Danfoss iSave 50, iSave 70 Operating guide

Frontpage
Operating guide
Manual del usuario
Energy Recovery Device
Manual de instalacn,
funcionamiento y mantenimiento
Maintenance Manual
iSave 40
hpp.danfoss.com
isave.danfoss.com
Operating guide | iSave 50 - 70
Table of Contents 1. Validity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.1 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.2 Target group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Manufacturer and customer service address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.5 Country specific information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.5.1 United Kingdom . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.6 Additional technical documents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3. Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
3.1 General ............................................................................... . 6
3.2 Intended use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
3.3 Application range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
3.4 Preferred system design. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4. Arrival, inspection, handling and storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
4.1 Arrival inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
4.2 Return to the supplier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
4.3 Handling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.4 Assembly iSave on electric motor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.5 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
4.6 Outdoor storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
5. Technical data and design review. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
5.1 Design details. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
5.2 Sound level of the iSave . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
5.3 Materials. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
5.4 Temperature and corrosion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.5 Dimensions and weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.6 Electrical motor data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
5.7 How does the iSave work?. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.8 Seawater quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.8.1 Pre-filtration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.8.2 Air bubbles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.8.3 Chemicals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.8.4 Initial start up and flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.9 Initial start up and setting of safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.10 Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.11 CIP or membrane cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
5.12 High pressure remains after shutdown. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
5.13 Over-pressurisation caused by low pressure isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
5.14 Over-pressurisation caused by high-pressure pump. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
5.15 Preferred system design and P&ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
6. On-site installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
6.1 Design details. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
6.2 Installation and alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
6.3 Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
6.4 Piping and joints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
6.5 Mounting of coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
6.6 Accessibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
6.7 Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
6.7.1 Electric motor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
6.7.2 Speed control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
6.7.3 Starting torque on the iSave. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
6.7.4 Torque overload pretection on the iSave. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
7. Commissioning, start-up and shutdown ................................................16
7.1 Safety regulations......................................................................16
7.2 Support................................................................................16
7.3 Commissioning ........................................................................16
2
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Operating guide | iSave 50 - 70
8. Service/Maintenance...................................................................17
8.1 Safety regulations......................................................................17
8.2 Support................................................................................17
8.3 Maintenance schedule .................................................................17
8.4 Recommended service intervals on internal parts .......................................18
8.5 Lubrication of bearings in electric motor................................................18
9. Trouble shooting.......................................................................19
9.1 Safety regulations......................................................................19
10. Appendices............................................................................21
10.1 Data sheet iSave 50-70 - (521B1378)) ....................................................23
10.2 Start and stop procedures (180R9213). ..................................................45
10.3 Membrane cleaning of the RO system with iSave unit (180R9214) . ......................51
10.4 APP pumps and iSave overload protection(180R9372)...................................57
10.5 Hose assembly and installation (180R9084) .............................................67
10.6 iSave part list 50-70 (521B1428) .........................................................75
10.7 Operating- and maintenance instruction, electric motor (180R9230).....................87
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
3
Operating guide | iSave 50 - 70
1. Validity Document information and copyright
Installation, Operation and Maintenance Manual. Danfoss can accept no responsibility for possible errors in the manual and instructions. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All rights reserved. Contents provided herein must neither be distributed, copied, reproduced, edited or processed for any other purpose, nor otherwise translated or published without Danfoss’ express written consent.
PUMP
Type iSave 50 ERD Code no. 180FXXXX
Serial no. XXXXXX02-XXX
MADE IN DENMARK
Danfoss A/S, 6430 Nordborg, Denmark
This manual is valid for iSave 50 -70
Code No./Description Serial no.
180F7020 iSave 50 without motor
180F7021 iSave 70 without motor
180F7038 iSave 50 Vertical (IEC motor)
180F7023 iSave 50 horizontal (IEC motor)
180F704 0 iSave 70 vertical (IEC motor)
180F7025 iSave 70 horizontal (IEC motor)
XXXXXX02-XXX
XXXXXX02-XXX
XXXXXX02-XXX
XXXXXX02-XXX
XXXXXX02-XXX
XXXXXX02-XXX
The serial number is referring to the Serial no. on the product label. The digits shown (02) indicate the version number of the pump. This document is only valid for ERD version 2 and upwards.
4
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Operating guide | iSave 50 - 70
2. Introduction 2.1 General
iSave is manufactured by Danfoss A/S, and is sold and marketed by a net of authorised distributors world wide.
This manual contains the necessary instructions for the installation, operation and service of the iSave.
All personnel who are responsible for the operation and maintenance of the iSave unit must read and fully understand these instructions, especially the section “Safety” before:
Transporting of the iSave unit.
Lifting the unit.
Installing the iSave unit on a frame.
Connecting the iSave unit to the fluid system.
Connecting the electrical motor and instrumentation.
Commissioning the unit.
Servicing the iSave unit, mechanics and electrics.
Decommissioning the iSave unit.
Ensure that these instructions are always readily available to all personnel concerned.
2.3 Symbols
Indicates something to be noted by
the reader.
Indicates a situation which will or
couldresult in damage to the iSave and its function.
Indicates a situation which will or could result in personal injury and/or damage to the iSave.
Electrical hazard. Indicates a high-voltage warning
Safety glasses required
Hearing protection required
Safety shoes required
Safety helmet required
2.4 Manufacturer and customer service
Danfoss A/S High Pressure Pumps DK-6430 Nordborg, Dinamarca Tel.: +45 7488 2222 E-mail: highpressurepumps@danfoss.com Homepage: hpp.danfoss.com
2.2 Target group
This manual is intended for use by personnel with qualified training and experience in the operation and maintenance of a Sea Water Reverse Osmosis (SWRO) or Brackish Water Reverse Osmosis (BWRO) system.
2.5 Country specific information
2.5.1 United Kingdom
Danfoss Ltd. 22 Wycombe End HP9 1NB Beaconsfield United Kingdom
2.6 Additional technical documents
Below documents are not present in this Operating guide. Please contact Danfoss.
