Installation, Operation and Maintenance
Manual.
Original operating manual document.
Danfoss can accept no responsibility for
possible errors in the manual and
instructions. Danfoss reserves the right
to alter its products without notice. This
also applies to products already on order
provided that such alterations can be made
without subsequential changes being
necessary in specifications already agreed.
All rights reserved. Contents provided
herein must neither be distributed, copied,
reproduced, edited or processed for any
other purpose, nor otherwise translated or
published without Danfoss’ express written
consent.
The serial number is referring to the Serial
no. on the product label. The digits shown
(02) indicate the version number of the
pump.
This document is only valid for ERD version 2
and upwards.
10.6 Operating- and maintenance instruction, electric motor (180R9230) . . . . . . . . 91
4
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
2. Introduction
2.1 General
iSave is manufactured by Danfoss A/S, and
is sold and marketed by a net of authorised
distributors world wide.
This manual contains the necessary instructions for the installation, operation and
service of the iSave.
All personnel who are responsible for
the operation and maintenance of the iSave
unit must read and fully understand these
instructions, especially the section “Safety”
before:
• Transporting of the iSave unit.
• Lifting the unit.
• Installing the iSave unit on a frame.
• Connecting the iSave unit to the fluid
system.
• Connecting the electrical motor and
instrumentation.
• Commissioning the unit.
• Servicing the iSave unit, mechanics and
electrics.
• Decommissioning the iSave unit.
2.3 Symbols
Indicates something to be noted by
NB!
the reader.
Indicates a situation which will or
couldresult in damage to the iSave
and its function.
Indicates a situation which will or
could result in personal injury and/or
damage to the iSave.
Electrical hazard. Indicates a
high-voltage warning
Safety glasses required
Hearing protection required
Safety shoes required
Safety helmet required
Ensure that these instructions are
always readily available to all personnel
concerned.
2.2 Target group
This manual is intended for use by
personnel with qualified training and
experience in the operation and
maintenance of a Sea Water Reverse
Osmosis (SWRO) or Brackish Water Reverse
Osmosis (BWRO) system.
Danfoss Ltd.
22 Wycombe End
HP9 1NB Beaconsfield
United Kingdom
2.6 Additional technical documents
Document nameContent
DatasheetDescription of the technical data and
dimensions of the iSave
iSave parts listSectional drawings, parts list and spare part
numbers.
Instruction:
start and stop of the SWRO with iSave unit
Instruction:
Membrane cleaning of RO system with
Description of how to start and stop the
iSave in the preferred RO system set-up.
Description of how to clean the membranes
in the preferred RO system set-up.
iSave unit
Instruction:
Hose assembly and installation
Operating and maintenance instructions,
electric motor
Guideline for Hose assembly and
installation
Operating and maintenance instructions for
the standard electric motor, delivered from
Danfoss.
See also appendix 10
6
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
3. Safety
3.1 General
The iSave must not be used for other
purposes than those recommended and
specified without first consulting your local
iSave distributor.
This manual must be read and completely
understood by the responsible specialist
personnel prior to installation and commissioning.
Use of this manual does not relieve operation and maintenance personnel of the
responsibility of applying normal good
judgment in the operation and care of this
product and its components.
This manual must be available to all personnel concerned at the site at all time.
An iSave must always be installed and used
in accordance with existing national and local sanitary and safety regulations and laws.
It is the responsibility of the safety officer or
the chief operator to assure compliance with
all local regulations that are not taken into
account in this manual.
• Improper installation can cause fatal
injuries.
• The iSave must not operate outside
the application range.
• During the initial start-up, slowly raise
the pressure of the system and adjust
the over-pressure protection
equipment for proper limit settings.
• Make sure that the pressure is
released from the iSave before the
iSave is disconnected from any pipe
or hose connections in the iSave.
• Make sure that the iSave can be
drained without injuring anyone and
without contaminating nearby
equipment or the environment.
• Before intervening in the
iSave/system, the power must be shut
off and the starting device must be
locked. When intervening in the iSave
unit, follow the instructions for
Service/Maintenance, chapter 8.
• A failure to follow the instructions can
result in personal injury and/or
damage to the iSave. It will also
invalidate the warranty.
Electrical
hazard
The iSave is a rotating machine that typically
operates at high pressure.
Always wear suitable safety and lifting
equipment when handling the iSave.
• Bolt the iSave properly to the base
before start-up to avoid personal
injury and/or damage to the iSave.
• The pipe connections to the iSave
must be stress-free mounted, securely
fastened to the iSave and well
supported. Improper installation will
or could result in personal injury
and/or damage to the iSave.
• Proper installation and care of
shutdown devices and over-pressure
protection equipment is essential.
• All electrical installation work must be
carried out by authorised personnel in
accordance with EN60204-1 and/or
local regulations.
• Install a lockable circuit breaker to
avoid inadvertent starting. Protect th
motor and other electrical equipment
from overloads with suitable
equipment.
• The electric motors must be supplied
with adequate cooling ventilation.
