Installation, Operation and Maintenance
Manual.
Original operating manual document.
Danfoss can accept no responsibility for
possible errors in the manual and
instructions. Danfoss reserves the right
to alter its products without notice. This
also applies to products already on order
provided that such alterations can be made
without subsequential changes being
necessary in specifications already agreed.
All rights reserved. Contents provided
herein must neither be distributed, copied,
reproduced, edited or processed for any
other purpose, nor otherwise translated or
published without Danfoss’ express written
consent.
The serial number is referring to the Serial
no. on the product label. The digits shown
(02) indicate the version number of the
pump.
This document is only valid for ERD version 2
and upwards.
10.6 Operating- and maintenance instruction, electric motor (180R9230) . . . . . . . . 91
4
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
2. Introduction
2.1 General
iSave is manufactured by Danfoss A/S, and
is sold and marketed by a net of authorised
distributors world wide.
This manual contains the necessary instructions for the installation, operation and
service of the iSave.
All personnel who are responsible for
the operation and maintenance of the iSave
unit must read and fully understand these
instructions, especially the section “Safety”
before:
• Transporting of the iSave unit.
• Lifting the unit.
• Installing the iSave unit on a frame.
• Connecting the iSave unit to the fluid
system.
• Connecting the electrical motor and
instrumentation.
• Commissioning the unit.
• Servicing the iSave unit, mechanics and
electrics.
• Decommissioning the iSave unit.
2.3 Symbols
Indicates something to be noted by
NB!
the reader.
Indicates a situation which will or
couldresult in damage to the iSave
and its function.
Indicates a situation which will or
could result in personal injury and/or
damage to the iSave.
Electrical hazard. Indicates a
high-voltage warning
Safety glasses required
Hearing protection required
Safety shoes required
Safety helmet required
Ensure that these instructions are
always readily available to all personnel
concerned.
2.2 Target group
This manual is intended for use by
personnel with qualified training and
experience in the operation and
maintenance of a Sea Water Reverse
Osmosis (SWRO) or Brackish Water Reverse
Osmosis (BWRO) system.
Danfoss Ltd.
22 Wycombe End
HP9 1NB Beaconsfield
United Kingdom
2.6 Additional technical documents
Document nameContent
DatasheetDescription of the technical data and
dimensions of the iSave
iSave parts listSectional drawings, parts list and spare part
numbers.
Instruction:
start and stop of the SWRO with iSave unit
Instruction:
Membrane cleaning of RO system with
Description of how to start and stop the
iSave in the preferred RO system set-up.
Description of how to clean the membranes
in the preferred RO system set-up.
iSave unit
Instruction:
Hose assembly and installation
Operating and maintenance instructions,
electric motor
Guideline for Hose assembly and
installation
Operating and maintenance instructions for
the standard electric motor, delivered from
Danfoss.
See also appendix 10
6
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
3. Safety
3.1 General
The iSave must not be used for other
purposes than those recommended and
specified without first consulting your local
iSave distributor.
This manual must be read and completely
understood by the responsible specialist
personnel prior to installation and commissioning.
Use of this manual does not relieve operation and maintenance personnel of the
responsibility of applying normal good
judgment in the operation and care of this
product and its components.
This manual must be available to all personnel concerned at the site at all time.
An iSave must always be installed and used
in accordance with existing national and local sanitary and safety regulations and laws.
It is the responsibility of the safety officer or
the chief operator to assure compliance with
all local regulations that are not taken into
account in this manual.
• Improper installation can cause fatal
injuries.
• The iSave must not operate outside
the application range.
• During the initial start-up, slowly raise
the pressure of the system and adjust
the over-pressure protection
equipment for proper limit settings.
• Make sure that the pressure is
released from the iSave before the
iSave is disconnected from any pipe
or hose connections in the iSave.
• Make sure that the iSave can be
drained without injuring anyone and
without contaminating nearby
equipment or the environment.
• Before intervening in the
iSave/system, the power must be shut
off and the starting device must be
locked. When intervening in the iSave
unit, follow the instructions for
Service/Maintenance, chapter 8.
• A failure to follow the instructions can
result in personal injury and/or
damage to the iSave. It will also
invalidate the warranty.
Electrical
hazard
The iSave is a rotating machine that typically
operates at high pressure.
Always wear suitable safety and lifting
equipment when handling the iSave.
• Bolt the iSave properly to the base
before start-up to avoid personal
injury and/or damage to the iSave.
• The pipe connections to the iSave
must be stress-free mounted, securely
fastened to the iSave and well
supported. Improper installation will
or could result in personal injury
and/or damage to the iSave.
• Proper installation and care of
shutdown devices and over-pressure
protection equipment is essential.
• All electrical installation work must be
carried out by authorised personnel in
accordance with EN60204-1 and/or
local regulations.
• Install a lockable circuit breaker to
avoid inadvertent starting. Protect th
motor and other electrical equipment
from overloads with suitable
equipment.
• The electric motors must be supplied
with adequate cooling ventilation.
• The iSave must never run dry. Dry
running produces heat and will cause
damage to internal parts.
• If the iSave does not function
satisfactorily, contact your local iSave
distributor.
Use of this manual does not relieve
NB!
operation and maintenance personnel
of the responsibility of applying normal
good judgment in the operation and
care of this product.
180R9401 | AQ261351057880en- 000801 | 01.2022
7
Operating guide | iSave 21 Plus
3.2 Intended use
The iSave is designed for use as energy
recovery device in Sea Water Reverse
Osmosis (SWRO) or Brackish Water Reverse
Osmosis (BWRO) system.
The iSave must not be used for other
purposes than recommended and quoted
for without consulting your local iSave
distributor.
3.3 Application range
For application range see data sheet
521B1464 available in appendix 10.3.
Applications not suitable for the iSave
can cause damages to the iSave unit,
with risk of personal injury.
3.4 Preferred system design
Danfoss recommends building systems with
a high degree of safety. The P&ID in chapter
5.16 shows the Danfoss preferred system
design.
• It is always the system builders’
responsibility that the system design
does not cause any form of hazard
and are adapted to local regulations.
• Proper installation and care of
shutdown devices and over-pressure
protectio equipment is essential.
8
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
4. Arrival inspection,
handling and storage
4.1 Arrival inspection
The iSave is packed in a wood container with
plugs in the port connections to protect the
unit from damage during transport.
Remove all packing materials immediately
after delivery. Immediately check the
shipment for damage on arrival and make
sure that the name plate/type designation is
in accordance with the packing slip and your
order.
In case of damage and/or missing parts, a
report should be drawn up and presented
to the carrier at once.
The identification label on the iSave states
the specific type, the serial number and the
code number of the iSave; see fig. below.
The last three digits of the Serial No. indicate
the week and year of production.
PUMP
Type iSave 21 Plus ERD
Code no. 180BXXXX
Serial no. XXXXXX02-XXX
MADE IN DENMARK
Danfoss A/S, 6430 Nordborg, Denmark
4.3 Handling
• Personnel involved in lifting and
transportation of the equipment must be
trained in proper handling and safety
procedures.
• Observe the local regulations regarding
lifting.
• Use suitable, permitted lifting equipment.
• The iSave (set) could slip the lifting
arrangement.
• Be aware of individuals located in the
operation area while lifting the
component.
4.2 Return to the supplier
Flush the iSave with clean water. Drain the
iSave and plug the port connections with a
cap/cover.
Pack the iSave into a suitable container and
make sure that it is suitably fastened to the
container.
Please contact your local authorised
distributor or:
Check the mass (weight) of the iSave unit.
All parts weighing more than 20 kg must be
lifted using lifting slings and suitable lifting
Secure lifting slings around the part of
the iSave and the back of the electric
motor. Make sure that the load is
balanced before attempting the lift.
devices, e.g. an overhead crane or industrial
truck. All iSave units weight more than
20 kg.
Once the lifting is done the lifting eye
must be removed from the pump.
Never lift the iSave unit with only one
fastening point.
Incorrect lifting can result in personally
injury and/or damage to the unit.
4.3.1 Centre of mass
604
Never lift the iSave in the bell housing.
Incorrect lifting can result in personally
injury and/or damage to the unit.
10
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
4.4 Storage
Each iSave is tested before shipment and
therefore holds water.
Storage temperature: 1 °C to +70 °C (33 °F to
158 °F) – provided that the pump is drained
of fluid and stored “plugged”.
Frost protection is required at temperatures
below 1°C. Danfoss recommends using
DOWFROST from DOW Chemical Company
or Chillsafe mono propylene glycol from
Arco Chemical Company.
If the iSave is protected against frost, the
storage temperature can be: -40 °C to +70
°C (-40 °F to 158 °F)
• The iSave is NOT delivered
frost-protected from the factory.
• Only remove caps from the openings
of the iSave at the time of installation.
4.5 Outdoor Storage
For outdoor storage cover the iSave
(set) with waterproof material.
180R9401 | AQ261351057880en- 000801 | 01.2022
11
Operating guide | iSave 21 Plus
5.1 Design details5. Technical data and
design review
11
12
17
1
18
15
109
16
14
8
1212
1: 2” Victaulic connections
2: Shaft
3: Low pressure shaft seal
4: Port flange
5: Port plate
6: Valve plate
6
5
1
13
7: Cylinder drum
8: Port flange
9: Port plate
10: Pins
11: Van es
12: Port plate
The noise level from the iSave including the
electrical motor is 78 dB (A). Measurements
according to EN ISO 20361. The test is made
It is therefore important that the iSave unit is
mounted correctly on a frame with dampers
to minimise vibrations and noise.
under following conditions:
1. iSave and electrical motor mounted
on Danfoss base plate.
2. Baseplate is isolated from concrete
ground by rubber vibration dampers.
3. Flexible hoses are used on high
pressure and low pressure sides of
the iSave.
4. Rotation speed 1,500 rpm
5. System pressure 60 barg and a booster pressure of 3 barg.
It is also strongly recommended to use
high-pressure flexible hoses between the
hard piping in the RO plant and the iSave.
See “hose assembly and installation” in
appendix 10.6. Alternative use multiple
flexible Victaulic® couplings on the hard
piping.
The noise level is influenced by:
• The speed of the iSave. High speed
creates more noise than low speed.
• Rigid mounting of the iSave baseplate
Influences
Since the iSave is mounted on a base plate
and connected to the electromotor by a bell
housing, the noise level can only be
determined for the complete unit (system).
12
180R9401 | AQ261351057880en- 000801 | 01.2022
generates more noise than flexible
mounting
• Pipe mounting directly to the iSave
increases the noise level compared to
flexible hoses.
Operating guide | iSave 21 Plus
5.3 Materials
All critical parts of the iSave are made of
super-duplex 1.4410/UN S32750 or the like.
Non-critical parts that are not in contact
with sea water are made of AISI 316.
The shaft to the electrical motor is sealed by
a standardised mechanical seal.
For a detailed material/part overview see
appendix
In order to minimise the risk of crevice
corrosion, always flush the iSave
according to the specified start/stop
procedure.
5.4 Temperature and corrosion
The chart below illustrates the corrosive
resistance of different types of stainless steel
related to NaCl concentration and
temperature.
Depending on the NaCl concentration, the
fluid temperature must be between: +2 °C to
+50 °C (+35.6 °F to 122 °F).
5.5 Dimensions and weights
For dimensions and weights please refer to
the iSave datasheet. See appendix 10.3
5.6 Electrical motor data
See datasheet in appendix 10.3 and
“Operating and Maintenance
instructions, electric motor” in
appendix 10.6
180R9401 | AQ261351057880en- 000801 | 01.2022
13
Operating guide | iSave 21 Plus
5.7 How does the iSave work?
Figure 5.1 shows a section view of the iSave
The iSave consists of a rotating isobargic
pressure exchanger and a positive
displacement pump, also called booster
pump. The rotation speed of the pressure
exchanger and the pump is exactly the
same, as they are driven by the same electric
motor.
