PRODUCT CATALOGUE
Assembly and installation
When hose installation is straight, allow enough slack in hose line to provide for length changes which will occur when pres-sure is applied.
Prevent twisting and distortion by bending hose in same plane as the motion of the boss to which hose is connected.
Avoid twisting of hose lines bent in two planes by clamping hose at change of plane.
Hose assembly routing tips
HIGH
PRESSURE
NO
PRESSURE
Correct hose installation is essential for safe and
satisfactory performance. The size of the hoses
impacts the installation recommendations. This
manual has therefore been split in recommendation for hoses up to 2” and recommendation
larger than 2”.
1. Hoses up to 2”When installing hoses, avoid twisting the hose as
the hose will try to straighten under pressure.
MIN. 10°
Always provide some angle on straight
hose installations, this reduces forces
and ensures that hose is only bending i
one direction. The Hose must have some
slack to compensate for hose length
variations.
Hose routing tips:
Danfoss recommends installing hose whip
restraints whenever your pressurized hose
assemblies are in proximity to personnel or
crucial equipment.
Check with these examples when installing
your hoses.
This can cause hose failure via hose blowout
from the fitting and/or hose burst at the point of
strain.
WRONG
RIGHT
When radius is below the required minimum, use an angle adap-
tor to avoid sharp bends.
At radius below required minimum, angle
adapters should be used to prevent sharp
hose bends.
NO
PRESSURE
To allow the hose to expand when
pressurized, clamps should not be used at
bends. If possible, do not clamp high and
low pressure lines together.
HIGH
PRESSURE
WRONG
RIGHT
Use proper angle adapters to avoid sharp twist
or bend of hose.
68
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Instruction | Right and wrong - Hose assembly routing tips
WRONG
WRONGRIGHT
To prevent hose collapse and flow restriction,
hose bend radii should be kept as large as
possible. Tight bends can also compromise
the hose reinforcement and cause premature
hose failure. Refer to hose specification table
on page 6 for minimum bend radii.
RIGHT
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
69
Instruction | Right and wrong - Hose assembly routing tips
2. Hoses larger than 2”
Whenever possible, high pressure hoses should
always be connected directly to Danfoss provided adapters and check valves. Elbows and
distance pipes should be avoided to prevent
excessive side loads.
MIN. 10°
Always provide some slack on straight hose installations. This compensates for hose length
variations with differences in internal fluid
pressures. A small angle will reduce the forces
from the hose and allow the hose to bend
when pressurized.
Danfoss 3” HP hoses are nylon reinforced; when
using hoses that are not steel reinforced the
connected items must be grounded to avoid
electrical stray currents.
EXPANSION
EXPANSION
EXPANSION
Flexing a metal hose in two separate planes of
movement will torque the hose assembly.
Always install the metal hose assembly so
that flexing occurs in one plan only and this
is the same plane in which bending occurs. If
multiple planes of motion are required use a
dog leg assembly.
The installation should allow a straight
distance S before bending the hose. Not
doing so may compromise the hose
reinforcement and cause hose failure.
Max. bending angle and distance S can be
found in table 1 on page 6.
WRONG
RIGHT
Hoses should not be twisted and should
only have one bend.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
70
Instruction | Right and wrong - Hose assembly routing tips
The use of pipe or fittings between pump
and iSave connectors and hoses should
be avoided. Such configurations can apply
excessive loads on the connectors and can
cause connector and/or connector bolt
failure. If this cannot be avoided, the piping
system must be protected by either hose
whip restraints mounted directly to the
frame or the hard piping must be fixed relative to any pump/iSave movements.
MAX.
BENDING
ANGLE
If hose is bent, ensure max. bending angle
and distance S from each connector (see
table 1 on page 5).
WRONG
WRONGRIGHT
To prevent hose collapse and flow restriction,
hose bend radii should be kept as large as
possible. Tight bends can also compromise
the hose reinforcement and cause premature
hose failure. Refer to hose specification table
on page 6 for minimum bend radii.
NO
NO
PRESSURE
PRESSURE
RIGHT
HIGH
HIGH
PRESSURE
PRESSURE
WRONG
RIGHT
The hose must have a distance S before
bending starts.