Document name Content
Service guide: 180R9387 Disassembling and assembling
Design guide: 180R9367 Pipe connection
Guide line: 180R9371 Pressure safety valve in SWRO systems
Guide line: 180R9370 Review sheet P&ID
Description of how to disassemble and assem­ble the iSave
Design guide on how to make har piping with Victaulic clamps
Guide line on how to evaluate if a safty valve is needed in a SWRO system
Detailed description about the need for each individual component in the preferred P&ID
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
5
Operating guide | iSave 50 - 70
3. Safety 3.1 General
The iSave must not be used for other purposes than those recommended and specified without first consulting your local iSave distributor.
This manual must be read and completely understood by the responsible specialist personnel prior to installation and commissioning. Use of this manual does not relieve operation and maintenance personnel of the responsibility of applying normal good judgment in the operation and care of this product and its components.
This manual must be available to all personnel concerned at the site at all time.
An iSave must always be installed and used in accordance with existing national and local sanitary and safety regulations and laws. It is the responsibility of the safety officer or the chief operator to assure compliance with all local regulations that are not taken into account in this manual.
The iSave is a rotating machine that typically operates at high pressure.
Improper installation can cause fatal injuries.
The iSave must not operate outside the application range.
During the initial start-up, slowly raise the pressure of the system and adjust the over-pressure protection equipment for proper limit settings.
Make sure that the pressure is released from the iSave before the iSave is disconnected from any pipe or hose connections.
Make sure that the iSave can be drained without injuring anyone and without contaminating nearby equipment or the environment.
Before intervening in the iSave/system, the power must be shut off and the starting device must be locked. When intervening in the iSave unit, follow the instructions for Service/Maintenance, chapter 8.
A failure not to follow the instructions can result in personal injury and/or damage to the iSave. It will also invalidate the warranty.
Always wear suitable safety and lifting equipment when handling the iSave.
Bolt the iSave properly to the base before start-up to avoid personal injury and/or damage to the iSave.
The pipe connections to the iSave must be stress-free mounted, securely fastened to the iSave and well supported. Improper installation will or could result in personal injury and/or damage to the iSave.
Proper installation and care of shutdown devices and over-pressure protection equipment is essential.
All electrical installation work must be carried out by authorised personnel in accordance with EN60204-1 and/or local regulations.
Install a lockable circuit breaker to avoid inadvertent starting. Protect the motor and other electrical equipment from overloads with suitable
equipment.
The electric motors must be supplied with adequate cooling ventilation.
The iSave must never run dry. Dry running produces heat and will cause damage to internal parts.
If the iSave does not function satisfacto­rily, contact your local iSave distributor.
Use of this manual does not relieve
operation and maintenance personnel of the responsibility of applying normal good judgment in the operation and care of this product.
3.2 Intended use
The iSave is designed for use as energy recovery device in Sea Water Reverse Osmosis (SWRO) or Brackish Water Reverse Osmosis (BWRO) system. The iSave must not be used for other purposes than recommended and quoted for without consulting your local iSave distributor.
3.3 Application range
For application range see data sheet 521B1378 available in appendix 10.1.
Applications not suitable for the iSave can cause damages to the iSave unit, with risk of personal injury.
6
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Operating guide | iSave 50 - 70
3.4 Preferred system design
Danfoss recommends building systems with a high degree of safety. Our preferred system design can be found in the data heet in appendix
10.1.
It is always the system builders’ responsibility that the system design does not cause any form of hazard and are adapted to local regulations.
Proper installation and care of shutdown devices and over-pressure protection equipment is essential.
4. Arrival inspection, handling and storage
4.1 Arrival inspection
The iSave is packed in a wood container. The iSave ports connector are protected by plastic caps that protect the iSave against dust and particles. Do not remove the caps before the system have been flushed and the iSave can be installed.
Remove all packing materials immediately after delivery. Immediately check the shipment for damage on arrival and make sure that the name plate/type designation is in accordance with the packing slip and your order.
In case of damage and/or missing parts, a report should be drawn up and presented o the carrier at once.
The identification label on the iSave states the specific type, the serial number and the code number of the iSave; see fig. below. The last three digits of the Serial No. indicate the week and year of production.
PUMP
Type iSave 50 ERD Code no. 180FXXXX
Serial no. XXXXXX02-XXX
4.2 Return to the supplier
Flush the iSave with clean water. Drain the iSave and plug the port connections with a cap/cover.
MADE IN DENMARK
Danfoss A/S, 6430 Nordborg, Denmark
4.3 Transport and Handling
Personnel involved in lifting and transportation of the equipment must be trained in proper handling and safety procedures.
Observe the local regulations regarding lifting.
Use suitable, permitted lifting equipment.
The iSave (set) could slip the lifting arrangement.
Be aware of individuals located in the operation area while lifting the component.
The weight of the iSave including electric motor can be found in the datasheet. All parts weighing more than 20 kg (44 lb) must be lifted using lifting slings and suitable lifting devices, e.g. an overhead crane or fork lift.
Do not use connections/nozzles for
lifting. Do not use only one sling! Make sure that the load is balanced before attempting the lift.
Pack the iSave into a suitable container and make sure that it is suitably fastened to the container.
Please coordinate the shipment with your local authorized distributor or contact anfoss direct to obtain a return shipping address.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
When lifting the ERD without motor use the lifting eye
s.
When you have finished using the lifting eyes, remove them to prevent corrosion.
7
Operating guide | iSave 50 - 70
When the iSave is mounted with an electric motor (horizontal), it must not be lifted in the lifting eye. An iSave assembled with motor (horizontal) must be handled by using two slings around the unit. One sling must be attached to the electric motor and one sling around the iSave. Make sure that the unit/load is balanced before lifting. The centre of the mass may vary.
Some motors and pumps have specific lifting eyes.
Do not use connections/nozzles for lifting! Always use two slings.