• The iSave must never run dry. Dry
running produces heat and will cause
damage to internal parts.
• If the iSave does not function
satisfactorily, contact your local iSave
distributor.
Use of this manual does not relieve
NB!
operation and maintenance personnel
of the responsibility of applying normal
good judgment in the operation and
care of this product.
180R9401 | AQ261351057880en- 000801 | 01.2022
7
Operating guide | iSave 21 Plus
3.2 Intended use
The iSave is designed for use as energy
recovery device in Sea Water Reverse
Osmosis (SWRO) or Brackish Water Reverse
Osmosis (BWRO) system.
The iSave must not be used for other
purposes than recommended and quoted
for without consulting your local iSave
distributor.
3.3 Application range
For application range see data sheet
521B1464 available in appendix 10.3.
Applications not suitable for the iSave
can cause damages to the iSave unit,
with risk of personal injury.
3.4 Preferred system design
Danfoss recommends building systems with
a high degree of safety. The P&ID in chapter
5.16 shows the Danfoss preferred system
design.
• It is always the system builders’
responsibility that the system design
does not cause any form of hazard
and are adapted to local regulations.
• Proper installation and care of
shutdown devices and over-pressure
protectio equipment is essential.
8
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
4. Arrival inspection,
handling and storage
4.1 Arrival inspection
The iSave is packed in a wood container with
plugs in the port connections to protect the
unit from damage during transport.
Remove all packing materials immediately
after delivery. Immediately check the
shipment for damage on arrival and make
sure that the name plate/type designation is
in accordance with the packing slip and your
order.
In case of damage and/or missing parts, a
report should be drawn up and presented
to the carrier at once.
The identification label on the iSave states
the specific type, the serial number and the
code number of the iSave; see fig. below.
The last three digits of the Serial No. indicate
the week and year of production.
PUMP
Type iSave 21 Plus ERD
Code no. 180BXXXX
Serial no. XXXXXX02-XXX
MADE IN DENMARK
Danfoss A/S, 6430 Nordborg, Denmark
4.3 Handling
• Personnel involved in lifting and
transportation of the equipment must be
trained in proper handling and safety
procedures.
• Observe the local regulations regarding
lifting.
• Use suitable, permitted lifting equipment.
• The iSave (set) could slip the lifting
arrangement.
• Be aware of individuals located in the
operation area while lifting the
component.
4.2 Return to the supplier
Flush the iSave with clean water. Drain the
iSave and plug the port connections with a
cap/cover.
Pack the iSave into a suitable container and
make sure that it is suitably fastened to the
container.
Please contact your local authorised
distributor or:
Check the mass (weight) of the iSave unit.
All parts weighing more than 20 kg must be
lifted using lifting slings and suitable lifting
Secure lifting slings around the part of
the iSave and the back of the electric
motor. Make sure that the load is
balanced before attempting the lift.
devices, e.g. an overhead crane or industrial
truck. All iSave units weight more than
20 kg.
Once the lifting is done the lifting eye
must be removed from the pump.
Never lift the iSave unit with only one
fastening point.
Incorrect lifting can result in personally
injury and/or damage to the unit.
4.3.1 Centre of mass
604
Never lift the iSave in the bell housing.
Incorrect lifting can result in personally
injury and/or damage to the unit.
10
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
4.4 Storage
Each iSave is tested before shipment and
therefore holds water.
Storage temperature: 1 °C to +70 °C (33 °F to
158 °F) – provided that the pump is drained
of fluid and stored “plugged”.
Frost protection is required at temperatures
below 1°C. Danfoss recommends using
DOWFROST from DOW Chemical Company
or Chillsafe mono propylene glycol from
Arco Chemical Company.
If the iSave is protected against frost, the
storage temperature can be: -40 °C to +70
°C (-40 °F to 158 °F)
• The iSave is NOT delivered
frost-protected from the factory.
• Only remove caps from the openings
of the iSave at the time of installation.
4.5 Outdoor Storage
For outdoor storage cover the iSave
(set) with waterproof material.
180R9401 | AQ261351057880en- 000801 | 01.2022
11
Operating guide | iSave 21 Plus
5.1 Design details5. Technical data and
design review
11
12
17
1
18
15
109
16
14
8
1212
1: 2” Victaulic connections
2: Shaft
3: Low pressure shaft seal
4: Port flange
5: Port plate
6: Valve plate
6
5
1
13
7: Cylinder drum
8: Port flange
9: Port plate
10: Pins
11: Van es
12: Port plate
The noise level from the iSave including the
electrical motor is 78 dB (A). Measurements
according to EN ISO 20361. The test is made
It is therefore important that the iSave unit is
mounted correctly on a frame with dampers
to minimise vibrations and noise.
under following conditions:
1. iSave and electrical motor mounted
on Danfoss base plate.
2. Baseplate is isolated from concrete
ground by rubber vibration dampers.
3. Flexible hoses are used on high
pressure and low pressure sides of
the iSave.