To allow the hose to expand when
pressurized, clamps should not be used at
bends. If possible, do not clamp high and
low pressure lines together.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
71
Instruction | Right and wrong - Hose assembly routing tips
S
3. Hose specification
table
High pressure hoses
Code
number
180Z0228
connection
material
EN 1.4410
Pipe
Pipe connection
[A]
1.5" Vic. OGSSuper duplex
1
Hose size
Inner
diameter
25.4 mm (1.0") 0.66 m (26")152 mm (6.08"), max. 90°79 mm (3.11”)
Hose length
ISO 1436
[B]
Bending radiusS
180Z02291.5" Vic. OGS
180Z0167
180Z0140
180Z02632.5" Vic. OGS
180Z0280
180Z0619
180Z0618
180Z0612
18 0Z0611
180Z1000
180Z1001
Low pressure hoses
180Z02982.0” Vic. OGS
180Z01443.0” Vic. OGS
1.5" Vic. OGSSuper duplex
2.0" Vic. OGSSuper duplex
2.5" Vic. OGSSuper duplex
2.5" Vic. OGSSuper duplex
2.5" Vic. OGSSuper duplex
3.0" Vic. OGSSuper duplex
3.0" Vic. OGSSuper duplex
3.0" Vic. OGSSuper duplex
3.0" Vic. OGSSuper duplex
Super duplex
EN 1.4410
EN 1.4410
EN 1.4410
)
Super duplex
EN 1.4410
EN 1.4410
EN 1.4410
EN 1.4410
EN 1.4410
EN 1.4410
EN 1.4410
EN 1.4410
Super duplex
EN 1.4410
Super duplex
EN 1.4410
25.4 mm (1.0")
38.0 mm (1.5") 1.16 m (45.7") 250 mm (9.84"), max. 180°85 mm (3.35”)
50 mm (2.0")1.25 m (49")630 mm (24.8"), max. 90°115 mm (4.53”)
50 mm (2.0")1.78 m (70")630 mm (24.8"), max. 180°115 mm (4.53”)
50 mm (2.0")1.00 m (39.4") 630 mm (24.8"), max. 90°115 mm (4.53”)
65 mm (2.5")1.78 m (70")200 mm (7.87"), max. 270°150 mm (5.90”)
65 mm (2.5")
76 mm (3.0")1.79 m (70.5") 250 mm (9.84"), max. 270°150 mm (5.90”)
76 mm (3.0")1.00 m (39.4") 250 mm (9.84"), max. 90°150 mm (5.90”)
76 mm (3.0")1,25 m (49")250 mm (9.84"), max. 180°150 mm (5.90”)
76 mm (3.0")1,6 m (63")250 mm (9.84"), max. 180°150 mm (5.90”)
1.16 m (45.7")
1.00 m
(9.4")
2.0 m
(79”)
2.0 m
(79”)
152 mm (6.08"), max. 180°79 mm (3.11”)
200 mm (7.87"), max. 90°150 mm (5.90”)
1)
The installation instuction for Style 77DX is located in the Victaulic document I-100 Field Installation Handbook (htpp://static.victaulic.com)
O. D.
r
α
S
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
When using flexible hoses, it is
recommened to use Hose Whip Restraint.
72
Instruction | Right and wrong - Hose assembly routing tips
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
2. Parts list iSave 50-70............................................................................................................................ 77
21Motor 18.5 kW IEC200 6-pole 3x400 V IE3180Z0530
21Motor 324TC 30 HP 3PH 1200 230/460/380180U2370
54Screw (not inluded in kit)
64Washer (not included in kit)
This manual concerns the following types of standard
induction motors from Hoyer:
HMA3, HMC3, HMA2, HMC2, HMD, HMT, MS, Y2E1, Y2E2, YDT
These motors are manufactured in accordance with IEC/EN
60034-4 and IEC/EN 60072.
Motors are rated for the ambient temperature range -20°C to
+40°C and site altitudes ≤1000 m above sea level.
Low-voltage motors are components for installation in
machinery. They are CE marked according to the Low Voltage
Directive 2014/35/EU.
Motors not fulfilling the IE3 efficiency level must be equipped
with a variable speed drive when used in EU.
Transport and storage
Check the motor for external damage immediately upon
receipt and, if found, inform the forwarding agent right away.
Check all rating plate data, and compare it with the
requirement of the motor.
Turn the shaft by hand to check free rotation, remove
transport locking if used.
Transport locking must be used again for internal transport
also. It is also important that transport locking is used when
motors are transported mounted on equipment.
All motors should be stored indoors, in dry, vibration- and
dust-free conditions.
Lifting eyebolts must be tightened before use. Damaged
eyebolts must not be used, check before use. Lifting eyes at
motor must not be used to lift the motor when it is attached
to other equipment.
Before commissioning, measure the insulation impedance. If
values are ≤ 10MΩ at 25°C, the winding must be oven dried.
The insulation resistance reference is halved for each 20°C
rise in motor temperature.
It is recommended that shafts are rotated periodically by
hand to prevent grease migration.
etc.) using suitable tools, never hit the drive components
with a hammer as this will cause damage to the bearing.
The motor are balancing with half key, ensure that the drive
components are also the same.
Correct alignment is essential to avoid bearing, vibration and
shaft failure.
Use appropriate methods for alignment.
Re-check the alignment after the final tightening of the bolts
or studs.