5.7.1 Pressure exchanger function:
The pressure exchanger consists of two port
plates, one at the concentrate side and one
at the seawater side. In between there is a
rotor with several ducts that connect the
concentrate side with the seawater side.
The pressure exchanger transfers pressure
from the high-pressure (HP) concentrate (HP
in) to the low-pressure (LP) seawater coming
from low-pressure feed pump (LP in).
To separate the HP side from the LP side
there is a sealing zone on both port plates.
A single duct in the rotor is either on the HP
side, or on the LP side or in the sealing zone.
A single duct is never in contact with more
than one zone at the time. When the rotor
rotates a duct will go from the LP zone over
the first sealing zone into the HP zone, and
hereafter from the HP zone over the second
sealing zone and back to the LP zone.
The flow through the HP side of the iSave is
forced and controlled by the booster pump.
When the high-pressure concentrate is
flowing into the iSave it pressurizes the sea
water in the duct coming from “LP in”. The
pressurized seawater is then pumped out of
“HP out”. Just before the HP concentrate in
the duct comes to the seawater port plate,
the duct goes into the sealing zone and the
flow in the duct stops. When the duct goes
into the LP zone the concentrate water is
de-pressurized. The (LP) seawater coming
from the LP feed pump (LP in) forces the LP
concentrate out of “LP out”.
This pressure exchange process is repeated
for each duct with every rotation of the
rotor, and the ducts are thus continuously
filling and discharging. The flow on the HP
side and LP side of the iSave is nearly
constant over time.
There is no physical barrier in the ducts
between the concentrate and seawater. This
means that there will be a small amount of
mixing between the two liquids.
NB!
Fig. 5.1.
HP-out
Seawater side
LP-in
When the iSave is rotating the water always
flows respectively from LP-in to HP-out,
AND from HP-in to LP-out. However, if the
feed flow into LP-in is higher than the flow
HP-in
Concentrate
side
LP-out
into HP-in, some of the LP feed flow will flow
directly to LP-out.
When the iSave is not rotating the seawater
can only run directly from LP-in to LP-out.
14
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
5.7.2 Booster pump
The booster pump is a positive
displacement pump, which means that the
flow is controlled by the speed of the
electric motor; e.g. if the rotation speed
of the electric motor is raised by 10%, the
flow will be 10% higher and vice versa. The
required rpm can be calculated based on
the “rated flow” of the particular iSave. See
datasheet in appendix 10.3.
At low speeds you may hear some minor
clicking sounds from the pump. This is
normal and is caused by the pins in the
vane pump.
5.7.3 Lubrication flow
To lubricate the moving parts in the
pressure exchanger there is a well defined
leak between the port plates and the rotor,
as well as in the high pressure bearing
between the pressure exchanger and the
booster pump. This leak is typically called
“lubricating flow”. The leaks go from the
high pressure side to the low pressure side
of the pressure exchanger, and from the
booster pump to the low pressure side of
the pressure exchanger.
5.7.4 Mixing
There is no physical barrier in the ducts
between the concentrate and seawater. This
means that there will be a small amount of
mixing between the two liquids. Because
the two liquids are in contact for a short
amount of time, the mixing is relatively low.
On the RO market the mixing rate is defined
as “balanced flow” when HP-out is equal to
LP-in. Experience from the market shows
that the corresponding increase in
membrane operating pressure is about 1
barg.
obtained when the energy loss on LP feed is
equal to or less than the energy loss caused
by the excess pressure at the membrane.
5.7.5 How does the iSave work in an RO
system?
The figure below illustrates a typical flow
path of an SWRO or BWRO with an iSave.
The high-pressure (HP) concentrate (7) flows
to the low-pressure (LP) concentrate outlet
(3).
The LP sea water (2) flows to the HP sea
water outlet (5).
The rotor, moving between the
high-pressure and low-pressure streams,
removes the high-pressure concentrate (7)
and replaces it with feed water (2).
The flow rate on the HP sea water outlet (5)
is controlled by the iSave alone.
The flow rate on the LP concentrate outlet
(3) is controlled by the sea water feed pump
(1) and the back pressure valve. This means
that changing the LP feed flow (2) will not
affect HP outlet flow (5) and, vice versa, that
changing the HP outlet flow (5) will not affect the LP outlet flow (3).
As LP sea water (2) is flushing the LP
concentrate to LP outlet (3), it is essential
that the flow on the LP inlet (2) is equal
to or slightly higher than the HP inlet (7).
Otherwise there will be an “under-flush” and
higher mixing will occur in the HP outlet (5).
This higher mixing will result in a slightly
higher pressure at the membrane.
The customer can reduce mixing by
over-flushing the LP feed with excess feed
water. See figure below. Over-flushing
means energy loss. Optimal over-flushing is
180R9401 | AQ261351057880en- 000801 | 01.2022
The booster pump integrated in the iSave
must only overcome the pressure drop from
the high-pressure outlet (5) to the
high-pressure inlet (7).
15
Operating guide | iSave 21 Plus
During the RO process operation, water is
pumped into the HP-membrane feed (6) by
the HP pump (4) and the iSave (5). Almost
all water coming from the HP pump (4)
penetrates the membranes (8). Only a slight
amount of the water is used as lubrication
flow in the iSave. The lubrication flow is
measured as the difference between the HP
pump flow rate (4) and the permeate flow
rate (8). The resistance to permeate in the
membrane pressurises the HP loop.
The isobaric pressure exchanger technology
in an SWRO or BWRO change the HP
concentrate into HP seawater that is feed
into the HP membranes. The iSave energy
recovery technology thus significantly
reduces flow needed from the main HP
pump (4).
Overall energy consumption of a SWRO or
BWRO plant using the iSave depends on the
recovery rate.
The operator can change the recovery rate
to optimise the RO system performance.
Changing the recovery rate in an RO system
equipped with iSave is easy. Using the VFD,
change the speed of the iSave and thereby
the flow in the HP flow rate. Then change
the LP feed (2) flow to the iSave to minimise
mixing and optimise energy consumption.
Make sure that flow and pressure are within
the rated parameter of the iSave in question.
5.8 Seawater quality
5.8.1 Pre-filtration
It is important that the incoming water is
filtered properly to assure optimum service
life of the iSave. A true graded density
melt-blown depth filter cartridge rated
at 3 μm is therefore recommended. Poor
pre-filtration of the feed water will result in
reduced service life of the iSave.
The iSave may request a different
pre-filter of the seawater than the HP
pump and other components in the
RO system.
As the various filters on the market
differ greatly, Danfoss High Pressure
Pumps recommends using cartridges
with consistent, reliable performance
and high efficiency, in which fibres are
blown continuously onto a central
support core.
Danfoss High Pressure Pumps does not
recommend cartridges requiring any
type of binders or resins.
It is important with selection of a
proper filter housing to ensure good
cartridge end sealing. If there is a high
risk of water by-pass it is
recommended to use a second stage
filter solution.
NB!
Filters can be purchased from Danfoss
High Pressure Pumps.
16
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
5.8.2 Air bubbles
Large bubbles in a pressurised RO system
can result in damage to piping and
equipment. All air must be bleed from both
the LP and HP before the RO system is
pressurised. Special consideration should
also be given to air bubbles in feed flow,
continuously fed into the HP pump and
iSave.
5.8.3 Chemicals
The iSave should not be exposed to
chemicals that will damage the RO
membranes.
5.9 Initial start up and flushing
Prior to the initial start-up, all piping
associated with the iSave unit should be
thoroughly flushed to assure that no
impurities enter the iSave. Inadequate
pre-flushing will strongly affect the life
of the iSave and may lead to its eventual
breakdown.
It is recommended to disconnect all
connections to the iSave and to thoroughly
flush the piping before the iSave is
connected to the inlet and outlet
connections.
5.10 Initial start-up and settings of safety
equipment
The high-pressure pump feed water into the
high pressure line may be able to generate a
pressure higher than the maximum
allowable pressure in the system. There is
thus a risk of personal injury and/or damage
to the iSave.
Depending of the type and size of the feed
pump of the RO system, this pump may
be able to generate a pressure higher than
the maximum allowable pressure in the LP
system. There is thus a risk that the iSave
or the LP equipment could be damaged by
over-pressurisation.
To prevent such over-pressurisation,
appropriate relief valves should be used and procedures should be
implemented to safeguard the HP and
LP sides of the iSave and/or the
RO system.
It is essential that the water used for
the final pre-flush is pre-filtered to a
level described in chapter 5.8
It is recommended to install temporary
basket strainers at both inlets to the iSave
during the initial start-up and
commissioning.
Also see “Instruction for start and stop of the
SWRO with iSave unit” in appendix 10.1.
180R9401 | AQ261351057880en- 000801 | 01.2022
17
Operating guide | iSave 21 Plus
5.11 Flushing
RO membranes require periodic flushing to
limit biological fouling.
There are two types of flushing: feed water
(Seawater) flush and fresh water (Permeate)
flush.
Regardless of the flush water used, the water
must be pre-filtered to the level described
in chapter 5.8. All parts of the iSave must be
flushed, i.e. LP- and HP flow channels.
Feed water flushing is part of a normal
shutdown sequence. After the HP pump has
been stopped, the permeate and concentrate production will continue until the
high-pressure drops below the osmotic
pressure. Both the iSave and the LP seawater
feed pump must run until the conductivity
measured at point (7) and (3) are satisfactory. See also P&ID in chapter 5.16.
Fresh water flushing is performed before
every extended shutdown of the RO plant.
Permeate is simultaneously fed into the
iSave at LP in (2), and either to the HP pump
inlet (1) or through some other injection
point such as the CIP connections or full
flow cleaning connection. See also P&ID in
chapter 5.16. Permeate may be produced
during this flushing process.
Special attention should be given to
NB!
the pressure in the HP line (7) as the
iSave may start to cavitate when it runs
at high speed and the pressure in the
HP line (7) drops below 3 bargs. This
can be avoided by reducing the speed
of the iSave to about 750 rpm and
keeping the pressure in the HP line at
the minimum of 3 barg. At this low
pressure the iSave may only run for a
maximum of 10 minutes.
5.12 CIP or membrane cleaning
The purpose of membrane cleaning is to
reduce scaling and fouling in the
membranes. For optimal performance
specific chemicals are required, depending
on the cause of the pollution. After
chemical treatment the system must be
flushed with fresh water.
The flush water coming out of the
membranes may consist of a large
amount of suspended inorganic
particles. It is important to assure that
these particles are not lead into the
iSave.
It is essential that the water used
for the final pre-flush is pre-filtered to
a level described in chapter 5.8.
The iSave should not be exposed to
chemicals that will damage the
RO membranes
Also see instruction “Membrane
cleaning of RO system with iSave unit”
in appendix 10.2.
5.13 High pressure remains after
shutdown
The HP line of the RO system equipped with
an iSave can remain pressurised for a long
time after shutdown. Pressure decreases as
water slowly leaks through the iSave. If more
rapid system depressurisation is required,
the system should be bled through a suitable valve on the HP concentrate line.
Always check the pressure in the
high-pressure lines before making
service in the HP lines or pressurised
equipment.
Failing to flush the iSave with fresh
water before extended shutdowns
may result in extensive biological
growth and cause corrosion in the
iSave and other equipment in the
RO system.
18
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
5.14 Over-pressurisation caused by low
pressure isolation
If the low-pressure side of the iSave is
blocked and the iSave is exposed to
high-pressure, there is a risk that the iSave
or the LP piping could be damaged by
over-pressurisation.
To prevent such over-pressurisation,
appropriate relief valves should be
used and procedures should be
implemented to assure that the HP of
the iSave is depressurised prior to the
isolation of the LP side.
5.15 Over-pressurisation caused by the
high pressure pump.
The HP pump may be able to generate a
pressure higher than the maximum
allowable pressure for the iSave or the
system – particularly if the HP pump is a
positive displacement pump, the pump
will be able to generate extremely high
levels of pressure.
To prevent such over-pressurisation,
appropriate relief valves should be
used and procedures should be
implemented to assure that the HP of
the iSave is protected against excess
pressure.