Lifting the iSave with electric motor (vertical):
The two lifting belts around the bell housing before lifting the unit.
Lift the iSave unit with only one fastening point. Incorrect lifting can result in personal injury and/ or damage of the unit.
4.4 Assembly iSave to electric motor
A: Elastic coupling B: Bell housing C: iSave shaft D. iSave flange
1. Mount the coupling flush or maximum 1 mm offset from the iSave shaft end. Ensure an air gap between coupling parts of 3-5 mm (0.12-0.2 inch).
2. Mount the bell housing on iSave. Secure nuts with the right torque.
3. Measure the longest distance “A” from top of bell housing to the button of coupling claw.
4. Mount the coupling on motor shaft. Ensure the coupling and motor flange are not in contact with each other.
5. Measure from motor flange to the top of the coupling. That measurement “B” shall be 3-5 mm (0.12-0.2 inch) shorter than the measure me nt “A”.
(“A” and “B” can be found on the next page).
8
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Operating guide | iSave 50 - 70
1: Bolts: torque 100 Nm 2: Screw: torque 40 Nm 3: Torque see table below
6. Adjust respectively, verify the measure ment, and secure both couplings with the right torques on the locking screws (see coupling operation & mounting instruc tion).
7. Mount the elastic gear ring and mount the bell housing/iSave on the motor. After mounting it must be possible to move the elastic gear ring 3-5 mm (0.12 -
0.2 inch) axial “C”. The check can be done through the inspection hole of bell housing. Secure flange bolts with the right torque.
2 3 1
If alternative mounting is desired, please contact Danfoss High Pressure Pumps.
Choose proper tolerances to ensure an easy mounting of the elastic coupling without use of tools.
Please take care to observe the recommended length tolerances of the chosen coupling, as an axial force on the pump will damage the pump.
(“C” can be found on the drawing below).
Thread size M5 M6 M8 M10
Torque (Nm) 2 4.8 10 17
Details on how to install iSave 50/70 on Danfoss vertical and horizontal frame can be found in the Service guide 180R9387.
4.5 Storage
When each iSave is tested before shipment in demineralized water. When tested the iSave is emptied and “plugged”, this will prevent frost damages. The storage temperature is is:
-40 °C to +70 °C (-40°F to 158 °F) – provided that the iSave is drained of fluid and stored “plugged”.
Frost protection is required if the iSave is not completely drained of fluids at temperatures below 1 °C .
Storage of iSave that have been in operation: For shorter periods of storage flush the iSave with permeate and store. For long term storage (more than 2 months) Danfoss recommends servicing the product and clean any biological growth of the surfaces. Store the pump dry witout water inside.
3-5 mm
Danfoss recommends using DOWFROST from DOW Chemical Company or Chillsafe mono propylene glycol from Arco Chemical Company.
For further information on anti-freeze media, please contact Danfoss High Pressure Pumps.
The iSave is NOT delivered frost-protected from the factory. Only remove caps from the openings of the iSave at the time of installation.
4.6 Outdoor Storage
For outdoor storage cover the iSave (set) with waterproof material.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
9
Operating guide | iSave 50 - 70
5. Technical data and design review
1: 3” Victaulic connections 2: Shaft 3: Low pressure shaft seal 4: Port flange 6: Valve plate 7: Cylinder drum 9: Port plate (brine) 10: Port pllate (sea water) 11: Vanes 12: Coupling 13: Intermediate flange 14: Rotor 15: Rotor element 16: Sealing plate 17: Stator 18: Motor end flange
5.1 Design details
5.2 Sound level of the iSave
The A-weighted sound pressure level @ 1m, L
is for the iSave including the iSave motor.
PA, 1M
Measurement are according to EN ISO 3744:2010. The test is made under following conditions:
1. iSave and electrical motor mounted on Danfoss base plate.
2. Baseplate is isolated from concrete ground by rubber vibration dampers.
3. Flexible hoses are used on high pressure and low pressure sides of the iSave.
4. Rotation speed is max. rpm
5. System pressure max. allowable working pressure and a booster pressure of 3 barg.
Influences
Since the iSave is mounted on a base plate and connected to the electromotor by a bell housing, the noise level can only be determined for the complete unit (system). It is therefore important that the iSave unit is mounted correctly on a frame with dampers to minimise vibrations and noise.
Alternativamente, emplee acoplamientos Victaulic® flexibles en la tubería rígida.
The noise level is influenced by:
The speed of the iSave. High speed creates more noise than low speed.
Rigid mounting of the iSave baseplate generates more noise than flexible mounting
Pipe mounting directly to the iSave increases the noise level compared to flexible hoses.
Higher pressure provides higher sound level.
5.3 Materials
All critical parts of the iSave are made of super-duplex 1.4410/UN S32750/1.4462/ UN S32205/S31803 or the like. Non-critical parts that are not in contact with sea water are made of AISI 316. The shaft to the electrical motor is sealed by a standardised mechanical seal.
It is also strongly recommended to use high­pressure flexible hoses between the hard piping in the RO plant and the iSave. See “Hose assembly and installation” ­180R9084 in chapter10.5 and Guide line Pipe connections 180R9367. Alternative use multiple flexible Victaulic® couplings on the hard piping.
10
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Operating guide | iSave 50 - 70
5.4 Temperature and corrosion
The chart below illustrates the corrosive resistance of different types of stainless steel related to NaCl concentration and temperature.
º
80
C
Duplex
70
60
50
316L
40
30
20
100
1000
160 1600
Depending on the NaCl concentration, the fluid temperature must be between:
+2 °C y 50 °C (35,6 °F y 122°F).
Super Duplex
10 000
16000
100 000
160000
CI ppm
NaCI ppm
-
In order to minimise the risk of crevice
corrosion, always flush the iSave according to the specified start/stop procedure.
5.5 Dimensions and weights
For dimensions and weights please refer to the iSave datasheet. See appendix 10.1
5.6 Electrical motor data
See datasheet in appendix 10.1 and “Operating and Maintenance instructions, electric motor” in appendix 10.7
5.7 How does the iSave work?
Figure 5.1 shows a section view of the iSave.