Check that drain holes and plugs face downwards. We
recommend opening the drain hole for motors placed
outdoors and not running 24 hours / day, so that the motor
can breathe, thus ensuring a dry motor.
Electrical connection
Work is only permitted to be carried out by qualified
specialists and must to be carried out in accordance with
local regulations.
Before work commences, ensure that all power is switched
off and cannot be switched on again. This also applies to the
auxiliary power circuits, e.g. anti-condense heaters.
Check that supply voltage and frequency are the same as
rated data.
Motors can be used with a supply deviation of ± 5% voltage
and ± 2% frequency, according to IEC60034-1.
Connection diagrams for main supply and accessory as PTC
or heater are located inside the terminal box.
Connections must be made in such a way as to ensure that
a permanently safe electrical connection is maintained, both
for the main supply and the earth connection.
We recommend that crimped connections are made in
accordance with IEC 60352-2.
Tightening torques for terminal board screws:
ThreadM5M6M8M10M12M16M20M24
T.(Nm)2.53.571218355580
Installation
The motor must be fixed on a stable, clear and flat foundation.
It must be sufficiently rigid to withstand possible short
circuit forces.
It is important to ensure that the mounting conditions do
not cause resonance with the rotational frequency and the
doubled supply frequency.
Only mount or remove drive components (pulley, coupling,
88
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Ensure that the terminal box is clean and dry.
Unused glands must be closed with blind caps.
Check the terminal box gasket before it is remounted.
Maintenance
Inspect the motor at regular intervals, keep it clean and
ensure free ventilation air flow, check the condition of shaft
seals and replace if necessary. Both electrical and mechanical
Motor
Manual
connections must be checked and tightened if necessary.
Bearing size and type are specified on the rating plate. Motor
types HMA3 and HMC3 is as standard with lifetime greased
bearings in motors size ≤180 for cast iron and size ≤132 for
aluminium. Motor types HMA2 and HMC2 is as standard
with lifetime greased bearing in motors size ≤225.
Motor types MS and Y2E is as standard with lifetime greased
bearing in motors size ≤160.
Typical duty hours for lifetime lubricated bearings.
Frame sizePolesTypical lifetime
56 - 1602 - 840,000h
180235,000h
200227,000h
225223,000h
180 - 2254 - 840,000h
Motors with a re-greasing system must be lubricated with
high quality lithium complex grease, NLGI grade 2 or 3, with
a temperature range of between -40°C to +150°C.
Motors are normal fitted with a data plate with greasing
information; if it is missing use the following re-greasing
intervals.
Frame
size
160204200700085008500
180204200700085008500
200253100650085008500
225253100650085008500
250352000600070007000
280352000600070007000
315501500550065006500
355601000400050006000
40080800300040006000
Grease
(g)
2 pole
(h)
4 pole
(h)
6 pole
(h)
8 pole
(h)
Grease the motor while running, open the grease outlet plug
and let the motor run 1-2 hours before the outlet grease plug
is closed again.
Grease the motor for the first time during commissioning.
The following applies in general for both lifetime lubricated
and re-lubricated bearings:
At 60Hz the time will be reduced by app. 20%.
Data for vertically mounted motors are half of the above
values.
The table values are based on an ambient temperature of
25°C. The values must be halved for every 15K increase in
bearing temperature.
Higher speed operations, e.g. frequency converter drive will
require shorter greasing intervals. Typically, doubling the
speed will reduce the values by 50%.
Special note for Atex Zone 22 and nA motors
Designation of motor according to IEC standard:
II 3D Ex tc IIIB T120°C
II 3G Ex nA IIC T3
The hazardous 3-phase asynchronous motors are in
accordance with International standard IEC 60079-31 and
IEC 60079-15.
Only one electrical installation may be installed in one
specified area (zone).
Only certificated cable glands may be used. Unused glands
must be closed.
Connections must be made in such a way as to ensure that
a permanently safe electrical connection is maintained, both
for the main supply and earth connection.
Installations must be in accordance with actual standards
for installation in hazardours area.
It is recommended that the IEC standard is followed according
to temperature and dust on the motor surface.
The use of motors with so much surface dust that the motor
temperature increases is not permitted.
Regularly cleaning is recommended.
The radial shaft sealing ring is part of the ATEX certification.
It is important that the ring is always intact.
The shaft sealing must be regularly checked, and if dry it
must be lubricated. It is recommended that the seal is relubricated regularly.
Always use the original seal ring when replaced.
Replacing bearings also means replacing the seals.
All machines must be inspected regularly for mechanical
damage.
The user is responsible for changing parts in accordance
with the lifetime of parts, in particular:
bearings, grease and lubrication of shaft sealing.
Maintenance, repairs and replacement on this type must
only be carried out by qualified specialists.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022