180R9401 | AQ261351057880en- 000801 | 01.2022
19
Operating guide | iSave 21 Plus
5.16 Preferred system design and P&ID
VFD
Media filter
1
Filter
3 micron
nominel
Fresh water
permeate flush
Filter
10 micron
PIPI
19
absolut
F
12
LP in
*
2
F
HP out
11
M
VFD
PI
PS
HP in
3
iSave
4
M
18
PS
PI
5
PS
1314
6
Full flow
cleaning
7
10
PI
PI
15
20
F
* Second stage filter: If recommended housing design and cartridges are not used, a second stage filter is required
Explanation of P&ID setup
• The pressure switch (3) must stop the
iSave (11) and the high-pressure pump
(4) at pressures lower than the minimum
inlet pressure or higher than the
allowable maximum pressure.
• The non-return valve (18) prevents the
high pressure flow from the membrane
to flow back through the HP pump and
into the low pressure piping. This may
occur when the high pressure pump
stops.
• The pressure relief valve (6) protects the
• Inlet filters assure proper water quality.
High quality water extends the service
life of the whole system.
• It is important with selection of
a proper filter housing to ensure good
cartridge end sealing. If there is a high
risk of water by-pass it is recommended
to use a second stage filter solution.
• The pressure switch (13) must stop the
iSave when the pressure is lower than
the minimum inlet pressure or higher
than the maximum pressure.
entire system against pressure overload
and relieves the water if the pressure
exceeds the maximum set pressure.
If the high pressure pump is a positive
displacement pump, the pump can
See “Start and stop” procedure,
“Membrane cleaning” procedure instruction in appendices
10.1 and 10.2
build up a very high pressure that will
exceed the mechanical strength of the
membrane housing, pipes and other
accessories.
• The valve (8) bleeds the air out of the
system. The valve must be placed at the
highest point in the system.
• The pressure relief valve (19) protects
the low pressure pipes against pressure
overload and relieves the water if the
pressure exceeds the maximum
allowable pressure.
17
Permeate
F
Flowmeter
8
9
16
28
CIP
27
Drain
20
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
6. On-site installation
6.1 General
For safety instructions see chapter 3.1
6.2 Installation and alignment
The figure below illustrates the major iSave components.
Fig. 1
Motor
Bolts
Flexible coupling
Bell housing
iSave
Base plate
Port connection
Support bracket
(AISI 316)
The iSave is connected to the electric motor
by the bell housing and a coupling. The
bell housing is not suitable for bearing the
weight of either the iSave or the motor. Both
the iSave and motor must be supported
without applying stress/load to the bell
housing.
Danfoss provides the iSave with a baseplate
and support brackets. Although the
baseplate is of a sturdy design, it can flex or
bend when it is bolted to the
foundation. The baseplate thus requires a
solid foundation such as concrete or rigid
steel frame. The baseplate itself must be
aligned to avoid bending caused by bolting
to an uneven foundation.
A rigid foundation for the iSave assembly is
important, and the iSave assembly must be
bolted to the foundation.
Bolts
To reduce noise it is recommended to use
resilient mounts between the baseplate and
the foundation. Make sure that the bolts are
properly locked and will stay locked over
time.
An unlocked bolt can result in personal
injury and/or damage to the iSave.
Misalignment of the base plate may
cause stress and/or damage to the bell
housing.
6.3 Orientation
The iSave can be mounted horizontally and
vertically.
When mounted vertically, the electric motor
must be placed above the iSave.
The bolts used must be of proper design
and must be installed in accordance with
the bolt manufacturer’s recommendations.
180R9401 | AQ261351057880en- 000801 | 01.2022
21
Operating guide | iSave 21 Plus
6.4 Piping and joints
Piping material and schedule is of high
importance. The strength of the Victaulic®
connections is influenced by the material
used for both the Victaulic® clamps and the
hard piping.
The hard piping and connections used must
be of proper design and must be installed in
accordance with the manufacturer’s
recommendations.
Hard piping to the iSave must be properly
aligned to avoid stress on the iSave port
connections. Pipe connections must be
aligned as shown in the figures below.
Don’t use the iSave as a strain for hard
piping.
Misalignment of the hard pipes may
place stress on the iSave port
connection and may damage the iSave
The hard piping and connections used
must be of proper design and must be
installed in accordance with the
manufacturer’s recommendations.
A failure to comply with this will or may
result in personal injury and/or damage
to the iSave.
The strength of the Victaulic® connections is
influenced by the material used for both the
Victaulic® clamps and hose couplings.
The flexible hose and connections used
must be of proper design and must be
installed in accordance with the
manufacturer’s recommendations.
See also “Hose assembly and installation” in
appendix 10.5
The flexible hose and connections
used must be of proper design and
must be installed in accordance with
the manufacturer’s recommendations.
A failure to comply with this will or may
result in personal injury and/or damage
to the iSave.
6.6 Mounting of coupling
The figure below illustrates how to mount
the flexible coupling between the iSave and
to connect it to the electric motor.
Any axial and radial load on the shaft
must be avoided.
A: Flexible coupling
B: Bell housing
C: Motor shaft
6.7 Mounting of bell housing on iSave
The figure below illustrates how to mount
the bell housing on the iSave.
Screw the 4 bolts through the bell housing
and into the iSave and tighten them to
30 Nm.
6.8 Accessibility
With respect to the service and replacement
of the complete iSave unit, it is
recommended to maintain sufficient space
around the unit.
The space must be sufficient enough to
allow for safe lifting of the equipment, with
no risk for personal injury and/or damage to
the iSave.
180R9401 | AQ261351057880en- 000801 | 01.2022
23
Operating guide | iSave 21 Plus
6.9 Drives
6.9.1 Electric motor
The iSave must only be driven by an electric
motor.
Using anything other than an
electric motor can lead to an
irreparable fracture of the iSave’s
internal parts.
6.9.2 Speed control
The rotation speed on the electric motor
can be controlled by a VFD.
The direction of rotation is engraved with an
arrow on the iSave.
Checking the direction of rotation can be
made by:
1. Looking at the fan in the end of the
electric motor.
2. Removing the plug in the bell housing
and watch the rotation of coupling.
3. Before assembly the iSave on the
electrical motor, check the rotation of
the shaft on the electrical motor.
It is required to use a VFD or a soft starter.
A minimum of 10 seconds is
required when ramping up the
speed from zero to maximum.
Otherwise, the torque on the iSave
will exceed the maximum limit and
may lead to an irreparable fracture
of the iSave’s internal parts.
6.9.4 Torque overloads protection on the
iSave
The electric motor and iSave must always be
protected against overload.
Both at start-up and at continues operation
the maximum torque on the iSave must be
monitored.
The electric motor must be shut of if the
maximum torque of the iSave exceeds the
defined limit. The response time of the
power shutoff to the iSave must be of
maximum 1 second.
If more electric motors are powered by the
same soft starter or VFD, each electric motor
must be equipped with “torque limit
equipment” to protect the iSave against
overload.
Special attention has to be on NON
PROTECTED – FREE ROTATING shaft
on the electrical motor. Ignorance
will or could result in personal
injury.
• Running the iSave in the wrong
direction for more than a few minutes can cause un-intended wear
on the iSave.
• If the electric motor is running at
a lower speed, extra care must be
taken to ensure that the electric
motor is NOT overheated. External
cooling may be necessary.
6.9.3 Starting torque on the iSave/ramping the electric motor
Because of the inertia of the iSave internal
parts and the fact that the iSave includes a
positive displacement pump, the torque will
exceed the maximum allowable torque for
the iSave when the speed is not ramped up
from zero to maximum.
Below are examples of equipment which
can measure the load on the electric motor
or limit the torque on the iSave.
1. VFD with integrated current monitoring
relays.
2. External current monitoring relays.
3. Torque limiter coupling.
See also examples of “iSave overload
protection” equipment in appendix 10.5
The electric motor and iSave must
always be protected against
overload.
Otherwise, the torque will exceed
the maximum limit and may lead to
an irreparable fracture of the iSave’s
internal parts.
24
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
7. Commissioning, start-up
and shutdown
7.1 Safety regulations
The operator ensures that all
inspection and installation work is
performed by authorised, qualified
specialist personnel who are
thoroughly familiar with the manual.
Before starting up the iSave and the
high pressure pump, make sure that
the following requirements are met:
• The iSave has been properly
connected to the electric power
supply and is equipped with all
protection devices in accordance
with EN60204-1.
• Check that all motor protections are
properly set.
• All safety equipment, auxiliary
equipment and connections
required are proper connected and
operational.
• Check all bolts in all connections
and in the foundation of the iSave
and the pumps.
7.2 Support
Danfoss A/S offers commissioning and
service at system manufacturer’s location.
Rate quotes are offered upon request.
7.3 Commissioning
Before starting up the iSave and the
high pressure pump make sure that the
following requirements are met:
• All pipes are flushed, free from
debris and full of water.
• The iSave has been bled and is full
of water.
• At pressure lower than 10 bargs, check the system for leakage.
Slowly raise the pressure in the system
and set all pressure switches to the
correct limit and continually check all
connections for leakage.
• Set pressure relief valve on both
low and high pressure at the
maximum system pressure.
• Check high pressure hoses for
proper assembly and inspect for
externa leakage for all connections.
• At low pressure, start the iSave and
check direction of rotation.
• Start the system according to the
“Start and stop procedure”
instructions in appendix. 10.1
180R9401 | AQ261351057880en- 000801 | 01.2022
25
Operating guide | iSave 21 Plus
8. Service/
Maintenance
8.1 Safety regulations
The operator ensures that all
maintenance, inspection and
installation work is performed by
authorised, qualified specialist
personnel who are thoroughly familiar
with the manual.
Before intervening in the iSave/system;
• The power must be shut off and the
starting device be locked.
• The pressure in the High Pressure lines
must be drained to the Low Pressure
side.
• The Water in all connected pipes must
be drained.
Always use suitable safety and lifting
equipment when handling the iSave,
and follow the instructions in
chapter 4.3
• When saftey equipment has been
adjusted make sure that proper
re-adjustment has been made before
start-up.
• When the system is re-started after
service and maintenance follow the
instructions in chapter 7 and in “Start
and stop procedures” in
appendix. 10.1
8.2 Support
Danfoss A/S offers commissioning and
service at the system manufacturer’s
location. Rate quotes are offered upon
request.
8.3 Maintenance schedule
The schedule of preventive maintenance
below will help ensure that the iSave
provides years of trouble-free performance.
One day after commissioning:
1. Re-check bolts in the foundation and
the baseplate of the iSave and
tighten the bolts to specified torque
if necessary.
2. Visually inspect all pipe connections
/ couplings for external leakage.
3. Re-check bolts in all pipe
connections / couplings and tighten
the bolts to specified torque if
necessar y.
4. Replace filters if necessary
5. Clean the filter housing and reinstall
filters. Make sure no debris enters
the system.
Three months after commissioning:
1. Re-check bolts in the foundation
and the baseplate of the iSave and
tighten the bolts to specified torque
if necessary.
2. Re-check alignment of iSave
baseplate and iSave.
3. Visually inspect all pipe connections
/ couplings for external leakage.
4. Re-check bolts in all pipe
connections / couplings and tighten
the bolts to specified torque if
necessary.
5. Replace filters if necessary.
6. Clean the filter elements and install
the new filters. Make sure no debris
enters the system.
7. Audibly inspect the iSave assembly. If
there is irregular sounds or vibrations
inspect the internals parts of the
iSave and replace if necessary.
26
180R9401 | AQ261351057880en- 000801 | 01.2022
Operating guide | iSave 21 Plus
8,000 hours of operation after commissioning:
1. Re-check bolts in the foundation
and the baseplate of the iSave and
tighten the bolts to specified torque
if necessary.
2. Re-check alignment of iSave
baseplate and iSave.
3. Visually inspect all pipe connections
/ couplings for external leakage.
4. Re-check bolts in all pipe
connections / couplings and tighten
the bolts to specified torque if
necessary.