The iSave consists of a rotating isobargic pressure exchanger and a positive displacement pump, also called booster pump. The rotation speed of the pressure exchanger and the pump is exactly the same, as they are driven by the same electric motor.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
11
Operating guide | iSave 50 - 70
5.8 Seawater quality
5.81 Pre-filtration
It is important that the incoming water is filtered properly to assure optimum service life of the iSave. A true graded density melt-blown depth filter cartridge rated at 3 μm is therefore recommended. Poor pre-filtration of the feed water will result in reduced service life of the iSave.
The iSave may request a different pre-filter of the seawater than the HP pump and other omponents in the RO system.
It is important to use a proper filter housing that allows a good seal between housing and filter cartridge. If there is a high risk of water by-pass it is recommended to use a second stage filter solution.
As the various filters on the market differ greatly, Danfoss High Pressure Pumps recommends using cartridges with consistent, reliable performance and high efficiency, in which fibres are blown continuously onto a central support core.
Danfoss High Pressure Pumps does not recommend cartridges requiring any type of binders or resins.
Filters can be purchased from Danfoss High Pressure Pumps.
5.8.3 Chemicals
The iSave can be flushed with biocide like the membranes. The biocide must be compatible with the materials used in the iSave. iSave material can be found in the parts list, appendix 10.6.
5.8.4 Initial start up and flushing
Prior to the initial start-up, all piping associated with the iSave unit should be thoroughly flushed to assure that no impurities enter the iSave. Inadequate pre-flushing will strongly affect the life of the iSave and may lead to its eventual breakdown. It is essential that the water used for the final pre-flush is pre-filtered to a level described in chapter 5.8 It is recommended to disconnect all connections to the iSave and to thoroughly flush the piping before the iSave is connected to the inlet and outlet connections.It is recommended to install temporary basket strainers at both inlets to the iSave during the initial start-up and commissioning. Strainers do not eliminate the need for thoroughly pipe flushing before commissioning.
Also see “Instruction for start and stop of the SWRO with iSave unit” - 180R9213 in appendix 10.2.
5.9 Initial start up and settings of safety equipment
The system designer is responsible to design the equipment according to the local regulations where the equipment is running. According to PED 2014/68/ EU a risk assessment must be made to identify and evaluate hazards which apply to his equipment on account of pressure.
For more information on the importance of proper filtration, please consult our publication “Filtration”, AI317041322125en-000201 which also will provide you with an explanation of filtration definitions and guidance on how to select the right filter.
5.8.2 A ir bubbles
Large bubbles in a pressurised RO system can result in damage to piping and equipment. All air must be bleed from both the LP and HP before the RO system is pressurised. Special consideration should also be given to air bubbles in feed flow, continuously fed into the HP pump and iSave.
Where under reasonable foreseeable conditions, the allowable limits could be exceeded, the pressure equipment must be fitted with, or provision made for fitting of a suitable protective device. Dischage pressure on the pump is generated only by the restriction in the pipelines, valves and membranes.
The pump can build up pressure that will exceed the mechanical strength of the membrane vessels, pipes and other accessories. The pressure rise can be fast and may exceed the response time for electrical safety equipment, like pressure switch and control loop.
12
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Operating guide | iSave 50 - 70
To prevent such over-pressurisation, appropri­ate relief valves should be used and proce­dures should be implemented to safeguard the HP and LP sides of the iSave and/or the RO system.
5.12 High pressure remains after shutdown
The HP line of the RO system equipped with an iSave can remain pressurised for a long time after shutdown. Pressure decreases as water slowly leaks through the iSave. If more rapid system depressurisation is required, the system should be bled through a suitable valve on the HP concentrate line.
trado HP.
5.10 Flushing
RO membranes require periodic flushing to limit biological fouling. There are two types of flushing: feed water (Seawater) flush and fresh water (Permeate) flush. Regardless of the flush water used, the water must be pre-filtered to the level described in chapter 5.8. All parts of the iSave must be flushed, i.e. LP- and HP flow channels.
Follow the guide line 180R9213 “Start and stop of the SWRO with iSave in appendix 10.2.
It is required to flush with permeate:
After chemical treatment
For stop more than 1 day the iSave must be rotated during permeate flush
Before long time shut down
It is required to flush with fresh sea water prior to every shut down.
Special attention should be given to the pressure in the HP line (7) as the iSave may start to cavitate when it runs at high speed and the pressure in the P line (7) drops below 2 bargs. This can be avoided by reducing the speed of the iSave and keeping the pressurein the HP line at the minimum of 2 barg. At this low pressure the iSave may only run for a maximum of 10 minutes.
Always check the pressure in the high-pressure lines before making service in the HP lines or pressurised equipment.
5.13 Over-pressurisation caused by low pressure isolation
If the low-pressure side of the iSave is blocked and the iSave is exposed to high-pressure, there is a risk that the iSave or the LP piping could be damaged by over-pressurisation.
To prevent such over-pressurisation, appropriate relief valves should be used and procedures should be implemented to assure that the HP of the iSave is depressurised prior to the isolation of the LP side..
5.14 Over-pressurisation caused by the high-pressure pump.
Discharge pressure on the pump is generated only by the restriction in the pipelines, valves and membranes. The pump can build up pressure that will exceed the mechanical strength of the membrane vessels, pipes and other accessories. The pressure rise can be fast and may exceed the response time for electrical safety equipment, like pressure switch and control loop.
Failing to flush the iSave with fresh water before extended shutdowns may result in extensive biological growth and cause corrosion in the iSave and other equipment in the RO system.
5.11 CIP or membrane cleaning
The purpose of membrane cleaning is to reduce scaling and fouling in the membranes. For optimal performance specific chemicals are required, depending on the cause of the pollution. After chemical treatment the system must be flushed with permeate.