4. Rotation speed 1,500 rpm
5. System pressure 60 barg and a booster pressure of 3 barg.
It is also strongly recommended to use
high-pressure flexible hoses between the
hard piping in the RO plant and the iSave.
See “hose assembly and installation” in
appendix 10.6. Alternative use multiple
flexible Victaulic® couplings on the hard
piping.
The noise level is influenced by:
• The speed of the iSave. High speed
creates more noise than low speed.
• Rigid mounting of the iSave baseplate
Influences
Since the iSave is mounted on a base plate
and connected to the electromotor by a bell
housing, the noise level can only be
determined for the complete unit (system).
12
180R9401 | AQ261351057880en- 000801 | 01.2022
generates more noise than flexible
mounting
• Pipe mounting directly to the iSave
increases the noise level compared to
flexible hoses.
Operating guide | iSave 21 Plus
5.3 Materials
All critical parts of the iSave are made of
super-duplex 1.4410/UN S32750 or the like.
Non-critical parts that are not in contact
with sea water are made of AISI 316.
The shaft to the electrical motor is sealed by
a standardised mechanical seal.
For a detailed material/part overview see
appendix
In order to minimise the risk of crevice
corrosion, always flush the iSave
according to the specified start/stop
procedure.
5.4 Temperature and corrosion
The chart below illustrates the corrosive
resistance of different types of stainless steel
related to NaCl concentration and
temperature.
Depending on the NaCl concentration, the
fluid temperature must be between: +2 °C to
+50 °C (+35.6 °F to 122 °F).
5.5 Dimensions and weights
For dimensions and weights please refer to
the iSave datasheet. See appendix 10.3
5.6 Electrical motor data
See datasheet in appendix 10.3 and
“Operating and Maintenance
instructions, electric motor” in
appendix 10.6
180R9401 | AQ261351057880en- 000801 | 01.2022
13
Operating guide | iSave 21 Plus
5.7 How does the iSave work?
Figure 5.1 shows a section view of the iSave
The iSave consists of a rotating isobargic
pressure exchanger and a positive
displacement pump, also called booster
pump. The rotation speed of the pressure
exchanger and the pump is exactly the
same, as they are driven by the same electric
motor.
5.7.1 Pressure exchanger function:
The pressure exchanger consists of two port
plates, one at the concentrate side and one
at the seawater side. In between there is a
rotor with several ducts that connect the
concentrate side with the seawater side.
The pressure exchanger transfers pressure
from the high-pressure (HP) concentrate (HP
in) to the low-pressure (LP) seawater coming
from low-pressure feed pump (LP in).
To separate the HP side from the LP side
there is a sealing zone on both port plates.
A single duct in the rotor is either on the HP
side, or on the LP side or in the sealing zone.
A single duct is never in contact with more
than one zone at the time. When the rotor
rotates a duct will go from the LP zone over
the first sealing zone into the HP zone, and
hereafter from the HP zone over the second
sealing zone and back to the LP zone.
The flow through the HP side of the iSave is
forced and controlled by the booster pump.
When the high-pressure concentrate is
flowing into the iSave it pressurizes the sea
water in the duct coming from “LP in”. The
pressurized seawater is then pumped out of
“HP out”. Just before the HP concentrate in
the duct comes to the seawater port plate,
the duct goes into the sealing zone and the
flow in the duct stops. When the duct goes
into the LP zone the concentrate water is
de-pressurized. The (LP) seawater coming
from the LP feed pump (LP in) forces the LP
concentrate out of “LP out”.
This pressure exchange process is repeated
for each duct with every rotation of the
rotor, and the ducts are thus continuously
filling and discharging. The flow on the HP
side and LP side of the iSave is nearly
constant over time.
There is no physical barrier in the ducts
between the concentrate and seawater. This
means that there will be a small amount of
mixing between the two liquids.
NB!
Fig. 5.1.
HP-out
Seawater side
LP-in
When the iSave is rotating the water always
flows respectively from LP-in to HP-out,
AND from HP-in to LP-out. However, if the
feed flow into LP-in is higher than the flow
HP-in
Concentrate
side
LP-out
into HP-in, some of the LP feed flow will flow
directly to LP-out.
When the iSave is not rotating the seawater
can only run directly from LP-in to LP-out.
14
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
5.7.2 Booster pump
The booster pump is a positive
displacement pump, which means that the
flow is controlled by the speed of the
electric motor; e.g. if the rotation speed
of the electric motor is raised by 10%, the
flow will be 10% higher and vice versa. The
required rpm can be calculated based on
the “rated flow” of the particular iSave. See
datasheet in appendix 10.3.
At low speeds you may hear some minor
clicking sounds from the pump. This is
normal and is caused by the pins in the
vane pump.
5.7.3 Lubrication flow
To lubricate the moving parts in the
pressure exchanger there is a well defined
leak between the port plates and the rotor,
as well as in the high pressure bearing
between the pressure exchanger and the
booster pump. This leak is typically called
“lubricating flow”. The leaks go from the
high pressure side to the low pressure side
of the pressure exchanger, and from the
booster pump to the low pressure side of
the pressure exchanger.