5. Replace filters if necessary.
6. Clean the filter elements and install
the new filter. Make sure no debris
enters the system.
7. Audibly inspect the iSave assembly.
If there is irregular sounds or
vibrations inspect the internals parts
of the iSave and replace if necessary.
8. Visually inspect pump coupling and
replace if necessary.
9. Audibly inspect the iSave assembly.
If there is irregular sounds or
vibrations inspect the internals
parts of the iSave and replace if necessary.
10.Check power consumption and flow
out of the iSave. If there is irregular
performances inspect the internals
parts of the iSave and replace if
necessary.
11.Inspect and replace, if necessary, the
vanes in the vane pump.
Dimensions of the vanes
iSave typeiSave 21 Plus
Original height (H)27 mm
Change when H is less than26 mm
Original length (L)79.84 mm
Change when L is less than79.64 mm
Annually:
1. See above section: “8,000 hour of
operation after commissioning”.
2. See “Operating- and maintenance
instruction, electric motor” in
appendix 10.6
Follow manufacturer’s recommendations for
electric motor service and maintenance.
180R9401 | AQ261351057880en- 000801 | 01.2022
27
Operating guide | iSave 21 Plus
9. Trouble-shooting
9.1 Safety regulations
The operator ensures that all
inspection and installation work is
performed by authorised, qualified
personnel who are thoroughly familiar
with the manual.
Before intervening in the iSave/system;
• The power must be shut off and the
starting device be locked.
• The pressure in the high-pressure
lines must be drained to
low-pressure side.
• The water in all connected pipes
must be drained.
The numbers in () correspond to the preferred system design and P&ID
ProblemPossible causeAction
VFD can’t start the iSave
at initial start-up.
VFD is not designed for constant torque.
Ramp-up settings in the VFD is
not correct. VFD is tilting.
Choose a VFD that is designed
for constant torque.
Set Ramp-up parameters
correct.
Valve (9) is closedOpen valve (9)
Torque on iSave too
high during operation
Pressure in the HP line (5) is
too high
Pressure difference from HPout (5) to HP-in (10) is too high.
Start the iSave only when the
pressure in the HP line is low.
Clean or change membranes.
Debris in the booster pump or
iSave.
Wear in the booster pump or
iSave.
Design of the basic plant
doesn’t fit the performance of
the iSave.
Permeate production is
too low (17).
Valves (6), (7), (8) or (16) are
leaking.
Repair or change valve.
Internal leakage in iSaveRepair iSave
HP pump flow (2) is to smallIncorrect speed on the HP
pump.
Check the HP pump and repair
if necessary.
Pressure on the mem-
Fouling on the membranesClean the membranes
branes (5) is too high.
Mixing in the iSave is too high. Check flow on LP-in (12) and
adjust flow.
Flow out of the iSave is too
low, causes a recovery rate
Check speed on iSave and
change if necessary.
that is too high.
Booster pump in the iSave is
worn out.
Perform service on the VP.
Pressure on the membranes (5) is too low.
Valves (6), (7), (8) or (16) are
leaking.
Repair or change valve (s).
Internal leakage in iSaveRepair iSave
HP pump flow (2) is too smallIncorrect speed on the HP
10.6 Operating- and maintenance instruction, electric motor (180R9230) . . . . . . . . 91
30
180R9401 | AQ261351057880en- 000801 | 01.2022
Design guide
iSave Energy Recovery Device
Start and stop of the SWRO with iSave
hpp.danfoss.com
Design guide | Start and stop of the SWRO with iSave unit
Table of ContentsPrior to start-up................................................................................................................................................................33
Starting up the system...................................................................................................................................................33
Daily system shutdown.................................................................................................................................................34
More than one day system shutdown........................................................................................................................35
32
180R9401 | AQ261351057880en- 000801 | 01.2022
Design guide | Start and stop of the SWRO with iSave unit
Below procedures are general guidelines for the
start-up and shut-down functions of SWROsystems with the Danfoss iSave Energy Recovery
Device.
Procedure details may differ depending on the
system design.
The numbers marked in () refer to the diagram
on page 5.
iSave can be both a single iSave and multiple
iSaves in parallel.
General SWRO system understanding with
ISave
• Basically the permeate flow is the same as the
flow from the high-pressure pump.
• The HP concentrate flow into iSave HP-in and
HP seawater-out is determined by the rpm of
the iSave.
• The iSave (s) HP flow determines the recovery
rate (higher rpm on the iSave gives lower
recovery rate and vice versa).
• Flow on the low-pressure side of the iSave is
determined by feed pump and the pressure
control valve LP-out (15) (not by the rpm of
the iSave).
• The flow on the low-pressure side must be at
least the same as on the high-pressure side
of the iSave (LP in flow = HP in flow; this is
called balanced flow).
• Continuously operation:
• To minimize mixing, the flow on the
low-pressure side can be adjusted up to 10%
higher than the high-pressure flow with the
limitation that the flow rate at LP inlet may not
exceed 70 m³/h.
Prior to start-up
High quality water extends the service life of the
whole system.
Both the APP pump and iSave are sensitive to
hard particles.
Before connecting any APP pump or iSave to
a piping system ALL pipes must be thorough
flushed with high quality pre-filtered water or
mechanical cleaned.
1. Install all filter cartridges in the system.
2. With the iSave(s) and APP pump(s) discon- nected from the piping, the system must be
flushed in order to remove possible
impurities from the system (pipes, hoses,
membranes etc.).
Flushing must run until the system can be ensured clean.
3. Connect the iSave(s) and APP pump(s) to
the pipework. The iSave(s) and APP pump(s)
are now ready for start-up.
Starting up the system
1. Make sure that all valves are set in normal
operating positions.
2. Start the seawater supply pump (A).
3. Make sure all pipework is flushed with water.
Vent all air from the system through air valve
(8) and iSave unit (11). After venting, close
valve (8).
At initial start-up also bleed the iSave(s) and
APP pump(s).
180R9401 | AQ261351057880en- 000801 | 01.2022
33
Design guide | Start and stop of the SWRO with iSave unit
4. Start the iSave(s).
In general: Only start the iSaves when the
pressure ”HP in” (10) is below 20 barg/290
psig. Always start the iSave unit before the
high-pressure pump is started.
There are in principle two ways to start multi
ple iSaves:
- Slowly ramp up all the iSaves at the same
time.
- Slowly ramp up one by one.
Starting sequence - one by one:
a) Start iSave #1.
b) After 5 sec. start iSave #2.
c) In a sequence of 5 sec. start the
remaining iSaves.
Comments:
- Ramp up time on iSaves is set between
10 –15 sec.
Starting sequence - Start all iSaves at the
same time.
Comments:
- Ramp up time on iSaves is set between
10 –15 sec.
If the pressure (10) at ”HP in” drops below
3 barg/43.5 psig, the sound will change of
the iSave. This is due to cavitation. ”HP in”
pressure at 3 barg/43.5 psig is acceptable
for less than 10 min. within a period of 6
hours.
If possible run the iSave at its min
allowable speed to reduce cavitation.
“LP-out” pressure (14) is below 1 barg/
14.5 psig, adjust the flow by raising the
flow from the seawater supply pump (A).
3. If the “LP-in” flow (12) is too high, reduce
flow by closing the pressure control
valve (15) or the flow from the seawater
supply pump (A).
10. For iSave 50 and iSave 70:Check the low pressure flow rates (12), and if
required, adjust flow with valve (15) to
achieve balanced flow to the iSave(s).
1. If the “LP-in” flow (12) is too low and the
“LP-in” pressure (21) is higher
than 2 barg/29 psig, increase flow and
decrease pressure by opening the
pressure control valve (15).
2. If the “LP-in” flow (12) is too low and the
“LP-in” pressure (21) is below 2 barg/
29 psig, adjust the flow by raising the
flow from the seawater supply pump
(A).
3. If the “LP-in” flow (12) is too high, reduce
flow by closing the pressure control
valve (15) or the flow from the seawater
supply pump (A).
Daily system shutdown
1. The system is running in normal operation
and producing permeate flow.
2. Stop the high-pressure pump (4).
5. With a pressure control valve (15), adjust the
back pressure of the “LP-out” to fulfill the
minimum presure requested in the Data sheet. (May only be necessary at initial start
up).
6. An “over flush” of the iSave can be done to
bleed any remaining air from the system.
Flush over a period of minimum 2 minutes.
7. Adjust the speed of the iSave unit to desired
flow (rpm). The speed is controlled by a VFD.
8. Start the high-pressure pump(s) (4), and the
system pressure (5) will rise until the
permeate flow (17) almost equals the flow (2)
from the high-pressure pump.
9. For iSave 21 and iSave 40:Check the low pressure flow rates (12), and if
required, adjust flow with valve (15) to
achieve balanced flow to the iSave(s).
1. If the “LP-in” flow (12) is too low and the
“LP-out” pressure (14) is higher
than 1 barg/14.5 psig, increase flow and
decrease pressure by opening the
pressure control valve (15).
2. If the “LP-in” flow (12) is too low and the
3. Keep the iSave(s) (11) running until the
TDS in the high-pressure line is equal to the
TDS in the low-pressure line.
NB! If the pressure (10) at “HP in” drops
below 3 barg/43.5 psig, the sound will
change of the iSave. This is due to
cavitation. “HP in” pressure at
3 barg/43.5 psig is acceptable for less
than 10 minutes within a period of 6
hours.
If possible run the iSave at its minimum
allowable speed to reduce cavitation.
4. Stop the iSave(s)(11).
5. Stop the seawater supply pump (A).
34
180R9401 | AQ261351057880en- 000801 | 01.2022
Design guide | Start and stop of the SWRO with iSave unit
More than one day system shutdown
1. Run the “daily system shutdown” procedure.
2. Supply permeate water to the SWRO system
by using fresh water/permeate flush
connection..
3. When the pressure ”HP in” (10) is below 20
barg/ 290 psig start the iSave(s).
NB! If the pressure (10) in “HP in” drops
below 3 barg/43.5 psig, the sound will
change of the iSave. This is due to
cavitation. “HP in” pressure at 3 barg/43.5
psig is acceptable for less than 10 minutes
within a period of 6 hours.
If possible run the iSave at its minimum
allowable speed.
4. Start the APP pump(s) in a period of 5 sec. by
using normal ramp-up settings.
5. Stop the APP pump(s) after 5 sec.
6. Run the iSave(s) until the TDS in the high-
pressure line is equal to the TDS in the low-
pressure line.
Energy Recovery Device
iSave
Membrane cleaning of RO-system
hpp.danfoss.com
Design guide Membrane cleaning of the RO-system with iSave ERD
Table of ContentsMembrane cleaning......................................................................................................................................................39
Starting up the system .................................................................................................................................................40
Starting up the system .......................................................................................................................................................... 41
38
180R9401 | AQ261351057880en- 000801 | 01.2022
Design guide Membrane cleaning of the RO-system with iSave ERD
Below procedures are general guidelines for
the membrane cleaning of SWRO-systems with
the Danfoss iSave. Procedure details may differ
depending on the system design.
The numbers marked in () refer to the
diagram’s below.
The purpose of membrane cleaning is to reduce
scaling and fouling in the membranes. For optimal performance specific chemicals are required,
depending on the cause of the contamination.
After chemical treatment the system must be
flushed with fresh water. The flushing water,
coming out of the membranes, may consist of a
large amount of suspended inorganic particles. It
is important to assure that these particles are not
fed into the iSave(s) or pump(s).
NB! It is recommended to disconnect the
piping from the “HP in” of the iSave and flush
the contaminated water from the membranes
directly to drain. By disconnecting the pipes
there will be no accumulation of
contaminations in the HP-piping and
HP-valves. See P&ID no 2.
Membrane cleaning
The procedures below are based on Dow’s
Cleaning and Sanitization: Cleaning steps
described in Dow’s Form No. 609-02090-1005.
Other procedure may be used depending on the
membranes used.
Below procedure is according P&ID no 1.