The flush water coming out of the membranes may consist of a large amount of suspended inorganic particles. It is important to assure that hese particles must not enter the iSave as the waste product of flushing exceed the iSave filtration.
Also see instruction “Membrane cleaning of RO system with iSave unit” in appendix 10.3.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
To prevent such over-pressurisation, appropriate relief valves should be used and procedures should be implemented to assure that the HP of the iSave is protected against excess pressure.
5.15 Explanation of P&ID set-up
See data sheet in appendix 10.1.
13
Operating guide | iSave 50 - 70
!
6. On-site installation 6.1 Design details
For safety instruction see chapter 3.
6.2 Installation and alignment
The figure below illustrates the major iSave components.
An unlocked bolt can result in personal injury and/or damage to the iSave
Misalignment of the base frame to the iSave may cause stress and/or damage.
6.3 Orientation
The iSave can be mounted horizontally and vertically.
When mounted vertically, the electric motor must be placed above the iSave.
6.4 Piping and joints
Piping material and schedule is of high importance. The strength of the Victaulic® connections is influenced by the material used for both the Victaulic® clamps and the hard piping.
The hard piping and connections used must be of proper design and must be installed in accordance with the manufacturer’s recommendations.
Hard piping to the iSave must be properly aligned to avoid stress on the iSave port connections. Pipe connection must be aligned as shown in the figures next page. Don’t use the iSave as a strain for hard piping.
The iSave is connected to the electric motor by the bell housing and a flexible coupling. If not using Danfoss base frame both the iSave and the motor must be supported without applying stress/load to the bell
Ccrrect piping alignment Incorrect piping alignment
housing. Danfoss provides the iSave with a base frame and support brackets. Although the base frame is of a sturdy design, it can flex or bend when it is bolted to the foundation. The base frame thus requires a solid foundation such as concrete or rigid steel frame. The base frame itself must be aligned to avoid bending caused by bolting to an uneven foundation.
Incorrect piping alignment
A rigid foundation for the iSave assembly is important, and must fulfil Eurocode 2: EN1992-1-1, and the iSave assembly must be bolted to the foundation with M12 bolts. The bolts used must be of proper design and must be installed in accordance with bolt manufacturer’s recommendations. To reduce noise it is recommended to use resilient mounts between the baseplate and
The hard piping and connections used must
be of proper design and must be installed in accordance with the manufacturer’s recom-
mendations. the foundation. Make sure that the bolts are properly locked and will stay locked over time.
A failure to comply with this will or may result
in personal injury and/or damage the iSave.
14
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Operating guide | iSave 50 - 70
Misalignment of the hard pipes may place stress on the iSave port connections and may damage the iSave.
6.5 Mounting of coupling
The figure below illustrates how to mount the flexible coupling between the iSave and to connect it to the electric motor..
100 NM ± 10 NM
Min. 3 -5 mm air space
A
PUMP
Type iSave 50 ERD Code no. 180FXXXX
Serial no. XXXXXX02-XXX
MADE IN DENMARK
Danfoss A/S, 6430 Nordborg, Denmark
When connecting to the power supply, check the direction of rotation. The rotation can only be checked with water connected and iSave bleeded. This can be made by:
1. Looking at the fan in the end of the electric motor.
2. Removing the plug in the bell housing and watch the rotation of coupling.
3. Before assembling the iSave on the electric motor, check the rotation of the shaft on the electric motor.
C
B
A: Flexible coupling
40 NM ± 4 NM
B: Bell housing C: Motor shaft
Any axial and radial load on the shaft must be avoided.
6.6 Accessibility
With respect to the service and replacement of the complete iSave unit, it is recommended to maintain sufficient space around the unit.
The space must be sufficient enough to allow for safe lifting of the equipment, with no risk for personal injury and/or damage to the iSave.
6.7 Drives
6.7.1 Electric motor
The iSave must only be driven by an electric motor.
Special attention has to be on NON PROTECTED - FREE ROTATING shaft on the electric motor. Ignorance will or could result in personal injury.
Running the iSave in the wrong direction for more than a few minutes can cause un­intended wear on the iSave. If the electric motor is running at a lower speed, extra care must be taken to ensure that the electric motor is NOT overheated. External cooling may be necessary.
6.7.3 Starting torque for the iSave
Because of the inertia and stick-slip friction of the iSave internal parts, the torque may exceed the maximum allowable operation torque for the iSave when the speed is ramped up from zero to maximum.
It is required to use a VFD. See Danfoss guide line 180R9372 “APP pumps and iSave overload protection”.
Using anything other than an electric motor can lead to an irreparable fracture of the iSave’s internal parts.
6.7.2 Speed control
The rotation speed on the electric motor can be controlled by a VFD. The VFD must be able to operate at constant torque over the whole range of speed. The direction of rotation can be seen on the identification label.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
15
Operating guide | iSave 50 - 70
7. Commissioning, start-up and shutdown
6.7.4 Torque overload protection on the iSave
The electric motor and iSave must always be protected against overload.
As continuously operation the maximum torque on the iSave must be monitored.
The electric motor must be shut off if the maximum torque of the iSave exceeds the defined limit.
If more electric motors are powered by the same VFD, each electric motor must be equipped with “torque limit equipment” to protect the iSave against overload.
Below are examples of equipment which can measure the load on the electric motor or limit the torque on the iSave.
7.1 Safety regulations
The operator ensures that all inspection and installation work is performed by authorised, qualified specialized personnel who are thoroughly familiar with the manual..
Before starting up the iSave and the high-pressure pump, make sure that the following requirements are met:
The iSave has been properly connected to the electric power supply and is quipped with all protection devices in accordance with EN 60204-1
Check that all motor protections are properly set.
All safety equipment, auxiliary equipment and connection required are properly connected and operational.
Check all bolts in all connections and in the foundation of the iSave and the pumps.
7.2 Support
Danfoss A/S offers commissioning and service at system manufacturer’s location. Rated quotes are offered upon request.