5.7.4 Mixing
There is no physical barrier in the ducts
between the concentrate and seawater. This
means that there will be a small amount of
mixing between the two liquids. Because
the two liquids are in contact for a short
amount of time, the mixing is relatively low.
On the RO market the mixing rate is defined
as “balanced flow” when HP-out is equal to
LP-in. Experience from the market shows
that the corresponding increase in
membrane operating pressure is about 1
barg.
obtained when the energy loss on LP feed is
equal to or less than the energy loss caused
by the excess pressure at the membrane.
5.7.5 How does the iSave work in an RO
system?
The figure below illustrates a typical flow
path of an SWRO or BWRO with an iSave.
The high-pressure (HP) concentrate (7) flows
to the low-pressure (LP) concentrate outlet
(3).
The LP sea water (2) flows to the HP sea
water outlet (5).
The rotor, moving between the
high-pressure and low-pressure streams,
removes the high-pressure concentrate (7)
and replaces it with feed water (2).
The flow rate on the HP sea water outlet (5)
is controlled by the iSave alone.
The flow rate on the LP concentrate outlet
(3) is controlled by the sea water feed pump
(1) and the back pressure valve. This means
that changing the LP feed flow (2) will not
affect HP outlet flow (5) and, vice versa, that
changing the HP outlet flow (5) will not affect the LP outlet flow (3).
As LP sea water (2) is flushing the LP
concentrate to LP outlet (3), it is essential
that the flow on the LP inlet (2) is equal
to or slightly higher than the HP inlet (7).
Otherwise there will be an “under-flush” and
higher mixing will occur in the HP outlet (5).
This higher mixing will result in a slightly
higher pressure at the membrane.
The customer can reduce mixing by
over-flushing the LP feed with excess feed
water. See figure below. Over-flushing
means energy loss. Optimal over-flushing is
180R9401 | AQ261351057880en- 000801 | 01.2022
The booster pump integrated in the iSave
must only overcome the pressure drop from
the high-pressure outlet (5) to the
high-pressure inlet (7).
15
Operating guide | iSave 21 Plus
During the RO process operation, water is
pumped into the HP-membrane feed (6) by
the HP pump (4) and the iSave (5). Almost
all water coming from the HP pump (4)
penetrates the membranes (8). Only a slight
amount of the water is used as lubrication
flow in the iSave. The lubrication flow is
measured as the difference between the HP
pump flow rate (4) and the permeate flow
rate (8). The resistance to permeate in the
membrane pressurises the HP loop.
The isobaric pressure exchanger technology
in an SWRO or BWRO change the HP
concentrate into HP seawater that is feed
into the HP membranes. The iSave energy
recovery technology thus significantly
reduces flow needed from the main HP
pump (4).
Overall energy consumption of a SWRO or
BWRO plant using the iSave depends on the
recovery rate.
The operator can change the recovery rate
to optimise the RO system performance.
Changing the recovery rate in an RO system
equipped with iSave is easy. Using the VFD,
change the speed of the iSave and thereby
the flow in the HP flow rate. Then change
the LP feed (2) flow to the iSave to minimise
mixing and optimise energy consumption.
Make sure that flow and pressure are within
the rated parameter of the iSave in question.
5.8 Seawater quality
5.8.1 Pre-filtration
It is important that the incoming water is
filtered properly to assure optimum service
life of the iSave. A true graded density
melt-blown depth filter cartridge rated
at 3 μm is therefore recommended. Poor
pre-filtration of the feed water will result in
reduced service life of the iSave.
The iSave may request a different
pre-filter of the seawater than the HP
pump and other components in the
RO system.
As the various filters on the market
differ greatly, Danfoss High Pressure
Pumps recommends using cartridges
with consistent, reliable performance
and high efficiency, in which fibres are
blown continuously onto a central
support core.
Danfoss High Pressure Pumps does not
recommend cartridges requiring any
type of binders or resins.
It is important with selection of a
proper filter housing to ensure good
cartridge end sealing. If there is a high
risk of water by-pass it is
recommended to use a second stage
filter solution.
NB!
Filters can be purchased from Danfoss
High Pressure Pumps.
16
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
5.8.2 Air bubbles
Large bubbles in a pressurised RO system
can result in damage to piping and
equipment. All air must be bleed from both
the LP and HP before the RO system is
pressurised. Special consideration should
also be given to air bubbles in feed flow,
continuously fed into the HP pump and
iSave.
5.8.3 Chemicals
The iSave should not be exposed to
chemicals that will damage the RO
membranes.
5.9 Initial start up and flushing
Prior to the initial start-up, all piping
associated with the iSave unit should be
thoroughly flushed to assure that no
impurities enter the iSave. Inadequate
pre-flushing will strongly affect the life
of the iSave and may lead to its eventual
breakdown.
It is recommended to disconnect all
connections to the iSave and to thoroughly
flush the piping before the iSave is
connected to the inlet and outlet
connections.