1. Stop the high-pressure pump(s) (4), and stop
the iSave(s) (11).
2. Stop the seawater supply pump (A).
3. Close valve (9 and 27) and open valve (16 and
28), and feed cleaning solution through valve
(7).
4. Pump mixed cleaning solutions to the vessel
at conditions of low flow rate and low pressure
to displace the process water. Use only
enough pressure to compensate for the
pressure drop from feed to concentrate.
The pressure should be low enough that
essentially no or little permeate is produced.
A low pressure minimizes re-deposition of
dirt on the membrane. Dump the brine/
concentrate to prevent dilution of the
cleaning solution.
180R9401 | AQ261351057880en- 000801 | 01.2022
5. Recycle: After the process water is displaced,
cleaning solution will be present in the
concentrate/ brine stream. Recycle the
cleaning solution from the piping to the
cleaning solution tank.
6. Turn of the pump and allow the elements
to soak.
39
Design guide Membrane cleaning of the RO-system with iSave ERD
7. Feed the cleaning solution at high flow into
the “full flow cleaning” adapter (7). The high
flow rate flushes out the foulants removed
from the membrane surface by the cleaning.
8. Flush RO permeate or deionised water into
the “full flow cleaning” adapter (7).
Flush out the cleaning solution.
It is essential that the water used for the final
pre-flush is pre-filtered to a level described
in the datasheet.
P&ID no. 1
4
2
26
Media filter
A
BC
Filter
3 micron
nominel
PI
Fresh water
permeate flush
10 micron
absolut
PI
F
*
PI
PS
21
24
19
3
Filter
PI
PS
F
1
12
LP in
HP out
11
iSave
HP in
M
VFD
2323
4
26
9. Open valve (9) and continue flushing.
The iSave(s) may start to rotate backward –
this is OK.
10. When flushing is finalised – assure that no
foulants remain in the piping or valve (9).
11. Close the high pressure “full flow cleaning”
valve (7) and close valve (16 and 28).
12. Open valve (27)
VFD
22
M
25
18
M
25
18
HP out
HP in
M
VFD
VFD
22
5
PI
6
PS
Flowmeter
Full flow
cleaning/CIP
7
1011
9
PI
13
14
PS
PI
15
20
F
8
16
28
27
Drain
17
Permeate
F
CIP
*
Second stage filter: If recommended housing design an d cartridges are not used, a second stage filter is required
Below procedure is according P&ID no 2.
1. Stop the high-pressure pump(s) (4), and stop
the iSave (11).
2. Stop the seawater supply pump (A).
3. Disconnect pipe in joint (9) and connect the
pipe to low pressure “Full flow cleaning”
joint (16).
4. Plug pipe in joint (9).
5. Close valve (27) and open valve (28)
6. Pump mixed cleaning solutions through valve
(7) to the vessel at conditions of low flow rate
and low pressure to displace the process
water. Use only enough pressure to
compensate for the pressure drop from feed
to concentrate.
The pressure should be low enough that
essentially no or little permeate is produced.
A low pressure minimizes re-deposition of dirt
on the membrane. Dump the brine/
concentrate to prevent dilution of the
cleaning solution.
7. Recycle: After the process water is displaced,
cleaning solution will be present in the
concentrate stream. Recycle the cleaning
solution from the piping to the cleaning
solution tank.
8. Turn of the pump and allow the elements to
soak.
9. Feed the cleaning solution at high flow into
the “full flow cleaning” adapter (7) on the
feed side of the membrane. The high flow rate
flushes out the foulants removed from the
membrane surface by the cleaning.
40
180R9401 | AQ261351057880en- 000801 | 01.2022
Design guide Membrane cleaning of the RO-system with iSave ERD
P&ID no. 2
10. Flush RO permeate or deionised water into
the “full flow cleaning” adapter (7) on the
feed side of the membrane. Flush out the
cleaning solution.
It is essential that the water used for the final
pre-flush is pre-filtered to a level described in
the datasheet.
M
4
2
26
Media filter
A
BC
Filter
3 micron
nominel
PI
Fresh water
permeate flush
10 micron
PI
F
*
PI
PS
21
24
19
3
Filter
PI
PS
absolut
F
1
12
LP in
HP out
11
HP in
M
VFD
2323
26
iSave
18
M
4
18
M
VFD
11. When flushing is finalised – Close the high
pressure “full flow cleaning” valve (7) and
close valve (28).
12. Connect the high pressure pipe to joint (9)
again.
VFD
22
VFD
25
25
HP out
HP in
5
PI
PS
PS14PI
22
6
Full flow
cleaning/CIP
7
1011
PI
9
13
15
20
F
Flowmeter
8
16
Drain
17
Permeate
F
28
CIP
v
27
*
Second stage filter: If recommended housing design and car tridges are not used, a second stage filter is required
VFD
22
M
4
2
26
Media filter
A
BC
Filter
3 micron
nominel
PI
PI
*
PI
PS
21
Fresh water
permeate flush
24
19
*
Second stage filter: If recommended housing design and car tridges are not used, a second stage filter is required
3
Filter
PI
10 micron
PS
absolut
F
1
F
12
LP in
HP out
11
HP in
M
VFD
2323
4
26
iSave
25
18
M
25
18
HP out
HP in
M
VFD
VFD
22
5
PI
6
PS
Full flow
cleaning/CIP
7
1011
PI
9
13
15
20
PS14PI
F
Flowmeter
8
16
Drain
17
Permeate
F
28
CIP
27
180R9401 | AQ261351057880en- 000801 | 01.2022
41
Danfoss A/S
High Pressure Pumps
Nordborgvej 81
SK-6430 Nordborg
Denmark
12.3 Re p air .................................................................................70
44
180R9401 | AQ261351057880en- 000801 | 01.2022
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
1. General information
iSave 21 Plus
iSave 40
1. 2” Victaulic connections
2. Shaft
3. Low pressure shaft seal
4. Port flange
5. Port plate
6. Valve plate
7. Cylinder drum
8. Port flange
9. Port plate
10. Pins
11. Vane s
12. Port plate
13. Coupling
14. Adapter flange
15. Rotor
16. Stator
17. Port flange
18. Outlet flange
The iSave 21 Plus and iSave 40 consists of an
isobaric pressure exchanger, a high-pressure
positive displacement booster pump and an
electric motor.
The isobaric pressure exchangers are based on
the technology used in the Danfoss APP pumps,
and the high-pressure booster pumps are based
on the vane pump principle enabling a very light
and compact design. The design of iSave 21 Plus
and iSave 40 ensures lubrication of the moving
parts by the fluid itself.
All parts included in the iSave 21 Plus and iSave
40 are designed to provide long service life with
a constant high efficiency and minimum service
required.
1.1 iSave 21 Plus
109
11
12
17
1
18
15
16
14
8
1212
The vane pumps are fixed displacement pumps
in which the flow is proportional to the number
of revolutions of the driving shaft – enabling flow
control.
The electric motor provides speed control of
both the pressure exchanger and the highpressure booster pump on the same shaft
– preventing overspin/overflushing.
The iSaves need a VFD that allows the motor to
apply a constant torque from low speed to
maximum speed.
The sectional drawings below illustrate the main
components of the iSave 21 Plus and iSave 40,
respectively
6
5
1
13
6
7
5
1
4
2
3
1
180R9401 | AQ261351057880en- 000801 | 01.2022
45
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
1.2 iSave 40
1. 3” Victaulic connections
2. Shaft
3. Low pressure shaft seal
4. Port flange
5. Port plate
6. Valve plate
7. Cylinder barrel
8. Port flange
9. Sealing plate
10. Pins
11. Vane s
12.Port plate
13. Coupling
14. Adapter flange
15. Rotor
16. Stator
17. Port plate
18. Outlet flange
2. Benefits
• One of the smallest and lightest energy recovery
devices on the market
• Few components
• High efficiency
• No need for high-pressure flow meters
• No expensive high-pressure mechanical seal
• No risk of over spin/over flushing
• Easy modular service
• All parts of the device are made of high
corrosion-resistant materials e.g. Super Duplex
(HP)
High-pressure outlet
(LP)
Low-pressure inlet
(HP)
High-pressure inlet
(LP)
Low-pressure outlet
46
180R9401 | AQ261351057880en- 000801 | 01.2022
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
3. Technical data
3.1 iSave without motor
iSave sizeiSave 21 PlusiSave 40
Code number180F701518 0F 7011
Geometric displacement
Pressure
Differential pressure HP in - HP out max.
HP max. outlet pressure
HP min. inlet pressure
HP max. inlet pressure
HP inlet min. pressure,
intermittent
2) 3)
LP inlet max. pressure
LP inlet max. pressure intermittent
3)
LP outlet min. pressure
LP differential LP in - out at HP max. flow
Speed
Min. speedrpm500600
Max. speedrpm1500120 0
Typical flow
HP outlet flow range
4)
at max. differential pressure
Lubrication flow at 60 barg (871 psig) max.
LP inlet max. flow
Torque
Torque at max. differential pressure
operation
1)
Max. starting torque (stick/slip)
Media temperature
5)
Ambient temperature
Filtration requirements (nominal)
6)
Salinity increase at membrane at 40% recovery rate2-3 %
Weight
1)
Continuous torque a bove max. differential pre ssure
will reduce the lifetime of the iSave.
2)
Pressure can reach this pressure level at start-up
and permeate flush.
3)
Intermittent pressure is acceptable for less than 10
180R9401 | AQ261351057880en- 000801 | 01.2022
cm³/rev273626
In³/r ev16.738.2
bar55
1)
psi72.572.5
barg8383
psig120 0120 0
barg1520
psig217290
barg8383
psig120 0120 0
barg33
psig4444
barg55
psig7272
barg1010
psig145145
barg11
psig14. 514. 5
bar0.91.2
psi1317.5
m³/h6-2221-41
gpm26-9692-180. 5
m³/h0.40.8
gpm1.83.5
m³/h3367
gpm145295
Nm49102
lbf-ft3675
Nm50150
lbf-ft37110
o
C2-402-40
o
F36 -12236 -122
o
C0-500-50
o
F32-10432-10 4
3 micron melt-blow
kg47123
lb103271
minutes within a period of 6 hours.
4)
Typical average flow at 60 bar.
5)
Dependent on NaCI concentation.
6)
Please see section 7. filtration.
47
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
3.2 iSave with IEC motor
iSaveiSave 21 Plus A)iSave 21 Plus iSave 40
Code number horizontal180F7016180F7 017180 F700118 0F7004
Code number vertical180F701618 0F7017180F7003180F7005
Motor size IEC version IEC 400 V,
1)
50 Hz
Frame size
Motor data
Nominal speedrpm14501450970970
Min. speed at 400 Vrpm500
Max. speed at 400 Vrpm150 0150 0
Rated current at 400 VA1115.22230
Torque
Motor torque at norminal speed
Motor torque at min. speed
3)
Motor ambient temperature, max.
Motor insulationClassBBBB
Motor degrees of protectionIP55555555
Sound pressure level max.
6)
Weight
Footprint (horizontal/vertical)
kW5.57.51115
HP7. 5101520
IEC132 S132 M160 L180 L
pole4466
Nm3649
3) 4)
lbf-ft26.53680107.7
Nm273695129
lbf-ft20277095
o
C40404040
o
F12212212 212 2
dB(A)78798484
kg105116254305
lb231255560672
m²0.310.320.5/0.160.54/0.17
foot²3.343.455.38/1.725.81/1.83
2)
500600600
3)
110 012 00
5)
108146
A)
Differential pressure HP in - HP out max. is limited
to 3 bar [44 psi]
1)
Three-phase-asynchronous-motor according to
DIN-IEC and VDE 0530 standards.
• Voltage and frequency according to IEC 38
• The motors are fitted with a rating plate in
multi-tension: 380-420 V / 660-720 V, 50 Hz or
440-480 V, 60 Hz
• Tolerance ± 5% according to VDE 0530
• Standard coating according to IEC 60721-2-1
2)
If voltage is below 400 V we recommend to use
another size of electric motor.