1. VFD with integrated current monitoring relays.
2. External current monitoring relays suitable­for VFD control.
The electric motor and iSave must always be protected against overload. See Danfoss guide line 180R9372 “APP pumps and iSave overload protection” in the appendix
10.4.
If torque exceeds the maximum operation torque, it may lead to an irreparable fracture of the iSave’s internal parts.
7.3 Commissioning
Before starting up the iSave and the highpres­sure pump, make sure the following requirements are met:
All pipes are flushed, free from debris and full of water.
The iSave has been bled and is full of water.
At pressure lower that 10 barg, check the system for leakage.
Slowly raise the pressure in the system and set all pressure switches to the correct limit and continually check all connections.
If pressure relief valve is present, set pressure relief valve on both low and high-pressure at the maximum system pressure.
Check high-pressure hoses for proper assembly and inspect for external leakage for all connections.
At low pressure, start the iSave and check direction of rotation.
“Start and stop procedure” Guide line 180R9213. - appendix 10.2.
16
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Operating guide | iSave 50 - 70
8. Service/Maintenance 8.1 Safety regulations
The operator ensures that all maintenance, inspection and installation work is performed by authorised, qualified specialist personnel who are thoroughly familiar with the manual.
Before intervening in the iSave/system:
The power must be shut off and the main switch must be locked.
The pressure in the high-pressure lines must be drained to the low-pressure side.
The water in all connected pipes must be drained.
Always use suitable safety and lifting equip­ment when handling the iSave, and follow the instructions in chapter 4.3.
Assure correct settings of safety equip­ment before start-up.
When the system is re-started after service and maintenance follow the instruction in chapter 8 and in “Start and stop procedures” in guide line 180R9213 in appendix 10.2.
Three months after commissioning:
1. Re-check bolts in the foundation and the base plate of the iSave and tighten the bolts to specified torque if necessary.
2. Re-check alignment of the iSave base plate and iSave.
3. Visually inspect all pipe connections/ couplings for external leakage.
4. Re-check bolts in all pipe connections/ couplings and tighten the bolts to specified torque if necessary.
1. Replace filters if necessary.
2. Clean the filter housing and install the new filter. Make sure no debris enters the system.
3. Audibly inspect the iSave assembly. If there is irregular sounds or vibration inspect the internal parts of the iSave and replace if necessary.
Half year:
1.
For vertical mounted electric motor lubricate motor bearings.
8.2 Support
Danfoss A/S offers commissioning and service at the system manufacturer’s location. Tates/quotes are offered upon request.
8.3 Maintenance schedule
The schedule of preventive maintenance below will help ensure that the iSave provides years of trouble-free performance.
One day after commissioning:
1. Re-check bolts in the foundation and the base plate of the iSave and tighten the bolts to specified torque if necessary.
2. Visually inspect all pipe connections/ couplings for external leakage.
3. Re-check bolts in all pipe connections/ couplings and tighten the bolts to specified torque if necessary.
1. Replace filters if necessary.
2. Clean the filter housing and reinstall filters. Make sure no debris enters the system.
Annually:
1. Re-check bolts in the foundation and the baseplate of the iSave and tighten the bolts to specified torque if necessary.
2. Re-check alignment of iSave base plate and iSave.
3. Visually inspect all pipe connections/ couplings for external leakage.
4. Re-check bolts in all pipe connections/ couplings and tighten the bolts to specified torque if necessary.
1. Replace filters if necessary.
2. Clean the filter housing and nstall the new filter. Make sure no debris enters the system.
3. Visually inspect iSave coupling and replace if necessary.
4. Audibly inspect the iSave assembly. If there is irregular sounds or vibrations inspect the internals parts of the iSave and replace if necessary.
5. Check power consumption. If there are irregular parts of the iSave and replace if necessary.
6. Lubricate motor bearings.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
17
Operating guide | iSave 50 - 70
8.4 Recommended service intervals on internal parts
Se below table. For detailed information on parts see Service guide 180R9392 Parts list.
Description Service interval Service interval (2nd, 3rd)
Tool kit Screw and seal kit 32.000 hours 26.000 hours Shaft seal kit 32.000 hours 26.000 hours Coupling kit 56.000 hours 56.000 hours
Port plate kit (PE), iSave 50
32.000 hours 26.000 hours
Port plate kit (PE), iSave 70 32.000 hours 26.000 hours Vane kit (8 pcs) Valve kit, Pressure exchanger 32.000 hours 26.000 hours Rotor element and sealing plates kt 32.000 hours 26.000 hours
8.5 Lubrication of bearings in electric
motor
Motors with a re-greasing system must be lubricated with high quality lithium complex grease, NLGI grade 2 or 3 with a temperature range between -40 °C to 150 °C.
For electric motors in vertical mount; grease every 6 months.
For electric motor in horizontal mount; grease every 12 months.
If the motor has increased vibrations or sound check the bearings.
Follow manufacturer’s recommendations for electric motor service and maintenance, see appendix 10.7.
18
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Operating guide | iSave 50 - 70
9. Trouble-shooting 9.1 Safety regulations
Before intervening in the iSave/system: The operator ensures that all inspection and installation work is performed by authorised, qualified specialist personnel who are thoroughly familiar with the manual.
The power must be shut off and the starting device be locked.
The pressure in the high-pressure lines must be drained to lowpressure side.
The water in all connected pipes must be drained.