5.10 Initial start-up and settings of safety
equipment
The high-pressure pump feed water into the
high pressure line may be able to generate a
pressure higher than the maximum
allowable pressure in the system. There is
thus a risk of personal injury and/or damage
to the iSave.
Depending of the type and size of the feed
pump of the RO system, this pump may
be able to generate a pressure higher than
the maximum allowable pressure in the LP
system. There is thus a risk that the iSave
or the LP equipment could be damaged by
over-pressurisation.
To prevent such over-pressurisation,
appropriate relief valves should be used and procedures should be
implemented to safeguard the HP and
LP sides of the iSave and/or the
RO system.
It is essential that the water used for
the final pre-flush is pre-filtered to a
level described in chapter 5.8
It is recommended to install temporary
basket strainers at both inlets to the iSave
during the initial start-up and
commissioning.
Also see “Instruction for start and stop of the
SWRO with iSave unit” in appendix 10.1.
180R9401 | AQ261351057880en- 000801 | 01.2022
17
Operating guide | iSave 21 Plus
5.11 Flushing
RO membranes require periodic flushing to
limit biological fouling.
There are two types of flushing: feed water
(Seawater) flush and fresh water (Permeate)
flush.
Regardless of the flush water used, the water
must be pre-filtered to the level described
in chapter 5.8. All parts of the iSave must be
flushed, i.e. LP- and HP flow channels.
Feed water flushing is part of a normal
shutdown sequence. After the HP pump has
been stopped, the permeate and concentrate production will continue until the
high-pressure drops below the osmotic
pressure. Both the iSave and the LP seawater
feed pump must run until the conductivity
measured at point (7) and (3) are satisfactory. See also P&ID in chapter 5.16.
Fresh water flushing is performed before
every extended shutdown of the RO plant.
Permeate is simultaneously fed into the
iSave at LP in (2), and either to the HP pump
inlet (1) or through some other injection
point such as the CIP connections or full
flow cleaning connection. See also P&ID in
chapter 5.16. Permeate may be produced
during this flushing process.
Special attention should be given to
NB!
the pressure in the HP line (7) as the
iSave may start to cavitate when it runs
at high speed and the pressure in the
HP line (7) drops below 3 bargs. This
can be avoided by reducing the speed
of the iSave to about 750 rpm and
keeping the pressure in the HP line at
the minimum of 3 barg. At this low
pressure the iSave may only run for a
maximum of 10 minutes.
5.12 CIP or membrane cleaning
The purpose of membrane cleaning is to
reduce scaling and fouling in the
membranes. For optimal performance
specific chemicals are required, depending
on the cause of the pollution. After
chemical treatment the system must be
flushed with fresh water.
The flush water coming out of the
membranes may consist of a large
amount of suspended inorganic
particles. It is important to assure that
these particles are not lead into the
iSave.
It is essential that the water used
for the final pre-flush is pre-filtered to
a level described in chapter 5.8.
The iSave should not be exposed to
chemicals that will damage the
RO membranes
Also see instruction “Membrane
cleaning of RO system with iSave unit”
in appendix 10.2.
5.13 High pressure remains after
shutdown
The HP line of the RO system equipped with
an iSave can remain pressurised for a long
time after shutdown. Pressure decreases as
water slowly leaks through the iSave. If more
rapid system depressurisation is required,
the system should be bled through a suitable valve on the HP concentrate line.
Always check the pressure in the
high-pressure lines before making
service in the HP lines or pressurised
equipment.
Failing to flush the iSave with fresh
water before extended shutdowns
may result in extensive biological
growth and cause corrosion in the
iSave and other equipment in the
RO system.
18
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
5.14 Over-pressurisation caused by low
pressure isolation
If the low-pressure side of the iSave is
blocked and the iSave is exposed to
high-pressure, there is a risk that the iSave
or the LP piping could be damaged by
over-pressurisation.
To prevent such over-pressurisation,
appropriate relief valves should be
used and procedures should be
implemented to assure that the HP of
the iSave is depressurised prior to the
isolation of the LP side.
5.15 Over-pressurisation caused by the
high pressure pump.
The HP pump may be able to generate a
pressure higher than the maximum
allowable pressure for the iSave or the
system – particularly if the HP pump is a
positive displacement pump, the pump
will be able to generate extremely high
levels of pressure.
To prevent such over-pressurisation,
appropriate relief valves should be
used and procedures should be
implemented to assure that the HP of
the iSave is protected against excess
pressure.
180R9401 | AQ261351057880en- 000801 | 01.2022
19
Operating guide | iSave 21 Plus
5.16 Preferred system design and P&ID
VFD
Media filter
1
Filter
3 micron
nominel
Fresh water
permeate flush
Filter
10 micron
PIPI
19
absolut
F
12
LP in
*
2
F
HP out
11
M
VFD
PI
PS
HP in
3
iSave
4
M
18
PS
PI
5
PS
1314
6
Full flow
cleaning
7
10
PI
PI
15
20
F
* Second stage filter: If recommended housing design and cartridges are not used, a second stage filter is required
Explanation of P&ID setup
• The pressure switch (3) must stop the
iSave (11) and the high-pressure pump
(4) at pressures lower than the minimum
inlet pressure or higher than the
allowable maximum pressure.