Please contact Danfoss High Pressure Pumps for
further information.
3)
Torque load for iSave and motor see diagram on
page 23 and 25.
4)
Due to iner tia and stick-slip frictio n of the iSave, the
torque may exceed the maximum allowable
operation torque for the iSave when it is taken into
use and/ or speed is ramped up from zero to
maximum. A VFD or a soft starter must be used for
ramp up.
5)
The starting torque must not exceed the values
stated under “Max. starting torque (stick/slip)”. The
VFD must be able to deliver 140% start torque. The
Danfoss VFD type FC 301 and FC 302 can be used.
For advice on VFD settings, please consult our
relevant guideline or contact Danfoss.
6)
A-weighted sound pressure level at 1 meter from
the pump unit surfaces (reference box) acc. to EN
ISO 20361 section 6.2. The noise measurements are
performed acc. to EN ISO 3744:2010 on ERD with
motor (motor-pump unit) at max. pressure and
speed.
48
180R9401 | AQ261351057880en- 000801 | 01.2022
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
3.3 iSave with NEMA motor (can only be ordered through Danfoss US)
iSaveiSave 21 Plus A)iSave 21 PlusiSave 40
Code number horizontal180U0013180U0052180U0012
Code number vertical180U0013180U0052180U0002
Motor size NEMA version
1)
High efficiency 460 V, 60 Hz
Frame size
Motor data
Nominal speedrpm
Min. speed continuous at 400 Vrpm500500600
Max. speed continuous at 400 Vrpm150 015001200
Motor rated current 460 VA12 .41824.2
Torque
Motor torque at norminal speed
Motor torque at min. speed
4)
Motor ambient temperature, max.
3,300 feet above sea level
Motor degrees of protectionIP555555
Sound pressure level max.
6)
Weight
Footprint (horizontal/vertical)
A)
Differential pressure HP in - HP out max. is limited
to 3 bar [44 psi]
kW7.51115
HP101520
NEMA215TC254286TC
pole446
Nm
3) 4)
(lbf-ft)29.444
Nm203195
(lbf-ft)14. 72370
o
C404040
(oF) 122122 122
dB(A)7879
kg152206324
(lb)335454715
m²0.380.45/0.160.65/0.23
foot²4.094.85/1.727.0/2.48
2)
176017651175
4059.7119
*)
Tested with IEC motor
5)
88.2
*)
84
1)
Three-phase-asynchronous-motor according to
NEMA MG-1 and UL 1004-1 standards.
• Insulation class F, service factor 1.25.
• Fan-cooled TEFC (IC411). Voltage and frequency
according to NEMA MG-1 part 12.
• The motors are fitted with a rating plate 230 /
460 V, 60 Hz.
• Plus or minus 10% of rated voltage, with rated
frequency. Standard coating according to
motor supplier specifications.
2)
Max. speed for iSave 21 is 1500 rpm.
3)
Torque load for iSave and motor see diagramme on
page 23 and 25.
4)
Due to inertia and stick-slip friction of the iSave, the
torque may exceed the maximum allowable
operation torque for the iSave when it is taken into
use and/ or speed is ramped up from zero to
maximum. A VFD or a soft starter must be used for
ramp up.
5)
The starting torque must not exceed the values
stated under “Max. starting torque (stick/slip)”. The
VFD must be able to deliver 140% start torque. The
Danfoss VFD type FC 301 and FC 302 can be used.
For advice on VFD settings, please consult our
relevant guideline or contact Danfoss.
6)
A-weighted sound pressure level at 1 meter from
the pump unit surfaces (reference box) acc. to EN
ISO 20361 section 6.2. The noise measurements are
performed acc. to EN ISO 3744:2010 on ERD with
motor (motor-pump unit) at max. pressure and
speed.
180R9401 | AQ261351057880en- 000801 | 01.2022
49
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
ppm
iSave 21 Plus
iSave 40
0
22
44
66
88
110
132
154
176
198
0
5
10
15
20
25
30
35
40
45
500600700800900100011001200130014001500
gpm
m3/h
rpm
Flow at HP out vs. rpm
4. Flow at different rpmThe diagram shows that the HP flow can be
changed by changing the rotation speed of the
iSave. The flow/rpm ratio is constant, the
required flow is obtainable by changing the
rotation speed to a required value.
For accurate data please use our selection tool
which is available on our website:
www.isave.danfoss.com
The iSave is delivered with a 3.1 performance
certificate according to EN10204.
5. Corrosion
5.1 Operation
The chart below illustrates the corrosive
resistance of different types of stainless steel
related to NaCl concentration and temperature.
All critical parts of the iSave is made of
Super Duplex 1.4410/UNS 32 750 or Duplex
1.4462/UNS 32803.
º
80
C
70
60
50
40
316L
30
20
100
1601600
1000
Always flush the iSave with fresh water at
operation stop in order to minimize the risk of
crevice corrosion.
Duplex
Super Duplex
10 000
16000
100 000
160000
CI
ppm
NaCI
-
50
180R9401 | AQ261351057880en- 000801 | 01.2022
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
6. Noise levelThe noise level for the iSaves is measured at max.
speed, a pressure of80 barg and a booster
pressure of5 bar.Since the iSave is mounted on a
bell housing and electric motor, the noise level
can only be determined for the complete unit
(system).
It is therefore important that a horizontal iSave
unit is mounted correctly on a frame with
dampeners to minimize vibrations and noise.
We recommend to mount a vertical iSave directly
to the floor with bolts. It is also strongly recommended to use high-pressure flexible hoses
between the hard piping in the RO-plant and the
iSave or to use multiple connections with
Victaulic clamps.
The noise level is influenced by:
Speed:
• High rpm makes more fluid/structure-borne
pulsations/vibrations than low rpm due to
higher frequency.
Noise level (dB(A) measured for the iSave 21 Plus and 40 at different speed and system pressure.
Booster pressure 3 bar.
Pressure:
• High pressure makes more noise than low
pressure.
Mounting:
• Rigid mounting makes more noise than flexible mounting due to structure-borne
vibrations.
Connections to iSave:
• Pipes connected directly to the iSave make
more noise than flexible hoses due to structure-borne vibrations.
• Variable frequency drives (VFD):
Motors regulated by VFDs can increase noise
level if the VFD does not have the right
settings.
7. Filtration
iSave 21 PlusiSave 40
barg/psig
rpm
500606268
1000697274
150 0777878
20/29060/87080/1160
It is important that the incoming water is filtered
properly to ensure optimum service life. A true
graded density, melt-blown depth filter cartridge
barg/psig
rpm
support core. High Pressure Pumps does not
recommend cartridges requiring any type of
binders or resins.
rated at 3 μm is therefore recommended.
Filters can be purchased from Danfoss
It is important with selection of a proper filter
housing to ensure good cartridge end sealing.
If there is a high risk of water by-pass it is
recommended to use a second stage filter
solution.
High Pressure Pumps. Please see section 10.0,
“RO systems with an iSave”, for installation of
filter. For more information on the importance of
proper filtration, please consult our publication
“Filtration” (code number 521B1009), which also
will provide you with an explanation of filtration
As the various filters on the market differ greatly,
Danfoss High Pressure Pumps recommends
definitions and a guidance on how to select the
right filter.
using cartridges with consistent, reliable
performance and high efficiency and where
fibres are blown continuously onto a central
30/43560/87080/1160
800737778
1000767981
120 0788284
180R9401 | AQ261351057880en- 000801 | 01.2022
51
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
8. iSave drawings8.1 Assembled iSave 21 Plus and iSave 40
without electric motor
iSave 21 Plus
52
180R9401 | AQ261351057880en- 000801 | 01.2022
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
iSave 40
180R9401 | AQ261351057880en- 000801 | 01.2022
53
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
8.2 Assembled iSave 21 Plus
and iSave 40
with IEC electric motor
iSave 21 Plus, 5.5 kW, 4 pole, IEC motor
54
180R9401 | AQ261351057880en- 000801 | 01.2022
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
iSave 21 Plus, 7.5 kW, 4 pole, IEC motor
180R9401 | AQ261351057880en- 000801 | 01.2022
55
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
iSave 40 - horizontal, 11 kW, 6 pole, IEC motor
56
180R9401 | AQ261351057880en- 000801 | 01.2022
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
iSave 40 - horizontal, 15 kW, 6 pole, IEC motor
180R9401 | AQ261351057880en- 000801 | 01.2022
57
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
iSave 40 - vertical, 11 kW, 6 pole, IEC motor
58
180R9401 | AQ261351057880en- 000801 | 01.2022
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
iSave 40 - vertical, 15 kW, 6 pole, IEC motor
180R9401 | AQ261351057880en- 000801 | 01.2022
59
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
8.3 Assembled iSave 21 Plus
and iSave 40
with NEMA motor
iSave 21 Plus, 10 HP, 4 pole, NEMA motor
60
180R9401 | AQ261351057880en- 000801 | 01.2022
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
iSave 21 Plus, 15 HP, 4 pole, NEMA motor
180R9401 | AQ261351057880en- 000801 | 01.2022
61
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
iSave 40 - horizontal, 20 HP, 6 pole, NEMA motor
62
180R9401 | AQ261351057880en- 000801 | 01.2022
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
iSave 40 - vertical, 20 HP, 6 pole, NEMA motor
180R9401 | AQ261351057880en- 000801 | 01.2022
63
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
9. Installation
Orientation
iSave 21 Plus and iSave 40 can be mounted
horizontal and vertical. iSave 40 can be mounted
horizontally and vertically - when mounted
vertically, the electric motor must be placed at
the top of the iSave.
The iSave 21 Plus baseplate can be used for both
horizontal and vertical installations.
The iSave 40 has a base when installed vertical.
A: Flexible coupling
B: Bell housing
C: Motor shaft
The iSave is connected to the electric motor by a
bell housing and coupling.
If a horizontal iSave is delivered without base
plate it is important to support the iSave and
motor. The bell housing is not able to carry the
weight of either the iSave or the motor when
using horizontal mounting.
Mounting
The figure below illustrates how to mount
the iSave and connect it to the electric
motor.
Note: Any axial and radial load on the shaft
must be avoided.
min. 3 - 5 mm air sp ace
A B C
The iSave and motor must be supported without
applying stress/overload to the bell housing.
If a horizontal iSave is delivered with a baseplate,
a rigid mounting surface is required such as
concrete foundation, optional base frame or a
container with suitable steel substructure.
64
1: Motor2: Flexible coupling3: Bell housing4: Base plate
180R9401 | AQ261351057880en- 000801 | 01.2022
5: Pressure exchanger6: Booster pump7: Port connection
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
10. RO systems with an
iSave
P&ID setup
VFD
Media filter
1
Filter
3 micron
nominel
Fresh water
permeate flush
Filter
10 micron
PIPI
19
*
Second stage filter: If recommended housing design and cartridges are not used, a second stage filter is required
absolut
F
12
LP in
*
2
F
HP out
11
M
VFD
PI
PS
HP in
3
iSave
4
M
18
PS
Explanation of P&ID setup
A. Place inlet filters on LP string in front of the
iSave (11). Inlet filters assure proper water
quality. High quality water extends the
service life of the whole system. It is impor
tant with selection of a proper filter housing
to ensure good cartridge end sealing. If there
is a high risk of water by-pass it is recom mended to use a second stage filter solution.
Please consult section 7, “Filtration” for guidance on how to select the right filter.
Thoroughly clean pipes and flush system
prior to start-up.
B. Place a monitoring pressure switch set (3) at
minimum inlet pressure between filter and
pump inlet. The monitoring switch must stop
the iSave (11) and the high-pressure pump (4)
at pressures lower than minimum inlet
pressure.
C. Dimension the piping to obtain minimum
pressure loss (large flow, minimum pipe
length, minimum number of bends/connec-
tions and fittings to prevent pressure loss and
flow turbulence). Use flexible hoses to
minimize vibrations and noise.