The numbers in () correspond to the preferred system design and P&ID (see data sheet)
Problem Possible cause Action
VFD cannot start the iSave at initial start-up VFD is not designed for constant torque
VFD cannot deliver sufficient start torque
Ramp-up settings in the VFD are not cor­rect. VFD is tilting
Choose a VFD that is designed for constant torque
Choose a VFD that is designed for sufficient start torque. See guide line 180R9372
Set ramp-up parameters correct. See guide line 180R9372
Valve (9) is closed Open valve (9)
Start the iSave only when the pressure in the HP line is low
Clean or change membranes
Torque on iSave is too high during opera­tion
Pressure in the HP line (5) is too high
Pressure difference from HP-out (5) to HP­in (10) is too high
Debris in the booster pump or iSave Clean the system
Wear in the booster pump or iSave Repair or change the parts
Design of the basic plant does not fit the performance of the iSave
Change design to fit the iSave performance
Permeate production is too low (17) Valves (6), (7), (8) or (16) are leaking Repair or change valve(s)
Internal leakage in iSave Repair iSave HP pump flow (2) is too small Correct speed on the HP pump
Check the HP pump and repair if necessary
Pressure on the membranes (5) is too high
Fouling on the membranes Clean the membranes Mixing in the iSave is too high Check flow on LP-in (12) and adjust flow
Flow out of the iSave is too low and causes a recovery rate that is too high
Check speed on iSave and change if neces­sary
Booster pump in the iSave is worn out. Perform service on the VP
Pressure on the membranes (5) is too low
Valves (6), (7), (8) or (16) are leaking Repair or change valve (s) Internal leakage in iSave Repair iSave Pressure on the membranes (5) is too low Incorrect speed on the HP pump
Check the HP pump and repair, if necessary
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
19
Operating guide | iSave 50 - 70
20
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Appendices
Energy Recovery Device
hpp.danfoss.com
Operating guide | iSave 50 - 70
10. Appendices............................................................................21
10.1 Data sheet iSave 50-70 - (521B1378)) ....................................................23
10.2 Start and stop procedures (180R9213). ..................................................45
10.3 Membrane cleaning of the RO system with iSave unit (180R9214) . ......................51
10.4 APP pumps and iSave overload protection(180R9372)...................................57
10.5 Hose assembly and installation (180R9084) .............................................67
10.6 iSave part list 50-70 (521B1428) .........................................................75
10.7 Operating- and maintenance instruction, electric motor (180R9230).....................87
22
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Data sheet
iSave® Energy Recovery Device
iSave 50 / iSave 70
hpp.danfoss.com
Data sheet | iSave 50 and iSave 70
Table of Contents Contents
1. General information....................................................................25
2. Benefits................................................................................25
3. Applications ...........................................................................25
4. Technical data .........................................................................26
4.1 iSave without motor ...................................................................26
4.2 iSave with IEC motor ...................................................................28
4.3 iSave with NEMA motor ................................................................29
5. Performance curves....................................................................30
5.1 Flow at different rpm...................................................................30
5.2 iSave 50 flow curves....................................................................30
5.3 iSave 70 flow curves....................................................................30
5.4 Torque curve for iSave 50 and iSave 70..................................................31
5.5 Mixing curve...........................................................................31
6. Temperature and corrosion.............................................................32
6.1 Operation..............................................................................32
7. Installation.............................................................................32
7.1 Operation and mounting...............................................................32
7.2 Horizontal mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
7.3 Connection to inlet or discharge ports: .................................................33
7.4 Filtration...............................................................................33
7.5 N o ise ..................................................................................33
7.5 RO systems with an iSave...............................................................34
8. Dimensions and connections...........................................................36
8.1 iSave 50-70 without electric motor .....................................................36
8.2 iSave 50-70 with with IE3 motor 18.5 kW on base frame vertical_front mounted .........37
8.3 iSave 50-70 with with IE3 motor 18.5 kW on base frame vertical_back mounted..........38
8.4 iSave 50-70 with with IE3 motor 18.5 kW on base frame horizontal.......................39
8.4 iSave 50-70 with NEMA motor 30 HP on base frame vertical - front mounted .............40
8.5 iSave 50-70 with NEMA motor 30 HP on base frame vertical - back mounted .............41
8.5 iSave 50-70 with NEMA motor 30 HP on base frame horizontal ..........................42
9. Service.................................................................................43
9.1 Warranty...............................................................................43
9.2 Operational conditions of concern......................................................43
9.3 Maintenance...........................................................................43
9.4 Repair assistance .......................................................................43
10. Accessories ............................................................................43
11. Useful documents......................................................................43
24
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Data sheet | iSave 50 and iSave 70
1. General information Energy Recovery Devices (ERD) are used in
reverse osmosis (RO) systems to recycle the energy held in discharged brine from the membranes. Thus, iSave 50 and iSave 70 are designed for use with low viscosity and corrosive fluid such as sea water.
The Danfoss iSave Energy Recovery Devices all consist of an isobaric pressure exchanger and a positive displacement pump combined into one compact unit. The high-pressure booster pump is based on the vane pump principle enabling a very light and compact design. The vane pumps are fixed displacement pumps in which the flow is proportional to the number of revolutions (rpm) of the driving shaft – enabling flow control. Speed control is made by a VFD. The iSave design ensures lubrication of the moving parts by the fluid itself.
1. 3” Victaulic connections
2. Shaft
3. Low pressure shaft seal
4. Port flange
6. Valve plate
7. Cylinder barrel
9. Port plate (brine)
10. Port plate (sea water)
11. Vane s
12. Coupling
13. Intermediate flange
14. Rotor
15. Rotor element
16. Sealing plate
17. Sta t or
18. Motor end flange
All parts included in the iSave 50 & 70 are designed to provide long service life with a constant high efficiency and minimum service required. Unlike a centrifugal pump, it produces a similar flow at a given speed no matter what discharge pressure.