• The non-return valve (18) prevents the
high pressure flow from the membrane
to flow back through the HP pump and
into the low pressure piping. This may
occur when the high pressure pump
stops.
• The pressure relief valve (6) protects the
• Inlet filters assure proper water quality.
High quality water extends the service
life of the whole system.
• It is important with selection of
a proper filter housing to ensure good
cartridge end sealing. If there is a high
risk of water by-pass it is recommended
to use a second stage filter solution.
• The pressure switch (13) must stop the
iSave when the pressure is lower than
the minimum inlet pressure or higher
than the maximum pressure.
entire system against pressure overload
and relieves the water if the pressure
exceeds the maximum set pressure.
If the high pressure pump is a positive
displacement pump, the pump can
See “Start and stop” procedure,
“Membrane cleaning” procedure instruction in appendices
10.1 and 10.2
build up a very high pressure that will
exceed the mechanical strength of the
membrane housing, pipes and other
accessories.
• The valve (8) bleeds the air out of the
system. The valve must be placed at the
highest point in the system.
• The pressure relief valve (19) protects
the low pressure pipes against pressure
overload and relieves the water if the
pressure exceeds the maximum
allowable pressure.
17
Permeate
F
Flowmeter
8
9
16
28
CIP
27
Drain
20
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
6. On-site installation
6.1 General
For safety instructions see chapter 3.1
6.2 Installation and alignment
The figure below illustrates the major iSave components.
Fig. 1
Motor
Bolts
Flexible coupling
Bell housing
iSave
Base plate
Port connection
Support bracket
(AISI 316)
The iSave is connected to the electric motor
by the bell housing and a coupling. The
bell housing is not suitable for bearing the
weight of either the iSave or the motor. Both
the iSave and motor must be supported
without applying stress/load to the bell
housing.
Danfoss provides the iSave with a baseplate
and support brackets. Although the
baseplate is of a sturdy design, it can flex or
bend when it is bolted to the
foundation. The baseplate thus requires a
solid foundation such as concrete or rigid
steel frame. The baseplate itself must be
aligned to avoid bending caused by bolting
to an uneven foundation.
A rigid foundation for the iSave assembly is
important, and the iSave assembly must be
bolted to the foundation.
Bolts
To reduce noise it is recommended to use
resilient mounts between the baseplate and
the foundation. Make sure that the bolts are
properly locked and will stay locked over
time.
An unlocked bolt can result in personal
injury and/or damage to the iSave.
Misalignment of the base plate may
cause stress and/or damage to the bell
housing.
6.3 Orientation
The iSave can be mounted horizontally and
vertically.
When mounted vertically, the electric motor
must be placed above the iSave.
The bolts used must be of proper design
and must be installed in accordance with
the bolt manufacturer’s recommendations.
180R9401 | AQ261351057880en- 000801 | 01.2022
21
Operating guide | iSave 21 Plus
6.4 Piping and joints
Piping material and schedule is of high
importance. The strength of the Victaulic®
connections is influenced by the material
used for both the Victaulic® clamps and the
hard piping.
The hard piping and connections used must
be of proper design and must be installed in
accordance with the manufacturer’s
recommendations.
Hard piping to the iSave must be properly
aligned to avoid stress on the iSave port
connections. Pipe connections must be
aligned as shown in the figures below.
Don’t use the iSave as a strain for hard
piping.
Misalignment of the hard pipes may
place stress on the iSave port
connection and may damage the iSave
The hard piping and connections used
must be of proper design and must be
installed in accordance with the
manufacturer’s recommendations.
A failure to comply with this will or may
result in personal injury and/or damage
to the iSave.
The strength of the Victaulic® connections is
influenced by the material used for both the
Victaulic® clamps and hose couplings.
The flexible hose and connections used
must be of proper design and must be
installed in accordance with the
manufacturer’s recommendations.
See also “Hose assembly and installation” in
appendix 10.5
The flexible hose and connections
used must be of proper design and
must be installed in accordance with
the manufacturer’s recommendations.
A failure to comply with this will or may
result in personal injury and/or damage
to the iSave.
6.6 Mounting of coupling
The figure below illustrates how to mount
the flexible coupling between the iSave and
to connect it to the electric motor.
Any axial and radial load on the shaft
must be avoided.
A: Flexible coupling
B: Bell housing
C: Motor shaft
6.7 Mounting of bell housing on iSave
The figure below illustrates how to mount
the bell housing on the iSave.
Screw the 4 bolts through the bell housing
and into the iSave and tighten them to
30 Nm.
6.8 Accessibility
With respect to the service and replacement
of the complete iSave unit, it is
recommended to maintain sufficient space
around the unit.
The space must be sufficient enough to
allow for safe lifting of the equipment, with
no risk for personal injury and/or damage to
the iSave.