D. To balance the flow between high-pressure
out and low-pressure in, place a variable area
flow meter (12) on low-pressure inlet to the
iSave.
E. In order to eliminate the risk of damage and
cavitation, a positive pressure at the
PI
5
PS
1314
6
Full flow
cleaning
7
10
PI
PI
20
F
9
15
17
Permeate
F
Flowmeter
8
16
28
CIP
27
Drain
low- pressure outlet from the iSave is always
to be maintained at minimum 1 barg (14.5
psig) and maximum 10 barg (145 psig). It is
recommen ded to install monitoring pressure
switch (13) in order to prevent high/low-pres
sure.
F. Install a VFD to control the speed of the iSave.
G. Install a pressure and flow control valve (15) to
control pressure in low-pressure out.
H. Although the iSave 21 Plus automatically will
bleed itself, there should be an air bleed valve
(8) installed on the highest point of the high-pressure piping to ensure proper bleeding of the RO system.
I. The pressure relief valve (6) protects the
whole system against pressure overload and
relieves the water if the pressure exceeds the
maximum set pressure.
If the high-pressure pump is a positive
displacement pump, the pump can built up a
very high pressure that will exceed mechanical strength of the membrane housing, pipes
and other accessories.
J. The pressure relief valve (19) protects the
low-pressure pipes against pressure overload
and relieves the water if the pressure exceeds
the maximum allowable pressure.
For alternative P&ID setup, please contact
Danfoss High Pressure Pumps sales organisation.
180R9401 | AQ261351057880en- 000801 | 01.2022
65
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
22,030,839,648,457,266,074,883,792,5101,3110,1
0,0
2,9
5,8
8,7
11,6
14,5
17,4
20,3
23,2
26,1
0,0
0,2
0,4
0,6
0,8
1,0
1,2
1,4
1,6
1,8
5,07,09,011,013,015,017,019,021,023,025,0
gpm
psi
bar
m3/h
Differential pressure vs. flow at LPin
60 ba rg
22,030,839,648,457,266,074,883,792,5101,3110,1
30 ba rg
0,00
0,22
0,44
0,66
0,88
1,10
1,32
1,54
1,76
0,00
0,05
0,10
0,15
0,20
0,25
0,30
0,35
0,40
5,07,09,011,013,015,017,019,021,023,025,0
gpm
gpm
m3/h
m3/h
Lubrication flow vs. flow at HPout
11. Performance curves
11.1 Performance and torque curves iSave 21 Plus
66
180R9401 | AQ261351057880en- 000801 | 01.2022
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
Torque for iSave 21 and motor at 60 barg system pressure
180R9401 | AQ261351057880en- 000801 | 01.2022
67
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
11.2 Performance and torque curves iSave 40
Differential pressure, low pressure
bar
1.40
psi100140180
20
1.20
1.00
15
0.80
10
0.60
0.40
5
0.20
0.00
20.0
22.0
24.0
26.0
28.0
30.0
32.0
34.0
36.0
38.0
40.0
42.0
m
44.0
Lubrication flow
m3/hgpm
1.00
3
/h
0.90
60 barg
0.80
3
0.70
0.60
0.50
30 barg
0.40
1.5
0.30
0.20
0.10
0.00
42
40
38
36
34
32
30
28
26
24
22
20
m3/h
44
68
180R9401 | AQ261351057880en- 000801 | 01.2022
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
Torque for iSave 40 motor at 60 barg system pressure
Nmlbf ft
150
140
130
120
110
100
90
80
70
60
50
40
30
20
600
650
X
700
750
800
850
110.63
103.26
95.89
88.50
X
900
950
X
X
i
s
p
5
.
2
7
r
a
b
5
r
a
b
4
r
a
b
3
b
2
b
1
1000
i
s
p
8
5
i
s
p
5
.
3
4
i
s
p
9
2
r
a
r
a
1050
i
s
p
5
.
4
1
1100
1150
81.13
73.75
66.38
59.00
51.63
44.25
36.88
29.50
22.13
rpm
1200
Important:
The marked area at 1100-1200 rpm shows the operation
area which cannot be reached with a 11 kW motor at 400
voltage supply. A 15 kW is needed if max rpm (1100-1200)
and max differential pressure (4 to 5 bar) is required.
Max motor torque for 15 kW, IEC180L-6, 50 Hz, 400 V
Max motor torque for 20 HP, NEMA286TC-6, 60 Hz, 460 V
Max motor torque for 11 kW, IEC160L-6, 50 Hz, 400 V
X
Max motor torque for 11 kW, IEC160L-6, 60 Hz, 480 V
The straight pressure lines (1 to 5 bar) show the needed
shaft torque for the iSave at different pressures.
180R9401 | AQ261351057880en- 000801 | 01.2022
69
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
12. Service
12.1 Warranty
The Danfoss iSave is designed for long operation,
low maintenance and reduced lifecycle costs.
Provided that the iSave has been running
according to the Danfoss specifications, Danfoss
guarantees 8,000 hours service-free operation,
however, max. 18 months from date of production.
The life of an iSave may be greatly shortened if
Danfoss recommendations concerning system
design are not followed.
Standstill
The iSave is made of Duplex or Super Duplex
materials with excellent corrosion resistance.
However, it is always required to flush the iSave
when the system is shut down.
12.2 Maintenance
In our experience, poor filtration is the number
one cause of iSave damage. Danfoss recommends an periodic inspection where worn parts,
if any, must be replaced. This is done in order to
to prevent a potential breakdown of the iSave.
12.3 Repair
In case of irregular function of the iSave, please
contact Danfoss High Pressure Pumps.
70
180R9401 | AQ261351057880en- 000801 | 01.2022
Data sheet | Energy Recovery Device | iSave 21 Plus and iSave 40
180R9401 | AQ261351057880en- 000801 | 01.2022
71
Danfoss A/S
High Pressure Pumps
DK-6430 Nordborg
Denmark
Danfoss ca n accept no respons ibility for pos sible errors in ca talogues, bro chures and other pr inted material. Da nfoss reserve s the right to alter its p roducts with out notice.
This also a pplies to produc ts already on ord er provided that su ch alterations ca n be made without su bsequential cha nges being nece ssary in speci fications alread y agreed.
All trade marks in this mate rial are proper ty of the respec tive companies . Danfoss and the Danf oss logotyp e are trademark s of Danfoss A/S. Al l rights reserv ed.
Exploded view iSave 21 Plus .......................................................................81
74
180R9401 | AQ261351057880en- 000801 | 01.2022
Parts list | Energy Recovery Device iSave 21 Plus
iSave 21 Plus
This part list provides an overview of the content of various service sets for the iSave 21 Plus as well as
exploded views of the iSave, pressure exchanger and booster pump.
180R9401 | AQ261351057880en- 000801 | 01.2022
75
Parts list | Energy Recovery Device iSave 21 Plus
Pressure exchanger
Note: The parts listed are not sold seperately, only in various kits
Exploded view, see following pages.
Pos.Qnt.DesignationMaterial
Valve
plate
1011PE HousingDuplex
180 F4101
1021
1031
1041
1051
1062Int. Valve plateSuper DuplexX
1071Cylinder barrelSuper Duplex
1081ShaftSuper Duplex
1091Spring stopSuper Duplex
1102
1111
1121CoverSuper Duplex
1131
1141Clips iSavePPS HP VX
1152Pin Ø6 x 10PEEKXXX
1162Pin Ø6 × 10AISI 316X
11729
11812
1191Shaft seal Ø18AISI 316X
1203
1214
1222
1233
1241
1251
12624Backup ringPTFEX
12724
1281
1291Bush/BearingPEEK
1301Key 5 × 5 × 20AISI 316TiX
1311
Mounting
flange
Intermediate
flange
Port plate
Sea water
Port plate
Brinea
Victaulic studs
2”
2” victaulic
studs
Ass. HP Be aring
support
Screw
M8 × 45,0,
A4-80
Screw M6 × 16
CS RS A4
Compression
spring ø1,4 ×
ø9,5
Screw
M10 × 30 A4-80
O-rin g 135,00
× 3,00
O-rin g 50,00
× 2,00
O-rin g 40,00
× 2,00
O-rin g Ø30,00
× 2,00
O-rin g 18,00
× 2,00
O-rin g 17,00 ×
3,00 NBR 70
Liftin g eye M8
(DIN 580E)
Super Duplex
Super Duplex
«Super Duplex
PEEK»
«Super Duplex
PEEK»
Super Duplex
Super Duplex
«Super Duplex
PEEK»
AISI 316X
AISI 316X
Hastelloy C276
AISI 316X
NBR 70X
NBR 70X
NBR 70X
NBR 70XX
NBR 90X
NBR 70X
AISI 316
180 F4102
Port plate,
brine
X
180 F4155
Port plate,
sea water
X
180 F4156
HP
bearing
X
180 F4157
Sealing
kit
76
180R9401 | AQ261351057880en- 000801 | 01.2022
Parts list | Energy Recovery Device iSave 21 Plus
Booster Pump (vane pump)
Note: The parts listed are not sold seperately, only in various kits
Instruction | Right and wrong - Hose assembly routing tips
HOSES & HOSE COUPLINGS
GS-HYDRO PRODUCT CATALOGUE
Assembly and installation
When hose installation is straight, allow enough slack in hose line to provide for length changes which will occur when pres-sure is applied.
Prevent twisting and distortion by bending hose in same plane as the motion of the boss to which hose is connected.
User proper angle adaptors to avoid sharp twist or bend in hose.Adequate hose length is necessary to distribute movement on
flexing applications and to avoid abrasion.
When radius is below the required minimum, use an angle adap-tor to avoid sharp bends.
Avoid twisting of hose lines bent in two planes by clamping hose at change of plane.
Hose assembly routing tips
HOSES & HOSE COUPLINGS
GS-HYDRO PRODUCT CATALOGUE
Assembly and installation
When hose installation is straight, allow enough slack in hose line to provide for length changes which will occur when pres-sure is applied.
Prevent twisting and distortion by bending hose in same plane as the motion of the boss to which hose is connected.
Avoid twisting of hose lines bent in two planes by clamping hose at change of plane.
Hose assembly routing tips
HIGH
PRESSURE
NO
PRESSURE
Correct hose installation is essential for safe and
satisfactory performance. The size of the hoses
impacts the installation recommendations. This
manual has therefore been split in recommendation for hoses up to 2” and recommendation
larger than 2”.
1. Hoses up to 2”When installing hoses, avoid twisting the hose as
the hose will try to straighten under pressure.
MIN. 10°
Always provide some angle on straight
hose installations, this reduces forces
and ensures that hose is only bending i
one direction. The Hose must have some
slack to compensate for hose length
variations.
Hose routing tips:
Danfoss recommends installing hose whip
restraints whenever your pressurized hose
assemblies are in proximity to personnel or
crucial equipment.
Check with these examples when installing
your hoses.
This can cause hose failure via hose blowout
from the fitting and/or hose burst at the point of
strain.
WRONG
RIGHT
When radius is below the required minimum, use an angle adap-
tor to avoid sharp bends.
At radius below required minimum, angle
adapters should be used to prevent sharp
hose bends.
NO
PRESSURE
To allow the hose to expand when
pressurized, clamps should not be used at
bends. If possible, do not clamp high and
low pressure lines together.
HIGH
PRESSURE
WRONG
RIGHT
Use proper angle adapters to avoid sharp twist
or bend of hose.
84
180R9401 | AQ261351057880en- 000801 | 01.2022
Instruction | Right and wrong - Hose assembly routing tips
WRONG
WRONGRIGHT
To prevent hose collapse and flow restriction,
hose bend radii should be kept as large as
possible. Tight bends can also compromise
the hose reinforcement and cause premature
hose failure. Refer to hose specification table
on page 6 for minimum bend radii.
RIGHT
180R9401 | AQ261351057880en- 000801 | 01.2022
85
Instruction | Right and wrong - Hose assembly routing tips
2. Hoses larger than 2”
Whenever possible, high pressure hoses should
always be connected directly to Danfoss provided adapters and check valves. Elbows and
distance pipes should be avoided to prevent
excessive side loads.