2. Benefits Corrossion resistance (all wetted parts are made
Significant power savings and low specific energy consumption (SEC)
Simple and space-saving installation with both pump and pressure exchanger in one
of high corrosion-resistant materials e.g. Super Duplex or Duplex)
Fewer components
unit
Simple system design and monitoring without requirement for high-pressure flow meters
Simple operation with design that prevents overspin/overflushing
Easy modular service
3. Applications
Danfoss iSave ERDs are built into a broad range of RO desalination plant around the world. Typical applications for iSave 50 - 70 will be:
Containerized solutions for hotels and resorts on islands as well as coastal regions
Onboard systems for ships
Offshore platforms for the oil and gas industry
Municipal and private waterworks
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
25
Data sheet | iSave 50 and iSave 70
4. Technical data 4.1 iSave without motor
iSave size iSave 50 iSave 70
Code number 180F7020 180F7021
Pressure
Max. differential pressure (HP out - HP in)
Min. pressure HP out (min. allowable working pressure)
Max. pressure HP out (Max. allowable working pressure, MAWP)
Min. pressure on HP in, intermittent
Max. pressure LP in (MAWP)
Max. pressure LP in, peak
Min. allowable working pressure LP in
Max. differential pressure (LP in - LP out)
Max. static test pressure (HP in and HP out)
Max. static test pressure (LP in and LP out)
Speed
Min. speed rpm 525 625
Max. speed rpm 650 875
Typical flow
Flow at min. speed, HP out
Flow at max. speed. HP out
Max. lubrication flow at 60 barg (871 psig)
Peak flow, LP in
Max. allowable working flow, LP in
1)
2) 3)
4)
10)
barg 5 5
psig 72 72
barg 40 40
psig 580 580
barg 83 83
psig 120 0 120 0
barg 2 2
psig 29 29
1)
barg 5 5
psig 72 72
barg 10 10
psig 145 145
barg 2 2
psig 29 29
barg 0.53 0.79
psig 7. 69 11.46
barg 108 108
psig 1566 1566
barg 13 13
psig 189 189
m³/h 42 50
gpm 184 220
m³/h 52 70
gpm 228 308
l/min 25 25
gpm 6.6 6.6
m³/h 120 120
gpm 528 528
7)
m³/h 57. 2 70
gpm 252 308
26
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
Data sheet | iSave 50 and iSave 70
Technical specifications
Media temperature
Ambient temperature
Filtration requirements (nominal)
Salinity increase at membrane at 40% recovery rate at balanced flow
Weight (dry)
Weight (operation with water)
Noise
Sound pressure level L
Torque data
Max. allowable working torque
Max. starting torque (stick/slip)
o
5)
6)
9)
C 2-35 2-35
o
F 36-95 36-95
o
C 0-50 0-50
o
F 32-122 32-122
3 micron melt-blown
2-3%
kg 164 164
lb 362 362
kg 172 172
lb 379 379
8)
PA
1 m
dB(A) 83 86
Nm 170 19 0
lbf-ft 12 5 140
Nm 18 0 180
lbf-ft 132 132
1)
Max. allowable working pressure of continous operation. For lower and higher pressure, please contact Danfoss.
2)
Typical pressure level at start-up and permeate
flush.
3)
Intermittent pressure is acceptable for less than 10
minutes within a period of 6 hours.
4)
Typical average flow at 60 barg and 3 barg
differential pressure
5)
Dependent on NaCI concentation.
6)
Please see section 7.4 filtration.
7)
Continuous operation: iSave can operate continuously with up to 10% over flush with the limitation that the flow rate at LP inlet shall not exceed 70 m3/h.
8)
A-weighted sound pressure level at 1 m from the pump unit surfaces (reference box) acc. to EN ISO 20361 section 6.2. The noise measurements are performed acc. to EN ISO 3744:2010 on a motor- pump-unit at max. pressure and rpm.
9)
Balanced flow: The mixing rate is defined at balanced flow when HP-out is equal to LP-in.
10)
At system start-up: iSave can run for up to 10 min. with 150% of max. rated flow at LP inlet. The time where max. rated flow is exceeded should be kept as short as possible to minimize wear.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
27
Data sheet | iSave 50 and iSave 70
4.2 iSave with IEC motor
i
iSave size iSave 50 iSave 70
Code number (vertical) 180F7038 180F7040
Code number (horizontal) 180F7023 180F7025
Pressure, Speed, Flow, Temperature and Torwue are identical with 180F7020 and 180F7021 Efficiency
Efficiency at max. speed at 60 barg (871 psig) % 93.7 92.4
Technical specifications
Media temperature
Filtration requirements (nominal)
Weight (dry) vertical/horizontal
Weight (operation with water) vertical/ horizontal
Noise
Sound pressure level L
Footprint
Footprint (vertical position)
Footprint (horizontal position)
Torque data
Max. allowable working torque
Max. starting torque (stick/slip)
Motor data
Nominal speed rpm 985 985
Rated current at 400V A 37 37
Motor size
Frame size
Rated motor torque at nominal speed
Rated motor ambient temperature
Motor insulation Class B B
Motor degrees of protection IP 55 55
5)
°C 2-35 2-35
°F 36-95 36-95
6)
3 micron melt-blown
kg 441/463 441/463
lb 972/1021 972/1021
kg 470/471 470/471
lb 1036/1038 1036/1038
2)
PA
1 m
3)
dB(A) 83 86
0.44 0.44
foot² 4.71 4.71
3)
0.76 0.76
foot² 8.14 8.14
Nm 170 177
lbf-ft 125 130.5
Nm 180 180
lbf-ft 132 132
kW 18. 5 18.5
HP 30.0 30.0
IEC 200 L 200 L
Poles 6 6
Nm 177 177
lbf-ft 130.5 130.5
4)
°C 40 40
°F 104 104
28
2)
A-weighted sound pressure level at 1 m from the ERD unit surfaces (reference box) acc. to EN ISO 20361 section 6.2. The noise measurement are performed acc. to EN ISO 3744:2010 on an ERD with motor (motor pump unit) from min. to max. pressure and speed.
3
Area covered with recommended IE3 motor
configurations (excl. of space to service the ERD)
4)
For higher temperature, contact Danfoss.
5)
Dependent on NaCI concentation.
180R9357 | AQ265943679828en-001001 IOM iSave 50 - 70 | 02.2022
)
6)
Please see section 7.4 Filtration
7)
Typical efficiency for pressure exchanger, .. booster pump, electrical motor and VFD at 3 barg differential pressure after a system has ... been commissioned and run in.
Loading...
+ 64 hidden pages