180R9401 | AQ261351057880en- 000801 | 01.2022
23
Operating guide | iSave 21 Plus
6.9 Drives
6.9.1 Electric motor
The iSave must only be driven by an electric
motor.
Using anything other than an
electric motor can lead to an
irreparable fracture of the iSave’s
internal parts.
6.9.2 Speed control
The rotation speed on the electric motor
can be controlled by a VFD.
The direction of rotation is engraved with an
arrow on the iSave.
Checking the direction of rotation can be
made by:
1. Looking at the fan in the end of the
electric motor.
2. Removing the plug in the bell housing
and watch the rotation of coupling.
3. Before assembly the iSave on the
electrical motor, check the rotation of
the shaft on the electrical motor.
It is required to use a VFD or a soft starter.
A minimum of 10 seconds is
required when ramping up the
speed from zero to maximum.
Otherwise, the torque on the iSave
will exceed the maximum limit and
may lead to an irreparable fracture
of the iSave’s internal parts.
6.9.4 Torque overloads protection on the
iSave
The electric motor and iSave must always be
protected against overload.
Both at start-up and at continues operation
the maximum torque on the iSave must be
monitored.
The electric motor must be shut of if the
maximum torque of the iSave exceeds the
defined limit. The response time of the
power shutoff to the iSave must be of
maximum 1 second.
If more electric motors are powered by the
same soft starter or VFD, each electric motor
must be equipped with “torque limit
equipment” to protect the iSave against
overload.
Special attention has to be on NON
PROTECTED – FREE ROTATING shaft
on the electrical motor. Ignorance
will or could result in personal
injury.
• Running the iSave in the wrong
direction for more than a few minutes can cause un-intended wear
on the iSave.
• If the electric motor is running at
a lower speed, extra care must be
taken to ensure that the electric
motor is NOT overheated. External
cooling may be necessary.
6.9.3 Starting torque on the iSave/ramping the electric motor
Because of the inertia of the iSave internal
parts and the fact that the iSave includes a
positive displacement pump, the torque will
exceed the maximum allowable torque for
the iSave when the speed is not ramped up
from zero to maximum.
Below are examples of equipment which
can measure the load on the electric motor
or limit the torque on the iSave.
1. VFD with integrated current monitoring
relays.
2. External current monitoring relays.
3. Torque limiter coupling.
See also examples of “iSave overload
protection” equipment in appendix 10.5
The electric motor and iSave must
always be protected against
overload.
Otherwise, the torque will exceed
the maximum limit and may lead to
an irreparable fracture of the iSave’s
internal parts.
24
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
7. Commissioning, start-up
and shutdown
7.1 Safety regulations
The operator ensures that all
inspection and installation work is
performed by authorised, qualified
specialist personnel who are
thoroughly familiar with the manual.
Before starting up the iSave and the
high pressure pump, make sure that
the following requirements are met:
• The iSave has been properly
connected to the electric power
supply and is equipped with all
protection devices in accordance
with EN60204-1.
• Check that all motor protections are
properly set.
• All safety equipment, auxiliary
equipment and connections
required are proper connected and
operational.
• Check all bolts in all connections
and in the foundation of the iSave
and the pumps.
7.2 Support
Danfoss A/S offers commissioning and
service at system manufacturer’s location.
Rate quotes are offered upon request.
7.3 Commissioning
Before starting up the iSave and the
high pressure pump make sure that the
following requirements are met:
• All pipes are flushed, free from
debris and full of water.
• The iSave has been bled and is full
of water.
• At pressure lower than 10 bargs, check the system for leakage.
Slowly raise the pressure in the system
and set all pressure switches to the
correct limit and continually check all
connections for leakage.
• Set pressure relief valve on both
low and high pressure at the
maximum system pressure.
• Check high pressure hoses for
proper assembly and inspect for
externa leakage for all connections.
• At low pressure, start the iSave and
check direction of rotation.
• Start the system according to the
“Start and stop procedure”
instructions in appendix. 10.1
180R9401 | AQ261351057880en- 000801 | 01.2022
25
Operating guide | iSave 21 Plus
8. Service/
Maintenance
8.1 Safety regulations
The operator ensures that all
maintenance, inspection and
installation work is performed by
authorised, qualified specialist
personnel who are thoroughly familiar
with the manual.
Before intervening in the iSave/system;
• The power must be shut off and the
starting device be locked.
• The pressure in the High Pressure lines
must be drained to the Low Pressure
side.
• The Water in all connected pipes must
be drained.
Always use suitable safety and lifting
equipment when handling the iSave,
and follow the instructions in
chapter 4.3
• When saftey equipment has been
adjusted make sure that proper
re-adjustment has been made before
start-up.
• When the system is re-started after
service and maintenance follow the
instructions in chapter 7 and in “Start
and stop procedures” in
appendix. 10.1
8.2 Support
Danfoss A/S offers commissioning and
service at the system manufacturer’s
location. Rate quotes are offered upon
request.