MIN. 10°
Always provide some slack on straight hose installations. This compensates for hose length
variations with differences in internal fluid
pressures. A small angle will reduce the forces
from the hose and allow the hose to bend
when pressurized.
Danfoss 3” HP hoses are nylon reinforced; when
using hoses that are not steel reinforced the
connected items must be grounded to avoid
electrical stray currents.
EXPANSION
EXPANSION
EXPANSION
Flexing a metal hose in two separate planes of
movement will torque the hose assembly.
Always install the metal hose assembly so
that flexing occurs in one plan only and this
is the same plane in which bending occurs. If
multiple planes of motion are required use a
dog leg assembly.
The installation should allow a straight
distance S before bending the hose. Not
doing so may compromise the hose
reinforcement and cause hose failure.
Max. bending angle and distance S can be
found in table 1 on page 6.
WRONG
RIGHT
Hoses should not be twisted and should
only have one bend.
86
180R9401 | AQ261351057880en- 000801 | 01.2022
Instruction | Right and wrong - Hose assembly routing tips
The use of pipe or fittings between pump
and iSave connectors and hoses should
be avoided. Such configurations can apply
excessive loads on the connectors and can
cause connector and/or connector bolt
failure. If this cannot be avoided, the piping
system must be protected by either hose
whip restraints mounted directly to the
frame or the hard piping must be fixed relative to any pump/iSave movements.
MAX.
BENDING
ANGLE
If hose is bent, ensure max. bending angle
and distance S from each connector (see
table 1 on page 6).
WRONG
WRONGRIGHT
To prevent hose collapse and flow restriction,
hose bend radii should be kept as large as
possible. Tight bends can also compromise
the hose reinforcement and cause premature
hose failure. Refer to hose specification table
on page 6 for minimum bend radii.
NO
NO
PRESSURE
PRESSURE
RIGHT
HIGH
HIGH
PRESSURE
PRESSURE
WRONG
RIGHT
The hose must have a distance S before
bending starts.
To allow the hose to expand when
pressurized, clamps should not be used at
bends. If possible, do not clamp high and
low pressure lines together.
180R9401 | AQ261351057880en- 000801 | 01.2022
87
Instruction | Right and wrong - Hose assembly routing tips
S
3. Hose specification
table
High pressure hoses
Code
number
180Z0228
Pipe connection1
[A]
1.5" Vic. OGSSuper duplex
Pipe
connection
material
EN 1.4410
Hose size
Inner
diameter
25.4 mm (1.0") 0.66 m (26")152 mm (6.08"), max. 90°79 mm (3.11”)
Hose length
ISO 1436
[B]
Bending radiusS
180Z02291.5" Vic. OGS
180Z0167
180Z0140
180Z02632.5" Vic. OGS
180Z0280
180Z0619
180Z0618
180Z0612
18 0Z0 611
180Z1000
180Z1001
Low pressure hoses
180Z02982.0” Vic. OGS
180Z01443.0” Vic. OGS
1.5" Vic. OGSSuper duplex
2.0" Vic. OGSSuper duplex
2.5" Vic. OGSSuper duplex
2.5" Vic. OGSSuper duplex
2.5" Vic. OGSSuper duplex
3.0" Vic. OGSSuper duplex
3.0" Vic. OGSSuper duplex
3.0" Vic. OGSSuper duplex
3.0" Vic. OGSSuper duplex
Super duplex
EN 1.4410
EN 1.4410
EN 1.4410
)
Super duplex
EN 1.4410
EN 1.4410
EN 1.4410
EN 1.4410
EN 1.4410
EN 1.4410
EN 1.4410
EN 1.4410
Super duplex
EN 1.4410
Super duplex
EN 1.4410
25.4 mm (1.0")
38.0 mm (1.5") 1.16 m (45.7") 250 mm (9.84"), max. 180°85 mm (3.35”)
50 mm (2.0")1.25 m (49")630 mm (24.8"), max. 90°115 mm (4.53”)
50 mm (2.0")1.78 m (70")630 mm (24.8"), max. 180°115 mm (4.53”)
50 mm (2.0")1.00 m (39.4") 630 mm (24.8"), max. 90°115 mm (4.53”)
65 mm (2.5")1.78 m (70")200 mm (7.87"), max. 270°150 mm (5.90”)
65 mm (2.5")
76 mm (3.0")1.79 m (70.5") 250 mm (9.84"), max. 270°150 mm (5.90”)
76 mm (3.0")1.00 m (39.4") 250 mm (9.84"), max. 90°150 mm (5.90”)
76 mm (3.0")1,25 m (49")250 mm (9.84"), max. 180°150 mm (5.90”)
76 mm (3.0")1,6 m (63")250 mm (9.84"), max. 180°150 mm (5.90”)
1.16 m (45.7")
1.00 m
(9.4")
2.0 m
(79”)
2.0 m
(79”)
152 mm (6.08"), max. 180°79 mm (3.11”)
200 mm (7.87"), max. 90°150 mm (5.90”)
1)
The installation instuction for Style 77DX is located in the Victaulic document I-100 Field Installation Handbook (htpp://static.victaulic.com)
O. D.
r
α
88
S
180R9401 | AQ261351057880en- 000801 | 01.2022
When using flexible hoses, it is
recommened to use Hose Whip Restraint.
Instruction | Right and wrong - Hose assembly routing tips
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in
product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and
is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures,
videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be
made without changes to form, fit or function of the product. All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are
trademarks of Danfoss A/S. All rights reserved.
This manual concerns the following types of standard
induction motors from Hoyer:
HMA3, HMC3, HMA2, HMC2, HMD, HMT, MS, Y2E1, Y2E2, YDT
These motors are manufactured in accordance with IEC/EN
60034-4 and IEC/EN 60072.
Motors are rated for the ambient temperature range -20°C to
+40°C and site altitudes ≤1000 m above sea level.
Low-voltage motors are components for installation in
machinery. They are CE marked according to the Low Voltage
Directive 2014/35/EU.
Motors not fulfilling the IE3 efficiency level must be equipped
with a variable speed drive when used in EU.
Transport and storage
Check the motor for external damage immediately upon
receipt and, if found, inform the forwarding agent right away.
Check all rating plate data, and compare it with the
requirement of the motor.
Turn the shaft by hand to check free rotation, remove
transport locking if used.
Transport locking must be used again for internal transport
also. It is also important that transport locking is used when
motors are transported mounted on equipment.
All motors should be stored indoors, in dry, vibration- and
dust-free conditions.
Lifting eyebolts must be tightened before use. Damaged
eyebolts must not be used, check before use. Lifting eyes at
motor must not be used to lift the motor when it is attached
to other equipment.
Before commissioning, measure the insulation impedance. If
values are ≤ 10MΩ at 25°C, the winding must be oven dried.
The insulation resistance reference is halved for each 20°C
rise in motor temperature.
It is recommended that shafts are rotated periodically by
hand to prevent grease migration.
etc.) using suitable tools, never hit the drive components
with a hammer as this will cause damage to the bearing.
The motor are balancing with half key, ensure that the drive
components are also the same.
Correct alignment is essential to avoid bearing, vibration and
shaft failure.
Use appropriate methods for alignment.
Re-check the alignment after the final tightening of the bolts
or studs.
Check that drain holes and plugs face downwards. We
recommend opening the drain hole for motors placed
outdoors and not running 24 hours / day, so that the motor
can breathe, thus ensuring a dry motor.
Electrical connection
Work is only permitted to be carried out by qualified
specialists and must to be carried out in accordance with
local regulations.
Before work commences, ensure that all power is switched
off and cannot be switched on again. This also applies to the
auxiliary power circuits, e.g. anti-condense heaters.
Check that supply voltage and frequency are the same as
rated data.
Motors can be used with a supply deviation of ± 5% voltage
and ± 2% frequency, according to IEC60034-1.
Connection diagrams for main supply and accessory as PTC
or heater are located inside the terminal box.
Connections must be made in such a way as to ensure that
a permanently safe electrical connection is maintained, both
for the main supply and the earth connection.
We recommend that crimped connections are made in
accordance with IEC 60352-2.
Tightening torques for terminal board screws:
ThreadM5M6M8M10M12M16M20M24
T.(Nm)2.53.571218355580
Installation
The motor must be fixed on a stable, clear and flat foundation.
It must be sufficiently rigid to withstand possible short
circuit forces.
It is important to ensure that the mounting conditions do
not cause resonance with the rotational frequency and the
doubled supply frequency.
Only mount or remove drive components (pulley, coupling,
92
180R9401 | AQ261351057880en-000801 | 01.2022
Ensure that the terminal box is clean and dry.
Unused glands must be closed with blind caps.
Check the terminal box gasket before it is remounted.
Maintenance
Inspect the motor at regular intervals, keep it clean and
ensure free ventilation air flow, check the condition of shaft
seals and replace if necessary. Both electrical and mechanical
Motor
Manual
connections must be checked and tightened if necessary.
Bearing size and type are specified on the rating plate. Motor
types HMA3 and HMC3 is as standard with lifetime greased
bearings in motors size ≤180 for cast iron and size ≤132 for
aluminium. Motor types HMA2 and HMC2 is as standard
with lifetime greased bearing in motors size ≤225.
Motor types MS and Y2E is as standard with lifetime greased
bearing in motors size ≤160.
Typical duty hours for lifetime lubricated bearings.
Frame sizePolesTypical lifetime
56 - 1602 - 840,000h
180235,000h
200227,000h
225223,000h
180 - 2254 - 840,000h
Motors with a re-greasing system must be lubricated with
high quality lithium complex grease, NLGI grade 2 or 3, with
a temperature range of between -40°C to +150°C.
Motors are normal fitted with a data plate with greasing
information; if it is missing use the following re-greasing
intervals.
Frame
size
160204200700085008500
180204200700085008500
200253100650085008500
225253100650085008500
250352000600070007000
280352000600070007000
315501500550065006500
355601000400050006000
40080800300040006000
Grease
(g)
2 pole
(h)
4 pole
(h)
6 pole
(h)
8 pole
(h)
Grease the motor while running, open the grease outlet plug
and let the motor run 1-2 hours before the outlet grease plug
is closed again.
Grease the motor for the first time during commissioning.
The following applies in general for both lifetime lubricated
and re-lubricated bearings:
At 60Hz the time will be reduced by app. 20%.
Data for vertically mounted motors are half of the above
values.
The table values are based on an ambient temperature of
25°C. The values must be halved for every 15K increase in
bearing temperature.
Higher speed operations, e.g. frequency converter drive will
require shorter greasing intervals. Typically, doubling the
speed will reduce the values by 50%.
Special note for Atex Zone 22 and nA motors
Designation of motor according to IEC standard:
II 3D Ex tc IIIB T120°C
II 3G Ex nA IIC T3
The hazardous 3-phase asynchronous motors are in
accordance with International standard IEC 60079-31 and
IEC 60079-15.
Only one electrical installation may be installed in one
specified area (zone).
Only certificated cable glands may be used. Unused glands
must be closed.
Connections must be made in such a way as to ensure that
a permanently safe electrical connection is maintained, both
for the main supply and earth connection.
Installations must be in accordance with actual standards
for installation in hazardours area.
It is recommended that the IEC standard is followed according
to temperature and dust on the motor surface.
The use of motors with so much surface dust that the motor
temperature increases is not permitted.
Regularly cleaning is recommended.
The radial shaft sealing ring is part of the ATEX certification.
It is important that the ring is always intact.
The shaft sealing must be regularly checked, and if dry it
must be lubricated. It is recommended that the seal is relubricated regularly.
Always use the original seal ring when replaced.
Replacing bearings also means replacing the seals.
All machines must be inspected regularly for mechanical
damage.
The user is responsible for changing parts in accordance
with the lifetime of parts, in particular:
bearings, grease and lubrication of shaft sealing.
Maintenance, repairs and replacement on this type must
only be carried out by qualified specialists.