8.3 Maintenance schedule
The schedule of preventive maintenance
below will help ensure that the iSave
provides years of trouble-free performance.
One day after commissioning:
1. Re-check bolts in the foundation and
the baseplate of the iSave and
tighten the bolts to specified torque
if necessary.
2. Visually inspect all pipe connections
/ couplings for external leakage.
3. Re-check bolts in all pipe
connections / couplings and tighten
the bolts to specified torque if
necessar y.
4. Replace filters if necessary
5. Clean the filter housing and reinstall
filters. Make sure no debris enters
the system.
Three months after commissioning:
1. Re-check bolts in the foundation
and the baseplate of the iSave and
tighten the bolts to specified torque
if necessary.
2. Re-check alignment of iSave
baseplate and iSave.
3. Visually inspect all pipe connections
/ couplings for external leakage.
4. Re-check bolts in all pipe
connections / couplings and tighten
the bolts to specified torque if
necessary.
5. Replace filters if necessary.
6. Clean the filter elements and install
the new filters. Make sure no debris
enters the system.
7. Audibly inspect the iSave assembly. If
there is irregular sounds or vibrations
inspect the internals parts of the
iSave and replace if necessary.
26
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
8,000 hours of operation after commissioning:
1. Re-check bolts in the foundation
and the baseplate of the iSave and
tighten the bolts to specified torque
if necessary.
2. Re-check alignment of iSave
baseplate and iSave.
3. Visually inspect all pipe connections
/ couplings for external leakage.
4. Re-check bolts in all pipe
connections / couplings and tighten
the bolts to specified torque if
necessary.
5. Replace filters if necessary.
6. Clean the filter elements and install
the new filter. Make sure no debris
enters the system.
7. Audibly inspect the iSave assembly.
If there is irregular sounds or
vibrations inspect the internals parts
of the iSave and replace if necessary.
8. Visually inspect pump coupling and
replace if necessary.
9. Audibly inspect the iSave assembly.
If there is irregular sounds or
vibrations inspect the internals
parts of the iSave and replace if necessary.
10.Check power consumption and flow
out of the iSave. If there is irregular
performances inspect the internals
parts of the iSave and replace if
necessary.
11.Inspect and replace, if necessary, the
vanes in the vane pump.
Dimensions of the vanes
iSave typeiSave 21 Plus
Original height (H)27 mm
Change when H is less than26 mm
Original length (L)79.84 mm
Change when L is less than79.64 mm
Annually:
1. See above section: “8,000 hour of
operation after commissioning”.
2. See “Operating- and maintenance
instruction, electric motor” in
appendix 10.6
Follow manufacturer’s recommendations for
electric motor service and maintenance.
180R9401 | AQ261351057880en- 000801 | 01.2022
27
Operating guide | iSave 21 Plus
9. Trouble-shooting
9.1 Safety regulations
The operator ensures that all
inspection and installation work is
performed by authorised, qualified
personnel who are thoroughly familiar
with the manual.
Before intervening in the iSave/system;
• The power must be shut off and the
starting device be locked.
• The pressure in the high-pressure
lines must be drained to
low-pressure side.
• The water in all connected pipes
must be drained.
The numbers in () correspond to the preferred system design and P&ID
ProblemPossible causeAction
VFD can’t start the iSave
at initial start-up.
VFD is not designed for constant torque.
Ramp-up settings in the VFD is
not correct. VFD is tilting.
Choose a VFD that is designed
for constant torque.
Set Ramp-up parameters
correct.
Valve (9) is closedOpen valve (9)
Torque on iSave too
high during operation
Pressure in the HP line (5) is
too high
Pressure difference from HPout (5) to HP-in (10) is too high.
Start the iSave only when the
pressure in the HP line is low.
Clean or change membranes.
Debris in the booster pump or
iSave.
Wear in the booster pump or
iSave.
Design of the basic plant
doesn’t fit the performance of
the iSave.
Permeate production is
too low (17).
Valves (6), (7), (8) or (16) are
leaking.
Repair or change valve.
Internal leakage in iSaveRepair iSave
HP pump flow (2) is to smallIncorrect speed on the HP
pump.
Check the HP pump and repair
if necessary.
Pressure on the mem-
Fouling on the membranesClean the membranes
branes (5) is too high.
Mixing in the iSave is too high. Check flow on LP-in (12) and
adjust flow.
Flow out of the iSave is too
low, causes a recovery rate
Check speed on iSave and
change if necessary.
that is too high.
Booster pump in the iSave is
worn out.
Perform service on the VP.
Pressure on the membranes (5) is too low.
Valves (6), (7), (8) or (16) are
leaking.
Repair or change valve (s).
Internal leakage in iSaveRepair iSave
HP pump flow (2) is too smallIncorrect speed on the HP
pump.
Check the HP pump and repair
if necessary.
28
180R9401 | AQ261351057880en- 000801 | 01.2022
Appendices
Energy Recovery Device
iSave 21 Plus
Installation, Operation and
Maintenance Manual
hpp.danfoss.com
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.